AIM AirBox Pressure Controller Box User Manual
- June 13, 2024
- AIM
Table of Contents
AIRBOX
USER MANUAL
AirBox Pressure Controller Box
THE INFORMATION CONTAINED HEREIN IS THE PROPERTY OF AIM ROBOTICS APS AND SHALL
NOT BE REPRODUCED IN WHOLE OR IN PART WITHOUT PRIOR WRITTEN APPROVAL BY AIM
ROBOTICS APS. THE INFORMATION IS SUBJECT TO CHANGES WITHOUT NOTICE AND SHOULD
NOT BE CONSTRUED AS A COMMITMENT BY AIM ROBOTICS APS. THIS MANUAL WILL BE
PERIODICALLY REVIEWED AND REVISED.
AIM ROBOTICS APS ASSUME NO RESPONSIBILITY FOR ANY ERRORS OR OMISSIONS IN THIS
DOCUMENT.
COPYRIGHT (C) 2022-2023 BY AIM ROBOTICS APS.
TECHNICAL DATA
- Full control via robot
- Over and Under Pressure monitor
- Intuitive URCap
Connection Diagram
1| White| Set Pressure I/O
2| Brown| +24VDC
3| Green| Vacuum Switch I/O
4| Yellow| Inlet Pressure Sensor
5| Grey| Outlet Pressure Sensor
6| Pink| N/C
7| Blue| GND
8| Red| N/C
M12 8-pin pinout
Technical Data at 24V DC and 20 °C
Dimensions| 220 x 75 x 192 mm 8,65 x 2.95 x 7.55 inch
Supply Voltage| 24 V DC ±10 % Ripple P-P 10 % or less
Current Consumption| Up to 1A
Air Input| Clean, dry air up to 8 bar 120 psi
Air Output| 0.1-7.0 bar 1.5-100 psi
Short Circuit Protection| Incorporated
Response time| 100 ms or less
Pressure Set Linearity| +/- 1% F.S. or less
Hysteresis| 0.5% F.S or less
Operating temperature| -10 to +55 °C 14 to +131 °F (No dew condensation or
icing)
IP Class| IP65 (IEC)
Housing Material| Aluminum 6061
Weight| 1800g 4.0lbs
Model # AB
URCap version ≥1.0
INSTALLATION
-
Place the box in a convenient place in near vicinity to the robot
-
Plug-in cable in AirBox and connect it to the control box I/O using the color schematic seen on the back of the AirBox or in the datasheet
-
In the I/O tab select Digital Output that matches where you connected the power. In this case DO4 as seen by the placement of brown wire in the illustration above.
SOFTWARE CONFIGURATION
- Install URCap *
- If password protected:
- Enter Manual Mode: Press and select manual
- Enter Password
- If not protected by password:
- Press and select Settings > System > URCaps
- Press symbol to add a new URCap: Navigate to a USB device and select Aim AirBox URCap
Accept when the robot prompts to restart before continuing.
* Multiple URCaps
- If multiple URCaps are installed the tool might not perform as intended.
- Some tools are programmed to take over and control the Tool IO and will not allow the Aim URCap to change the Tool IO.
- It is recommended to remove all other tool URCaps to avoid this OR ensure that Tool IO is controlled by the user and input manually entered as described in point 3. Installation of FD unit.
- If multiple URCaps are required, please use our Aim USB2RS485 kit.
INSTALLATION
AirBox Setup node in Installation
- Go to the installations tap.
- Go to the URCaps tap and choose AirBox setup.
General settings:
- Pressure Units: Select which unit you prefer. (Bar,PSI, hPa
- Dispence I/O: Select which analog output the output pressure-sensor is connected to. (White wire in control box).
- Inlet pressure sensor: Select which analog output the inlet pressure-sensor is connected to. (Yellow wire in control box).
- Vacuum I/O: Select which digital output the vacuum switch is connected to. (Green wire in control box).
- Outlet Pressure Sensor: select which analog output the inlet pressure-sensor is connected to. (Grey wire in control box).
Pressure Monitor:
- Inlet Pressure: This is to monitor the high pressure Input for the AirBox.
- Outlet Pressure: This is to monitor the pressure going out of the AirBox for the dispenser (around 4 bars).
Note:
If Inlet Pressure and/or Outlet pressure dosn’t fit what is applied, you can
callibrate the sensors under the “Advanced settings” tap
PROGRAMMING
AirBox under URCaps under Program
How to use the AirBox to dispense
- Go to URCaps
- Find AirBox tap. An AirBoxnode will pop up in the program, and a setting page will show
• Dispensing Pressure: This is where you insert how fast you want to dispense.
This number depends of the viscosity of your medium, but is usually around 4 bar.
• Prefeed Duration: Time the AirBox has to reach the desired pressure. This number is usually around 1 sec. This is done to assure a consistent flow when dispensing.
• Enable Vacuum Control: The vacuum is used to stop the dispenser from dripping. If enabled it will activate right before the program moves on from the “AirBoxnode”.
• Vacuum: amount of vacuum applied. around 20-40% should be fine.
• Vacuum Duration: This sets how long to hold the vacuum before moving on.
• Vacuum End Delay: Delay to avoid dripping do to internal delay in AirBox. (usually around 0.5 sec is enough).
Inside the “AirBoxnode” you add a move command from the program tree and set the waypoints you want.
AirBox Setup node in Installation
Preset:
The settings from the AirBoxnode page can also be set beforehand in the preset
settings tap under the AirBox setup in the installation tap. This makes it
allot easier if you have the same settings you want to use multiple times in a
program.
Go to the installation tap and chose URCaps and AirBox setup, and fill in
everything like from the previous page.
- Then, when you are done and want to use it in the program, just go to the program tap (see page 5) and find the AirBoxnode.
- In the AirBoxnode page you will find these the buttons:
- Click the box icon and the page will fill with the preset values.
CALIBRATION
AirBox Setup node in Installation
Advanced settings
Pressure Calibration Settings:
- Inlet Sensor Constant: Adjust this to fix the value of the Input Pressure in the “General Settings tap” so it matches the value of the applied pressure.
- Outlet sensor constant: Adjust this to fix the value of the outlet pressure in the “General Settings tap” so it matches the value of the set pressure for the dispenser when the dispenser is active
These values can also be seen in the dropdown toolbar at the top.
- Under-pressure setpoint: This allows for a pressure warning if the inlet pressure is under the set value
- Over-pressure setpoint: This allows for a pressure warning if the inlet pressure is over the set amount
- Action: Fill this with a URscript command to say whish action to be done when the above warnings happens
SAFETY
AVOID: Clamping between tips and work item
- Select the right (low) force settings in the safety system of the UR robot.
- Move slowly towards the work item.
AVOID: Entrapment of fingers / limbs
Entrapment of fingers or limbs can happen if the operator has extremities
within the robot’s movement area.
- If possible select the right (low) torque/force settings in the safety system of the robot.
- Whenever possible limit rotational range of joint 6.
- Rotate at low speeds or when clearance to robot links is small.
Never use frayed, damaged or deteriorated hoses.
- Always store hoses properly and away from heat sources or direct sunlight. A hose failure can cause serious injury.
- Hose Reels can decrease your chances of injury, as well as help hoses last longer.
Trip Hazards
Avoid trip hazards that can occur when hoses are left on walkways or underfoot
by paying close attention to the location of the air hoses in your facility
and placing them out of the way when not in use.
RECOMMENDATION
It is recommended that products from Aim Robotics are integrated into
compliance with the following standards, technical reports, and
specifications:
- ISO 10218-2:2012
- ISO 10218-1:2012
- §5.10 and one or more of the requirements in 5.10.2 to 5.10.5
- ISO 12100:2011
- ISO/TR 20218-1:2018
- ISO/TS 15066:2016
CERTIFICATION
EU Declaration of Incorporation in accordance with ISOi lEC 17050-1.2010
Manufacturer.| Aim Robotics ApS
Maskinvej 5
DK-2860 Seborg Denmark| CSR 40494197
www.am-robotics.com
Description and identification of the partially completed machine(s)
Product and Function:| Pneumatic dispensing controller
Model:| AirBox
Serial Number.| YEAR-model-sequential numbering restarting at 0 each year,
starting from 2022-AB-0000
Incorporation:
The Aim Robotics product shall only be put into service upon being integrated
into a final complete machine (robot system, cell or application), which
conforms with the provisions of the Machinery Directive and other applicable
Directives.
When this incomplete machine is integrated and becomes a complete machine, the
integrator is responsible for determining that the completed machine fulfils
all applicable Directives, updating the relevant harmonized standards, other
standards and documents.
It is declared that the above product, for what is supplied, fulfil the
following directives with reference to harmonised standards:
I. Machinery Directive 2006/42/EC: It is declared that the relevant technical
documentation has been compiled in accordance with Part B of Annex VII.
A. EN 12100:2010
II. EMC Directive 2014/30/EU
A.EN 61000-6-2:2005
B.EN 61000-6-4:2007/A1:2011
III. RoHS Directive 2011/65/EU
A. EN 50581:2012
IV. WEEE Directive 2012/19/EU
The relevant information on the partly completed machinery shall be
transmitted in response to a reasoned request by the national authorities.
Person authorized to compile the relevant technical documentation:
Mie Haraldsted, CEO| Aim Robotics ApS Maskinvej 5
DK-2860 Seborg Denmark
signature
Seborg,
Denmark
24.08.2022
DESIGNED IN DENMARK BY AIM ROBOTICS APS
AIM-ROBOTICS.COM / CONTACT@AIM-
ROBOTICS.COM
ORIGINAL INSTRUCTIONS (EN) VERSION 1.0
Documents / Resources
| AIM
AirBox Pressure Controller
Box
[pdf] User Manual
AirBox Pressure Controller Box, AirBox, Pressure Controller Box, Controller
Box, Box
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>