ZITON ZP787-3 Addressable Outdoor Manual Call Point Installation Guide
- June 13, 2024
- ZITON
Table of Contents
ZITON ZP787-3 Addressable Outdoor Manual Call Point
Product Usage Instructions
Installation
Caution: This product must be installed by qualified personnel adhering to the CEN/TS 54-14 standard and any applicable local regulations or ordinances. This product is designed for surface mounting and cannot be flush mounted.
- Set the device address using the seven-segment DIP switch (SW1). Each switch segment represents a value, and the address is the sum of all the switch segments in the ON position. The switch can be set to represent any address from 1 to 127.
- Install the backbox by using the provided screws. Bring the field wiring into the backbox and cover unused holes with the provided plugs.
- Make the wiring connections as shown in Figure 2.
- Slide the front housing onto the backbox and press to snap them together. For additional security, secure the front housing at the top and bottom using the provided screws.
Description
The ZP787-3 Addressable Outdoor Manual Call Point (MCP) is used to manually initiate a fire alarm. It is designed for outdoor use and features an IP67 enclosure. Available models are shown in the table below.
Table 1: Available models
Number | Description |
---|---|
ZP787-3 | Addressable Outdoor Manual Call Point (MCP), Ziton |
ZP787-3S30 | Addressable Outdoor Manual Call Point (MCP), Chubb |
The MCP is shipped with a four-way connector, a test key, and an EN 54 universal glass. A red LED on the front of the unit displays its status:
- Off = normal
- Flashing = active
Figures
Figure 1: Product illustration
Figure 2: Wiring diagram
- Loop + IN
- Loop − IN
- Loop + OUT
- Loop − OUT
- Shield
Figure 3: Installing the front housing
- Front housing assembly
- Backbox
Figure 4: Removing the front housing
Figure 5: Test-reset and glass or resettable element replacement
- Test and reset procedure
- Replacing the glass or resettable element
Installation
Caution: This product must be installed by qualified personnel adhering to the CEN/TS 54-14 standard and any applicable local regulations or ordinances.
This product is designed for surface mounting and cannot be flush mounted.
To install the MCP, follow these general steps.
- Set the device address
- Install the backbox
- Wire the MCP
- Install the MCP
Setting the device address
Use the seven-segment DIP switch (SW1) to assign the device address. Each switch segment represents the value shown below. The address is the sum of all the switch segments in the ON position. The switch is used to set the device address in binary code. The switch may be set to represent any address from 1 to 127. For example, to select a device address of 007, set SW1-1, SW1-2, and SW1-3 to the ON position and the remaining switch segments to the OFF position.
Installing the backbox
The MCP is designed for surface mounting only. The unit is comprised of a front housing and a backbox, as shown in Figure 3.
- Install the backbox using the screws provided.
- Bring the field wiring into the backbox.
- Use the plugs provided to cover unused holes in the backbox.
Wiring
- Make the wiring connections shown in Figure 2.
Installing the front housing
- Slide the front housing onto the backbox, and then press to snap them together as shown in Figure 3.
- For additional security, the front housing can be secured at the top and bottom using the four screws provided.
- Test the MCP for proper operation using the test key shown in Figure 5, item 1.
Removing the front housing
- If the front housing is secured to the backbox using screws, remove the four screws (two at the top and two at the bottom).
- Insert a screwdriver into the slot as shown in Figure 4, and then twist the screwdriver to separate the housing from the backbox.
Maintenance
Figure 5, item 1 illustrates how to perform a test and reset for the device. Use the supplied test key to perform routine testing without breaking the glass element. Insert the key to simulate breaking the glass element; remove the key to reset the call point automatically. Figure 5, item 2 shows how to replace the glass or resettable element.
Caution: When changing the resettable element from glass to flexi, press the element after installation to confirm the operation.
Specifications
Operating voltage | 19.5 to 20.5 VDC pulsed |
---|
Current consumption Standby
Alarm
| ****
0.400 mA
0.450 mA
Addressing method| Seven segment DIP switch
Mounting| Surface
Wiring| Two-core loop
Construction
Material IP rating Colour Weight
Dimensions (H x W x D)
| ****
Moulded ABS IP67
Red 187 g
97.5 × 93 × 27.5 mm
Operating environment Temperature Storage temperature Relative humidity| ****
−25°C to +70°C
−20 to +70°C
10 to 95% noncondensing
Regulatory information
This section provides a summary on the declared performance according to the Construction Products Regulation (EU) 305/2011 and Delegated Regulations (EU) 157/2014 and (EU) 574/2014. For detailed information, see the product Declaration of Performance (available at firesecurityproducts.com).
Conformity| |
---|---|---
Notified/Approved body| 2831| 0832
Manufacturer| Honeywell Life Safety – Romania, Str Salmilor, Nr 2 bis.,
Lugoj, Romania RO 305500.
Authorized EU manufacturing representative:
Carrier Fire & Security B.V., Kelvinstraat 7, 6003 DH Weert, Netherlands.
Year of first CE marking| 19|
Year of first UKCA marking| 22|
Declaration of Performance number| 360-4211-0799
EN 54| EN 54-11|
Product type| Type A: for outdoor use
Product identification| See model number on product identification label
---|---
Intended use| See the product Declaration of Performance
Declared performance/s| See the product Declaration of Performance
| 2012/19/EU (WEEE Directive): Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union. For proper recycling, return this product to your local supplier upon the purchase of equivalent new equipment, or dispose of it at designated collection points. For more information see: recyclethis.info.
Contact information and product documentation
- For contact information or to download the latest product documentation, visit firesecurityproducts.com.
© 2022 Carrier. All rights reserved.