Danfoss ESMD Temperature Sensor Installation Guide

June 4, 2024
Danfoss

Danfoss ESMD Temperature Sensor Installation Guide

Danfoss ESMD Temperature Sensor Installation Guide

ESMD

  1. Drill a 6.5 mm hole in the middle of the air duct at a place where the temperature sensor is not influenced by stratified air, heat or humidifiers. Place the temperature sensor in the air duct (A).

  2. Drill two 4 mm holes though the flange holes (B) of the ESMD. It is recommended to mount the ESMD with the cable inlet facing down. Use two 5 mm self-cutting screws (not delivered) for mounting the ESMD.

  3. Make a small hole in the black rubber cable inlet and put the cable through the inlet (C).
    Press the orange tabs to connect wires. Polarity not important.

  4. Mount white front cover onto the ESMD.

Dimensions

Danfoss ESMD Temperature Sensor - Dimensions

ESMD:www.danfoss.com

https://www.youtube.com/user/DanfossHeating
- > Playlists -> How-to Videos -> District Energy installation videos

Danfoss ESMD Temperature Sensor

References