St ubli MA429 Switch Cabinet
Product Information
- Product Name: Coffret de coupure CCGE400
- Order Number: 19.6075
- Manufacturer: Staubli
- Manufacturer Address: Stockbrunnenrain 8, 4123 Allschwil, Switzerland
- Contact:
- Tel: +41 61 306 55 55,
- Fax: +41 61 306 55 56,
- Email: ecch@staubli.com
Product Usage Instructions
Safety Instructions
- The products may be assembled and installed by electrically skilled or instructed persons duly observing all applicable safety regulations.
- Protection against electric shock shall be checked in the end-use applications too.
- Each time the connector is used, it should previously be inspected for external defects (particularly the insulation). If there are any safety concerns, an electrically skilled person must be consulted or the connector must be replaced.
Article Supplied
- Cleaning Tool (Can be ordered separately: Order No 195524)
- Triangular key for the cabinet locks
Connecting the Box
Refer to illustration 4 for connecting the box.
Power On
Refer to illustrations 5-7 for powering on the device.
Phase Control VAT
Refer to illustration 8 for phase control VAT.
Palletising and Rackable Function
Refer to illustrations 9-11 for palletising and rackable function.
Operating Instructions
Refer to illustrations 12-13 for operating instructions.
Maintenance Instructions
Before each connection, a visual inspection is needed to ensure there are
no external defects or tools that could damage the product’s contact surfaces.
Safety instructions
- Use only the components and tools specified by Stäubli. In case of self-assembly, do not deviate from the preparation and assembly instructions as stated herein, otherwise Stäubli cannot give any guarantee as to safety or conformity with the technical data. Do not modify the product in any way.
- Connectors not originally manufactured by Stäubli which can be mated with Stäubli elements and in some cases are even described as ”Stäubli-compatible” by certain manufacturers do not conform to the requirements for safe electrical connection with long-term stability, and for safety reasons must not be plugged together with Stäubli elements. Stäubli therefore does not accept any liability for any damages resulting from mating such connectors (i.e. lacking Stäubli approval) with Stäubli elements.
- Stäubli Electrical Connectors (Stäubli) does not accept any liability in the event of failure to observe these warnings.
Installation, electrotechnical expertise
The products may be assembled and installed by electrically skilled or
instructed persons duly observing all applicable safety regulations.
Caution, risk of electric shock
- Work in a de-energized state.
- Follow the five safety rules, when working on electrical installations.
- After the respective electrical installations have been identified, the following five essential requirements shall be undertaken in the specified order unless there are essential reasons for doing otherwise:
- disconnect completely;
- secure against re-connection;
- verify absence of operating voltage;
- carry out grounding and short-circuiting;
- provide protection against adjacent live parts.
- Any person engaged in this work activity shall be electrically skilled or instructed, or shall be supervised by such a person. Source: EN 50110-1:2013
- Protection against electric shock shall be checked in the end-use applications too.
Do not disconnect under load
Connecting and disconnecting when live is permitted.
Caution
- Each time the connector is used, it should previously be inspected for external defects (particularly the insulation). If there are any safety concerns, an electrically skilled person must be consulted or the connector must be replaced.
- The plug connectors are watertight in accordance with the product specific IP protection class.
Useful hint or tip
For further technical data please see the product catalog
Article supplied
Tools supplied
- (ill. 1)
- CLC spanner with torque limiter set at 18 N m.
- Can be order separately: Order N° 19.5509
- (ill. 2)
- Cleaning Tool.
- Can be order separately: Order No. 19.5524
- (ill. 3)
Triangular key for the cabinet locks.
Connecting the box
Power on
-
(ill. 5)
Circuit position “Open”. -
(ill. 6)
Disconnector locking function with padlock (Ø 5 mm). -
(ill. 7)
Circuit position “closed”.
Phase control VAT
(ill. 8)
Ø 4 mm socket connection.
Palletising
(ill. 9)
The trolley can be secured (on a pallet, for example) using 4 Ø 8 mm screws
(not supplied by Staubli).
Rackable function
-
(ill. 10)
Vertical storage of cabinets.
Attention:
Stack maximum 2 cabinets -
(ill. 11)
Secure with a strap (not supplied by Staubli).
Operating instructions
-
(ill. 12)
While keeping the CV on its lower part, insert the male Isolated CV spanner equipped with its torque limiter.
Order No. : 19.5509
Attention:
If the torque wrench trips before making at least 8 turns, unscrew the connector and check the condition of the threads and tapping. -
(ill.13)
- Insert the CV into the socket by pushing on the protective flaps.
- While pushing, screw on the connector with the Allen key, taking care not to screw in crookedly.
- Screw until the connector holds itself.
- From this position, tighten to a torque of 18 N m with the torque spanner, to ensure contact quality.
- After correctly tightening the connector, check that it can rotate freely
Maintenance instructions
Before each connection a visual inspection is needed.
Cleaning (power off!):
- Cleaning of the contacts is necessary on the contact faces.
- For this purpose, we recommend the cleaning tool, order No. 19.5524. You can also use:
- Compressed air or hoover to remove dust, dirt, etc.
- Spraying an alcohol-based solvent to dilute impurities.
- Wipe with a clean cloth.
- For cleaning, do not use aggressive tools (wire brushes, rigid tools) which could damage the surface treatment present on the contact surfaces. This would considerably harm the electrical performance of the product.
- Don’t grease! Dirt particles might agglomerate and obstruct the M12 screw system.
- In case of special use, ask the advice of Stäubli technical service.