Ferono FTH-30 Universal Thermostat Instruction Manual

June 13, 2024
Ferono

Ferono FTH-30 Universal Thermostat

Installation Manual

Installation Manual

Product Summary

FTH-30 series of thermostats are mainly used to control the 2-pipe &3-speed fan coil and valve in the civil, commercial and industrial constructions.

Technical Parameter:

2.1 Power Supply: AC220V±10%, 50Hz.
2.2 Temperature Controlling Range: 5~35°C.
2.3 Standard Load: <3A (Resistive Load).
2.4 Power Consumption: <3W.
2.5 Sensing Element: NTC .
2.6 Temperature Controlling Precision: 0/-2°C.
2.7  Transportation Storage Environment: Temperature:-10~+55°C.
Relative Humidity: RH<85%(no condensation).
2.8 Working Environment Temperature:0~+50°C.
2.9 External Material: PC Engineering Plastic, Fire-resistant.
2.10 Dimension: 86×86×40.5 (mm).
2.11 Installation: Standard 86 Junction Box (Standard EU Junction Box).

Main Function

3.1 Large screen of LCD, English display, with blue backlight.
3.2  Display the room temperature, clock and week simultaneously
3.3 With week programmable function, 4 time periods per day for the setting of temperature and starting time
3.4 24-hours timer switch(optional).
3.5 8-hours of sleep function (optional).
3.6 Fan controlled anti-condensation, anti-cold air function.
3.7 With temperature correction function.
3.8 Backup function, can recover the foregoing working state before power off.
3.9 With key lock function, can prevent the mis-operation.
3.10 Hotel special card (optional), no card into the economic operation mode.

Installation Explanation

4.1 Please do the operations of installation by professionals after the power is cut off.
4.2 Choose the correct installation location, do not install the product under direct sunshine or near high humidity areas.
4.3 Working Environment Temperature: -10°C~+50.0°C.
4.4 When it need be installed in the high humidity places, such as the bathroom, please use a special waterproof cover.
4.5 Height above sea level: 2000m at most

Installation Step

5.1 Detach the panel and base according to the diagram, then loose the wire base of power panel and take down the wire.
5.2 Firmly connect the power wire and load wire with the correspondent terminals according to the wiring diagram on this manual.
5.3 Fix the base into the pre-buried standard 86 junction box by the screws in the supplied accessories.
5.4 Insert the wire into the power panel, and attach the front cover to the base according to the marked direction.

Installation Diagram

Installation diagram of back cover

Installation Diagram

External Dimension

Product Summary

Product Summary

  1. Power Restored

  2. Time Period Display

  3. Set Temperature
    System Clock

  4. Weekday Display

  5. Mode/Confirmation Key

  6. Increasing Key

  7. Decreasing Key

  8. On/Off/Fan-speed Key

  9. Water Valve Symbol

  10. No card Mark

  11. Timer On

  12. Timer Off

  13. Sleep Mode

  14. Room Temperature

  15. Key Lock.

  16. Fan Speed

  17. Working Mode

Product Summary

ON-OFF Operation

Under standby state, long press key over 3 seconds to turn on the system; under power-on state, long-press key over 3 seconds to turn off the system.

Product Summary

System Running Operation

  • Under power on state, short press key to circularly switch the system running mode:

Ventilation Mode Constant Mode Heating Mode Coolmg Mod

  • With week programmable function thermostat under power on state, long press key to switch between auto (time period) running mode and manual temperature setting running mode.
  • Without week programmable function thermostat under power on state, long press key enter timer off set condition.
  • Under power on state, short press key to circularly switch the fan speed:

Auto Fan Speed AUTO Low Speed Mid Speed High Speed

  • Under power on state, short(long)press ▲ key or ▼ key change the set temperature.
    Notice: Card type thermostat only have card status change set temperature.

Set Timer On/Off (Timing thermostat

  • Under standby state, press key enter timer on set interface, press ▲key or press ▼key to change the set time, and the adjustive step is half of one hour (30 minutes), after finish press key confirm.
  • Under power on state, long press key enter timer off set interface, press ▲key or press ▼key to change the set time, and the adjustive step is half of one hour (30 minutes), after finish press key confirm.
  • Timing when the time is up, after automatic startup will operate by the last time startup working mode and set temperature.
  • If you want to cancel the timer switch, please timed time settings for zero; after artificial startup will automatically cancel the current boot settings and after artificial shutdown will cancel timer shut off setting.

Timing on set and display interface

Timing off set interface

Enter Sleep Mode

  • Under power on state, long press key and key at the same time, after display sleep mode mark release the key will enter sleep mode operation, the same operation can cancel the sleep mode.
  • Sleep mode at a constant temperature, ventilation mode is invalid; after into sleep mode clients can change set temperature, but the temperature do not be saved, after finish sleep mode return to normal mode of set temperature.

Sleeping mode display interface

Keylock interface under standby state

Default Value Recovery Interface

Lock (Unlock) Keyboard

  • Under the standby or power on state, press ▲ and ▼ keys at the same time over 3 seconds, loose them when displaying symbol and then keyboard is locked; you can unlock the keyboard by doing the same operations.

▲Recover the default value

  • Under the power on state, press , ▲and▼ at the same time over 3 seconds, then loose them when the default value recovery interface is displayed. And the interface will show the software version of thermostat, as the version 2.1 shown on the picture;
  • Press key to confirm, the display interface will restore to the standby interface 5 seconds later, which means the operation is  successful; if you only want to check the version, press key to return the power on state.

▲Setting System Parameters

Program State Interface

Temperature Correction State Interface

  • Under power on state, press and ▼ at the same time 3 seconds;
  • Enter setting state, programmable menu F(blinking display) is under selected;
  • Short press ▲ key(or short press ▼ key) switch menu options F0-F6;
  • Short press key enter the parameter settings state of corresponding menu;
  • Press ▲ key(or press ▼ key)change parameter value;
  • Short press confirm this setting, return to the previous menu or select the next parameter;
  • Short press key cancel this setting, and return to the previous menu.

Week Programmable Thermostats Menu Function and Explanation

Menu Function Range Explanation
F0 System Time Adjustment Week 1-1

parameter, press             key 10 confirm and the internal second count will be !eared at the same time, which can realize the precise time set.
Hour| 0-23
Minute| o-s9
F1| Set the data of 4 time periods (Pl – P4) from the 1st day to 5th day| Starting Hour| 0-23| The starting times of 4 time periods (Pl,.,.P4) are without sequence, one time period will bethrown away if you set the same starting time, that is, the next time period will screen the previous one out.
Starting Minute| 0-59
Setting

Temperature

| 5-35
F2| Set the time periods of the6thday| The same as F1
F3| Set the time periods of the 7th day| The same as F1
F4| Fan under Control or not| 0| Fan out of control
1 {Default)| Fan under Control
FS| Power on Recover Function| 0 (Default)| Power-on recovery function is forbidden
1| Power-on recovery function is available.
F6| Room Temperature Correction| -5·c- +5·c| Increase or decrease the room temperature by O.S”C

Week Programmable Thermostat System Default Value in the Period of Constant, Heating and Cooling

Period| Starling
Time| Temperature Set (t)
---|---|---
Monday – Friday| Saturday, Sunday
Constant| Heating| Cooling| Constant| Heating| Cooling
P1:     6:00-8:00| 6:00| 20| 20| 24| 20| 20| 24
P2:     8:00-16:00| 8:00| 22| 18| 26| 22| 18| 26
P3:     16:00-22:00| 16:00| 20| 20| 24| 20| 20| 24
P4:     22:00-next 6:00| 22:00| 24| 18| 26| 24| 18| 26

Timing Thermostat Menu Function and Explanation

Menu Function Set range Explanation
F0 System Time Adjustment Week 1 – 7

press ‘Stec key to confirm, the inetrnal second count will be cleared at the same time, which can realize the precise time set.
Hour| 0 – 23
Minute| 0 – 59
F1| Fan under control se.| 0| Fan out of control
1 ‘Default)| Fan under control
F2| Power-on recovery set| 0 (Default Value)| Power-on recovery function is forbidden
1| Power-on recovery function is available
F3| Adjust room temperature| -5°C – +5°C| The room temperature will be increased or reduced by 0.55°C

Insert Card Thermostat Menu Function and Explanation

Menu Function Set range Explanation
F0 System Time Adjustment Week 1- 7

press Glib key to confirm, the internal second count will be cleared at the same time, which can realize the precise time set.
Hour| 0 – 23
Minute| 0 – 59
F1| No card heating set temperature| 5°C-22°C (Default 18°C)| Under no card status system will adjust the set temperature into the corresponding economic operation temperature, to achieve no card energy saving operation.
F2| No card cooling set temperature| 24°C-35°C (Default 26°C)
F3| No card thermostat set temperature| 20C-26°C (Default 22°C)
F4| Fan under control set| 0| Fan out of control
1 (Default Value)| Fan under control
F5| Power-On recovery set| 0 (Default Value)| Power-on recovery function is forbidden
1| Power-on recovery function is available
F6| Adjust room
temperature| 5°C – +5°C| The room temperature will be increased or reduced by 0.5°C

Insert Card Function Explanation

  • If the clients select the insert card type thermostat, please properly connected to the card in accordance with wiring diagram in the product bed. No card mark is displayed on the LCD panel when no card, the system into the economic operation mode, the set temperature pre-programmed by the staff.
  • A card into the normal operating mode, the user can set the temperature and wind speed. Economic model without card, the user can switch, but can not change the set temperature, can not set system parameters and recovery system.

System Function Explanation:

Valve Control

T: Room Temperature

S: Set Temperature

Es: Converted Deviation (Default 3°C)

Functional Diagram of Heating, Cooling and Constant Mode

Fan Control

T : Room Temperature S : Set Temperature

Es: Converted Deviation (Default 3°C)

Fan Speed Switch Diagram of Heating/Cooling Mode

Sleep Mode

Sleep Mode

The solution of abnormal problems

Please check again if the N-wire and L-wire are connected correctly; if the cooling and heating running mode set is in accordance with the requirements.

Faxlion Range Expbnatlon

Display off when the

power is on.

| Did not switch on the ON/OFF key| Long press Key
There Is no display when power on| Terminal **1  is ****not connected ****with**

L-wire,Temilnal 7 is not connected with N.wire

| Make sure the power of terminal 1 and 7 is correct.
The connection of LCD Main Board and drive power are loose.| Check the wires.
The actual fan speed does not comply with the display.| The connecting sequence of terminal 2, 3 and a is wrong| Check the external lines.
Normal display, but wrong control| The wires are not connected well or loose.| Check the wires
The wire connection Is wrong| Check the external lines.
Room temperature (Measured temperature) deviation| Temperature has not been adjusted.

Adj

| dust the measured temperature again
NTC (Sensor)| Check the sensor
The Installation location is unsuitable| Improve the installation environment.
Display trouble code Ertl| Internal sensor goes wrong.| Exchange the internal sensor

Notice

11.1 Please read the manual carefully before using, if you have any questions, please contact with the professional engineer of our company;
11.2 This thermostat must have individual electrical power control equipment. If you will not use it for a long time(over one month), please cut off the electrical power;
11.3The thermostat should be installed correctly by the professionals according to the manual;
11.4 Please don’t install the thermostat near the high temperature heat source or in bad environment;
11.5 Please make sure the power is the same as the voltage marked on the controller before installation;
11.6 The functions and specification of thermostat will be updated gradually without further notice;

Warning:

The symbol means the unit is being installed, it may cause electrical shock hazard during maintaining, so please make sure it is operated by the professional technical worker.

Read User Manual Online (PDF format)