MyVallox Control User Manual

June 13, 2024
VALLOX

Model
MyVallox Control
Document
D5311
Valid from
13.05.2022
Updated
16.05.2022MyVallox Control

SAFETY

Safe and appropriate handling requires knowledge of the basic safety regulations, and of the intended use of the ventilation system. Read this manual before operating the ventilation unit.
Retain the manual for later reference. If you lose the manual, it can be downloaded from our website.
This user manual contains all the information necessary for safe operation of the system. All persons who operate and maintain the ventilation system must follow the instructions provided in this manual. Furthermore, all local accident  prevention regulations must be observed.

NOTE
For further information, go to www.vallox.com

Installation
Installation and setup should be carried out only by qualified experts. Electrical installations and connections must be carried out only by an electrician and in compliance with local regulations.

WARNING
The unit is not intended for use by children under 8 or by persons with reduced sensory, physical or mental capabilities, or whose lack of knowledge and experience do not ensure safe operation of the unit.
Such persons can use the unit under supervision, or by following the instructions of someone who is responsible for their safety.
Children must be supervised and not be allowed to play with the device.

GUARANTEE

The guarantee and liability exclude damage resulting from:

  • Inappropriate use of the ventilation system or the control unit
  • Incorrect or inappropriate installation, setup or use
  • Neglect of instructions concerning transportation, installation, use, or maintenance
  • Structural or electronic modifications or changes made to the software

INTENDED USE
All Vallox ventilation units have been designed to provide appropriate and continuous ventilation so as to present no threat to health and to maintain structures in good condition.
IMPORTANT
In order to ensure that the indoor air presents no harm to health and remains optimal also for the structures of the building, ventilation must be kept on without disruptions. It is recommended that ventilation be left turned on during  long holidays also. This keeps the indoor air fresh and prevents humidity from condensing in the ventilation ducts and structures. It also reduces the risk of moisture damage.
DANGER
Indicates a hazard that will result in death or serious injury if not avoided.
WARNING
Indicates a hazard that can result in death or serious injury if not avoided.
CAUTION
Indicates a hazard that can result in minor or moderate injury if not avoided.
IMPORTANT
Indicates a hazard that can result in damage to  property or loss of dataif not avoided.
NOTE
Indicates essential information about the product.
TIP
Provides additional information about the use of the product and its benefits.

COMPATIBILITY OF THE MYVALLOX CONTROL PANEL

The control panel is compatible with the following ventilation units

MODELS TYPE
Vallox TSK Multi 50 MV, ValloMulti 200 MV EH 3609, A3609
ValloMulti 200 MV 3609-1, A3609-1
Vallox TSK Multi 80 MV, ValloMulti 300 MV EH 3608, A3608, B3608
ValloMulti 300 MV 3608-1, A3608-1, B-3608-1 (EH = post-heating)
ValloMulti 300 MV EHX 3608-2, A3608-2, B3608-2 EHX= post-heating and

additional heating)
Vallox 51 MV, ValloPlus 180 MV| 3750, A3750
Vallox 51K MV, ValloPlus 180 MV-K| 3751, A3751
Vallox 90 MV, ValloPlus 240 MV, ValloPlus 240 MV-E| 3527, A3527
Vallox 90K MV, ValloPlus 240 MV-K| 3528, A3528
Vallox 096 MV, ValloPlus 270 MV| 3722, A3722
Vallox 101 MV| 3741, A3741
Vallox 110 MV, ValloPlus 350 MV, ValloPlus 350 MV-E| 3702, A3702
Vallox 145 MV, ValloPlus 510 MV, ValloPlus 510 MV-E| 3712, A3712
Vallox 245 MV, ValloPlus 850 MV, ValloPlus 850 MV-E| 3732, A3732
Vallox 245 MV VKL, ValloPlus 850 MV WNH, ValloPlus 850 MV-E WNH| 3732, A3732

SYSTEM DESCRIPTION

  1. Internet
  2. WLAN
  3. Router
  4. WLAN/LAN
  5. Additional switch
  6. Sensors

MyVallox Control - DESCRIPTION

VENTILATION UNIT CONTROL

Ventilation unit control options
Operation of the Vallox ventilation unit can be controlled by the following means:

  • Through the control panel installed in the building
  • Through the MyVallox Home local area network connection and the MyVallox Home/Cloud user interface.
  • Through the MyVallox Cloud service and the MyVallox Home/Cloud user interface.
  • Through a remote monitoring service or building automation that uses voltage signals or Modbus messages

In addition to the integrated carbon dioxide and humidity sensors, ventilation can also be adjusted automatically by using the optional external carbon dioxide, VOC and humidity sensors.
When these are used, ventilation remains optimal even when the dwelling is unoccupied.
Each user can use the week clock to adjust the ventilation to fit their individual lifestyle.

NOTE
For the MyVallox Cloud/Home instructions, please go to www.techmanuals.info/ValloxMV/ENG/onlinehelp/webhelp

CONNECTING THE VENTILATION UNIT TO THE CLOUD SERVICE
The ventilation unit can be connected to the MyVallox Cloud service. The cloud service allows for controlling ventilation remotely also, using e.g. a smartphone or tablet. Also the unit software is updated automatically through the cloud service. To connect to the cloud service, the ventilation unit must be connected to the Internet via LAN and registered with the cloud service. At the same time you create a MyVallox Cloud account for yourself. Read more about the service
at www.myvallox.com.
To register your Vallox ventilation unit with the MyVallox Cloud service:

  1. Connect one end of the network cable to the grey connector of the Vallox ventilation unit and the other end to the router.

  2. Open the network settings on the computer by selecting Start → My Computer → Network. A computer icon with the text Vallox and a series of numbers will be displayed. Open the MyVallox Home user interface by double clicking  on the icon. The MyVallox Home user interface opens.
    OR
    From the MyVallox Control panel, select Service menu → Diagnostics display → IP address. Type in the IP address and press Enter. The MyVallox Home user interface opens.

  3. Select Special functions.

  4. The MyVallox Cloud area will open and you can see whether you are signed in to the cloud service.

  5. Select Connect.

  6. The registration page of the MyVallox Cloud service opens. A unique identification number of the ventilation unit will be automatically generated into the field.

  7. Enter the following information on the form:
    • Ventilation unit name — Enter the ventilation unit name of your choice in this field.
    • Language — Select the desired language from the drop down menu
    • Country — Select the desired country from the drop down menu
    • Select username — Enter the username of your choice in this field.
    • Email address — Enter the email address of your choice in this field.
    • Password — Enter the password of your choice in this field.
    • Retype password — Retype your password in this field.

  8. Select the I want to receive notifications related to my ventilation unit box if you want to receive notifications related to your ventilation unit in your inbox.

  9. Read the conditions of use and select I have read and accept the conditions of use of the MyVallox Cloud service . The use of the services requires that the user has accepted the conditions of use of the service.

  10. Select Create a MyVallox Cloud account. The ventilation unit will generate a unique identification code and send it to the service. The service will remember the unit next time you sign in into the cloud service.

  11. A confirmation message will be sent to your email address. Click on the link contained in the message to confirm your email address and to sign in into the cloud service for the first time.

  12. Once you have signed in, the MyVallox Cloud service will open and the main page of the MyVallox Cloud account will be displayed in your browser.

CONTROL PANEL BUTTONS

NOTE
The MyVallox Control panel contains the buttons described in the following table. You can press the graphical user interface buttons by using the buttons below the control panel. The control panel does not have a touch screen.

BUTTON DESCRIPTION
The Change mode button changes the ventilation mode or the operating status

used.
****| The Mode information button allows you to view the currently active mode information.
| The Temperature button displays temperature and sensor information.
| The Settings button opens the settings menu.
| The Back button takes you backwards in the menu.
◀| The Left arrow button takes you leftward in the menu.
▶| The Right arrow button takes you rightward in the menu.
| The OK button accepts the selected option.
| Press the Cancel button to cancel selection.
| Press the Select button to select the desired option.
| The Edit button allows you to edit settings.
| The Plus button allows you to:
• Increase the value of the selected setting.
• Move to the next menu item.
• Move from a one-day view to a week view in the temperature, relative humidity of air, carbon dioxide or VOC level graphs.
| The Minus button allows you to:
• Reduce the value of the selected setting.
• Return to the previous menu item.
• Move from a week view to a one-day view in the temperature, relative humidity of air, carbon dioxide or VOC level graphs.
▲| The Up arrow button takes you upward in the menu.
▼| The Down arrow button takes you downwards in the menu.
| The Statistics button opens the temperature, relative humidity of air, carbon dioxide or VOC level graphs (1  day or 1 week).
| This icon indicates when the feature is turned off at your user level.

STARTING UP AND SHUTTING DOWN THE UNIT
Unit software
We recommend that the latest software version be always used.
Check and download the latest version at http://www.cloud.vallox.com either before or immediately after setup.
The current software version of the ventilation unit is shown on the control panel display when the unit is connected to the mains or factory settings are restored. Alternatively, the current software version can be checked from the Unit  information display of the Service menu.
Updating the unit software

  1. Unplug the ventilation unit from the mains or turn off the fuse.
  2. Connect the computer to the control panel of the ventilation unit using a USB MicroB connector.
  3. Start the ventilation unit. A USB sign will appear on the display of the control panel and the control panel of the ventilation unit cannot be used when it is connected to the computer.
  4. Transfer the update file you have downloaded onto the ventilation unit. Copy the update file HSWUPD.
    BIN (Please note! Do not alter the file name!) you have downloaded at the root of the control panel (the control panel will be displayed on your computer as a mass memory or a removable disk drive). When the file has uploaded  onto the control panel, remove the USB cable. Next, the control panel will take a while to load the update. The control panel will now start to load the update file onto the motherboard. This can take several hours. The control panel  will remain turned on, but it is recommended that the control panel be not used during that time. When the update is ready, the unit will restart automatically.

Starting the unit
If you are starting the ventilation unit for the first time or after a maintenance procedure, first connect it to the mains. This will start the unit.
If the ventilation unit was turned off from the control panel (see Turning the unit off), you can start it by pressing any control panel button.
Turning the unit off
To turn the ventilation unit off:

  1. Use the arrow buttons to select Turn unit off.
  2. Select OK.
  3. Press OK to confirm the selection. The ventilation unit has now been turned off.

IMPORTANT
It is recommended that the ventilation be kept turned on without disruptions.

SETUP SETTINGS

The following settings will be configured during the setup of the ventilation system:

  • user interface language
  • time and date
  • system administrator lock code
  • parental controls, if turned on
  • fan settings
  • mode settings, such as the temperature.

The qualified ventilation installer must complete the fan settings in accordance with the ventilation plan. Do not change these settings.

  1. Start the Vallox ventilation unit.
  2. When the unit is started for the first time, the language menu opens on the control panel display.

TIP
The MyVallox Control panel automatically switches to the sleep mode when the Sleep time set in the Display settings has elapsed.
You can wake up the control panel by pressing any control panel button.

Select the language

  1. Use the arrow buttons to select the language.
  2. Select OK.
  3. The language has now been set, and the control panel will move on to the time settings.

Set the time

  1. Use the Plus and Minus buttons to set the hours.
  2. Select Right arrow.
  3. Use the Plus and Minus buttons to set the minutes.
  4. The time is now set.
  5. Proceed to the next phase by selecting Right arrow.

MyVallox Control - SETTINGS

Set the 24- or 12-hour clock
The 24-hour clock is used by default.
To use the 12-hour clock:

  1. Select Down arrow. The 24-Hour time setting value is changed to Off.
  2. Proceed to the next phase by selecting Right arrow.

Set the automatic daylight saving time
By default, the automatic daylight saving time is on.
To use the manual daylight saving time setting:

  1. Select Down arrow. The Daylight saving time setting value is changed to Off.
  2. The manual daylight saving time setting is now on.
  3. Proceed to the next phase by selecting Right arrow.

Set the date

  1. Use the Plus and Minus buttons to set the date.
  2. Select Right arrow.
  3. Use the Plus and Minus buttons to set the month.
  4. Select Right arrow.
  5. Use the Plus and Minus buttons to set the year.
  6. Select OK.
  7. The date is now set.

TIP
You can browse the Time and date settings by using the Right arrow button.

User level
There are three user levels:

  • Extensive – The user can modify all settings of the ventilation unit.
  • Normal – The user can view the ventilation unit information and modify some of its settings.
  • Limited – The user can change the ventilation mode and view the ventilation unit information.
    MyVallox Control - User

For more information on user levels, see Chapter “User level diagrams”.

  1. Use the Arrow buttons to set the user level.
  2. The user level is now set.
    Proceed to the next phase by selecting Right arrow.

Lock code
NOTE
The default lock code is 0000, i.e. the lock code inquiry is turned off.

  1. To set a lock code, press the Edit button.
  2. Use the Arrow buttons to set the first digit of the lock code. Proceed to the next digit by selecting Right arrow.
  3. Set the remaining digits of the lock code in the same way.
  4. Select OK.
  5. The lock code is now set.

Parental controls
Parental controls lock the control panel so that no damage can be done to the ventilation unit by random pressing of the control panel buttons.

  1. By default, the parental controls are turned off. Use the Arrow buttons to turn the parental controls on.
  2. Select OK.
  3. The parental controls are now set.
    TIP
    You can browse the Lock code and access rights settings with the Right arrow button.
    NOTE
    The access code of the parental controls cannot be changed. The access code is always 1001.

Basic fan settings
IMPORTANT
Adjust the air flows according to the values specified in the ventilation plan. It is recommended that the air flows be adjusted without having to choke the air flows at the valves. This is the most energy-efficient set up.
First, set both values as close to the ideal value as possible by looking at the supply and extract air fan curves. If the ratio between the air flows is very high at first, the ventilation unit may have to carry out extra defrosting cycles in sub- zero temperatures, thus making adjustment of the air flows more complicated. Check the air flows by measuring them at the valves, and fine-tune the percentage values as required.
NOTE
If the outdoor air is extremely cold (below -10°C on an aluminium cell or below -3°C on a plastic cell), the ventilation unit may have to defrost the heat recovery cell. If this happens, the Defrosting icon will be displayed on the control  panel. The air flows cannot be adjusted during defrosting.
IMPORTANT
The supply and extract air settings have been completed by a specialist during setup of the ventilation unit. These settings should be changed only when the ventilation unit is reconfigured, and not at any other time. Changing the ventilation settings so that overpressure is created can result in damage to the structures of the building.

