About this document

  • Please read carefully and keep in a safe place.
  • Under copyright. Reproduction either in whole or in part only with our consent.
  • Subject to change in the interest of technical progress.

Symbols

Hazard warning!

Reference to other information in the document.

General safety precautions

Disconnect the power supply before attempting any work on the sensor.

  • During installation, the electric power cable being connected must not be live. Therefore, switch off the power first and use a voltage tester to make sure the wiring is off-circuit.
  • Installing the sensor involves work on the mains power supply. This work must therefore be carried out professionally in accordance with national wiring regulations and electrical operating conditions.
  • Only use genuine replacement parts
  • Repairs may only be made by specialist workshops.

IR Quattro HD-2  DALI-2 IPD

Proper use

  • Sensor for ceiling mounting indoors.
  • Connection to a DALI bus system.

The IR Quattro HD-2 DALI-2 IPD provides high-resolution, highly sensitive motion detection. The square detection zone can be set with absolute precision. The sensor is particularly suitable for offices, classrooms and large industrial spaces.

UP: concealed version
AP: surface-mounted version

Package contents (Fig. 3.1, Fig. 3.4)

Product dimensions (Fig. 3.2, Fig. 3.5)

Product components (Fig. 3.3, Fig. 3.6)

A Surface-mounting adapter
B Load module
C Connecting terminal
D Sensor module
E Reach adjustment

Detection zone (Fig. 3.7)

Technical specifications

  • Dimensions (H × W × D)
    Concealed (UP): 103 × 103 × 69 mm
    Surface-mounted (AP): 123 × 123 × 64 mm

  • Mounting height: 2.5-10 m

  • Angle of coverage: 360°

  • IR-Quattro HD-2 reach (mounted at a height of 2.8 m):
    presence 9 × 9 m
    max. 24 × 24 m

  • Sensor values: Light measurement,
    Temperature: 0-40°C,
    Relative humidity: 0-100%

  • Temperature range: 0°C to +40°C

  • IP rating: IP20

  • Bluetooth frequency: 2.4-2.48 GHz

  • Bluetooth transmission power: 5 dBm / 3 mW

  • Power consumption via DALI (12 – 22.5 V DC, no SELV):

    • Max. current consumption in accordance with IEC 62386-101: 84 mA / 42 users
    • Max. current consumption at an input voltage of 10 V in regular operation:* 32 mA / 16 users
    • Typical current consumption at an input voltage of 16 V in regular operation:* 19 mA / 10 users
  • DALI start-up time: < 1 s

  • These values will not be exceeded in regular operation and can be used as the basis for planning.

Electrical connection

DA+ = Connection to the DALI BUS (brown)

DA- = Connection to the DALI BUS (blue)

Surface-mounted connection (Fig. 4.1)
Concealed connection (Fig. 4.2)

Installation

  • Check all components for damage.
  • Do not use the product if it is damaged.
  • Select an appropriate mounting location, taking the reach and motion detection into consideration. (Fig. 3.7)

Mounting procedure

  • Switch off power supply (Fig. 4.1/4.2)

Concealed mounting

  • Make connection. (Fig. 5.1/4.2)
  • Firmly screw load module into mounting box. (Fig. 5.2)
  • Fit magnetic sensor module on frame. (Fig. 5.3)
  • Switch ON power supply. (Fig. 5.3)
  • Make settings.
    “6. Function and settings”

Surface mounting

  • Mark drill holes and drill. (Fig. 5.4)
  • Feed through cable. Screw load module into place. (Fig. 5.5)
  • Make connection. (Fig. 5.6/4.1)
  • Break out the mounting tab. (Fig. 5.7)
  • Fit surface-mounting adapter. (Fig. 5.8)
  • Fit magnetic sensor module. (Fig. 5.9)
  • Switch ON power supply. (Fig. 5.9)
  • Make settings.
    “6. Function and settings”

Function and settings

The sensor is put into operation in accordance with the applicable DALI 2 standard. All functions and commands of the DALI standard IEC 62386 Part 101, Part 103, Part 303 and Part 304 are available.

  • All sensor values (motion, light level, temperature and humidity) can be requested from the DALI-2 Application Controller.
  • Automatic or time-based cyclical transmission can also be selected for motion and light levels.

