EVCO EV3 WEB Gateway Network 10 Devices Instruction Manual

June 13, 2024
EVCO

EVCO Logo EV3 WEB
Gateway for a network of up to 10 devicesEVCO EV3 WEB Gateway Network
10 Devices Installer Manual
1143W01E4.01 – 08/2022

WARNING
Read and fully understand user manual before using this device. Failure to follow these instructions can result in death or serious injury.

IMPORTANT INFORMATION

Liability and residual risks
EVCO assumes no liability for any damage caused by the following (by way of example; this is not an exhaustive list):

  • Installation/use for purposes other than those specified and, in particular, not adhering to the safety provisions set out by current regulations in the country in which the product is installed and/or contained in this manual;
  • Use in appliances that do not guarantee sufficient protection against electric shocks, water and dust within the installation conditions created;
  • Use in appliances that allow access to hazardous parts without the use of a keyed or tooled locking mechanism when accessing the instrument;
  • Tampering and/or modifying the product;
  • Installation/use in appliances which do not comply with current regulations in the country in which the product is installed.
    The customer/manufacturer is responsible for ensuring their machine complies with these regulations.
    EVCO’s responsibility is limited to the correct and professional use of the product in accordance with regulations and the instructions contained in this manual and other product support documents.
    To comply with EMC standards, observe all the electrical connection instructions. As it depends on the wiring configuration as well as the load and the installation type, compliance must be verified for the final machine as specified by the relevant product standard.

Disclaimer
This document is the exclusive property of EVCO. It contains a general description and/or a description of the technical specifications for the features offered by the products listed herein. This document should not be used to determine the suitability or reliability of these products in relation to specific user applications. Each user or integration specialist should conduct their own complete and appropriate risk analysis, in addition to carrying out a product evaluation and test in relation to its specific application or use. Users can send us comments and suggestions on how to improve or correct this publication. Neither EVCO nor any of its associates or subsidiaries shall be held responsible or liable for improper use of the information contained herein.
EVCO has a policy of continuous development, therefore reserves the right to make changes and improvements to any product described in this document without prior notice.
The images in this document and other documentation supplied with the product are provided for illustrative purposes only and may differ from the product itself.
The technical data in this manual is subject to change without prior notice.
Terms and Conditions of use
Permitted use
The device must be installed and used in accordance with the instructions provided and, in particular, hazardous live parts must not be accessible under normal conditions.
The device must be suitably protected from water and dust with regard to its application and must also only be accessible with the aid of a tool (with the exception of the front panel).
Only qualified personnel may install the product or perform technical support procedures on it.
The customer must only use the product as described in the documentation relating to that product.
Prohibited use
Any use other than those described in the “Permitted use” section and in the product support documentation is prohibited.
Disposal
The device must be disposed of according to local regulations governing the collection of electrical and electronic equipment.
Consider the environment
The company strives to respect the environment, taking account of customer requirements, technological innovations in terms of materials and the expectations of the community to which we belong. EVCO places great importance on respecting the environment, encouraging all associates to become involved with company values and guaranteeing safe, healthy and functional working conditions and workplaces.
Please consider the environment before printing this document.

IMPORTANT SAFETY INFORMATION

Read this document carefully before installation and take all precautions before using the device. Only use the device in accordance with the methods described in this document. The following safety messages may be repeated several times in the document, to provide information regarding potential hazards or to attract attention to information which may be useful in explaining or clarifying a procedure.

This symbol is used to indicate a risk of electric shock.

It is a safety indication and as such, should be observed to avoid potential accidents or fatalities.

This symbol is used to indicate a risk of serious personal injury.

It is a safety indication and as such, should be observed to avoid potential accidents or fatalities.
DANGER
DANGER
indicates a situation of imminent danger which, if not avoided, will result in death or serious injury.
WARNING
WARNING indicates a situation of imminent danger which, if not avoided, may result in death or serious injury.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, could cause minor or moderate injury.
NOTICE
NOTICE indicates a situation not related to physical injuries but which, if not avoided, could damage the equipment.
N.B. The maintenance, repair, installation and use of electrical equipment must only be entrusted to qualified personnel.
QUALIFIED PERSONNEL
Only suitably trained and experienced personnel capable of understanding the content of this manual and all documentation regarding the product are authorised to work on and with this equipment. Furthermore, the personnel must have completed courses in safety and must be able to recognise and prevent the implied dangers. The personnel must have suitable training, knowledge and experience at a technical level, and be capable of anticipating and detecting potential risks caused by using the product, as well as changing the settings and modifying the mechanical, electric and electronic equipment for the entire system in which the product is used. All personnel working on and with the product must be entirely familiar with the relevant standards and directives, as well as safety regulations.

SAFETY INFORMATION RELATING TO THE PRODUCT

Before carrying out any work on the equipment, read these instructions carefully, making sure you understand everything.
DANGER
RISK OF ELECTRIC SHOCK, EXPLOSION OR ELECTRIC ARC

  • Only use electrically insulated measuring devices and equipment.
  • Do not install the equipment while the power supply is connected.
  • Switch off all equipment, including connected devices, before installing or uninstalling the device.
  • Always use a correctly calibrated voltmeter to check the system is switched off.
  • Do not touch the unshielded components or the terminals while they are live.
  • Do not open, disassemble, repair or modify the product.
  • Do not expose the equipment to liquids or chemicals.
  • Before applying voltage to the equipment:
  • Make sure all protective elements, such as covers, hatches and grilles, are fitted and/or closed.
  • Check all wiring connections.

DANGER
RISK OF ELECTRIC SHOCK AND FIRE

  • Do not use the device with loads greater than those indicated in the technical specifications.
  • Do not exceed the temperature and humidity ranges indicated in the technical specifications.
  • Use the required safety interlocks (fuses and/or magnetothermal switches) of a suitable size.

DANGER
RISK OF ELECTRIC SHOCK OR MALFUNCTIONING OF THE EQUIPMENT
Do not use damaged products or accessories.
This device was designed to operate in non-hazardous environments, excluding applications that generate, or could potentially generate, hazardous atmospheres. Only install this device in areas and for applications which are reliably free from hazardous atmospheres
DANGER
RISK OF EXPLOSION

  • Only install and use this device in sites that are not at risk.
  • Do not install or use this device in applications which are capable of generating hazardous atmospheres, such as applications that use flammable refrigerants

WARNING
MALFUNCTIONING OF THE EQUIPMENT

  • Perform the wiring carefully, in compliance with electromagnetic compatibility requirements.
  • Make sure the wiring is correct for the application.
  • Use shielded cables for all I/O signal and communication cables.
  • Minimise the length of the connections as much as possible and avoid winding the cables around electrically connected parts.
  • The signal cables (analogue and digital inputs, communication and corresponding power supplies), power cables and power supply cables for the device must be routed separately.
  • Before applying the power supply, check all the wiring connections.
  • Use the required safety interlocks where personnel and/or equipment hazards exist.
  • Install and operate this equipment in a cabinet appropriately rated for its intended environment and secured by a keyed or tooled locking mechanism.
  • Power line and output circuits must be wired and fused in compliance with local and national regulatory requirements for the rated current and voltage of the particular equipment.
  • Do not use this equipment in safety-critical machine functions.
  • Do not disassemble, repair or modify this equipment.
  • Do not connect wires to unused terminals and/or to terminals labelled “No connection “(N.C.)”.

INTRODUCTION

1.1 DESCRIPTION
EVCO EV3 Web controllers remotely monitor up to 10 EPoCA-compatible controllers on the EPoCA cloud via the on-board Ethernet and RS-485 serial ports.
EV3 Web is compliant with HACCP regulations for food safety during food processing.
1.2 FEATURES
The main features of EV3 Web are:

  • 1 digital input;
  • 1 analogue input for NTC/PTC probes;
  • 1 relay output;
  • 1 Ethernet RJ45 Modbus TCP/IP compatible serial port;
  • 1 micro-B USB serial port;
  • 1 RS-485 serial port;
  • 1 32 MB internal memory;
  • 1 year of HACCP data recording with 5-minute intervals, up to 3 probes;
  • RTC shared with subnetwork;
  • EPoCA compatible.

1.3 ACCESSORIES
The following accessories are available for EV3 Web controllers:

Type P/n Description
EVTPN615F200 SND NTC TERM 1,5M 6×15 COSTFL
EVTPN630F200 SND NTC TERM 3,OM 6×15 COSTFL
EVTPP815P200 SND PTC PVC2 1,5M 6×30 STEEL67
EVTPP830P200 SND PTC PVC2 3,OM 6×30 STEEL67
810500023 USB A-micro-B cable 1.5 m
EVIF22TSX Module for TTL/RS-485 serial interface
EV3KEY Programming key for EV3 regulation parameters

TECHNICAL SPECIFICATIONS

All the system components of the EV3 Web controllers meet the requirements of the European Community (EC) for electric equipment. They must be installed in a casing or other location designated for the specific ambient conditions and to keep the possibility of involuntary contact with dangerous electrical voltages to a minimum. Use metal casings to improve the immunity of the EV3 Web system to electromagnetic fields. This equipment meets EU requirements as shown in the tables below.
WARNING
MALFUNCTIONING OF THE EQUIPMENT
Do not exceed the nominal values given in this section.
2.1 TECHNICAL SPECIFICATIONS

Type Description
The product complies with the following harmonised standards: EN60730-1 and

EN60730-2-9
Device construction:| Built-in electronic device
Device purpose:| Operating control device
Type of action:| 1
Pollution category:| 2
Overvoltage category:| III
Rated impulse withstand voltage:| 4000 V
Power supply:| 115…230 Vac, ±10%, 50/60 Hz
Consumption:| 10 VA maximum
Ambient operating conditions:| 0 … 50 °C (32 … 122 °F) 10 … 90 % RH non- condensing
Transportation and storage conditions:| -20 … 70 °C (-4 … 158 °F) 10 … 90 % RH non-condensing
Software class:| A
Environmental front protection:| IP65
Clock (RTC):| Built-in lithium battery
Clock drift:| s 60 s/month at 25 °C (77 °F)
Battery life:| 30 days
Battery charging time:| 24 h through device’s power supply
Data memory:| 32 MB
Data memory per device:| —2.7 MB

2.2 I/O FEATURES

Type|

Description

---|---
Digital inputs:| 1 voltage-free digital input
Analogue inputs for temperature:| 1 analogue input for NTC/PTC probes
Digital output with non-hazardous voltage (SELV):| 1 relay output
Serial:| 1 Ethernet RJ45 10/100 MAC serial port
1 USB serial port

Analogue input features

| Default| NTC 10 kΩ at 25 °C BETA 3435| PTC KTY 81-121 990 Ω at 25 °C
---|---|---|---
Pb1| Probe Temperature| |
Range| —| -40…105 °C
(-40…220 °F)| -50…150 °C
(-58…302 °F)
---|---|---|---
Resolution| —| 0.1 °C (1 °F)| —
Input impedance| —| 10 kΩ| 990 Ω

Digital output features

| Default| Description| Load (at 250 Vac)| Type of load
---|---|---|---|---
Out4| AUX| SPDT| 5 A| Resistive

MECHANICAL ASSEMBLY

3.1 BEFORE STARTING
Read this manual carefully before installing the system.
In particular, the safety instructions, electrical requirements and current regulations for the machine or the process in which this device is involved must be observed. The use and application of the information contained herein require experience in the design and programming of automated control systems. Only the user, system integrator or machine builder can be aware of all the conditions and factors present during the installation, configuration, operation and maintenance of the machine or process, and can therefore determine the associated automation equipment and the related safeties and interlocks which can be effectively and properly used. When selecting automation and control equipment and any other related equipment or software for a particular application, always consider all the applicable local, regional or national standards and/or regulations.
WARNING
REGULATORY NON-COMPLIANCE

Make sure all the equipment used and the systems comply with all the applicable local, regional and national regulations.
3.2 INFORMATION ON INSTALLATION AND THE ENVIRONMENT
Before carrying out any work on the equipment, read these instructions carefully, making sure you understand everything.
DANGER
RISK OF ELECTRIC SHOCK, EXPLOSION OR ELECTRIC ARC

  • Only use electrically insulated measuring devices and equipment.
  • Do not install the equipment while the power supply is connected.
  • Switch off all equipment, including connected devices, before installing or uninstalling the device.
  • Always use a correctly calibrated voltmeter to check the system is switched off.
  • Do not touch the unshielded components or the terminals while they are live.
  • Do not open, disassemble, repair or modify the product.
  • Do not expose the equipment to liquids or chemicals.
  • Before applying voltage to the equipment:
  • Make sure all protective elements, such as covers, hatches and grilles, are fitted and/or closed.
  • Check all wiring connections.

This device was designed to operate in non-hazardous environments, excluding applications that generate, or could potentially generate, hazardous atmospheres. Only install this device in areas and for applications which are reliably free from hazardous atmospheres.
DANGER
RISK OF EXPLOSION

  • Only install and use this device in sites that are not at risk.
  • Do not install or use this device in applications which are capable of generating hazardous atmospheres, such as applications that use flammable refrigerants.

WARNING
MALFUNCTIONING OF THE EQUIPMENT

  • Perform the wiring carefully, in compliance with electromagnetic compatibility and safety requirements.
  • Make sure the wiring is correct for the application.
  • Use shielded cables for all I/O signal and communication cables.
  • Minimise the length of the connections as much as possible and avoid winding the cables around electrically connected parts.
  • The signal cables (analogue and digital inputs, communication and corresponding power supplies), power cables and power supply cables for the device must be routed separately.
  • Before applying the power supply, check all the wiring connections.
  • Use the required safety interlocks where personnel and/or equipment hazards exist.
  • Install and operate this equipment in a cabinet appropriately rated for its intended environment and secured by a keyed or tooled locking mechanism.
  • Power line and output circuits must be wired and fused in compliance with local and national regulatory requirements for the rated current and voltage of the particular equipment.
  • Do not use this equipment in safety-critical machine functions.
  • Do not disassemble, repair or modify this equipment.
  • Do not connect wires to unused terminals and/or to terminals labelled “No connection “(N.C.)”.

3.3 DIMENSIONS

EVCO EV3 WEB Gateway Network 10 Devices - DIMENSIONS

3.4 INSTALLATION

EVCO EV3 WEB Gateway Network 10 Devices - INSTALLATION

3.4.1 Minimum distances

EVCO EV3 WEB Gateway Network 10 Devices - Minimum
distances

ELECTRICAL CONNECTIONS

4.1 WIRING BEST PRACTICES
The following information describes the wiring guidelines and best practices which should be observed when using the equipment described in this manual.
DANGER
RISK OF ELECTRIC SHOCK, EXPLOSION OR ELECTRIC ARC

  • Only use electrically insulated measuring devices and equipment.
  • Do not install the equipment while the power supply is connected.
  • Switch off all equipment, including connected devices, before installing or uninstalling the device.
  • Always use a correctly calibrated voltmeter to check the system is switched off.
  • Do not touch the unshielded components or the terminals while they are live.
  • Do not open, disassemble, repair or modify the product.
  • Do not expose the equipment to liquids or chemicals.
  • Before applying voltage to the equipment:
  • Make sure all protective elements, such as covers, hatches and grilles, are fitted and/or closed.
  • Check all wiring connections.

4.1.1 Wiring guidelines
When wiring the controllers, observe the following instructions:

  • The I/O and communication wiring must be kept separate from the power supply wiring. These two types of wiring must be routed in separate ducts.
  • Make sure the operating environment and conditions fall within the specified values.
  • Use wires with the correct diameter, suited to the voltage and current requirements.
  • Use copper conductors (compulsory).
  • Use shielded twisted pair cables for analogue/digital I/O connections.
    Use correctly earthed shielded cables for all analogue inputs or outputs and for communication connections. If shielded cables are not used for these connections, electromagnetic interference could cause the signal to deteriorate. Deteriorated signals can lead to unpredictable operation of the controller or modules and connected equipment.

WARNING
MALFUNCTIONING OF THE EQUIPMENT

  • Perform the wiring carefully, in compliance with electromagnetic compatibility and safety requirements.
  • Make sure the wiring is correct for the application.
  • Use shielded cables for all I/O signal and communication cables.
  • Minimise the length of the connections as much as possible and avoid winding the cables around electrically connected parts.
  • The signal cables (analogue and digital inputs, communication and corresponding power supplies), power cables and power supply cables for the device must be routed separately.
  • Before applying the power supply, check all the wiring connections.
  • Use the required safety interlocks where personnel and/or equipment hazards exist.
  • Install and operate this equipment in a cabinet appropriately rated for its intended environment and secured by a keyed or tooled locking mechanism.
  • Power line and output circuits must be wired and fused in compliance with local and national regulatory requirements for the rated current and voltage of the particular equipment.
  • Do not use this equipment in safety-critical machine functions.
  • Do not disassemble, repair or modify this equipment.
  • Do not connect wires to unused terminals and/or to terminals labelled “No connection (N.C.)”.

4.1.2 Fixed screw terminal blocks guidelines
Suitable wiring for power supply and I/O SELV
Step 5.08 mm (0.199 in.)

EVCO EV3 WEB Gateway Network 10 Devices - Minimum distances
1

4.1.3 Permitted lengths of wiring
NOTICE
INOPERABLE DEVICE

  • When connecting the probes, the digital inputs and the power supply, use cables with a maximum length of 10 m (32.80 ft).
  • When connecting the power supply of the controller and the relay outputs, use cables with a maximum length of 10 m (32.80 ft.).

4.2 WIRING DIAGRAM

EVCO EV3 WEB Gateway Network 10 Devices - WIRING
DIAGRAM

TERMINALS


4-6| Power supply input| USB| USB 2.0 input for communication
5-6| Relay output Out2 (AUX)| ETHERNET| RJ45 connector to connect to Ethernet serial port
8-10| Digital input ID1 (Door switch)| LED| LD1| Red| Flashes with messages from subnetwork
9-10| Digital input ID3 (Multifunction) (if P4 =0) Probe input Pb3 (if P4 ≠ 0)| LD2| Green| Stays on if connected to EPoCA
LD3| Red| Stays on with Ethernet link-up
11-10| Analogue input Pb1 (Temperature)| LD4| Green| Stays on with Ethernet activity
13-14-15| RS-485 serial input| LEDs off: No communication
LT| 1| ON = Termination resistor inserted|
2| Reserved

USER INTERFACE

5.1 INTERFACE

EVCO EV3 WEB Gateway Network 10 Devices - USER
INTERFACE

5.2 TOUCH KEYS
A description of the touch keys is given below:

Key…| Press and release to…|

Press for at least 3 seconds to…

---|---|---
| •  Scroll up through values
•  Move within a menu| —
| •  Scroll down through values
•  Move within a menu| Access the FNC functions menu (functions activated by key)
| —| Switch the device on/off (stand-by)
| •  Confirm values on the display
•  Set the setpoint| Enter the parameter menu

5.3 ICONS

Icon| ON| Flashing|

OFF

---|---|---|---


| Temperature displayed in °C| —| •  Over-heating ON
•  Over-cooling ON


| Temperature displayed in °F| —


| •  AUX function ON
•  AUX digital output ON| —|
| Compressor maintenance request| •  Parameters being changed
•  Access to FNC menu (functions activated by key)
•  Active connection with EVconnect| —


| Device off| —| Device on

5.4 CONTROLLER OPERATION
5.4.1 Switching the controller ON/OFF
With the function enabled (POF = 1), press the key for at least 3 seconds to switch the controller on/off.

EVCO EV3 WEB Gateway Network 10 Devices - CONTROLLER

5.4.2 Unlocking the keypad
After about one minute of inactivity, the device automatically locks the keypad (the code Loc appears for a few seconds).
To unlock the keypad, hold down any key for about 3 seconds until the code UnL appears to confirm the keypad has been unlocked.

EVCO EV3 WEB Gateway Network 10 Devices - keypad

5.4.3 Setting/changing the setpoint
With the keypad unlocked, touch and release the key to access the setpoint menu. Scroll the values with the or keys and touch to confirm the setpoint value.

EVCO EV3 WEB Gateway Network 10 Devices - . Accessing

5.4.4 Functions that can be activated by key
To choose the function, touch the key for at least 3 seconds to access the function menu; use the scroll through and choose the following functions:

  • RTC: sets/changes the clock;
  • Pb1: displays the temperature read by probe Pb1;

5.4.5 Activating the AUX digital output by key
With the keypad unlocked, touch and release the on. key to manually activate the AUX digital output. The AUX icon will come

EVCO EV3 WEB Gateway Network 10 Devices - . parameters

5.4.6 Accessing the parameters
With the keypad unlocked, touch the appear. Touch the key; then use the 1 key to enter the password, scrolling with the key for at least 3 seconds to access and change the parameters. The code PA will keys and confirming with the or keys to scroll the list of parameters.

EVCO EV3 WEB Gateway Network 10 Devices - . parameters
1

REGULATORS

6.1 FAN
EV3 Web manages a fan according to the Pb1 probe temperature and the SP setpoint.
The configuration parameters are:

Par.| Description| UM|

Range

---|---|---|---
SP| Temperature setpoint.| °C/°F| r1r2
r0| Setpoint differential.| °C/°F| 0.1…15.0
r1| Minimum value attributable to setpoint.| °C/°F| -30.0… r2
r2| Maximum value attributable to setpoint.| °C/°F| r1 …99.0

6.1.1 Operation

EVCO EV3 WEB Gateway Network 10 Devices - Operation

REMOTE COMMUNICATION CONFIGURATION

7.1 INTRODUCTION
EV3 Web can be configured to connect with EPoCA in two different ways:

In both cases, the devices must be visible on the local network. If the local network requires a static IP address, configure using the micro-B USB cable.
If used in a subnetwork, configure the BLE parameter for every device from 1 to 10 before searching on the network.
7.1.1 Configuration diagram when using a PC with direct connection via USB

EVCO EV3 WEB Gateway Network 10 Devices - USB

7.1.2 Configuration diagram when using a PC with connection via Ethernet

EVCO EV3 WEB Gateway Network 10 Devices - USB 1

7.1.3 Configuration diagram when using a smartphone and the EPoCA START app.

EVCO EV3 WEB Gateway Network 10 Devices - START app

7.2 FIRST CONFIGURATION
7.2.1 Configuration using a PC
Connecting using a micro-B USB cable

  1. Connect the micro-B USB cable from the PC to the device;
  2. Make sure EPoCA.exe has been installed in the PC and boot up EPoCA.exe;
  3. Set the Plant and Device data, save the configuration by pressing and continue by pressing EVCO EV3 WEB Gateway Network 10 Devices - PC 2N.B.: Save to continue with configuration by pressing .
    NOTICE
    WRONG OR FORGOTTEN ACCESS CREDENTIALS
    Keep your access credentials in a safe place.
    case of incorrect or lost login credentials, log in using a USB cable to skip the login procedure.
    Other commands:

Command

|

Description

---|---
Erase Config.| Cancels current configuration
Save Config.| Saves current configuration
Upload Plantfile| Uploads a previously saved plant file
Export Plantfile| Saves the plant file in a folder chosen by the user
4. Set the date, time and local time used and press Next ; 5. Set the name of the controllers connected via RS-485 to EV3 Web and pressEVCO EV3 WEB Gateway Network 10 Devices - controllersAutoaddress : if the devices are switched on one at a time, this key automatically configures the BLE parameter of the device being switched on.EVCO EV3 WEB Gateway Network 10 Devices - BLE parameterTo erase a device and its failed configuration, press Addr. X. A pop-up appears where you can choose to erase the recordings or the configuration of the device. **** 6. Set the type of IP address and press Next ; 7. Set the Modbus RTU and Modbus TCP communication parameters and press Next 8. press to complete configuration of the deviceEVCO EV3 WEB Gateway Network 10 Devices - device

Connecting using an Ethernet cable (with connection to modem)

  1. Make sure EPoCA.exe has been installed in the PC;

  2. Boot up EPoCA.exe, the programme scans the local network (LAN) which the PC is connected to to detect the devices;

  3. Select the device to configure and press Next ;

  4. Set the Plant and Device data, save the configuration by pressing Save Config. and continue by pressingEVCO EV3 WEB Gateway Network 10 Devices - Save ConfigN.B.: Save to continue with configuration.
    NOTICE
    WRONG OR FORGOTTEN ACCESS CREDENTIALS
    Keep your access credentials in a safe place.
    case of incorrect or lost login credentials, log in using a USB cable to skip the login procedure.

  5. Set the date, time and local time used and press Next ;

  6. Set the name of the controllers connected via RS-485 to EV3 Web and press Next EVCO EV3 WEB Gateway Network 10 Devices - Save Config 1Set the type of IP address and press ;

  7. Press Configure to complete configuration of the device.

  8. Set the Modbus RTU and Modbus TCP communication parameters and press .

  9. Press   to end the instrument configuration phase.

EVCO EV3 WEB Gateway Network 10 Devices -
configuration

  • Enable modbus-tcp: Enables/disables Modbus TCP communication.
  • Operation Mode: Establishes the operating mode of the Modbus TCP network:
  • Raw Bridge: operation for EVCO controllers without functions with RTC and not EPoCA compatible or for third-party controllers;
  • Cloud: operation for EPoCA compatible controllers.
  • Delay after booting: establishes the minimum time between the controller powering on and the start of communication.
  • Modbus RTU: Sets the Modbus RTU serial communication parameters:
  • Port: sets the Modbus RTU communication port number on which the device waits for connection requests
  • Baud rate: sets the Modbus RTU communication speed (in baud) with the controller;
  • Parity: sets the parity bit for data-bit error checking;
  • Stop bits: sets the number of stop bits of Modbus RTU communication with the controller;
  • Timeout: sets the maximum time allowed for the controller to respond to a request;
  • Idle time: sets the minimum time between receiving a response and the subsequent request.
  • Modbus TCP: Sets the Modbus TCP serial communication parameters:
  • Listening port: sets the Modbus TCP communication port number on which the device waits for connection requests;
  • Connection timeout: sets the idle time of Modbus TCP communication to terminate the connection;
  • Exception on timeout: sets whether to send an error code after the expiry of the Timeout.
    NOTE: Do not change value 502 TCP Port.
    NOTE: In case of use with EPoCA do not modify the displayed defaults.