Adjusting the supply and extract air flows

  1. Use the Plus and Minus buttons to set the supply air fan ratio as a percentage of the maximum output ratio. The fan speed (rpm) will change accordingly.
  2. Measure and adjust the supply air flows from the valves.
  3. Press the Right arrow button.
  4. Use the Plus and Minus buttons to set the extract air fan ratio as a percentage of the maximum output ratio. The fan speed (rpm) will change accordingly. Measure and adjust the extract air flows from the valves.
  5. Select OK. Supply and extract air flow settings are now complete.
  6. Record the set percentages in the measurement log. Do not change the output ratio between the supply and extract air fans once the settings are complete. The same ratio is also used in the Away and Boost modes.
    MyVallox Control - flows 1

TIP
You can browse the Basic fan settings by using the Right arrow button.
NOTE
If the use of the ventilation unit has been started before airflow adjustment, the airflow must be measured through the air volume adjustment menu (see “Save and restore settings”). This ensures that the unit settings are optimal for the  adjustment of the airflows.

VENTILATION MODES

Four ventilation unit modes
At home
Use this mode when the dwelling or the premises are occupied.
Away
Use this mode when the dwelling or premises are unoccupied, e.g. during a trip or other long absence.
Boost
Use this mode to increase the ventilation rate, e.g. when there are more people than usual in the dwelling or elsewhere on the premises.
Fireplace mode
Use this mode when, for example, you are making a fire in the fireplace. The mode is primarily used to create momentary overpressure in the dwelling.

TIP
Using the At home, Away, and Boost modes according to need saves energy.
IMPORTANT
Prolonged overpressure can result in damage to the structures of the building.

Symbols for ventilation modes
The following symbols are used on the main displays of the modes:

SYMBOL DESCRIPTION
The mode in use is either At home, Away, or Boost. The week clock is turned

off.
| The mode in use is either At home, Away, or Boost. The week clock is on.

| The Fireplace mode is used. The week clock might be turned on.

The mode in use is either At home, Away, or Boost. The programmable input has become
activated.

| These fan symbols indicate the currently used mode.
• Fan and one shaded bar — The Away mode is in use.
• Fan and two shaded bars — The At home mode is in use.
• Fan and three shaded bars — The Boost mode is in use.
| Droplet symbols indicate the relative humidity of air.
• Droplet and one shaded bar — A humidity sensor has been installed and the relative humidity of air is normal.
• Droplet and two shaded bars — The relative humidity of air is slightly higher than normal. Ventilation efficiency needs to be  boosted. When the automatic fan speed  control based on the relative humidity of the air is turned on, ventilation is boosted  automatically.
•  Droplet and three shaded bars — The relative humidity of air is significantly higher than normal. The fan speed will be  automatically increased if automatic adjustment is allowed.
| CO2 symbols indicate the carbon dioxide or the VOC level in the air.
• CO2 and one shaded bar — The carbon dioxide or VOC sensor has been installed and the level is normal.
• CO2 and two shaded bars — The carbon dioxide or VOC level is slightly higher than normal. The fan speed will be automatically increased if automatic adjustment is allowed.
• CO2 and three shaded bars — The carbon dioxide or VOC level is significantly higher than normal. The fan speed will be automatically increased if automatic adjustment is allowed.

VENTILATION MODE SETTINGS

NOTE
By default, the fan speed used in the At home mode is the higher of the percentage values set for basic ventilation airflows.
We recommend that this basic ventilation setting be used with the At home mode. Once you have set the fan speed for the At home mode, the fan speed for the Away mode will by default be set to -30% of the At home mode fan speed. We recommend that the default fan speed settings be used. However, the settings can be changed as required.

At home and Away modes
To set the ventilation settings of the modes:

  1. Use the Plus or Minus buttons to set the mode fan speed as a percentage of the maximum output ratio.
  2. The fan speed is now set for the mode.
  3. Proceed to the next phase by selecting Right arrow.
  4. Use the Plus or Minus buttons to set the desired supply air temperature for the mode. You can adjust the temperature setting in the range +5°C … +25°C.
  5. The supply air temperature of the mode is now set.
  6. Proceed to the next phase by selecting Right arrow.
  7. Use the Arrow buttons to turn the automatic fan speed control based on relative humidity of air on or off.
  8. The automatic fan speed control, based on the relative humidity of air, is now set.
  9. Proceed to the next phase by selecting Right arrow.
  10. Use the Arrow buttons to turn the automatic fan speed control based on carbon dioxide or VOC level on or off.
  11. The automatic fan speed control, based on the carbon dioxide or VOC level, is now set.
  12. Select OK.
  13. Move to the settings of the next mode by selecting OK.

MyVallox Control - home

NOTE
Once you have set the fan speed for the At home mode, the fan speed for the Boost mode will by default be set to +30% of the At home mode fan speed. It is recommended that this fan speed setting be used for the Boost mode. However, the setting can be changed as required.
TIP
You can browse the At home mode settings with the Right arrow button.

Boost mode
The fan speed, supply air temperature, and the automatic fan speed control (based on relative humidity of air or carbon dioxide or VOC level) is set for the Boost mode in the same way as for the At home and Away modes. The Boost mode also has a timer setting.

  1. Use the Arrow buttons to select whether the mode timer function is used or not. The options are: • On — When the timer is on, the Boost mode is used only for the period specified in the timer.
    • Off — When the timer is off, the Boost mode is used until the mode is changed, either manually or automatically by the week clock.

  2. Proceed to the next phase by selecting Right arrow.

  3. Use the Plus and Minus buttons to set the mode timer duration in minutes.

  4. Proceed to the next phase by selecting Right arrow.

  5. Use the Plus or Minus buttons to set the mode fan speed as a percentage of the maximum output ratio.

  6. The fan speed is now set for the mode.

  7. Proceed to the next phase by selecting Right arrow.

  8. Use the Plus or Minus buttons to set the desired supply air temperature for the mode. You can adjust the temperature setting in the range +5°C … +25°C.

  9. The supply air temperature of the mode is now set.

  10. Proceed to the next phase by selecting Right arrow.

  11. Use the Arrow buttons to turn the automatic fan speed control based on relative humidity of air on or off.

  12. The automatic fan speed control, based on the relative humidity of air, is now set.

  13. Proceed to the next phase by selecting Right arrow.

  14. Use the Arrow buttons to turn the automatic fan speed control based on carbon dioxide or VOC level on or off.

  15. The automatic fan speed control, based on the carbon dioxide or VOC level, is now set.

  16. Move to the settings of the next mode by selecting OK.

TIP
You can browse the settings of the Boost or the Fireplace mode by using the Right arrow button.
TIP
It is recommended that a higher supply air fan speed be used in the fireplace mode to create overpressure in the ventilation zone.
Reducing the extract air fan speed is not recommended. The recommended duration is 15-30 min.

Fireplace mode

  1. Use the Arrow buttons to select whether the mode timer function is used or not. The options are: On — When the timer is in use.
    The Fireplace mode is only used for the period specified in the timer.
    Off — When the timer is not in use.
    The Fireplace mode will be used until you (or the week clock) change the mode.

  2. The mode timer function is now set.

  3. Proceed to the next phase by selecting Right arrow.

  4. Use the Plus and Minus buttons to set the Fireplace mode timer duration in minutes.

  5. The duration of the Fireplace mode is now set.

  6. Proceed to the next phase by selecting Right arrow.

  7. Use the Plus and Minus buttons to set the supply air fan speed of the Fireplace mode as a percentage of the maximum output ratio.

  8. The supply air fan speed of the Fireplace mode is now set.

  9. Proceed to the next phase by selecting Right arrow.
    MyVallox Control - Fireplace

  10. Use the Plus and Minus buttons to set the extract air fan speed of the Fireplace mode as a percentage of the maximum output ratio.

  11. The extract air fan speed of the Fireplace mode is now set.

  12. Select OK.

IMPORTANT
The timer function of the Fireplace mode can only be turned off when the external fireplace switch has a timer.

Finishing the setup
Once you have completed all phases of the setup, finish up the setup as follows:

  1. To change any of the set values, use the arrow buttons to return to the desired line and then press OK.
  2. When you are satisfied with the settings, use the arrow buttons to select Start and then press OK.

CHANGING THE MODE

  1. Press the Change mode button until the desired ventilation mode icon appears on the display.
  2. Wait until the main display of the selected ventilation mode appears.
  3. The ventilation mode has now been changed.

Browsing the information of the At home, Away, and Boost modes
To view the ventilation mode settings:MyVallox Control -
Browsing

  1. Open the main display of the desired ventilation mode.

  2. Select Mode information.
    The following information is shown on the first information display of the mode:
    • Supply air — Indicates the temperature of the air blown into the building and its set value (in brackets), if the supply air is warmer than the set value.
    • Outdoor air — Indicates the outdoor temperature.
    • Fan speed — Indicates the fan speed. If the automatic fan speed boost is turned on, the set value is shown in brackets first followed by the actual fan speed.
    • HR cell status — The statuses of the ventilation unit heat recovery cell are:
    • Heat recovery — The heat recovery cell heats the air streaming in from outdoors.
    • Cool recovery — The heat recovery cell cools the air flowing in from the outdoors.
    • Cell bypass — The inflowing air bypasses the heat recovery cell.
    • Defrosting the HR cell — The heat recovery cell is being defrosted.

