EPH CONTROLS UFH10 10 Zone Underfloor Heating Wiring Thermostat Installation Guide

June 13, 2024
EPH CONTROLS

UFH10
Wiring CentreEPH CONTROLS UFH10 10 Zone Underfloor Heating Wiring
Thermostat Installation and Operation Guide

Factory Default Settings

Zone 9 Switch: UFH
Zone 10 Switch: UFH
Grey and Orange terminals of the UFH valve are electrically linked. If UFH valve is fitted, remove this link.

Specifications

Power supply: 230Vac 50-60Hz Admissible ambient humidity: 5-95%RH
Number of Zones: 10 Dimensions: 380 x 165 x 50 mm
Power Supply Indication: Yes Heat Enable contact rating: 3A
Heat Enable Indication: Yes UFH Pump contact rating: 3A
UFH Valve Indication: Yes IP rating: IP20
Zone 1 to Zone 10 Indication: Yes Max. No. of actuators per zone 4
Ambient temperature: 0…45°C Max. Permissible Load 5A Resistive

Mounting and Installation

  1. Remove the UFH10 from its packaging.
  2. The UFH10 can be directly mounted on  a wall using the fixing holes on the base  of the unit or it can be directly mounted on DIN rail.

EPH CONTROLS UFH10 10 Zone Underfloor Heating Wiring Thermostat -
Mounting

Wiring Centre Terminals

Power Supply
L 230Vac Live
E Earth
N Neutral
Programmer
L 230Vac to the programmer.
E Earth to the programmer.
N Neutral to the programmer.
1 Zone 1 output from programmer to the wiring centre.
2 Zone 2 output from programmer to the wiring centre.
3 Zone 3 output from programmer to the wiring centre.
4 Zone 4 output from programmer to the wiring centre.
Thermostats (Zone 1 to Zone 8)
L Live supply to the thermostat.
1 Timed switch live to room stat from programmer zone 1.
2 Timed switch live to room stat from programmer zone 2.
E Earth.
N Neutral supply to the thermostat.
S/L Switch live from the thermostat to the wiring centre.
Note: With thermostats 1 to 8, you have an option of; one of two time inputs.
Thermostats (Zone 9 and Zone 10)
L Live supply to the thermostat.
1 Timed switch live to room stat from programmer zone 1
2 Timed switch live to room stat from programmer zone 2
3 Timed switch live to room stat from programmer zone 3
4 Timed switch live to room stat from programmer zone 4
E Earth.
N Neutral supply to the thermostat.
S/L Switch live from the thermostat to the wiring centre.
Note: With thermostats 9 & 10, you have an option of; one of four time inputs.
Heat Enable (Boiler / Heat Pump On)
LS Live supply
E Earth
LR Live return
This is a volt free relay which is switched on when there is a call for heat.
If 230V is applied to terminal LS and there is a call for heat, 230V will come back on terminal LR.
UFH Pump (Underfloor Heating Pump)
L 230Vac Live
E Earth
N Neutral
When an underfloor heating zone calls for heat, 230V is sent to the underfloor heating manifold pump. Best practice is to wire the underfloor heating manifold pump through a high limit thermostat which is mounted on the manifold.
UFH Valve (Underfloor Heating Valve)
GR Grey Switch Live
OR Orange Permanent Live
L Live
E Earth
N Neutral
When an underfloor heating zone calls for heat, 230V is sent  to the Underfloor heating valve.
The valves auxiliary contacts are wired to the GR and OR terminals.
Note: Please refer to factory default settings on page 1.
Actuators (Zone 1 to Zone 8)
L 230V Live supply to the actuator.
N Neutral supply to the actuator.
There are two terminals marked L & N for each zone.
Actuators (Zone 9 and Zone 10)
L Live supply to the actuator.
N Neutral supply to the actuator.
There are two terminals marked L and two terminals marked N for each zone.
Both zones 9 and 10 have a switch associated with each zone.
This allows the installer to use these zones as underfloor heating zones or radiator / hot water zones.
Operation of Zone 9 & 10 UFH – RAD / HW switches
If set to UFH – When the thermostat calls for heat, the actuator, boiler and pump / valve outputs are enabled.
If set to RAD / HW – When the thermostat calls for heat, the actuator is enabled.
To enable the boiler output, the actuator auxiliary contacts (Grey and Orange wires) must be connected to the LS & LR terminals of the Heat Enable.

SWITCH
SELECTED| HEAT
ENABLE| UFH
PUMP| UFH
VALVE| ZONE VALVE
ACTUATOR
---|---|---|---|---
UFH| On| On| On| On
RAD| Off| Off| Off| On

UFH10 – 10 x Underfloor Heating Zones

c/w Mains Operated Programmable Thermostats.
Options:

Note: Please refer to individual thermostat wiring diagrams.

CONTROLS INSTALLED
UFH Pump Yes
UFH Valve Yes
UFH Actuators Yes
Programmer
RAD Valve
HW Valve

EPH CONTROLS UFH10 10 Zone Underfloor Heating Wiring Thermostat - Heating
Zones 1

230V on OR & L when a UFH zone calls for heat. If no valve is fitted, GR & OR must be linked out.
UFH10 – 10 x Underfloor Heating Zones
c/w Mains Operated Non- Programmable Thermostats.
Options:

EPH CONTROLS UFH10 10 Zone Underfloor Heating Wiring Thermostat - Heating
Zones 2

CONTROLS INSTALLED
UFH Pump Yes
UFH Valve Yes
UFH Actuators Yes
Programmer R47
RAD Valve
HW Valve

In this example:
Zone 1 on the programmer is controlling thermostats 1, 2, 3 & 4
Zone 2 on the programmer is controlling thermostats 5, 6, 7 & 8
Zone 3 on the programmer is controlling thermostat 9
Zone 4 on the programmer is controlling thermostat 10

EPH CONTROLS UFH10 10 Zone Underfloor Heating Wiring Thermostat - Heating
Zones 3

230V on OR & L when a UFH zone calls for heat. If no valve is fitted, GR & OR must be linked out.

UFH10 – 10 x Underfloor Heating Zones
c/w Mains Operated Non- Programmable Setback Thermostats.
Options:

Note: Please refer to individual thermostat wiring diagrams

CONTROLS INSTALLED
UFH Pump Yes
UFH Valve Yes
UFH Actuators Yes
Programmer R47
RAD Valve
HW Valve

In this example:
Zone 1 on the programmer is controlling thermostats 1, 2, 3 & 4
Zone 2 on the programmer is controlling thermostats 5, 6, 7 & 8
Zone 3 on the programmer is controlling thermostat 9
Zone 4 on the programmer is controlling thermostat 10

EPH CONTROLS UFH10 10 Zone Underfloor Heating Wiring Thermostat - Heating
Zones 5

230V on OR & L when a UFH zone calls for heat. If no valve is fitted, GR & OR must be linked out.

UFH10 – 8 x Underfloor Heating Zones

– 1 x Radiator Zone
– 1 x Hot Water Zone
c/w Mains Operated Non- Programmable Thermostats. Options:

EPH CONTROLS UFH10 10 Zone Underfloor Heating Wiring Thermostat - Water
Zone

Note: Please refer to individual thermostat wiring diagrams.

CONTROLS INSTALLED
UFH Pump Yes
UFH Valve Yes
UFH Actuators Yes
Programmer R47
RAD Valve V22_P
HW Valve V22_P

In this example:
Zone 1 on the programmer is controlling thermostats 1, 2, 3 & 4
Zone 2 on the programmer is controlling thermostats 5, 6, 7 & 8
Zone 3 on the programmer is controlling thermostat 9
Zone 4 on the programmer is controlling thermostat 10

EPH CONTROLS UFH10 10 Zone Underfloor Heating Wiring Thermostat - Water Zone
1

230V on OR & L when a UFH zone calls for heat. If no valve is fitted, GR & OR must be linked out.

EPH Controls IE

technical@ephcontrols.com
www.ephcontrols.com/contact-us
T +353 21 471 8440

WWW.ephcontrols.com

EPH Controls UK
technical@ephcontrols.co.uk
www.ephcontrols.co.uk/contact-us
T +44 1933 322 072

www.ephcontrols.co.uk

EPH Controls Ltd.

UFH10 is compatible with the following EPH thermostats
Electro – Mechanical Thermostats

EPH CONTROLS UFH10 10 Zone Underfloor Heating Wiring Thermostat - EPH
thermostats

Documents / Resources

| EPH CONTROLS UFH10 10 Zone Underfloor Heating Wiring Thermostat [pdf] Installation Guide
CDTP2, CP4M, RDTP, CDT2, HDT, RDT, EDBS, UFH10 10 Zone Underfloor Heating Wiring Thermostat, 10 Zone Underfloor Heating Wiring Thermostat, Underfloor Heating Wiring Thermostat, Heating Wiring Thermostat, Thermostat
---|---

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals