TECH PS-10 230 Thermostatic Valve Controller Instruction Manual

June 13, 2024
TECH

TECH PS-10 230 Thermostatic Valve Controller

  • The PS-10 230 is a thermostatic valve controller dedicated for underfloor heating system. Is equipped with:
    • 9 voltage outputs (8 outputs dedicated to support thermostatic actuators and 1 output dedicated as pump)
    • 1 voltage-free contact
    • 2 Two-state inputs
  • The operating conditions of individual devices connected to the controller are programmed in the Sinum Central device. It is designed to be mounted on a DIN rail. It communicates with the Sinum central device using radio signal.

Description

  • Power supply diode
  • Manual mode diode – Current status of the voltage-free output (ON/OFF)
  • Communication
  • 1-8 – Current status of the voltage output (ON/OFF)
  1. Manual operation button
  2. Registration button
  3. Voltage-free contact output
  4. Voltage outputs
  5. Power supply
  6. Two-state inputs

Manual mode

In order to switch to the manual operation mode, press the manual operation button (1). The registration button (2) is used to switch between the controlled outputs in the manual mode. Using the button (1) (pressing it once), the user forces a change of the status (ON / OFF) – if the process has been successful, it is confirmed by a light signal from the LED labelled 1-8. When the manual mode is on, it is impossible to control the contact via the website or the application. To disable the manual mode, press the button (1) again and hold it for 1-2 seconds. Once the manual mode has been switched off, all the output status LEDs go off and resume the state set in the Sinum application.

How to register the device in the sinum system

When registering the device, it is recommended to use the heating creator. To run the creator, enter the address of the Sinum Central device in the browser and log in to the device. In the main panel, click the Settings > System > Heating creator and after starting it, add the device by clicking the registration button (2) at the right moment. Then follow the creator to create virtual thermostats, among other things. The device can be registered also by going to Settings > Devices > SBUS Devices > (+) , then briefly press the registration button (2) on the device. Each two-state input and voltage output will be added separately, in addition, virtual thermostats must be created and assigned to the appropriate room.

Technical data

  • Power supply: 230V ±10% /50Hz
  • Max. power consumption: 4W
  • Operation temperature: 5°C ÷ 50°C
  • Pump max. output load: 0,5A
  • Rated load of the voltage-free contact: 230V AC / 0,5A (AC1) * 24V DC / 0,5A (DC1) **
  • Operation frequency: 868 MHz
  • Max. transmission power: 25 mW

EU Declaration of conformity

  • Tech Sterowniki II Sp. z o.o. , ul. Biała Droga 34, Wieprz (34-122) Hereby, we declare under our sole responsibility that the thermostatic valve controller PS-10 230 is compliant with Directive 2014/53/EU

  • Wieprz, 01.07.2023

  • AC1 load category: single-phase, resistive or slightly inductive AC load

  • DC1 load category: direct current, resistive or slightly inductive load.

  • The full text of the EU declaration of conformity and the user manual are available after scanning the QR code or at

  • www.tech-controllers.com/manuals.

Notes

TECH Controllers is not responsible for any damages resulting from improper use of the system. The range depends on the conditions in which the device is used and the structure and materials used in the object construction. The manufacturer reserves the right to improve devices, update software and related documentation. The graphics are provided for illustration purposes only and may differ slightly from the actual look. The diagrams serve as examples. All changes are updated on an ongoing basis on the manufacturer’s website. Before using the device for the first time, read the following regulations carefully. Not obeying these instructions may lead to personal injuries or controller damage. The device should be installed by a qualified person. It is not intended to be operated by children. It is a live electrical device. Make sure the device is disconnected from the mains before performing any activities involving the power supply (plugging cables, installing the device etc.). The device is not water resistant.The product may not be disposed of to household waste containers. The user is obliged to transfer their used equipment to a collection point where all electric and electronic components will be recycled.

CONTACT

CZ

SK

DE

NL

RO

HU

ES

UA

RU

www.techsterowniki.pl/manuals

www.tech-controllers.com/manuals

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

TECH User Manuals

Related Manuals