RAB EXIT-NY-E LED Exit Sign Instructions
- June 13, 2024
- RAB
Table of Contents
Instructions
EXIT-NY-E LED Exit Sign
IMPORTANT
READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN THESE INSTRUCTIONS FOR
FUTURE REFERENCE.
RAB fixtures must be wired in accordance with the National Electrical Code and
all applicable local codes. Proper grounding is required for safety. THIS
PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE
BY A PERSON FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND
THE HAZARDS INVOLVED.
» When revamping, only use lamps specified in the exit. Using other lamp types
may result in transformer damage or unsafe conditions.
– Battery (when applicable) in the unit may not be fully charged. After
electricity is connected to the unit, let the battery charge up format least
24 hrs. The normal operation of the unit should then take effect.
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be
followed including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
- Do not use outdoors.
- Do not mount near gas or electric heaters.
- Use caution when handling batteries. Avoid possible shorting.
- Equipment should be mounted in locations and at heights where it will not be subject to tampering by unauthorized personnel.
- The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
- Do not use this equipment for other than its intended use.
- Before wiring to power supply, tum off electricity at fuse or circuit breaker.
- Consult local building code for approved wiring and installation.
- Installation and servicing should be performed by qualified personnel.
Installation
GENERAL
This exit is shipped with an EXTRA FACE PLATE & RED LENS to make the sign
double faced. Replace the BACK PLATE with the extra face plate & lens at the
start of the installation process if the application calls for a double-face
sign.
CEILING or END MOUNT
-
Slide out front exit panel face plate & lens/filter by removing the screw on the bottom of the unit.
-
Remove the (3) KOs from either the side (forfend mount) or top (for ceiling mount) of the fixture that lines up with holes on the CANOPY/J-BOX COVER. (Note: For CEILING MOUNT, you must remove the INTERNAL TRANSFORMER COVER on the
inside top of the fixture. Please re-insert after installation.) 3.Using the (2) 1/2″ long 8-32 screws and lock nuts, attach the canopy to the proper area of the exit sign (as shown in Figure 1). -
Determine if ADAPTER PLATE will be needed for proper orientation of the exit sign. If it is needed, install it now remaining (2) 1/2″ long 8-32 screws (as shown in Figure 2).
-
Mount sign to the J-Box using the (2) 1-1/2″ long 8-32 screws (Figure 2), making sure to route the AC SUPPLY wires into the fixture. Use the included 20″ jumper wires if needed for this step.
-
Connect AC SUPPLY WIRES to fixture input wires. BLACK is 120V, RED is 277V, and WHITE is COM.
-
Connect bi-pin BATTERY CONNECTOR to PC BOARD (when applicable).
-
Replace front panel and red lens and secure with bottom screw.
|
---|---
BACKMOUNTING
- Slide out the front exit panel face plate and lens/filter by removing the screw on the bottom of the unit.
- Determine which mounting holes will be used to mount the fixture to J-BOX and then punch out proper K/Os from the K/O pattern on the back panel of the housing.
- Mount sign to the J-BOX using the (2) 1-1/2″ long 8-32 screws, making sure to route the AC SUPPLY wires into the fixture. Use the included 20″ jumper wires if needed for this step.
- Connect AC SUPPLY wires to fixture input wires. BLACK is 120V, RED is 277V, and WHITE is COM.
- Connect bi-pin BATTERY CONNECTOR to PC BOARD (when applicable).
- Replace front panel and red lens and secure with bottom screw.
WIRING DIAGRAMS
NOTE: Properly insulate the unused lead with a wire nut or other approved
means.
WARNING: Unused wires must be capped using enclosed wire nuts.
RAB Lighting is committed to creating high-quality, affordable, well-designed
and energy-efficient LED lighting and controls that make it easy for
electricians to install and end users to save energy.
We’d love to hear your comments. Please call the Marketing Department at
888-RAB-1000 or email:
marketing@rablighting.com
© 2023 RAB LIGHTING Inc.
Cranbury, New Jersey 08512 USA
EXNY3-IN-0123
Easy Answers
rablighting.com Visit our website for product info
Tech Help Line
Call our experts: 888 722-1000
e-mail Answered promptly –
sales@rablighting.com
Free Lighting Layouts
Answered online or by request
RAB WARRANTY: MB’s warranty is subject to all terms and conditions found
at rablighting.com/warranty.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>