SIEMENS PXG3.L BACnet Router Instruction Manual
- June 13, 2024
- SIEMENS
Table of Contents
SIEMENS PXG3.L BACnet Router
BACnet router for
- BACnet/IP
- BACnet/LonTalk
- BACnet MS/TP
- Routing between BACnet/IP , BACnet/LonTalk (PXG3.L only), and BACnet MS/TP
- Supports BACnet/IPv4 and BACnet/IPv6
- BACnet standard compliant
- ISO 16484-5 compliant
- BTL label (BACnet communications passed the BTL test)
- BBMD support (BACnet Broadcast Management Device)
- Third-party device support
- Configuration via Xworks Plus or Web browser (via IPv4)
- Web browser access to network statistics
- Firmware update via Ethernet and USB Device
- LED indication for Ethernet link and activity
- LED indication for BACnet/LonTalk and BACnet MS/TP (diagnostics)
- 2-port Ethernet switch for low-cost cabling (10/100 baseT)
- BACnet MS/TP (RS-485) baud rates: 9600, 19200, 38400, 76800, 115200
- Plug-in screw terminal blocks for supply, LONWORKS, and MS/TP
- RJ45 plug for PXM20 (LONWORKS)
- Operating voltage: AC 24 V or DC 24 V
- DIN rail mounting
- BACnet MS/TP Slave Proxy
- SNMP (v2), MIB-2
- BACnet NAT
Use
The PXG3… BACnet router connects a BACnet/IP network to a BACnet/LonTalk network (PXG3.L only), and/or a BACnet MS/TP channel. BACnet objects are transmitted simultaneously throughout any and all networks.
Router functions
Four-way routing| The PXG3… BACnet router transmits BACnet protocol between a
BACnet/IPv4 network, a BACnet/IPv6 network, a BACnet/LonTalk network (PXG3.L
only), and a BACnet MS/TP channel. BACnet objects are simultaneously
transmitted throughout any and all networks.
---|---
BBMD| Broadcast Management Device, used to distribute BACnet Broadcast
messages across IP Routers.
Web server| The BACnet router includes a Device Object and can be operated by
a BACnet Client. Present operating state, date and time as well as statistics
on sent packages can be viewed via web server.
MS/TP Slave Proxy| The BACnet router can serve as a Slave Proxy for slaves
that are connected to its MSTP port. In other words, it responds to Who-Is
messages on the slaves’ behalf by sending an I-Am message.
SNMP v2| Simple Network Management protocol MIB-2, for monitoring and
diagnosing the BACnet router network interface.
BACnet NAT| Supports setup of a BACnet network over a NAT device.
Additionally, remote access from a public network to BACnet devices is
possible on a private network. Important: the public IP address must be
static. For security reasons we recommend using VPN tunneling with BACnet NAT.
BACnet/IP to BACnet/IP| When routing between BACnet/IP and BACnet/IP on one IP
network, the BACnet router address must be the same on both BACnet networks.
The difference is that different BACnet UDP ports are used on the BACnet
network.
Communication
- The router complies with BACnet standard and ISO 16484-5.
- A 2-port Ethernet switch allows low-cost cabling via line topology. This is the preferred commissioning medium.
- The LONWORKS network is connected via a 2-pin connection terminal.
- The MS/TP channel is connected via RS485 or a 3-pin connection terminal.
- An RJ45 plug on the device front allows connecting to a PXM20 operator unit (PXG3.L only).
- A USB port is available for connecting the tool.
Type summary
Type (ASN)
| Product number (SSN)| Name| Ethernet ports| LONWORKS|
MS/TP
---|---|---|---|---|---
PXG3.L
| S55842-Z105-A100| BACnet Router Ethernet/IPLonTalk-MS/TP| 2| x|
x
PXG3.M
| S55842-Z106-A101| BACnet Router Ethernet/IP-MS/TP| 2| |
x
Mechanical design
- Plastic housing
- Plug-in terminal block (operating voltage)
- 2-port Ethernet switch (with 2 LEDs each for display purposes)
- LEDs for device and system status indication
- RJ45 interface for PXM20 (PXG3.L only)
- Tool interface (USB Device)
- Service button for identification on network (Ethernet, LONWORKS)
- LONWORKS terminal block (PXG3.L only)
- MS/TP terminal block
- Slider for mounting on DIN rail
LEDs
LED | Color | Activity | Function |
---|---|---|---|
RUN | Green |
- Continuously ON
- Continuously OFF
- Flashing
|
- Device ready.
- At least one internal power supply out of range.
- Start-up of device.
FLT| Red|
- Continuously OFF
- Continuously ON
- Flashing
|
- OK
- HW fault or program fault.
- Incorrect or corrupt FW.
INF| —| —| (Not used)
COM1| Yellow|
- Flashing
|
- Sends MS/TP packages.
COM2| Yellow|
- Flashing
|
- Sends LONWORKS packages (PXG3.L only).
SVC| Red|
- Continuously OFF
- Continuously ON
- Flashing
- Flashing per wink command *)
|
- Configured.
- Defective Hardware.
- Unconfigured.
- Physical identification of the router.
Ethernet 1 / 2| Green|
- Continuously ON
- Continuously OFF
- Flashing
|
- Link active
- Link inactive
- Network activity
Yellow|
- Continuously ON
- Continuously OFF
|
- Link 100 Mbps
- Link 10 Mbps
*) Wink command pattern:
Service button
Button | Press | Description |
---|---|---|
1 | Short | Physical identification on the network (Ethernet). |
Proceed as follows to reset the device to a factory state : |
- Power off device.
- Power on device.
- Wait for all LEDs to light up and turn off again, then push the SVC button.
- Keep SVC button pressed until all LEDs light up, then release. _Up to Desigo V6SP (FW V01.15.15.144) : Keep SVC button pressed until the green RUN LED flashes, then release.
- Wait for device to fully start up unconfigured (RUN LED on, SVC LED flashes). Any device passwords and other settings are lost.
Engineering
-
The router does not require programming. It is configured either using Xworks
Plus or the Desigo SSA-DNT via Ethernet or using a USB device. For details see SSA (Setup & Service Assistant) Commissioning, CA111050). -
Each device has a unique identification number to ensure efficient commissioning. The number is located on a removable barcode label.
-
Each device has a unique MAC address.
For more details see document “Ethernet, TCP/IP, MS/TP and BACnet – Principles” (CM110666).
Installation
Note
Ethernet: See installation manual Desigo TRA, CM111043.
LONWORKS: See installation manual Desigo RXC, CA110336.
HMI (RJ45 plug): only the PXM20 can be connected. Otherwise the PXG3.L or
the mistakenly connected device may be damaged.
Mounting
The router is designed for mounting on a standard mounting rail or on a wall. Power is supplied by connecting the plug-in screw terminal blocks.
Commissioning
To prevent equipment damage and/or personal injuries adhere to local safety regulations and related safety standards.
Maintenance
No maintenance required. A supercap supports the real-time clock (3 days).
Disposal
The devices are considered electronic devices for disposal in terms of the
European Directive 2012/19/EU (WEEE) and may not be disposed of as domestic
waste.
Dispose of the devices via the proper channels. Observe all local and
applicable laws.
Technical data
Operating voltage | Operating voltage | AC 24 V ± 20 % (SELV/PELV) or |
---|---|---|
Half-wave load = Technical ground | AC/DC 24 V class 2 (US) 48…63 Hz Symmetric | |
Power consumption | At AC 24 V At DC 24 V | |
Max. permissible transit power AC/DC 24 V (RJ45 interface, HMI) Internal fuse |
Max. 9 VA Max. 4 WMax. 0.5 A With PTC
Hardware information| Processor Series B Series C| Atmel ARM9 Texas
Instruments AM3352, 600MHz
| Memory Series B Series C| 256 MB Flash, 64 MB SDRAM 512 MB Flash, 512 MB
SDRAM (DDR3)
Response to power / communication failure| Energy reserve (Supercap) to
support real-time clock (3 days). Data available only if saved to flash
memory.
Ethernet interface| Plug Interface type Bit rate Protocol| 2 x RJ45, screened
100BaseTX, IEEE 802.3 compatible 10/100 Mbps, half / full duplex, auto-
negotiation BACnet over UDP/IP
HMI interface| Generic, for HMI (LONWORKS)| RJ45 (PXG3.L only
USB interface| Plug Data rate (USB 1.0 full speed) Galvanic isolation of ^
Protective switch against surges and overcurrent| Type B (USB device) 12 Mbps
No Yes
LONWORKS interface (PXG3.L only| Interface type Transceiver Galvanic isolation
Bit rate Protocol| TP/FT-10 FT 5000 smart transceiver Yes 78 kbps BACnet over
LonTalk
MS/TP interface| Interface type Galvanic isolation Baud rates Protocol| RS485
Yes 9600, 19200, 38400, 76800, 115200 BACnet over MS/TP
Connection terminals, plug-in| Design type Cu-wire or Cu-strand with wire end
sleeve Cu-strand without wire end sleeve Screwdriver Max. tightening torque|
Plug-in screw terminals 1 x 0.6 mm dia. to 2.5 mm2 or 2 x 0.6 mm dia. to 1.0
mm2 1 x 0.6 mm dia. to 2.5 mm2 or 2 x 0.6 mm dia. to 1.5 mm2 Slot screws
Screwdriver, size 1 with shaft dia. ≤ 4.5 mm Max. tightening torque 0.6 Nm
Assignment as per EN 60730| Operation of automatic controller Degree of
pollution Design type| Type 1 2
Housing protection standard| Protection type as per EN 60529 Front parts in
the DIN section Terminal part| IP30 IP20
Ambient conditions| Operation Climatic conditions Temperature Humidity
Mechanical conditions Transport Climatic conditions Temperature Humidity
Mechanical conditions| As per IEC 60721-3-3 Class 3K5 –5 … 50 °C 5…95% r.h.
(non-condensing) Class 3M2 As per IEC 60721-3-2 Class 2K3 -25…70 °C 5…95% r.h.
(non-condensing) Class 2M2
Standards, directives, and approvals| Product standard EN 60730-1
Product family standard EN 50491-x
Electromagnetic compatibility (Applications)
EU conformity (CE)
UL certification (US)
RCM-conformity (EMC)
EAC conformity| Automatic electrical controls for household and similar use
General requirements for Home and Building Electronic Systems (HBES) and
Building Automation and Control Systems (BACS) For use in residential,
commerce, light-industrial and industrial environments CM1T9270xx 1 ) UL 916,
http://ul.com/database CM1T9222en_C1 1 ) Eurasia conformity Certificate:
www.bacnetinternational.net/btl/search.php
2 )
Environmental compatibility| Product environmental declaration (contains data
on RoHS compliance, materials composition, packaging, environmental benefit,
disposal)| CM1E9270 1 )
Color| Housing| RAL 7035 (light-gray)
| Housing as per DIN 43880, see dimensions|
| Without/with packaging| 286 g / 332 g
Connection terminals and interfaces
1, 2 | 2 x RJ45 interface for Ethernet | |
---|---|---|
3 | 24 V ~ ^, | AC/ DC 24 V operating voltage |
5 | CLA, CLB | LONWORKS interface (PXG3.L only) |
+, –, | MS/TP interface | |
HMI | RJ45 interface for HMI (PXG3.L only) | |
USB | USB tool interface | |
Service | Service button |
RJ45 pin assignment for HMI
Pin | Name | Description | Pin | Name | Description |
---|---|---|---|---|---|
1 | CLA | LONWORKS A | 5 | nc | Not connected |
2 | CLB | LONWORKS B | 6 | nc | Not connected |
3 | AC24V_N | AC24V Neutral | 7 | nc | Not connected |
4 | AC24V_L | AC24V Line max. 500mA | 8 | nc | Not connected |
Operating voltage pin assignment
Pin | Name | Description |
---|---|---|
1 | 24 V ~ | AC 24 V |
2 | System neutral | |
3 | **** | Technical ground |
LONWORKS pin assignment
Pin | Name | Description |
---|---|---|
4 | CLA | LONWORKS A |
5 | CLB | LONWORKS B |
MSTP pin assignment
Pin | Name | Description |
---|---|---|
+ | + | Data + |
– | – | Data – |
**** | **** | Reference wire |
Dimensions
All dimensions in mm
CUSTOMERS SUPPORT
Issued by
Siemens Switzerland Ltd
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
Tel. +41 41-724 24 24
www.siemens.com/buildingtechnologies
© Siemens Switzerland Ltd 2012
Delivery and technical specifications subject to change