Product Information

  • The product in question is a Rack Automatic Transfer Switch (ATS) manufactured by APC. There are two models mentioned in the user manual: AP7721 and AP7723. The ATS is designed for use with a 208 Vac power supply. It is important to note that the power cord is not provided with the unit.
  • For the AP7721 model, a UL Listed, CSA-certified power cord rated 300 Vac, 15 A, 14 AWG should be used. For the AP7723 model, a UL Listed, CSA-certified power cord rated 300 Vac, 20 A, 12 AWG should be used. Both power cords must be used with an approved plug and outlet. The maximum length of the power supply cord should not exceed 4.5 m, while the minimum length should be 1.5 m unless it is intended for a special installation.
  • The default settings of the Rack ATS are 230 Vac nominal voltage and a default transfer range set to medium. However, when using the Rack ATS in a 208-Vac application, it is necessary to change the nominal voltage setting to 208 Vac to prevent damage. If the nominal voltage is not reset, the Rack ATS will switch between power source A and power source B when the load drops below 207 Vac.

Product Usage Instructions

Changing Nominal Voltage Setting
To change the nominal voltage setting of the Rack ATS, follow these steps:

Using the Web Interface:

  1. Select the “Unit” tab.
  2. Select “frequency/voltage” under the “Configuration” left navigation menu option.
  3. Change the “Line VRMS” field to “208” and select “Apply” to save the change.

Using the Control Console:

  1. Select “Device Manager” from the main menu of the Control Console interface.
  2. Select “ATS Configuration” from the Device Manager menu.
  3. Select “Line VRMS” from the ATS Configuration menu.
  4. Enter “208” and press “ENTER”.
  5. Select “Accept Changes” from the ATS Configuration menu to save the changes.

For further information on accessing and configuring the Rack ATS settings through the Web interface or control console, please refer to the Rack ATS User’s Guide.

If you require customer support or warranty information, it is available on the APC website at www.apc.com.
For additional information, please refer to the user manual provided at <https ://manual-hub.com/>.

Available power cords

Note: A power cord is not provided with the unit.
For AP7721, use a UL Listed, CSA certified power cord rated 300 Vac, 15 A, 14 AWG. For AP7723, use a UL Listed, CSA certified power cord rated 300 Vac, 20 A, 12 AWG. Both should be used with an approved plug and outlet.
The length of a power supply cord shall not exceed 4.5 m. The minimum length of a power supply cord shall be 1.5 m unless it is intended for a special installation, such as dedicated equipment intended to be mounted near a receptacle.

Voltage setting

  • Warning: The AP7721 and AP7723 Rack Automatic Transfer Switches (ATS) have default settings of 230 Vac nominal voltage and a default transfer range set to medium or ± 23 Vac.
  • Before using the Rack ATS in a 208-Vac application, change the nominal voltage setting to 208 Vac through the Web interface or control console.
  • Change the nominal voltage setting to prevent the Rack ATS from being damaged. If you do not reset the nominal voltage, the Rack ATS will switch between power source A and power source B when the load drops below 207 Vac.

Setting the nominal voltage

See the “Web Interface” or “Control Console” chapters in the Rack ATS User’s Guide for further information about accessing and configuring the Rack ATS settings through the Web interface or control console.

Web interface.

  1. Select the Unit tab.
  2. Select frequency/voltage under the Configuration left navigation menu option.
  3. Change the Line VRMS field to 208 and select Apply to save the change.

Control console.

  1. Select Device Manager from the main menu of the Control Console interface.
  2. Select ATS Configuration from the Device Manager menu.
  3. Select Line VRMS from the ATS Configuration menu.
  4. Enter 208 and press ENTER.
  5. Select Accept Changes from the ATS Configuration menu to save changes.

Customer support and warranty information is available at the APC Web site, www.apc.com.
© 2008 American Power Conversion. All rights reserved. All APC trademarks are property of American Power Conversion. Other trademarks are property of their respective owners.

www.apc.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals