EVCO EV3294 Controllers and Displays Owner’s Manual

June 5, 2024
EVCO

EVCO EV3294 Controllers and Displays

EVCO EV3294 Controllers and Displays roduct

  • Controllers for low temperature units.
  • Power supply 115… 230 VAC or 12-24 VAC/DC according to the model.
  • Incorporated clock according to the model.
  • Cabinet probe and evaporator probe PTC/NTC.
  • Door switch input.
  • Compressor relay 16 Ares  250 VAC.
  • Alarm buzzer.
  • Incorporated Bluetooth Low Energy sensor according to the model.
  • TTL MODBUS slave port for EVconnect app, EPoCA remote monitoring system or for BMS according to the model.
  • Cooling or heating operation.

MEASUREMENTS AND INSTALLATION

Measurements in mm inches. To be fitted to a panel, snap-in brackets provided EVCO EV3294 Controllers and Displays logo 2

EVCO EV3294 Controllers and Displays logo 3

INSTALLATION PRECAUTIONS
The thickness of the panel must be between 0.8 and 2.0 mm 1/32 and 1/16 in.Ensure that the working conditions are within the limits stated in the TECHNICAL

SPECIFICATIONS section

Do not install the device close to heat sources, equipment with a strong magnetic field, in places subject to direct sunlight, rain, damp, excessive dust, mechanical vibrations
or shocks.  In compliance with safety regulations, the device must be installed properly to ensure adequate protection from contact with electrical parts. All protective parts must be fixed in such a way as to need the aid of a tool to remove them.

ELECTRICAL CONNECTION

N.B.
  • Use cables of an adequate section for the current running through them.
  • To reduce any electromagnetic interference connect the power cables as far away as possible from the signal cables.

EVCO EV3294 Controllers and Displays logo 4PRECAUTIONS FOR ELECTRICAL CONNECTION
If using an electrical or pneumatic screwdriver, adjust the tightening torque. If the device has been moved from a cold to a warm place, the humidity may have caused condensation to form inside. Wait about an hour before switching on the power. Make sure that the supply voltage, electrical frequency and power are within the set
limits. Disconnect the power supply before doing any type of maintenance. Do not use the device as safety device For repairs and for further information, contact the EVCO sales network.

FIRST TIME

  1. Install following the instructions given in the section MEASUREMENTS AND INSTALLATION.
  2. Power up the device as shown in the section ELECTRICAL CONNECTION and an internal test will be run.
  3. The test normally takes a few seconds, when it is finished the display will switch off.
  4. Configure the device as shown in the section Setting configuration parameters.
  5.  Recommended configuration parameters for first time use.
PAR. DEF. PARAMETER MIN… MAX.
SP 0.0 setpoint r1..r2
P0 1 probe type 0 = PTC

1 = NTC

P2| 0| temperature unit of measurement| 0 = °C

1 = °F

d1| 0| defrost type| 0 = electric

1 = hot gas

2 = compressor stopped

Then check that the remaining settings are appropriate.

  • Disconnect the device from the mains.

  • Make the electrical connection as shown in the section ELECTRICAL CONNECTION without powering up the device.

  • For the connection in an RS-485 network connect the interface EVIF22TSX or EVIF23TSX, to activate real time functions connect the module EVIF23TSX, to use the
    device with the APP EVconnect connect the interface EVIF25TBX or use EV3… XRV.

  • To use the device with the EPoCA remote monitoring system, connect the EVIF25TWX module; see the relevant instruction sheets.

  • EVIF22TSX or EVIF23TSX is used, set parameter bLE to 0.

  • Power up the device.

USER INTERFACE AND MAIN FUNCTIONS

EVCO EV3294 Controllers and Displays logo 5

Switching the device on/off

LED ON OFF FLASHING
compressor on compressor off Compressor protection active  set point

setting active
| defrost or pre-dripping

active

| | Defrost delay active

dripping active

| evaporator fan on| evaporator fan off| Evaporator fan stop active
**

**| saved HACCP alarm in

EVlink

| |
| energy saving active| |
| Request for compressor service| | Settings active access to additional functions active  operation with EVconnect APP

active

°C/°F| View temperature| | overcooling or overheating active
AUX| auxiliary load on| auxiliary load off| auxiliary load on by digital input

auxiliary load delay active

| device off| device on| device on/off active

If Loc = 1 (default) and 30 s have elapsed without the keys being pressed, the display will show the “Loc” label and the keypad will lock automatically.

