SIEMENS PXG3.L BACnet Router Instruction Manual

June 13, 2024
SIEMENS

SIEMENS PXG3.L BACnet Router

SIEMENS PXG3.L BACnet Router

BACnet router for

  • BACnet/IP
  • BACnet/LonTalk
  • BACnet MS/TP
  • Routing between BACnet/IP , BACnet/LonTalk (PXG3.L only), and BACnet MS/TP
  • Supports BACnet/IPv4 and BACnet/IPv6
  • BACnet standard compliant
  • ISO 16484-5 compliant
  • BTL label (BACnet communications passed the BTL test)
  • BBMD support (BACnet Broadcast Management Device)
  • Third-party device support
  • Configuration via Xworks Plus or Web browser (via IPv4)
  • Web browser access to network statistics
  • Firmware update via Ethernet and USB Device
  • LED indication for Ethernet link and activity
  • LED indication for BACnet/LonTalk and BACnet MS/TP (diagnostics)
  • 2-port Ethernet switch for low-cost cabling (10/100 baseT)
  • BACnet MS/TP (RS-485) baud rates: 9600, 19200, 38400, 76800, 115200
  • Plug-in screw terminal blocks for supply, LONWORKS, and MS/TP
  • RJ45 plug for PXM20 (LONWORKS)
  • Operating voltage: AC 24 V or DC 24 V
  • DIN rail mounting
  • BACnet MS/TP Slave Proxy
  • SNMP (v2), MIB-2
  • BACnet NAT

Use

The PXG3… BACnet router connects a BACnet/IP network to a BACnet/LonTalk network (PXG3.L only), and/or a BACnet MS/TP channel. BACnet objects are transmitted simultaneously throughout any and all networks.

Use

Router functions

Four-way routing| The PXG3… BACnet router transmits BACnet protocol between a BACnet/IPv4 network, a BACnet/IPv6 network, a BACnet/LonTalk network (PXG3.L only), and a BACnet MS/TP channel. BACnet objects are simultaneously transmitted throughout any and all networks.
---|---
BBMD| Broadcast Management Device, used to distribute BACnet Broadcast messages across IP Routers.
Web server| The BACnet router includes a Device Object and can be operated by a BACnet Client. Present operating state, date and time as well as statistics on sent packages can be viewed via web server.
MS/TP Slave Proxy| The BACnet router can serve as a Slave Proxy for slaves that are connected to its MSTP port. In other words, it responds to Who-Is messages on the slaves’ behalf by sending an I-Am message.
SNMP v2| Simple Network Management protocol MIB-2, for monitoring and diagnosing the BACnet router network interface.
BACnet NAT| Supports setup of a BACnet network over a NAT device. Additionally, remote access from a public network to BACnet devices is possible on a private network. Important: the public IP address must be static. For security reasons we recommend using VPN tunneling with BACnet NAT.
BACnet/IP to BACnet/IP| When routing between BACnet/IP and BACnet/IP on one IP network, the BACnet router address must be the same on both BACnet networks. The difference is that different BACnet UDP ports are used on the BACnet network.

Communication

  • The router complies with BACnet standard and ISO 16484-5.
  • A 2-port Ethernet switch allows low-cost cabling via line topology. This is the preferred commissioning medium.
  • The LONWORKS network is connected via a 2-pin connection terminal.
  • The MS/TP channel is connected via RS485 or a 3-pin connection terminal.
  • An RJ45 plug on the device front allows connecting to a PXM20 operator unit (PXG3.L only).
  • A USB port is available for connecting the tool.

Type summary

Type (ASN)

| Product number (SSN)| Name| Ethernet ports| LONWORKS|

MS/TP

---|---|---|---|---|---

PXG3.L

| S55842-Z105-A100| BACnet Router Ethernet/IPLonTalk-MS/TP| 2| x|

x

PXG3.M

| S55842-Z106-A101| BACnet Router Ethernet/IP-MS/TP| 2| |

x

Mechanical design

Mechanical design

  1. Plastic housing
  2. Plug-in terminal block (operating voltage)
  3. 2-port Ethernet switch (with 2 LEDs each for display purposes)
  4. LEDs for device and system status indication
  5. RJ45 interface for PXM20 (PXG3.L only)
  6. Tool interface (USB Device)
  7. Service button for identification on network (Ethernet, LONWORKS)
  8. LONWORKS terminal block (PXG3.L only)
  9. MS/TP terminal block
  10. Slider for mounting on DIN rail

LEDs

LED Color Activity Function
RUN Green
  • Continuously ON
  • Continuously OFF
  • Flashing

|

  • Device ready.
  • At least one internal power supply out of range.
  • Start-up of device.

FLT| Red|

  • Continuously OFF
  • Continuously ON
  • Flashing

|

  • OK
  • HW fault or program fault.
  • Incorrect or corrupt FW.

INF| —| —| (Not used)
COM1| Yellow|

  • Flashing

|

  • Sends MS/TP packages.

COM2| Yellow|

  • Flashing

|

  • Sends LONWORKS packages (PXG3.L only).

SVC| Red|

  • Continuously OFF
  • Continuously ON
  • Flashing
  • Flashing per wink command *)

|

  • Configured.
  • Defective Hardware.
  • Unconfigured.
  • Physical identification of the router.

Ethernet 1 / 2| Green|

  • Continuously ON
  • Continuously OFF
  • Flashing

|

  • Link active
  • Link inactive
  • Network activity

Yellow|

  • Continuously ON
  • Continuously OFF

|

  • Link 100 Mbps
  • Link 10 Mbps

*) Wink command pattern:

LEDs

Service button

Button Press Description
1 Short Physical identification on the network (Ethernet).
Proceed as follows to reset the device to a factory state :
  1. Power off device.
  2. Power on device.
  3. Wait for all LEDs to light up and turn off again, then push the SVC button.
  4. Keep SVC button pressed until all LEDs light up, then release. _Up to Desigo V6SP (FW V01.15.15.144) : Keep SVC button pressed until the green RUN LED flashes, then release.
  5. Wait for device to fully start up unconfigured (RUN LED on, SVC LED flashes). Any device passwords and other settings are lost.

Engineering

  • The router does not require programming. It is configured either using Xworks
    Plus or the Desigo SSA-DNT via Ethernet or using a USB device. For details see SSA (Setup & Service Assistant) Commissioning, CA111050).

  • Each device has a unique identification number to ensure efficient commissioning. The number is located on a removable barcode label.

  • Each device has a unique MAC address.

For more details see document “Ethernet, TCP/IP, MS/TP and BACnet – Principles” (CM110666).

Installation

Note

Ethernet: See installation manual Desigo TRA, CM111043.
LONWORKS: See installation manual Desigo RXC, CA110336.
HMI (RJ45 plug): only the PXM20 can be connected. Otherwise the PXG3.L or the mistakenly connected device may be damaged.

Mounting

The router is designed for mounting on a standard mounting rail or on a wall. Power is supplied by connecting the plug-in screw terminal blocks.

Commissioning

To prevent equipment damage and/or personal injuries adhere to local safety regulations and related safety standards.

Maintenance

No maintenance required. A supercap supports the real-time clock (3 days).

Disposal

The devices are considered electronic devices for disposal in terms of the
European Directive 2012/19/EU (WEEE) and may not be disposed of as domestic waste.
Dispose of the devices via the proper channels. Observe all local and applicable laws.

Technical data

Operating voltage Operating voltage AC 24 V ± 20 % (SELV/PELV) or
Half-wave load = Technical ground AC/DC 24 V class 2 (US) 48…63 Hz Symmetric
Power consumption At AC 24 V At DC 24 V
Max. permissible transit power AC/DC 24 V (RJ45 interface, HMI) Internal fuse

Max. 9 VA Max. 4 WMax. 0.5 A With PTC
Hardware information| Processor Series B Series C| Atmel ARM9 Texas Instruments AM3352, 600MHz
| Memory Series B Series C| 256 MB Flash, 64 MB SDRAM 512 MB Flash, 512 MB SDRAM (DDR3)
Response to power / communication failure| Energy reserve (Supercap) to support real-time clock (3 days). Data available only if saved to flash memory.
Ethernet interface| Plug Interface type Bit rate Protocol| 2 x RJ45, screened 100BaseTX, IEEE 802.3 compatible 10/100 Mbps, half / full duplex, auto- negotiation BACnet over UDP/IP
HMI interface| Generic, for HMI (LONWORKS)| RJ45 (PXG3.L only
USB interface| Plug Data rate (USB 1.0 full speed) Galvanic isolation of ^ Protective switch against surges and overcurrent| Type B (USB device) 12 Mbps No Yes
LONWORKS interface (PXG3.L only| Interface type Transceiver Galvanic isolation Bit rate Protocol| TP/FT-10 FT 5000 smart transceiver Yes 78 kbps BACnet over LonTalk
MS/TP interface| Interface type Galvanic isolation Baud rates Protocol| RS485 Yes 9600, 19200, 38400, 76800, 115200 BACnet over MS/TP
Connection terminals, plug-in| Design type Cu-wire or Cu-strand with wire end sleeve Cu-strand without wire end sleeve Screwdriver Max. tightening torque| Plug-in screw terminals 1 x 0.6 mm dia. to 2.5 mm2 or 2 x 0.6 mm dia. to 1.0 mm2 1 x 0.6 mm dia. to 2.5 mm2 or 2 x 0.6 mm dia. to 1.5 mm2 Slot screws Screwdriver, size 1 with shaft dia. ≤ 4.5 mm Max. tightening torque 0.6 Nm
Assignment as per EN 60730| Operation of automatic controller Degree of pollution Design type| Type 1 2
Housing protection standard| Protection type as per EN 60529 Front parts in the DIN section Terminal part| IP30 IP20
Ambient conditions| Operation Climatic conditions Temperature Humidity Mechanical conditions Transport Climatic conditions Temperature Humidity Mechanical conditions| As per IEC 60721-3-3 Class 3K5 –5 … 50 °C 5…95% r.h. (non-condensing) Class 3M2 As per IEC 60721-3-2 Class 2K3 -25…70 °C 5…95% r.h. (non-condensing) Class 2M2
Standards, directives, and approvals| Product standard EN 60730-1
Product family standard EN 50491-x
Electromagnetic compatibility (Applications)
EU conformity (CE)
UL certification (US)
RCM-conformity (EMC)
EAC conformity| Automatic electrical controls for household and similar use General requirements for Home and Building Electronic Systems (HBES) and Building Automation and Control Systems (BACS) For use in residential, commerce, light-industrial and industrial environments CM1T9270xx 1 ) UL 916, http://ul.com/database CM1T9222en_C1 1 ) Eurasia conformity Certificate: www.bacnetinternational.net/btl/search.php 2 )
Environmental compatibility| Product environmental declaration (contains data on RoHS compliance, materials composition, packaging, environmental benefit, disposal)| CM1E9270 1 )
Color| Housing| RAL 7035 (light-gray)
| Housing as per DIN 43880, see dimensions|
| Without/with packaging| 286 g / 332 g

Connection terminals and interfaces

Connection terminals and interfaces

1, 2 2 x RJ45 interface for Ethernet
3 24 V ~ ^, AC/ DC 24 V operating voltage
5 CLA, CLB LONWORKS interface (PXG3.L only)
+, –, MS/TP interface
HMI RJ45 interface for HMI (PXG3.L only)
USB USB tool interface
Service Service button

RJ45 pin assignment for HMI

Connection terminals and interfaces

Pin Name Description Pin Name Description
1 CLA LONWORKS A 5 nc Not connected
2 CLB LONWORKS B 6 nc Not connected
3 AC24V_N AC24V Neutral 7 nc Not connected
4 AC24V_L AC24V Line max. 500mA 8 nc Not connected

Operating voltage pin assignment

Pin Name Description
1 24 V ~ AC 24 V
2 System neutral
3 **** Technical ground

LONWORKS pin assignment

Pin Name Description
4 CLA LONWORKS A
5 CLB LONWORKS B

MSTP pin assignment

Pin Name Description
+ + Data +
Data –
**** **** Reference wire

Dimensions

All dimensions in mm

Dimensions

CUSTOMERS SUPPORT

Issued by
Siemens Switzerland Ltd
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
Tel. +41 41-724 24 24
www.siemens.com/buildingtechnologies
© Siemens Switzerland Ltd 2012
Delivery and technical specifications subject to change