  3. Proceed to the next phase by selecting Right arrow.
    MyVallox Control - defrosted

The next information display of the mode shows the following information:

  • Humidity — Indicates the highest relative humidity of air measured by the sensors.
  • Carbon dioxide — Indicates the highest carbon dioxide level measured by the sensors. If a VOC sensor has been installed, it indicates the VOC level.
  • Replace filters — Indicates the next recommended filter replacement date.
  • Time in operation — Indicates how long the device has been running.

MyVallox Control - defrosted 2

Browsing the Fireplace mode information

  1. Open the main display of the fireplace mode:
  2. Select Mode information.
  3. The information display shows the following information:
    • Duration — Indicates the duration of the set Fireplace mode when the Fireplace mode is taken into use. The value is expressed in hours and minutes.
    • Remaining — Indicates the remaining duration of the Fireplace mode.
    • Supply fan speed — Indicates the percentage of the supply air fan speed relative to the maximum speed.
    • Extract fan speed — Indicates the percentage of the extract air fan speed relative to the maximum speed.

MyVallox Control - defrosted 3

Editing the ventilation mode settings

  1. Open the main display of the desired ventilation mode.
  2. Select Mode information.
  3. Select Edit.
  4. Make the desired changes as instructed in the section Setup wizard-> Ventilation mode settings.

Timer functions of the Fireplace and Boost modes
In addition, the timer function can be modified in the Fireplace and Boost modes. See Setup wizard-> Ventilation mode settings.

TEMPERATURES AND SENSORS

Viewing temperature data

  1. Select Settings > Temperatures and sensors.
  2. Select OK.
    The summary display of temperatures and sensors shows the following information:
    • Indoor air — Indicates the temperature of the air flowing into the unit to be removed from the premises.
    • Outdoor air — Indicates the temperature of the air flowing into the unit from outside.
    • Supply air — Indicates the temperature of the air flowing into the premises from the unit.
    • Exhaust air — Indicates the temperature of the air flowing outdoors from the unit.
    MyVallox Control - TEMPERATURES

TIP
The temperature and sensor data can also be viewed by pressing the temperature button on the mode display.

Viewing temperature statistics

  1. Select Settings > Temperatures and sensors.
  2. Select OK.
  3. Select Statistics.
  4. A graph appears on the display showing the indoor air temperature over the past 24 hours.
  5. Use the Plus and Minus buttons to alternate between weekly and daily statistics.
  6. Use the arrow buttons to view outdoor air, supply air, and exhaust air temperature statistics.
  7. On each display, use the Plus and Minus buttons to alternate between weekly and daily statistics.
  8. To exit the menu, press the Back button.
    NOTE
    A power cut erases daily statistics.

Viewing the relative humidity of air and the carbon dioxide and VOC levels measured by the sensors
To browse levels measured by individual sensors:

  1. Select Settings > Temperatures and sensors.
  2. Select OK.
  3. Use the arrow buttons to switch from the summary display of Temperatures and sensors to view the relative humidity of air and the carbon dioxide or VOC level measured by the humidity, carbon dioxide, or VOC sensors. The VOC  level is shown on the same display as the carbon dioxide level.
    MyVallox Control - levels

To browse statistics for the relative humidity of air or the carbon dioxide or VOC levels:

  1. Select Statistics next to the sensor group you wish to view.
  2. A graph opens on the display showing the relative humidity of air or the carbon dioxide or VOC levels recorded over the past 24 hours by the sensor with the highest values.
  3. Use the Plus and Minus buttons to alternate between weekly and daily statistics.
  4. To exit the menu, press the Back button.

NOTE
A power cut erases daily statistics.

The relative humidity of air and carbon dioxide and VOC level statistics

MyVallox Control - humidity

Relative humidity of air statistics for the past 24 hours. You can view the graph for a week or for a single day.| Carbon dioxide or VOC level statistics for the past week. You can view the graph for a week or  for a single day.

SETTINGS

Filter settings

  1. Select Settings > Filters.
  2. Select OK.
  3. The summary display of filter replacement shows the following information:
    • Reminder — Indicates whether the reminder is turned on or off or a special mode is in use.
    • Filters replaced — Indicates the date when the filters were last replaced.
    • Next reminder — Indicates the date when a reminder to replace the filters will next be shown.
    • Reminder interval — Indicates the filter replacement interval in months.
    • Automatic reset interval — Indicates the number of days that the filter reminder remains active.
    After this time period, the filter reminder is acknowledged automatically.