7.2.2 Configuration using a smartphone or tablet
To configure EV3 Web using a smartphone or tablet follow these steps:

  1. Make sure the EPoCA START app has been downloaded to the smartphone or tablet (otherwise download it from:
    • Google Play Store for smartphone/tablet Android 5.0 or later);
    To download the EPoCA START app from the Google Play Store, scan the QR code in the image below; this takes you directly to the download page.EVCO EV3
WEB Gateway Network 10 Devices - Qr Code https://play.google.com/store/apps/details?id=it.evco.epoca

  2. Boot up EPoCA START;

  3. Touch Configure Devices;

  4. Select the device to configure;
    EVCO EV3 WEB Gateway Network 10 Devices - Configure
Devices

  5. Touch Configure, set the Plant data and touch .EVCO EV3 WEB Gateway Network 10 Devices - plant

  6. Insert the device data and touch NEXT; .

  7. Set the date, time and local time used and touch .EVCO EV3 WEB Gateway Network 10 Devices - plant 1

  8. Set the name of the controllers connected via RS-485 to EV3 Web and touch NEXT .

  9. Set the type of IP address of the network and touch .EVCO EV3 WEB Gateway Network 10 Devices - plant 2When selecting a Static type of IP it is necessary to set other information:

    • The IP address that you want to assign;
    • Subnet mask (Netmask);
    • The Gateway;
    • Preferred DNS (DNS 1):
    • Alternative DNS (DNS 2).EVCO EV3 WEB Gateway Network 10 Devices - plant 3If necessary, configure the settings of the Modbus TCP network
  • Operation Mode: Establishes the operating mode of the Modbus TCP network:
  • Raw Bridge: operation for EVCO controllers without functions with RTC and not EPoCA compatible or for third-party controllers;
  • Cloud: operation for EPoCA compatible controllers.
  • Boot Delay: establishes the minimum time between the controller powering on and the start of communication.
  • Modbus: Sets the Modbus RTU serial communication parameters:
  • Baud rate: sets the Modbus RTU communication speed (in baud) with the controller;
  • Parity: sets the parity bit for data-bit error checking;
  • Stop bits: sets the number of stop bits of Modbus RTU communication with the controller;
  • Timeout: sets the maximum time allowed for the controller to respond to a request;
  • Idle time: sets the minimum time between receiving a response and the subsequent request.
  • Modbus TCP: Sets the Modbus TCP serial communication parameters:
  • Connection timeout: sets the idle time of Modbus TCP communication to terminate the connection;
  • TCP port: sets the Modbus TCP communication port number on which the device waits for connection requests;
  • Exception on timeout: sets whether to send an error code after the expiry of the Timeout.

NOTE: Do not change the value 502 TCP Port.
NOTE: In case of use with EPoCA do not modify the displayed defaults.
Touch CONFIGURE to complete configuration of the device;
The next time the device is accessed, it will ask for the access credentials (Plant name, Password).

EVCO EV3 WEB Gateway Network 10 Devices - plant 5

REGULATION PARAMETERS

Description of columns in the Table of Parameters

  • Par.: List of configurable device parameters;

  • Description: Indicates parameter operation and any possible selections;

  • MU: Measurement unit relating to the parameter;

  • Range: Describes the interval of values that the parameter can assume. This can be correlated with other instrument parameters (indicated with the parameter code).
    NOTE: if the actual value is outside the permitted limits for that parameter (for example, because other parameters defining the aforementioned limits have been altered), the value of the violated limit is displayed instead of the actual value;

  • Default: Indicates the pre-set factory configuration;

  • PW: Indicates the access level for the parameter.

  • MODBUS address: Indicates the address of the MODBUS register containing the resource you want to access.

8.1 TABLE OF REGULATION PARAMETERS

Par.| Description| MU| Range|

Default

---|---|---|---|---

SETPOINT Group

SP| Temperature setpoint.| °C/°F| r1r2| 0,0

ANALOGUE INPUTS Group

CA1| Probe Pb1 offset.| °C/°F| -25.0…25.0| 0,0
P0| Type of probe. 0 = PTC; 1 = NTC.| —| 0/1| 1
P1| Enable decimal point in °C. 0 = No; 1 = Yes.| —| 0/1| 1
P2| Temperature measurement unit (if the value is changed, the temperature parameter limits
must be reset manually). 0 = °C; 1 = °F.| —| 0/1| 0

TEMPERATURE REGULATION Group

r0| Setpoint differential.| °C/°F| 0.1…15.0| 2,0
r1| Minimum setpoint.| °C/°F| -99.0… r2| -50,0
r2| Maximum setpoint.| °C/°F| r1 …199| 50,0

PASSWORD Group

POF| Enable stand-by key (ON/OFF). 0 = Disabled; 1 = Enabled.| —| 0/1| 1
PAS| Level 2 password to access parameters (installer).| —| -99… 999| -19
PA1| EVlink/EVconnect user password (not entered on device).| —| -99… 999| 426
PA2| EVlink/EVconnect service password (not entered on device).| —| -99… 999| 824

CLOCK Group

Hr0| Enable clock. 0 = Disabled; 1 = Enabled.| —| 0/1| 0

REMOTE COMMUNICATION Group

BLE| Reserved. Do not change.| —| —| 1
rE0| Recording interval.| min| 0…240| 15

MODBUS CONFIGURATION Group

LA| MODBUS protocol controller address.| —| 0…247| 247



Lb

| MODBUS transmission speed (baud rate).
0 = 2400;
1 = 4800;
2 = 9600;
3 = 19200.| baud| 0…3| 2

MODBUS TCP FUNCTIONS AND RESOURCES

9.1 INTRODUCTION
The Modbus TCP is a variant of Modbus and is based on the TCP that allows sending messages over an Intranet and the Internet.
The Modbus TCP uses binary data encoding and the TCP detection mechanism for transmission errors. It also uses the Master – Slave paradigm, in the Client – Server variant between devices connected to a TCP Ethernet network.
Four types of messages are used in this type of communication.

EVCO EV3 WEB Gateway Network 10 Devices - RESOURCES

The Modbus TCP message exchange service is used to exchange data in real time between two application devices, between application devices and other devices, between HMI (Human Machine Interface) or SCADA applications and devices, and between PCs and application devices that provide online services.
Only the client device identified as the master can initiate a transaction, building the message ADU, whose function code tells the server what action to take.

EVCO EV3 WEB Gateway Network 10 Devices - RESOURCES 1

For further information relating to the Modbus protocol, visit the official Modbus website: www.modbus.org.
9.2 MANAGING MODBUS CONNECTIONS OVER A TCP NETWORK
EV3 Web supports up to 5 concurrent Modbus client connections. If a new connection request is received and the number of connections is already at the limit, the connection is rejected.
9.3 MODBUS MESSAGE STRUCTURE
The Modbus protocol uses a 16-bit word. The Modbus message starts with a header. A Modbus message uses a Modbus unction code as the first byte.
A description of the structure of a modbus message header is given below.

Unique identifier| Type of protocol| Command length| Unit ID| Modbus message
---|---|---|---|---
2 bytes| 2 bytes| 2 bytes| 1 byte| N-bytes
Field associating a request with a response| The Modbus field value is always 0| The field value is the size of the rest of the message| This field is used to identify a remote server located on a non-TCP network (for serial connection)| The first byte is the Modbus function code

9.4 MODBUS FUNCTIONS AND REGISTERS
The Modbus registers for the device are organised around the four types of basic data reference indicated above, and this type of data is further identified by the first number of the address.
9.4.1 Available Modbus commands and data areas
The commands implemented are as follows:

Command|

Description

---|---
03 (hex 0x03)| Resource reading command
06 (hex 0x06)| Resource writing command
16 (hex 0x10)| Writing command for one or more registers

9.5 ADDRESS CONFIGURATION
Node address 0 is used exclusively for broadcast messages, recognized by all servers. To a broadcast message, the Server devices do not respond.
To work with Modbus TCP the BLE parameter must be 1. In this case the LA, Lb and BLE parameters must not be modified.
The address of a device within a Modbus message is set by the LA parameter.
Address 0 is only used for broadcast messages, recognised by all slaves. Slave devices do not respond to a broadcast message.
Unit address: this is the address of the node that allows communicating with the connected instrument or with other slaves.
Holding register number: modbus addresses of each instrument.
Modbus TCP default port: 502.
9.6 OPERATION
9.6.1 Stand-alone operation
To communicate solely with EV3 200 Web, set the Destination ID of the modbus message to 247 (value set by the BLE = 1 parameter).
NOTICE
NO COMMUNICATION
Do not change the default value of the BLE parameter.
9.6.2 Cloud + Modbus TCP
In this operating mode it is possible to use up to 10 devices (1 EV3 Web + 9 compatible EPocA devices)

EVCO EV3 WEB Gateway Network 10 Devices -TCP

Setup

  • Modbus TCP = 1;
  • Operation Mode = Cloud.

9.6.3 Modbus TCP only
In this operating mode it is possible to use up to 20 devices (1 EV3 Web + 19 compatible EPocA devices).

EVCO EV3 WEB Gateway Network 10 Devices -TCP only

Setup

  • Modbus TCP = 1;
  • Operation Mode = Raw Bridge.

9.7 MODBUS TABLES CONTENT
Table content description
The tables below contain the information required to access the resources properly and directly.
There are 2 tables:

  • Modbus parameter table, which contains all the configuration parameters for the device and the corresponding addresses
  • Modbus resource table, which contains all the status (I/O) and alarm resources in the device memory.

Description of columns in the Table of addresses

  • Par.: List of configurable device parameters;

  • Description: Indicates parameter operation and any possible selections;

  • UM: Measurement unit relating to the parameter;

  • Range: Describes the interval of values that the parameter can assume. This can be correlated with other instrument parameters (indicated with the parameter code).
    NOTE: If the actual value is outside the permitted limits for that parameter (for example, because other parameters defining the aforementioned limits have been altered), the value of the violated limit is displayed instead of the actual value;

  • Val. Adr.: Indicates the address of the Modbus register containing the resource you want to access;

  • Filter value: bit position of the data to be considered in the holding register. This information is always provided when the register contains more than one piece of information and it is necessary to distinguish which bits actually represent the data (the useful size of the data indicated in the DATA SIZE column should also be taken into account);
    NOTE: Some holding registers contain two separate fields: one contained in the MSB (most significant byte) and the other in the LESS.

  • R/W: Indicates the option of reading or writing the resource:

    • R : The resource is read-only;
    • W : The resource is write-only;
    • R/W : The resource can be both read and
    • CPL : When the fields indicates Y, the value read by the register needs to be converted because the value represents a number with a sign. In the other cases the value is always positive or zero.
    • DATA SIZE : Indicates the size in data bits:
    • WORD = 16 bits
    • Byte = 8 bits
    • The “ n ” bit = ..15 bit depending on the value of “n”.

