BOSCH FLM-420-I2-W Input Interface Module Type Wall Mount Installation Guide
- June 13, 2024
- Bosch
Table of Contents
**BOSCH FLM-420-I2-W Input Interface Module Type Wall Mount Installation Guide
**
Installations Instructions
| A| FPA-5000 FPA-1200| BZ 500 LSN, UEZ
2000 LSN, UGM 2020
---|---|---|---
1| 0| |
2| 1 – 254| |
3| 255 = CL| |
NOTICE!
Installation must only be performed by authorized and specialized personnel.
CAUTION!
Electrostatic discharge (ESD)! Electronic components could become damaged.
Ground yourself using a wrist strap or take other suitable actions.
Functional description
FLM-420-I2 Input Interface Modules provide three monitoring functions:
- Monitoring a line with EOL resistor for standby or triggering (interruption/short circuit)
- Monitoring a potential free contact for “open” and “closed” states
- Voltage monitoring between 0 and 30 V DC.
The FLM-420-I2-W type wall-mount can be flush mounted in standard device boxes in accordance with EN 60670; alternatively, it can be surface mounted in the FMX-IFB55-S interface box (see Figure 7, Page 7 to Figure 8, Page 7).
Address Setting
Address setting is carried out using the 8 DIP switches and a suitable pointed
object (see Figure 1, Page 3 toFigure 5, Page 5).
Address (A) | Operating mode |
---|---|
0 | Loop/stub in LSN improved version mode with automatic addressing |
1 – 254 | Loop/stub/T-taps in LSN improved version mode with manual addressing |
255 = CL | Loop/stub in LSN classic mode (address range 127 max.) |
Connection
See Figure 6, Page 6
Description | Function |
---|---|
LSN: a1- | b1+ |
LSN-POWER: 0 V | 0V |
through)
LSN-SHIELD| Cable shielding (if present)
IN: IN1+ | IN1- | IN2+ | IN2-| Input 1 / Input 2
Technical specifications
Inputs | 2, independent |
---|---|
LSN input voltage | 15 to 33 V DC |
Max. current consumption from LSN | 10.4 mA |
Contact monitoring: | |
– EOL resistor | Nominal, 3.9 kΩ |
– Max. current strength (current pulse) | 8 mA |
– Total resistance of the line | In standby: 1500 Ω to 6000 ΩShort- |
circuit: < 800 Ω Interruption: > 12000 Ω
Voltage monitoring:|
– Voltage range| 0 to 30 V DC
– Input resistance| > 50 kΩ
– Number of selectable threshold values| 4 (see programming software)
Permissible wire diameter| 0.6 to 2.0 mm2
Cable length per input| Max. 3 m
Permissible operating temperature/storage temperature| -20 °C to +65 °C / -25
°C to +80 °C
Permissible rel. humidity| <96 %, non-condensing
Protection class as per IEC 60529| IP 30
Classes of equipment as per IEC 60950| Class III equipment
Housing material and color| ABS + PC-Blend, signal white (RAL 9003)
Dimensions (Ø x H)| Approx. 76mm x 30 mm
0786
Bosch Sicherheitssysteme GmbH
Robert-Bosch-Platz 1, D-70839 Gerlingen
08
0786 – CPD – 20287
EN 54-18: 2005, EN 54-17: 2005