BEIJER REF 40CAS-L6 Cassette Panel
ENGINEERING AND SERVICE TIPS
- Concerning: 40CAS-L6
- Date issued: July 13th, 2022
- Issued : Mr. L. Voogd lvd@beijerref.com
- Subject: Connecting Carrier New Cassette Panel 40CAS-L6 for QTD024-060D8S
Step 1, remove the inlet grille in the centre of the panel
Step 2, remove the 4 corner panels
Step 3, install the panel to the cassette
Step 4, the panel has 3 different connectors
Step 5, connector 1 (=display)
Connect to indoor PCB, CN10 (cable is 10-core)
Step 6, connector 2 (=swing motor)
Connect to indoor PCB, CN14 (swing)
Step 7, connector 3 (=optional wired controller)
Connect to the optional wired controller (old model KJR-12B). Which we usually don’t use anymore. Using the current wired controller KJR-120G2 or KJR-120X2, directly connect to the indoor PCB, connector CN40