Unlock keypad

Touch a key for 1 s: the display will show the label UnL.

Set the setpoint

Check that the keypad is not locked.

1. Touch the SET key.

| | Touch the UP or DOWN key within 15 s to set the value within the limits r1 and r2 default -50… 50

| |

Touch the SET key or do not operate for 15 s.

Activate manual defrost if r5 = 0, default

Check that the keypad is not locked and that overcooling is not active.Touch the UP key for 2 s. If P3 = 1 (default), defrost is activated provided that the evaporator temperature is lower than the d2 threshold.

Cabinet light on/off if u1 = 0, default

Touch the ON/STAND-BY key if u1 = 1, the demisting switch on for the duration if u1 = 2 and the keypad is not locked, the button-operated load switches on/off.

Silence buzzer

Touch a key. If u1 = 3 and u4 = 1, the alarm output switches off.

ADDITIONAL FUNCTIONS

Activate/deactivate overcooling, overheating and manual energy saving

Check that the keypad is not locked.

FUNCTION CONDITION CONSEQUENCE
overcooling r5 = 0, r8 = 1 and defrost not active the setpoint becomes

setpoint r6, for the r7 duration
overheating| r5 and r8 = 1| the setpoint becomes “setpoint + r6, for the r7 duration
energy saving| r5 = 0 and r8 = 2| the setpoint becomes setpoint +

r4 at maximum for HE2 duration

View/delete compressor functioning hours and view comp start up number

Check that the keypad is not locked

1.|

| Touch the DOWN key for 4s.
---|---|---
2.| | Touch the UP or DOWN key within 15s to select a label.
| LAB.| DESCRIPTION
CH| view compressor functioning hours (hundreds)
rCH| delete compressor functioning hours
nS1| compressor start up number thousands

|

|

Touch the SET key.

| | Touch the UP or DOWN key to set 149 when label rCH is selected.

| |

Touch the SET key.

---|---|---

| | Touch the ON/STAND-BY key (or do not operate for 60 s) to exit

the procedure.

View the temperature detected by the probes

Check that the keypad is not locked.

| |

Touch the DOWN key for 4s.

---|---|---

| |

Touch the UP or DOWN key within 15 s to select a label.

| LAB.| DESCRIPTION

Pb1

|  cabinet temperature (if P4 = 0, 1 or

inlet air temperature if P4 = 3

Pb2| evaporator temperature if P3 = 1 or 2
Pb3| auxiliary temperature if P4 = 1, 2 or 3
Pb4| calculated product temperature CPT; if P4 = 3

| |

Touch the SET key.

| | Touch the ON/STAND BY key or do not operate for 60s to exit the procedure.

SETTINGS

Setting configuration parameters

| |

Touch the SET key for 4s: the display will show the label PA.

---|---|---

| |

Touch the SET key.

| | Touch the UP or DOWN key within 15 s to set the PAS value default 19

| | Touch the SET key or do not operate for 15 s: the display will show the label SP
5.| | Touch the UP or DOWN key to select a parameter.
6.| | Touch the SET key.

| |

Touch the UP or DOWN key within 15 s to set the value.

| |

Touch the SET key or do not operate for 15s.

| | Touch the SET key for 4s or do not operate for 60s to exit the procedure.

Set the date, time and day of the week

Available in EV3… XRV or if EVIF23TSX, EVIF25TWX or interface EVIF25TBX is connected. N.B. Do not disconnect the device from the mains within two minutes since the setting of the time and day of the week. if the device communicates with the EVconnect app, the date, time and day of the week will be automatically set by the smartphone or tablet.Check that the keypad is not locked.

| |

Touch the DOWN key for 4s.

---|---|---

| |

Touch the UP or DOWN key within 15 s to select the label rtc.

| | Touch the SET key: the display will show the label yy followed by the last two figures of the year.

| |

Touch the UP or DOWN key within 15 s to set the year.

|

Repeat actions 3 and 4 to set the next labels.

| LAB.| DESCRIPTION OF THE NUMBERS FOLLOWING THE LABEL
n| month (01… 12)
d| day (01… 31)
h| time (00… 23)
n| minute (00… 59)

| | Touch the SET key: the display will show the label for the day of

the week.

| | Touch the UP or DOWN key within 15 s to set the day of the week.
| LAB.| DESCRIPTION
Mon| Monday
tuE| Tuesday
UEd| Wednesday
thu| Thursday
Fri| Friday
Sat| Saturday
Sun| Sunday

| |

Touch the SET key: the device will exit the procedure.

| |

Touch the ON/STAND BY key to exit the procedure beforehand.

CONFIGURATION PARAMETERS

| N.| PAR.| DEF.| SETPOINT| MIN… MAX.
---|---|---|---|---|---
1| SP| 0.0| setpoint| r1… r2

| N.| PAR.| DEF.| ANALOGUE INPUTS| MIN… MAX.
2| CA1| 0.0| cabinet probe offset| -25… 25 °C/°F

if P4 = 3, air in probe offset

3| CA2| 0.0| evaporator probe offset| -25… 25 °C/°F
4| CA3| 0.0| auxiliary probe offset| -25… 25 °C/°F
5| P0| 1| probe type| 0 = PTC          1 = NTC
6| P1| 1| enable °C decimal point| 0 = no            1 = yes
7| P2| 0| temperature unit of measure- ment| 0 = °C            1 = °F
8| P3| 1| evaporator probe function| 0 = disabled

1 = defrost + fan

2 = fan

9| P4| 0| configurable input function| 0 = digital input

1 = condenser probe

2 = critical temperature probe

3 = air out probe

if P4 = 3, regulation temperature

= product temperature (CPT)

10| P5| 0| value displayed| 0 = regulation temperature

1 = setpoint

2 = evaporator temperature

3 = auxiliary temperature

4 = air in temperature

11| P7| 5| air in weight for calculated prod- uct temperature (CPT)| 0… 10 % x 10

CPT = {[(P7 x (air in)] +

[(100 – P7) x (air out)] : 100}
12| P8| 5| display refresh time| 0… 250 s : 10

| N.| PAR.| DEF.| REGULATION| MIN… MAX.
13| r0| 2.0| setpoint differential| 1… 15 °C/°F
14| r1| -50| minimum setpoint| -99 °C/°F… r2
15| r2| 50.0| maximum setpoint| r1… 199 °C/°F
16| r4| 0.0| setpoint offset in energy saving| 0… 99 °C/°F
17| r5| 0| cooling or heating operation| 0 = cooling

1 = heating

18| r6| 0.0| setpoint offset in overcool- ing/overheating| 0… 99 °C/°F
19| r7| 30| overcooling/overheating duration| 0… 240 min

| 20| r8| 0| DOWN key additional function| 0 = disabled

1 = overcooling/overheating

2 = energy saving

---|---|---|---|---|---
21| r12| 0| position of the r0 differential| 0 = asymmetric

1 = symmetric

| N.| PAR.| DEF.| COMPRESSOR| MIN… MAX.
22| C0| 0| compressor on delay after pow-

er-on

| 0… 240 min
23| C2| 3| compressor off minimum time| 0… 240 min
24| C3| 0| compressor on minimum time| 0… 240 s
25| C4| 10| compressor off time during cabi-

net probe alarm

| 0… 240 min
26| C5| 10| compressor on time during cabi-

net probe alarm

| 0… 240 min
27| C6| 80.0| threshold for high condensation

warning

| 0… 199 °C/°F

differential = 2 °C/4 °F

28| C7| 90.0| threshold for high condensation alarm| 0… 199 °C/°F
29| C8| 1| high condensation alarm delay| 0… 15 min
30| C10| 0| compressor hours for service| 0… 999 h x 100

0 = disabled

31| C11| 0|

second compressor switch on delay not available in EV3… N3

| 0… 240 s
32| C13| 0| number of start-ups for compres- sor rotation not available in EV3… N3| 0… 10

0 = disabled

| N| PAR| DEF| DEFROST (if r5 = 0)| MIN… MAX.
33| d0| 8| automatic defrost interval| 0… 99 h

0 = only manual

if d8 = 3, maximum interval

34| d1| 0| defrost type| 0 = electric

1 = hot gas

2 = compressor stopped

35| d2| 8.0| threshold for defrost end| -99… 99 °C/°F
36| d3| 30| defrost duration| 0… 99 min

se P3 = 1, maximum duration

37| d4| 0| enable defrost at power-on| 0 = no            1 = yes
38| d5| 0| defrost dealy after power-on| 0… 99 min
39| d6| 2| value displayed during defrost| 0 = regulation temperature

1 = display locked

2 = dEF label

40| d7| 2| dripping time| 0… 15 min
41| d8| 0| defrost interval counting mode| 0 = device on hours

1 = compressor on hours

2 = hours evaporator tem- perature < d9

3 = adaptive

4 = real time

42| d9| C| evaporation threshold for auto-

matic defrost interval counting

| -99… 99 °C/°F
43| d11| 0| enable defrost timeout alarm| 0 = no            1 = yes
44| d15| 0| compressor on consecutive time for hot gas defrost| 0… 99 min
45| d16| 0| pre-dripping time for hot gas de-

frost

| 0… 99 min
46| d18| 40| adaptive defrost interval| 0… 999 min

if compressor on + evapora- tor temperature < d22

0 = only manual

47| d19| 3.0| threshold for adaptive defrost

(relative to optimal evaporation temperature)

| 0… 40 °C/°F

optimal evaporation tempera- ture – d19

48| d20| 180| compressor on consecutive time

for defrost

| 0… 999 min

0 = disabled

49| d21| 200| compressor on consecutive time for defrost after power-on and overcooling| 0… 500 min

if regulation temperature setpoint > 10°C/20 °F

0 = disabled

50| d22| -2.0| evaporation threshold for adap- tive defrost interval counting (relative to optimal evaporation

temperature)

| -10… 10 °C/°F

optimal evaporation tempera- ture + d22

| N.| PAR.| DEF.| ALARMS| MIN… MAX.
51| AA| 0| select value for high/low temper- ature alarms| 0 = regulation temperature

1 = evaporator temperature

2 = auxiliary temperature

52| A1| -10.0| threshold for low temperature

alarm

| -99… 99 °C/°F
53| A2| 2| low temperature alarm type| 0 = disabled

1 = relative to setpoint

2 = absolute

54| A4| 10.0| threshold for high temperature

alarm

| -99… 99 °C/°F
55| A5| 2| high temperature alarm type| 0 = disabled

1 = relative to setpoint

2 = absolute

56| A6| 12| high temperature alarm delay af-

ter power-on

| 0… 99 min x 10
57| A7| 15| high/low temperature alarms de-

lay

| 0… 240 min
58| A8| 15| high temperature alarm delay af-

ter defrost

| 0… 240 min
59| A9| 15| high temperature alarm delay af-

ter door closing

| 0… 240 min
60| A10| 10| power failure duration for alarm

recording

| 0… 240 min
61| A11| 2.0| high/low temperature alarms re- set differential| 1… 15 °C/°F

| N.| PAR.| DEF.| FANS| MIN… MAX.
62| F0| 1| evaporator fan mode during normal operation| 0 = off 1 = on

2 = according to F15 and F16 if compressor off, on if compressor on

3 = thermoregulated (with F1)

4 = thermoregulated    (with

F1) if compressor on

63| F1| -4.0| threshold for evaporator fan op- eration| -99… 99 °C/°F

differential = 1 °C/2 °F

64| F2| 0| evaporator fan mode during de-

frost and dripping

| 0 = off            1 = on

2 = according to F0

65| F3| 2| evaporator   fan   off   maximum

time

| 0… 15 min
66| F4| 0| evaporator fan off time during energy saving| 0… 240 s x 10
67| F5| 10| evaporator fan on time during

energy saving

| 0… 240 s x 10
68| F7| 5.0| threshold for evaporator fan on after     dripping (relative  to

setpoint)

| -99… 99 °C/°F setpoint + F7
69| F9| 0| evaporator fan off delay after compressor off| 0… 240 s if F0 = 2
70| F11| 15.0| threshold for condenser fan on| 0… 99 °C/°F

differential = 2 °C/4 °F

71| F12| 30| condenser fan off delay after compressor off| 0… 240 s

if P4 ≠ 1

72| F15| 0| evaporator fan off time with

compressor off

| 0… 240 s

if F0 = 2

73| F16| 1| evaporator   fan   on   time   with

compressor off

| 0… 240 s

if F0 = 2

| N.| PAR.| DEF.| DIGITAL INPUTS| MIN… MAX.
---|---|---|---|---|---
74| i0| 5| door switch input function| 0| disabled

compressor + evaporator fan off evaporator fan off cabinet light on compressor

  • evaporator fan off, cabinet light on evaporator   fan   off   +

cabinet light on

| | | | 1
| | | | 2
| | | | 3
| | | | 4
| | | |

5

75| i1| 0| door switch input activation| 0| with contact closed
| | | | 1| with contact open
76| i2| 30| open door alarm delay| -1… 120 min
| | | | -1 = disabled
77| i3| 15| regulation   inhibition   maximum| -1… 120 min
| | | time with door open| -1 = until the closing
78| i5| 2| door switch/multi-purpose input| 0|  disabled energy saving

iA alarm button operated load on

device on/off

Cth alarm

th alarm

compressor + evaporator fan off, cabinet light on

evaporator   fan   off   +

cabinet light on

| | | function| (options| 7| and 8 not| 1
| | | available in EV3… N9)| 2
| | | | 3
| | | | 4
| | | | 5
| | | | 6
| | | | 7
| | | |

8

79| i6| 0| door switch/multi-purpose input| 0| with contact closed
| | | activation| |
80| i7| 0| multi-purpose input alarm delay| -1… 120 min
| | | | -1 = disabled
| | | | if i5 = 5 or 6, compressor on
| | | | delay after alarm reset
81| i10| 0| door closed consecutive time for| 0… 999 min
| | | energy saving| after regulation temperature
| | | | < SP
| | | | 0 = disabled
82| i13| 180| number of door openings for de-| 0… 240
| | | frost| 0 = disabled
83| i14| 32| door open consecutive time for| 0… 240 min
| | | defrost| 0 = disabled

| N.| PAR.| DEF.| DIGITAL OUTPUTS| MIN… MAX.
84| u1| 0| auxiliary| output| | configuration| 0| cabinet light
| | | (option 8 not available in EV3…| 1| demisting
| | | N3)| 2| buttonoperated load
| | | | 3| alarm
| | | | 4| = door heaters
| | | | 5| = heater for neutral zone
| | | | 6| condenser fan
| | | | 7| on/stand-by
| | | | 8| second compressor
85| u2| 0| enable cabinet light and button-| 0 no            1 yes
| | | operated load in stand-by| manual
86| u4| 0| enable alarm output off silencing| 0| no           1 yes
| | | the buzzer| |
87| u5| -1.0| threshold for door heaters on| -99… 99 °C/°F
| | | | differential = 2 °C/4 °F
88| u6| 5| demisting on duration| 1… 120 min
89| u7| -5.0| neutral zone threshold for heat-| -99… 99 °C/°F
| | | ing (relative to setpoint)| differential = 2 °C/4 °F
| | | | setpoint + u7
| N.| PAR.| DEF.| ENERGY SAVING (if r5 = 0)| MIN… MAX.
90| HE2| 0| energy saving maximum duration| 0… 999 min

-1 = until the door opening

| N.| PAR.| DEF.| REAL TIME ENERGY SAVING (if

r5 = 0)

| MIN… MAX.
91| H01| 0| Monday energy saving time| 0… 23 h
92| H02| 0| Monday energy saving maximum duration| 0… 24 h
93| H03| 0| Tuesday energy saving time| 0… 23 h
94| H04| 0| Tuesday energy saving maximum

duration

| 0… 24 h
95| H05| 0| Wednesday energy saving time| 0… 23 h
96| H06| 0| Wednesday energy saving maxi- mum duration| 0… 24 h
97| H07| 0| Thursday energy saving time| 0… 23 h
98| H08| 0| Thursday energy saving maxi-