You will find detailed information in the interface description on the Internet at: www.steinel.de

The IR Quattro HD-2 DALI2 IPD is intend- GB ed for connection to a DALI2 Application Controller (APC). The Bluetooth functionality is only intended for configuration via the Steinel Connect App. In addition to the DALI interface, this provides another option for setting up the input device.

Steinel Connect app
To read off the sensor values via smartphone or tablet, you must download the STEINEL Connect app from your app store. You will need a Bluetooth-capable smartphone or tablet.

LED function

Start up:
LED flashes blue rapidly for 10 seconds.

Initialisation:
LED permanently lights up blue.

Normal mode: LED OFF.

Identification
LED flashes blue slowly.

Firmware update: LED flashes cyan rapidly.

No application available
LED permanently lights up cyan.

Test mode, movement:
LED flashes green.

Error:
The LED flashes red rapidly.

Setting detection

The detection zone can also be set via the potentiometer (E) on the back of the sensor module in accordance with the table. (Fig. 3.7/6.1)

The sensitivity of the four pyros (A to D) can be set via the DALI bus.

Letters A to D are shown underneath the sensor housing. The letters designate the direction of detection the sensitivity setting relates to.

You will find detailed information in the interface description on the Internet at: www.steinel.de

Maintenance and care

Hazard from electrical power.

Contact between water and live parts can result in electrical shock, burns or death.

  • Only clean tool in a dry state.

Risk of damage to property!

Using the wrong detergent can damage the light.

  • Clean unit with a moist cloth without detergent.

Troubleshooting

Light does not switch ON.

  • No supply voltage.
    • Check supply voltage
  • No presence detection.
    • Ensure unobstructed sensor vision.
    • Check detection zone.

Lights do not switch OFF.

  • Objects moving in the detection zone.
    • Check detection zone.

Sensor switches OFF despite persons being present.

  • Reach set too low.
    • Change reach.

Light switches ON despite no persons being present.

  • Movement within adjacent rooms and floor levels.
    • Adjust detection zone via potentiometer.
    • Reduce sensitivity

Sensor not connecting with the app.

  • App or smartphone system crash.
    • Restart mobile end device.

Disposal

Electrical and electronic equipment, accessories and packaging must be recycled in an environmentally compatible manner.

Do not dispose of electrical and electronic equipment as domestic waste.

EU countries only

Under the current European Directive on Waste Electrical and Electronic Equipment and its implementation in national law, electrical and electronic equipment no longer suitable for use must be collected separately and recycled in an environmentally compatible manner.

Conformity

STEINEL Vertrieb GmbH hereby declares that the IR Quattro HD-2 DALI-2 IPD radio equipment type conforms to Directive 2014/53/EU. The full wording of the EU Declaration of Conformity is available for downloading from the following Internet address: www.steinel.de

Manufacturer’s Warranty

As purchaser, you are entitled to your statutory rights against the vendor. If these rights exist in your country, they are neither curtailed nor restricted by our Warranty Declaration. We guarantee that your STEINEL Professional sensor product will remain in perfect condition and proper working order for a period of 5 years. We guarantee that this product is free from material-, manufacturing- and design flaws. In addition, we guarantee that all electronic components and cables function in the proper manner and that all materials used and their surfaces are without defects.

Making Claims

If you wish to make a claim, please send your product complete and carriage paid with the original receipt of purchase, which must show the date of purchase and product designation, either to your retailer or contact us at STEINEL (UK) Limited, 25 Manasty Road, Axis Park, Orton Southgate, Peterborough, PE2 6UP , for a returns number. For this reason, we recommend that you keep your receipt of purchase in a safe place until the warranty period expires. STEINEL shall assume no liability for the costs or risks involved in returning a product.

For information on making claims under the terms of the warranty, please go to www.steinel-professional.de/garantie

If you have a warranty claim or would like to ask any question regarding your product, you are welcome to call us at any time on our Service Hotline 01733 366700.

STEINEL Vertrieb GmbH
Dieselstraße 80-84
33442 Herzebrock-Clarholz
Tel: +49/5245/448-188
www.steinel.de

Map and QR Code

110083392 01/2022 / Subject to technical modification without notice.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals