Danfoss KP 15 Pressure Switch Installation Guide
- June 4, 2024
- Danfoss
Table of Contents
Danfoss KP 15 Pressure Switch
Pressure switch
KP 15, KP 15A, KP 17W, KP 17B, KP 17WB, KP 47WB
Refrigerants:
R22, R134a, R404A, R407A, R407C, R407F, R422B, R422D, R448A, R449A, R450A,
R452A, R507A, R513A, R717) For complete list of approved refrigerants, go to
http://products.danfoss.com/all-products/ ) only for KP 15A
Ambient temperatures / Mounting requirements
- t1 min. KP 15: -40 °C (-40 °F)
- t1 min. KP 17, KP 47: -25 °C (-13 °F)
- t1 max. : 65 °C (149 °F)
- Relative humidity RH: 30 – 98%
- Vibrations resistance: 4 g (10 – 1000 Hz)
Test pressure (Best)
Connections
Mounting
Enclosure
CAUTION:
Disconnect power supply before wiring connections are made or service to avoid
possible electrical shock or damage to equipment. Do never touch live parts
with your fingers or with any tool.
- LP side: A-C opens on pressure drop
- HP side: A-C opens on pressure rise
Electrical rating – General
Short circuit protection:
Fuse 16 Amp
When used acc. to UL regulations
Listed refrigeration controller 61B5 | |
---|---|
Contacts | Voltage |
Pilot duty
AC| DC| A| A
A – B
A – C
| 240| –| 8| 48| 8 A| 3 A
120| –| 16| 96| 16 A
–| 240| –| –| –| 12 W
A – D| 240| –| –| –| –| 50 VA
Use copper wire only Tightening torque 20 lb. in
LP = Low Pressure
LP, aut. reset
LP = Low Pressure
LP, man. reset
HP = High Pressure
HP
Manual trip function
TRIP:
use FINGERS ONLY! (Do NOT use screwdriver)
Convertible reset
KP 15: LP/HP convertible, KP 17WB, KP 47WB: HP convertible
Insert a screwdriver into the slot on the lock disc and turn it to desired reset configuration. Do not turn the screw on the lock disc as it may damage the convertible reset mechanism.
Adjustment
Reset options
Note: Do not select automatic reset if safety of the system requires
manual reset.
Note: Selected reset configuration may be protected against unauthorized
actions applying a seal.
CAUTION:
Only for selected A2L refrigerants: R455A, R454C, R1234yf, R1234yz, R1234ze
For a complete list of approved A2L refrigerants, go to
http://products.danfoss.com/all-products/
Electrical rating
- AC-3: 16 A / 250 V AC
- AC-15: 10 A / 250 V AC
Voltage| Current range| Power factor
(cos phi)
| Frequency
---|---|---|---
250V AC| ≤ 4.0 A| PF ≥ 0,400| 50Hz/60Hz
250V AC| > 4.0 to 6.0 A| PF ≥ 0,594| 50Hz/60Hz
250V AC| > 6.0 to 16,0 A| PF ≥ 0,780| 50Hz/60Hz
IMPORTANT NOTICE
Safety requirements
- KP pressure switches shall only be employed in the units/systems which comply with the requirements for charge limits and requirements for avoiding ignition sources of IEC 60335-2-24, IEC 60335-2-40, IEC 60335-2-89, ISO 5149, EN378-1 or equivalent.
- Applying the overload on the KPs must be prevented. If by any chance it was damaged, the system/unit shall be stopped and KP shall be replaced as necessary.
- Electrostatic discharge protection and Electrical leakage protection shall be surely implemented by grounding or other measures.
- Only trained personnel are authorized to handle flammable refrigerant systems and may do the installation, maintenance, and exchange of the switch by using appropriate tools.
- It is recommended to regularly check the function of KP switch.
- KP pressure switches must be installed in an area with a low risk of mechanical damage.
- Corrosion protection of KP pressure switches must be taken into account when used in a corrosive environment.
- Cables shall not be in contact with sharp edges. The cables shall be connected with adequate stress relief in order to prevent pulling forces can be carried through the cable to the terminal.
- In the event of pressure pulsation in the system, where the switch is connected, these must be effectively dumped to prevent failure of the bellows. The cycle frequency of the KP switch shall be kept as low as possible.
- The KP switches shall not be installed in places where a high level of vibration is present.
Disclaimer
The user is responsible for ensuring that third parties also comply with this
Notice, e.g. in case the KP switches are supplied to third parties, and e.g.
that all installation guides are available with the KP switches during
installation. It is required that all conditions of this guide are being met
and secured when using KP pressure switches. Danfoss shall not be responsible
for any kind of direct and indirect or consequential damage or loss,
including, but not limited to, loss of property, production, loss of profit,
or human injury arising out of the explosion or fire caused by the flammable
nature of refrigerant. Any information, including, but not limited to
information on selection of product, its application or use, product design,
weight, dimensions, capacity or any other technical data in product manuals,
catalogs descriptions, advertisements, etc. and whether made available in
writing, orally, electronically, online or via download, shall be considered
informative and is only binding if and to the extent, explicit reference is
made in a quotation or order confirmation. Danfoss cannot accept any
responsibility for possible errors in catalogs, brochures, videos, and other
material. Danfoss reserves the right to alter its products without notice.
This also applies to products ordered but not delivered provided that such
alterations can be made without changes to the form, fit or function of the
product. All trademarks in this material are property of Danfoss A/S or
Danfoss group companies. Danfoss and the Danfoss logo are trademarks of
Danfoss A/S. All rights reserved.