MyVallox Control - SETTINGS 2

Setting the Filter replacement reminder interval

  1. Select Settings > Filters.

  2. Select OK.

  3. Select Edit.

  4. Use the Arrow buttons to set the desired reminder interval in months in the Reminder interval field.
    The interval value can be between 1 and 12 months. The default setting is 6 months.

  5. Select OK.

Setting the filter reminder

  1. Select Settings > Filters.

  2. Select OK.

  3. Select Edit.

  4. Select Right arrow > Reminder.
    Select the status of the filter reminder:
    • On — The filter reminder is both turned on and acknowledged manually.
    • Off — The filter reminder is turned off.
    • Special mode — The filter reminder is both turned on and acknowledged manually or, at the latest, when the automatic reset interval ends.

  5. Select OK.

Setting the automatic reset interval for filters

  1. Select Settings > Filters.
  2. Select OK.
  3. Select Edit.
  4. Select the Right arrow > Automatic reset interval.
  5. Set the desired automatic reset period in days. The interval value can be between 1 and 60 days. The factory setting is 14 days.
  6. Select OK.

NOTE
The automatic reset interval for filters can only be set it the status of the reminder is set to special mode.
Setting the date the filters were last replaced
Instructions for replacing the filters are provided in the Maintenance section.
After replacing the filters, enter the replacement date.

  1. Select Settings > Filters.
  2. Select OK.
  3. Select Edit.
  4. Select Right arrow > Changing the filters.
  5. Select OK, if you want to update the filters as having been replaced today.
    NOTE
    Based on the set reminder interval, the unit will automatically set the maintenance reminder to provide a reminder to replace the filters at the due time.
    MyVallox Control - DISPLAY

Filter maintenance reminder
The maintenance reminder reminds you of the filter replacement with a pop-up window.
The message can be acknowledged by selecting OK.
You can postpone the reminder for one week by pressing the Back button.

DISPLAY SETTINGS

Setting the sleep time

  1. Select Settings > Display settings.
  2. Select OK.
  3. Use the Plus and Minus buttons to set the Sleep time.
  4. Select OK.
    MyVallox Control - brightness

TIP
The MyVallox Control panel automatically switches to the sleep mode when the pre-set Sleep time has elapsed. To reactivate the MyVallox Control panel, press any button.

Adjusting the display brightness

  1. Select Settings > Display settings.
  2. Select OK.
  3. Select Right arrow.
  4. Use the Plus and Minus buttons to set the display brightness.
  5. Select OK.

Selecting the user interface language

  1. Select Settings > Language.
  2. Select OK.
  3. Select your language.
  4. Select OK.

TIME AND DATE

Setting the time and date
The available time settings are:

  • Time
  • 24- or 12-hour clock
  • Automatic daylight saving time
  • Date
    NOTE
    The ventilation unit time will withstand a power cut of a few hours.

Setting the time

  1. Select Settings > Time and date.
  2. Select OK.
  3. Use the Plus and Minus buttons to set the hours.
  4. Select Right arrow.
  5. Use the Plus and Minus buttons to set the minutes.
  6. Select OK.

Selecting the 24- or 12-hour clock
The 24-hour clock is used by default. To use the 12-hour clock:

  1. Select Settings > Time and date.
  2. Select OK.
  3. Select Right arrow.
  4. Select Down arrow. The 24-Hour setting value is changed to Off.
  5. Select OK.

Automatic daylight saving time
By default, automatic daylight-saving time is turned on. To use the manual daylight saving time setting:

  1. Select Settings > Time and date.
  2. Select OK.
  3. Select Right arrow until the 3/4 display opens.
  4. Select Down arrow. The Daylight saving time setting value is changed to Off.
  5. Select OK.

Setting the date

  1. Select Settings > Time and date.
  2. Select OK.
  3. Select Right arrow until the 4/4 display opens.
  4. Use the Plus and Minus buttons to set the date.
  5. Select Right arrow.
  6. Use the Plus and Minus buttons to set the month.
  7. Select Right arrow.
  8. Use the Plus and Minus buttons to set the year.
  9. Select OK.

WEEK CLOCK
The week clock allows you to pre-set a weekly ventilation program for the ventilation unit. For each hour of the week, one of the following modes can be configured:

  • At home — The At home mode is used.
  • Away — The Away mode is used.
  • Boost — The Boost mode is used.
  • Empty — The previous mode is used.

NOTE
If you change the mode manually when the week clock is on, the selected mode will remain active until the week clock switches to the next mode in the program.
If ventilation is being controlled by the humidity, carbon dioxide or VOC sensors, they will adjust the fan speed regardless of whether a mode has been manually selected or selected by the week clock.

TIP
You can turn the week clock on or off by pressing the OK button on the Week clock display for a few seconds.

Setting and editing the weekly program

  1. Select Settings > Week clock on/off.
  2. Select OK.
  3. Select Edit the week clock.
  4. Select OK.
  5. Use the Right arrow button to select the desired day.
  6. Use the Down arrow button to select the desired time.
  7. Use the Select button to browse and select the ventilation mode that will be turned on at the chosen time. The icons are:
    MyVallox Control - program| At home mode.
    ---|---
    Away mode.
    Boost mode.
  8. Once you have selected the modes for the week clock, select Settings.
  9. Select OK, if you want to save the changes made to the week clock. Select Cancel, if you do not want to save the changes. Select Back, if you want to go back to editing the week clock.

Turning the week clock on

  1. Select Settings > Week clock off.
  2. Select OK.
  3. Select Settings.
  4. Select Turn on.
  5. Select Select.
  6. The control panel confirms that the week clock is turned on.

Turning the Week clock off

  1. Select Settings > Week clock on.
  2. Select OK.
  3. Select Turn off.
  4. Select OK.
  5. The control panel will confirm that the week clock is turned off.
  6. The week clock is now turned off. If you have set a weekly program, it will be saved in the unit.

Removing the week clock settings
To delete the weekly program settings:

  1. Select Settings > Week clock on or Week clock off.
  2. Select Remove all settings.
  3. Select OK to accept deletion of the weekly program.
    The weekly program has now been deleted.

Example of setting a weekly program
In this example, the following weekly program has been set:

  • Mon-Fri 8-17, Away .
  • Mon-Fri 17-7, At home.
  • Sat 8-17, At home.
  • Sat 18-20, At home with a ventilation boost needed for cooking, for example.
  • Sat 21-Mon 8, At home.

To set the week clock, proceed as follows:

  1. Open the week clock.
  2. Select Monday, and input the following settings:
  3. For 08:00, select the Away mode.
  4. For 17:00, select the At home mode.
  5. Then input the corresponding settings for the other weekdays.
  6. Then select Saturday, and input the following settings:
  7. For 18:00, select the Boost mode.
  8. For 21:00, select the At home mode.
  9. Ensure that the week clock is turned on.
  10. The weekly program has now been set.

NOTE
Do not set a ventilation mode separately for every hour. Only include into the week program hours when you want the ventilation mode to change.MyVallox
Control - clock 2

The figures above show the aforementioned settings in the week clock.

TURNING THE UNIT OFF
To turn the ventilation unit off:

  1. Select Settings> Turn unit off.
  2. Select OK.
  3. Accept the command by selecting OK.
  4. The ventilation unit has now been turned off.

IMPORTANT
In order to ensure that the indoor air presents no harm to health and remains optimal for the structures of the building, ventilation must be kept on without disruptions. It is recommended that ventilation be left turned on during long  holidays also. This keeps the indoor air fresh and prevents humidity from condensing in the ventilation ducts and structures. It also reduces the risk of moisture damage.
TIP
To re-start the ventilation unit, press any key.MyVallox Control -
UNIT

TROUBLESHOOTING
NOTE
Error messages are displayed on the control panel and in the MyVallox Home and MyVallox Cloud services.

FAULT CAUSE MEASURES
Error message: Extract air fan The extract air fan has stopped. Make sure

that the fan is not running. The fan cabling and operation must be checked and, where required, the fan must be replaced. Contact the service centre.
Error message: Supply air fan| The supply air fan has stopped.| Make sure that the fan is not running. The fan cabling and operation must be checked and, where required, the fan must be replaced. Contact the service centre.
Error message:
Temperature sensor 1/2/3/4/5| The temperature sensor Indicated on the user Interface has become damaged.| The sensor installation must be checked and, where required, the sensor must be replaced. Contact the service centre.
Error message:
High supply air temperature| The supply air temperature Is too high.| The operation of the post and additional heating resistor must be checked. Contact the service centre.
Error message:
Low supply air temperature| The supply air temperature is too low.| The operation of the post and additional heating resistor must be checked. Ensure that the resistors are turned on In the user Interface. Contact the service centre If necessary.
The ventilation unit is not working: the control panel is not working.| Power input to the unit is lost or the safety switch catch of the door is not touching the safety switch.| Check:
• The fuse in the fuse box
• The glass tube fuse in the unit. Contact the service centre.
• Press the safety switch all the way down and test if the unit can be turned on. If the unit can be turned on. ensure that the safety switch catch is touching the safety switch.
The ventilation unit is working, but the control panel is not working.| Either the control panel 24 VDC power is lost, or the control panel is damaged.| Check the cables from the unit to the control panel. Contact the service centre.

USER LEVEL DIAGRAMS

MyVallox Control - DIAGRAMS

www.vallox.com
Vallox Oy | Myllykyläntie 9-11 | 32200 LOIMAA | FINLAND

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

VALLOX User Manuals

Related Manuals