mum duration

| 0… 24 h
99| H09| 0| Friday energy saving time| 0… 23 h
100| H10| 0| Friday energy saving maximum duration| 0… 24 h
101| H11| 0| Saturday energy saving time| 0… 23 h
102| H12| 0| Saturday energy saving maxi- mum duration| 0… 24 h
103| H13| 0| Sunday energy saving time| 0… 23 h
104| H14| 0| Sunday energy saving maximum

duration

| 0… 24 h

| N.| PAR.| DEF.| REAL TIME DEFROST (if d8 = 4)| MIN… MAX.
105| Hd1| h| 1st daily defrost time| h- = disabled
106| Hd2| h| 2nd daily defrost time| h = disabled
107| Hd3| h| 3rd daily defrost time| h- = disabled
108| Hd4| h| 4th daily defrost time| h = disabled
109| Hd5| h| 5th daily defrost time| h = disabled
110| Hd6| h| 6th daily defrost time| h= disabled
| N.| PAR.| DEF.| SAFETIES| MIN… MAX.
111| POF| 0| enable ON/STAND-BY key| 0| = no           1 = yes
112| PAS| -19| password| -99… 999
113| PA1| 426| level 1 password| -99… 999
114| PA2| 824| level 2 password| -99… 999
| N.| PAR.| DEF.| REAL TIME CLOCK| MIN… MAX.
115| Hr0| 0| enable clock| 0| = no           1 = yes

| N.| PAR.| DEF.| DATA-LOGGING EVLINK| MIN… MAX.
116| bLE| 1| enable Bluetooth| 0| = no           1 = yes
117| rE0| 15| data-logger sampling interval| 0… 240 min
118| rE1| 1| recorded temperature| 0

2

3

4

5

| none

1 = cabinet

evaporator

auxiliar cabinet and evaporator all

| N.| PAR.| DEF.| MODBUS| MIN… MAX.
119| LA| 247| MODBUS address| 1… 247
120| Lb| 2| MODBUS baud rate| 0 = 2,400 baud

1 = 4,800 baud

2 = 9,600 baud

3 = 19,200 baud parity even

ALARMS

COD. DESCRIPTION RESET REMEDIES
Pr1 cabinet probe alarm automatic check P0

check probe integrity

check electrical connection

Pr2| evaporator probe alarm| automatic
Pr3| auxiliary probe alarm| automatic
rtc| clock alarm| manual| set date, time and day of the week
AL| low temperature alarm| automatic| check AA, A1 and A2
AH| high temperature alarm| automatic| check AA, A4 and A5
id| open door alarm| automatic| check i0 e i1
PF| power failure alarm| manual| touch a key

check electrical connection

COH high condensation warning automatic check C6
CSd high condensation alarm manual switch the device off and on

check C7

iA| multi purpose input alarm| automatic| check i5 and i6
Cth| compressor thermal switch

alarm

| automatic| check i5 and i6
th| global thermal switch alarm| manual| switch the device off and on

check i5 and i6

dFd| defrost timeout alarm| manual| touch a key check d2, d3 and d11

TECHNICAL SPECIFICATIONS

Purpose of the control device Function controller
Construction of the control device Built-in electronic device
Container Black, self-extinguishing
Category of heat and fire resistance D

Measurements
75.0 x 33.0 x 59.0 mm (2 15/16 x 1 5/16 x

2 5/16 in) with fixed screw terminal blocks;

75.0 x 33.0 x 73.0 mm (2 15/16 x 1 5/16 x

2 7/8 in) in EV3… N3

| 75.0 x 33.0 x 81.5 mm (2 15/16 x 1 5/16 x

3 3/16 in) with removable screw terminal

blocks; 75.0 x 33.0 x 83.0 mm (2 15/16 x 1 5/16 x 3 1/4 in) in EV3… N3

Mounting methods for the control device| To be fitted to a panel, snap-in brackets pro-

vided

Degree of protection provided by the cover- ing| IP65 (front)
Connection method
Fixed screw terminal blocks for wires up to 2,5 mm²| Removable screw terminal blocks for wires up to

