Raritan NX1 Smart Intelligent PDU Instruction Manual
- June 13, 2024
- Raritan
Table of Contents
Raritan NX1 Smart Intelligent PDU
CONFIGURED PRODUCTS
POWER & CONNECTIVITY
NX1
METERED
RARITAN NX1 INTELLIGENT METERED PDUS
The Raritan NX1 Smart PDU has been designed to provide you with the best experience, from installation to effective data measuring.
Technical ID : NX1-F00006
MOUNTING POSITION | Zero U – vertical |
---|---|
– Length | 1974,00 mm |
– Width | 52,00 mm |
– Depth | 67,60 mm |
POWER CATEGORY | 3 phases, 400V, 32A (3P+N+E) |
CIRCUIT QUANTITY | 6 |
PROTECTION | MCB Magnetic + Hydraulic 16A (Single Pole) |
INPUT LOCATION | Bottom Front (Zero U) |
INLET TYPE / INPUT CABLE TYPE | Rotatable cable input |
CABLE EXTREMITY | IEC 60309 plug |
LSZH Cord | No |
CABLE LENGTH | 3,00 m |
OUTLETS | |
– C19 – IEC 60320 | 12 |
– C13 HD – IEC 60320 | 36 |
OPTIONS | |
– Base and Inlet Metering Module | YES |
– Monitoring | PHASE |
MARKING | |
– Outlet numbering | #1 starts at input |
MOUNTING BRACKETS | |
– Set of 2 standard fixing brackets | YES |
– Set of 2 buttons | YES |
TECHNICAL DATASHEETS
INTRODUCTION
NX1 intelligent PDUs provide electric power for IT equipment in 19” enclosures. They have been designed with specific features for Data Center applications. You can find hereafter the general product specifications. Depending on your configured product, please refer to the relevant chapters and data.
KEY FEATURES
NX1 intelligent PDUs provide electric power for IT equipment in 19”
enclosures.
They are connected devices enabling remote access to all measurements and
alerts.
- Modular concept : available in 2 versions, NODE version with all functions (controller with LCD screen and LAN connection) and BASE version. Deploy intelligent PDUs without the need to have a PDU controller in every unit.
- Cascading possibilities to save switch ports connections. Daisy-chain up to 31 BASE PDUs downstream to a NODE PDU.
- Hot swappable controller. Allow the replacement on a NODE PDU or the adding on a BASE PDU without powering down connected equipment.
- 2 levels of alerts physically visible on the PDU thanks to LED bar and remotely in Web User interface.
- Metering at inlet and circuit level with +/- 1% accuracy.
- User-friendly and responsive Web User Interface. Data aggregation capabilities in DCIM.
- Each C13 and C19 outlets are numbered and equipped with a cord locking system.
- Equipped with hydraulic magnetic circuit protection. Hydraulic magnetic circuit breakers are not affected by ambient temperature.
- Easy installation thanks to 330° rotating cable input and button-type brackets.
GENERAL SPECIFICATIONS
| NODE PDU version| BASE PDU version
---|---|---
Energy Metering| Voltage (V), Current (A), Active Power (kW), Apparent Power
(kVA), Energy (kWh), Power Factor
Metering Accuracy| ±1%
Metering per Input Phase| Yes
Metering per Branch Circuit Breaker| Yes
Metering per Outlet| No
Remote Outlet Switching| Metered PDU : No / Switched PDU : Yes
With display| Yes (Node)| No
Networking| Ethernet port. 10/100 BaseT| via the Ethernet port of the upstream
Node PDU
RS485 Cascading| Yes
Daisy chain up to 31 BASE PDUs downstream to a NODE PDU by RS485 bus (ethernet RJ45 patchcord). Max length: 250m in total and 30m between each PDU.
USB Cascading| Yes
Daisy chain up to 16 NODE PDUs via USB connection. Max length: 75m in total and 5m between each PDU.
| No
Remote management| HTTP(s), SSH, Telnet, SNMP version v2/v3, SMTP, JSON-RPC,
Modbus over TCP
Built-in processor| ARM Cortex A5 500MHZ (Microchip ATSAMA5D21C), 32MByte SPI
Flash, 256MByte DDR3 RAM.| No
Wireless connectivity| Yes, Zigbee 2.4 GHz chip embedded
Compatible Sensors| Wireless sensors (Green Power)
– Temperature/Humidity (cat number 6 460 03)
– Contact closure (cat number 6 460 04)
A maximum of 8 sensors can be paired to 1 PDU
Replaceable controller| Yes
– Hot swappable for node
– Cold swappable for base
| Yes
– Cold swappable for base
CONTROLLER
Node Controller (only in NODE PDU version)
Node controller is plugged on the base and is hot swappable.
Base
Networking | Via the NODE controller only |
---|---|
Wireless control (radio frequency) | Button for pairing wireless sensors |
LED indicator | RGB LED for visual indication and replicating configured alerts |
Normal operation
Warning threshold exceeded
Critical threshold exceeded
Wireless sensors pairing in progress
CASCADING MODES
RS485 – CASCADING
- Daisy chain up to 31 BASE PDUs downstream to a NODE PDU with Cat5e or higher RJ 45 patch cables (RS485 link).
- Only the NODE PDU is connected to your network.
- NODE controller aggregates all BASE units data into its user interface.
- Thresholds and alerts are configured directly in the NODE unit.
USB – CASCADING
- Daisy chain up to 16 NODE PDUs using their respective USB ports.
- Only the NODE PDU at the head of your daisy chain is connected to your network.
- Have one IP address for the daisy-chain with “port forwarding” method or one IP address for each PDU with “bridging” method.
MECHANICAL FEATURES
-
Casings: 6060 T5-R19 natural anodized aluminium.
-
Outlet modules:
PC/ABS
CW507L (CuZn 36) brass -
Fixing brackets:
DC01-A-mgalvanised steel
Color | Aluminium grey (casing) / black (outlet modules) |
---|---|
Casing | Zero-U or horizontal 19’’, aluminium |
IP | 20 |
IK | 04 |
ENVIRONMENTAL CHARACTERISTICS
Storage and transport tempe- rature | -20 to +70°C |
---|---|
Operating temperature | +5°C to +55°C |
Operating Relative Humidity | 5% to 95% |
Operating Elevation | 0 – 2000 m |
OPTIONS
OUTLETS
Legrand PDUs can be equipped with outlets of different standards.
C13 with cord locking system
2P+E 10 A
Outlet recess at 90° angle Conforms to standard IEC 60320-2-2
Switched C13 with cord locking system
LED on each outlet to see the outlet status (on/off)
2P+E 10 A
Outlet recess at 90° angle Conforms to standard IEC 60320-2-2
C13 HD with cord locking system
2P+E 10 A
Outlet recess at 0° angle
Conforms to standard IEC 60320-2-2
C19 with cord locking system
2P+E 16 A
Socket recess at 90° angle
Conforms to standard IEC 60320-2-2
C19 with cord locking system
LED on each outlet to see the outlet status (on/off)
2P+E 16 A
Socket recess at 90° angle
Conforms to standard IEC 60320-2-2
Cable locking system on C13/C19 sockets
The cable is locked mechanically into the socket to prevent any unintended
disconnection (caused by maintenance, vibrations, etc.).
Pull-out force 100 N
This universal solution is compatible with any standard compliant cord type on
the market.
French-Belgian
2P+E 16 A
Terminals equipped with protective shutters
Outlet recess at 55° angle
Conforms to standard IEC 60320-2-2
German
2P+E 16 A
Terminals equipped with protective shutters
Outlet recess at 55° angle
Conforms to standard IEC 60320-2-2
TERMINATION
Depending on the configuration, the PDUs can be connected in different ways.
Supplied with power cord
Some products are supplied with a power cord
PDUs can be supplied with a cable input via cable gland by special request.
Terminal block connection
Some products are supplied without a cable; they are designed to be wired on a
terminal block.
Example of terminal block connection for a Zero-U PDU with rotative cable
entry.
Connection via C14 or C20 connector
Connectors mounted on the front panel of the PDU. The PDU is powered via a separate cable that plugs into these connectors.
| C14| C20
---|---|---
Type| Male| Male
Nominal current| 10A| 16A
Voltage| 250 VAC| 250 VAC
IP| 20| 20
MOUNTING SOLUTIONS
Set of 2 buttons
Screwless fixing. The height of the fixing centre can be set at any point along the full height of the PDU by sliding the button slots into the groove on the rear of the PDU. Tightened using a screwdriver.
Set of 2 standard fixing brackets
Screw-fixing (screws not included)
Brackets for Nexpand racks
Screw-fixing (2 screws included)
Ref. 981227 Set of 2 brackets (for 1 PDU)
Ref. 981228 Set of 20 brackets (for 10 PDUs)
STANDARDS AND REGULATIONS
STANDARDS
Application | Standards |
---|---|
Safety | IEC 62368-1 |
C13 and C19, French-Belgian and German connectors for electrical equipment |
IEC 60320-2-2
IEC 62368-1
Circuit breakers| IEC 60934
IEC 60947-2
Industrial plugs| IEC 60309-1
Information and communication technology equipment| IEC 62368-1
Electromagnetic compatibility for radio equipment and services| EN 301489
(ETSI EN 301 489-1 V2.2.3, ETSI EN 301 489-17 V3.2.4)
Radio transmission equipment| ETSI EN 300 328-1
(V2.2.2 2020-02-08)
Electromagnetic compatibility| EN 62311 (2008) EMF
EN 50491-5-2
EN 50491-5-3
EN 55035
EN 55032
EN 61000-4-11
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6
EN 61000-3-2
REGULATORY APPROVALS
CE, UKCA, CMIM
RoHS directive (Restriction of Hazardous Substances) REACH regulations
(Registration, Evaluation, Authorisation & restriction of CHemicals)