9.8 EV3 WEB MODBUS ADDRESSES
9.8.1 Table of Modbus Parameters

Par.| Description| Val. Adr.| Filter value| R/W| DATA SIZE| CPL| Range|

MU

---|---|---|---|---|---|---|---|---
SETPOINT group
SP| Temperature setpoint.| 1538| —| RW| WORD| Y| r1r2| °C/°F

ANALOGUE INPUT group

CA1| Probe Pb1 offset.| 1539| —| RW| BYTES| Y| -25.0…25.0| °C/°F
P0| Probe type.| 1542| —| RW| BYTES| —| 0/1| —
P1| Enables decimal point in °C.| 1543| —| RW| BYTES| —| 0/1| —
P2| Temperature unit of measure (changing value means that the temperature parameter limits will need to be reset manually).| 1544| —| RW| BYTES| —| 0/1| —

TEMPERATURE MANAGEMENT group

r0| Setpoint differential.| 1550| —| RW| BYTES| —| 0.1…15.0| °C/°F
r1| Minimum setpoint.| 1551| —| RW| BYTES| Y| -99.0… r2| °C/°F

PASSWORD group

POF| Enable standby key (ON/OFF).| 1648| —| RW| BYTES| —| 0/1| —
PAS| Level 2 (Installer) parameters password.| 1649| —| RW| WORD| Y| -99… 999| —
PA1| EVlink/EVconnect user password (not via instrument).| 1650| —| RW| WORD| Y| -99… 999| —
PA2| EVlink/EVconnect password service (not via instrument).| 1651| —| RW| WORD| Y| -99… 999| —

CLOCK group

Hr0| Enable clock.| 1652| —| RW| BYTES| —| 0/1| —

REMOTE COMMUNICATION group

BLE| Reserved. Do not change.| 1653| —| RW| BYTES| —| —| —
rE0| Recording interval.| 1654| —| RW| BYTES| —| 0…240| min
rE1| Value to record.| 1655| —| RW| BYTES| —| 0…5| —

MODBUS CONFIGURATION group

LA| Modbus protocol controller address.| 1656| —| RW| BYTES| —| 0…247| —
Lb| Modbus transmission speed (baud rate).| 1657| —| RW| BYTES| —| 0…3| baud

9.8.2 Table of Modbus Resources

Code| Description| Val. Adr.| Filter value| R/W| DATA SIZE|

CPL

---|---|---|---|---|---|---
| Probe 1.| 514| —| R| WORD| Y
| AUX output.| 386| 3| R| 1 BIT| —
| Digital input ID3.| 258| 3| R| 1 BIT| —
| Device ON/OFF status.| 1282| —| RW| BYTES| —
| AUX status.| 1284| —| RW| 1 BIT| —
| Setpoint.| 1369| —| R| WORD| Y
| Service request.| 10439| 10| RW| 1 BIT| —
| Setpoint reached.| 10437| 11| RW| 1 BIT| —
| End of cooling.| 10437| 10| R| 1 BIT| —
| Real time clock. MonthYear.| 10321| —| RW| WORD| —
| Day of the week| 10322| —| RW| WORD| —
| Tenth of a second.| 10324| —| RW| WORD| —
| Minutes Hours.| 10323| —| RW| WORD| —
| Firmware identifier.| 65289| —| R| WORD| —
| Firmware revision.| 65290| 0…7| R| 8 BIT| —
| Firmware variations (MSB).| 65290| 8…15| R| 8 BIT| —
| Prog. Firmware.| 65291| —| R| WORD| —
| Serial number.| 65521 …
65524| —| R| WORD| —
iA| Digital input alarm ID3.| 770| 6| R| 1 BIT| —
Pr1| Temperature probe error.| 770| 0| R| 1 BIT| —
RTC| Clock alarm.| 770| 13| R| 1 BIT| —
Cth| Compressor thermal switch alarm.| 770| 12| R| 1 BIT| —

DIAGNOSTICS

The table below lists alarms with their corresponding solutions. To signal an alarm, the LED alarm lights up A and the buzzer sounds. Every alarm is recorded in the Alarm menu.
10.1 EV3 Web alarms table

Code Description Cause Effects Resolution
Prl Probe error •Probe not working

•Probe incorrectly connected
•Incorrect type of probe| •Code Prl displayed
•Alarm output ON
•Regulation suspended| •Check the type of probe (P0)
•Check probe wiring
•Change type of probe
rtc| Clock alarm| Clock (RTC) alarm not working| Clock-connected functions not present or not synchronised with the actual time| Set the right time.
If the error persists, replace the device (RTC battery dead)
iA| Multi-purpose input alarm| Digital input activated| •Code iA displayed
•No effect on regulation| Check for and remove the cause of the alarm on the digital input

This document and the solutions contained therein are the intellectual property of EVCO and thus protected by the Italian Intellectual Property Rights Code (CPI). EVCO forbids the reproduction and distribution, even in part, of the contents, unless express authorisation is obtained directly from EVCO.
The customer (manufacturer, installer or end user) assumes all responsibility for the configuration of the device.
EVCO accepts no liability for any possible errors in this document and reserves the right to make any changes at any time without prejudice to the essential functional and safety features of the equipment.

MADE IN ITALY
EVCO S.p.A.

Via Feltre 81, 32036 Sedico (BL) ITALY
Telephone: +39 0437 8422
Fax:+39 0437 83648
Email:info@evco.it
Web:www.evco.it

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

EVCO User Manuals

Related Manuals