EVCO EVIF22TSX Advanced Controller Instruction Manual
- June 6, 2024
- EVCO
Table of Contents
Multi-functional modules
(clock and/or non-optoisolated TTL/RS-485 serial interface)
EVIF22TSX & EVIF23TSX
– clock (not available for EVIF22TSX)
– TTL MODBUS port (input)
– RS-485 MODBUS port (output).
MEASUREMENTS AND INSTALLATION
Measurements in mm (inches); to be fitted on a rigid support, with a cable tie (not provided
INSTALLATION PRECAUTIONS
– Ensure that the working conditions are within the limits stated in the
TECHNICAL SPECIFICATIONS section
– Do not install the device close to heat sources, equipment with a strong
magnetic field, in places subject to direct sunlight, rain, dampness,
excessive dust, mechanical vibrations or shocks
– In compliance with safety regulations, the device must be installed properly
to ensure adequate protection from contact with electrical parts. All
protective parts must be fixed in such a way as to need the aid of a tool to
remove them.
ELECTRICAL CONNECTION
| N.B.
– Use cables of an adequate section for the current running through them
– To reduce any electromagnetic interference connect the power cables as far
away as possible from the signal cables and, if necessary, connect to an
RS-485 MODBUS network by using a twisted pair.
---|---
Example of electrical connection to a controller belonging to the EV3 series.
| LED | ON | OFF | BLINKING |
|---|---|---|---|
| TTL MODBUS | – | no TTL MODBUS activity | TTL MODBUS activity |
| RS-485 MODBUS | – device power up | ||
| – waiting RS-485MODBUS data | no RS-485 MODBUS activity | RS-485 MODBUS activity |
Fitting the termination resistor of RS-485 MODBUS network
To fit the RS-485 MODBUS network termination resistor, place the micro-switch in position ON.
PRECAUTIONS FOR ELECTRICAL CONNECTION
– If using an electrical or pneumatic screwdriver, adjust the tightening
torque
– If the device has been moved from a cold to a warm place, the humidity may
have caused condensation to form inside. Wait about an hour before connecting
it to the controller
– Disconnect the device from the controller before doing any type of
maintenance
– For repairs and for further information, contact the EVCO sales network.
FIRST-TIME USE
-
Install following the instructions given in the section MEASUREMENTS AND INSTALLATION.
-
Disconnect the device from the mains; see the relative instruction sheet.
-
Connect the TTL MODBUS port of the device to the TTL MODBUS port of the controller as shown in the section ELECTRICAL CONNECTION.
-
Connect the RS-485 MODBUS port of the device to the RS-485 MODBUS network as shown in the section ELECTRICAL CONNECTION.
-
Power up the controller and an internal test of the device will be run.
The test normally takes a few seconds, when it is finished the LED of the device will switch off. -
If EVIF23TSX is used, the controller shows the label “rtc” flashing: set the date and time of the controller.
Do not disconnect the device from the mains in the two minutes following the setting of the date and time.
TECHNICAL SPECIFICATIONS
| Container: | Black, self-extinguishing. |
|---|---|
| Category of heat and fire resistance: | D. |
| Measurements: | 176.0 x 30.0 x 25.0 mm (6 15/16 x 1 3/16 x1 in). |
| Mounting methods for the control device: | on a rigid support, with a cable tie |
(in dotazione).
Degree of protection provided by the covering:| IP00.
Connection method:
Pico-Blade connector| Fixed screw terminal block for wires up to 2.5 mm².
The maximum permitted length for connection cables:| RS-485 MODBUS port: 1,000
m (328 ft).
Operating temperature:| From 0 to 55 °C (from 32 to 131 °F).
Storage temperature:| From -25 to 70 °C (from -13 to 158 °F).
Operating humidity:| Relative humidity without condensate from 5 to 95%.
Compliance:
RoHS 2011/65/CE| WEEE 2012/19/EU
REACH (EC) Regulation no. 1907/2006| EMC 2014/30/UE.
Power supply:| the device is powered by the TTL MODBUS port of the controller.
Software class and structure:| A.
Clock| secondary lithium battery (not available in EVIF22TSX).
Clock drift:| ≤ 60s/month at 25°C (77 °F).
Clock battery autonomy in the absence of a power supply:| > 6 months at 25 °C
(77 °F).
Clock battery charging time:| 24h (the battery is charged by the power supply
of the device).
Visualizzazioni:| TTL MODBUS and RS-485 MODBUS communication status LED.
Communications ports:
1 TTL MODBUS slave port| 1 RS-485 MODBUS slave port.
Read User Manual Online (PDF format)