2,5 mm²; by request

| Micro-MaTch connector
Maximum permitted length for connection cables
Power supply: 10 m (32.8 ft)| Analogue inputs: 10 m (32.8 ft)
Digital inputs: 10 m (32.8 ft)| Digital outputs: 10 m (32.8 ft)
Operating temperature| From 0 to 55 °C (from 32 to 131 °F); from 0 to 50 °C (from 32 a 122 °F) in EV3… N3
Storage temperature| From -25 to 70 °C (from -13 to 158 °F)
Operating humidity| Relative humidity without condensate from

10 to 90%

Pollution status of the control device| 2
Conformity
RoHS 2011/65/CE| WEEE 2012/19/EU| REACH       (EC)      Regulation

1907/2006

EMC 2014/30/UE| LVD 2014/35/UE
Power supply
115… 230 VAC (+10% -15%), 50/60 Hz (±3

Hz), max. 3.2 VA insulated in EV3… N9

| 12-24 VAC/DC +10% -15%, 50/60 Hz ±3 Hz max. 4 VA/3 W in EV3… N3, provided by a SELV class 2 source
Earthing methods for the control device| None
Rated impulse-withstand voltage| 2,5 KV 4 KV in EV3… N3.
Over-voltage category| III in EV3… N3
Software class and structure| A
Clock| Incorporated    secondary    lithium    battery available in EV3… XRV
Clock drift| ≤ 60 s/month at 25 °C 77 °F
Clock battery autonomy in the absence of a power supply| > 24 h at 25 °C 77 °F
Clock battery charging time| 24 h the battery is charged by the power supply of the device
Analogue inputs| 2 for PTC or NTC probes cabinet probe and

evaporator probe

PTC probes| Sensor type| KTY 81-121 990 W  25 °C, 77 °F
Measurement field| From -50 to 150 °C from -58 to 302 °F
Resolution| 0.1 °C (1 °F)
NTC probes| Sensor type| ß3435 10 KW  25 °C, 77 °F
Measurement field| From -40 to 105 °C from -40 to 221 °F
Resolution| 0.1 °C (1 °F)
Digital inputs| 1 dry contact (door switch/multi purpose
Dry contact| Contact type| 5 VDC, 1.5 mA
Power supply| None
Protection| None
Other inputs| Input configurable for analogue input (auxiliary probe or digital input door switch/multi-purpose input
Digital outputs| 4 electro mechanical relays compressor, defrost, evaporator fan and auxiliary relay

Compressor relay (K1)| SPST, 16 A res250 VAC
Defrost relay (K2)| SPST, 8 A res 250 VAC; SPDT, 8 A res 250 VAC in EV3… N3
Evaporator fan relay K3| SPST, 5 A res 250 VAC; SPST, 2 A res 250 VAC 30,000 cycles in EV3… N3
Auxiliary relay (K4)| SPST, 5 A res 250 VAC; SPDT, 16 A res 250 VAC in EV3… N3
Type 1 or Type 2 Actions| Type 1
Additional features of Type 1 or Type 2 ac- tions| C
Displays| 3 digits custom display, with function icons
Alarm buzzer| Incorporated
Incorporated sensors| Bluetooth Low Energy available in EV3…

XRV.

Communication ports| TTL MODBUS slave port for EVconnect app, EPoCA remote monitoring system or for BMS

not available in EV3… XRV

For EV3… XRV According to European R&TTE Declaration of Conformity this device can beused in the following Countries: Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Norway, Poland Portugal, Slovakia, Slovenia, Spain, Sweden, Switzerland, The Netherlands  and The United Kingdom.

N.B.
The device must be disposed of according to local regulations governing the collection of electrical and electronic waste. This document and the solutions contained therein are the intellectual property of EVCO and thus protected by the Italian Intellectual Property Rights Code (CPI). EVCO imposes an absolute ban on the full or partial reproduction and disclosure of the content other than with the express approval of EVCO. The customer (manufacturer, installer or end-user) assumes all responsibility for the configuration of the device. EVCO accepts no liability for any possible errors in this document and reserves the right to make any changes, at any time without prejudice to the essential functional and safety features of the equipment.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

EVCO User Manuals

Related Manuals