Watts 800M4 Series Pressure Vacuum Breaker Assemblies Owner’s Manual
- June 13, 2024
- WATTS
Table of Contents
Watts 800M4 Series Pressure Vacuum Breaker Assemblies
Product Information
The product is a Series 800M4 and LF800M4 Pressure Vacuum Breaker Assembly. It is designed to prevent backflow and protect against contamination of potable water supply. The assembly includes a freeze sensor that alerts building/irrigation management systems when the temperature nears the freezing point. The product should be installed by a licensed contractor in accordance with local building and plumbing codes. It is important to consult the local codes prior to installation, as modifications may be required.
The freeze sensor included in the assembly provides alerts about possible freeze events, but it cannot prevent freeze events from occurring. User action is required to prevent freeze conditions from causing damage to the product or property.
For installations in Australia and New Zealand, line strainers should be installed between the upstream shutoff valve and the inlet of the backflow preventer. In fire sprinkler systems, all mechanical checks, including alarm checks and backflow preventers, should be flow tested and inspected internally according to NFPA 13 and NFPA 25.
Product Usage Instructions
Testing: For field testing procedure, refer to Watts installation sheets ISTKDL, ISTK9A, ISTK99D, and ISTK99E at www.watts.com. For repair kits and service parts, refer to the Backflow Prevention Products Repair Kits & Service Parts price list PLRPBPD at www.watts.com. For technical assistance, contact your local Watts representative.
Freeze Sensor Activation: An addon connection kit is required to activate the freeze sensor. Without the connection kit, the sensor is a passive component with no communication with any other device. The connection kit can also be used to retrofit existing installations. Refer to the Addon/Retrofit Sensor Connection Kit for ordering details.
Installation Guidelines:
- Pressure – Temperature: The working temperature range is between 15 psi (103 kPa) and 150 psi (10.3 bar).
- Startup Procedure:
1. Close shutoff No. 2 (outlet).
2. Open shutoff No. 1 (inlet) until water discharges from the bonnet, then quickly open to pressurize the valve.
3. Open shutoff No. 2.
- Freeze Protection: Use the following procedure to purge the PVB assembly with pressurized air (refer to Figure 2):
1. Close the main shutoff valve.
2. Open the upstream drain, test cocks, and isolation ball valves to an angle to drain ball valves and prevent casting damage.
Please note that proper installation, operation, and maintenance of the PVB assembly should comply with all required instructions, codes, and regulations. Watts is not responsible for the failure of alerts due to connectivity or power issues.
Series 800M4, LF800M4
Pressure Vacuum Breaker Assemblies
WARNING:
Read this Manual BEFORE using this equipment. Failure to read and follow
all safety and use information can result in death, serious personal injury,
property damage, or damage to the equipment. Keep this Manual for future
reference.
WARNING:
Local building or plumbing codes may require modifications to the information
provided. You are required to consult the local building and plumbing codes
prior to installation. If the information provided here is not consistent with
local building or plumbing codes, the local codes should be followed. This
product must be installed by a licensed contractor in accordance with local
codes and ordinances.
WARNING:
Need for Periodic Inspection/Maintenance: This product must be tested
periodically in compliance with local codes, but at least once per year or
more as service conditions warrant. All products must be retested once
maintenance has been performed. Corrosive water conditions and/or unauthorized
adjustments or repair could render the product ineffective for the service
intended. Regular checking and cleaning of the product’s internal and external
components helps assure maximum life and proper product function.
WARNING:
The Freeze sensor solely provides alerts about a possible freeze event and
cannot prevent a freeze event from occurring. User action is required to
prevent freeze conditions from causing product and/or property damage.
NOTICE:
For Australia and New Zealand, line strainers should be installed between the
upstream shutoff valve and the inlet of the backflow preventer. If installed
on a fire sprinkler system, all mechanical checks, such as alarm checks and
backflow preventers, should be flow tested and inspected internally in
accordance with NFPA 13 and NFPA 25.
Testing
For field testing procedure, refer to Watts installation sheets IS-TK-DL, IS-
TK-9A, IS-TK-99D, and IS-TK-99E at www.watts.com.
For other repair kits and service parts, refer to the Backflow Prevention
Products Repair Kits & Service Parts price list PL-RP-BPD at
www.watts.com.
For technical assistance contact your local Watts representative.
800M4FR-FZ
Series 800M4 and LF800M4 antisiphon PVBs (FR and QT versions) include a
freezer sensor to signal building/irrigation management systems when
temperature nears the freezing point.
NOTICE:
An add-on connection kit is required to activate the freeze sensor. Without
the connection kit, the sensor is a passive component that has no
communication with any other device. (The kit can also be used to retrofit
existing installations. See “Add-on/Retrofit Sensor Connection Kit,” for
ordering details.)
NOTICE:
Use of the freeze sensor and activation kit with FZ models does not replace
the need to comply with all required instructions, codes, and regulations
related to installation, operation, and maintenance of the PVB assembly. Watts
is not responsible for the failure of alerts due to connectivity or power
issues.
Installation Guidelines
Pressure Temperature
- Working Temperature: 33°F to 140°F (0.5°C to 60°C)
- Maximum Pressure: 150 psi (10.3 bar)
- Minimum Pressure: 15 psi (103 kPa)
Requirements
- Install 12″ above the highest point of downstream piping. (See Figure 1.)
NOTICE: Installation as stated above is essential for proper operation
- Install bonnet side up and allow access for testing/service.
- Install where discharge or spillage is not objectionable.
- Do not undersize supply or oversize the valve relative to demand.
- Do not install where backpressure can occur.
- Protect from freezing. For freeze protection, specify Model 800M4FR or LF800M4FR. Or, consider the WattsBox insu- lated enclosure. For more information, download ES-WB at www.watts.com.
- Follow ASSE Standard 1020 that the atmospheric vent valve remains open until the valve body pressure exceeds 1 lb. Until this pressure is reached, some amount of spillage occurs at the atmospheric vent. To minimize this leakage on start-up, close the downstream shutoff valve and open the inlet shutoff valve quickly.
Start-up Procedure
- Close shutoff No. 2 (outlet).
- Open shutoff No. 1 (inlet) until water discharges from the bonnet then quickly open to pressurize the valve.
- Open shutoff No. 2.
Freeze Protection
Use the following procedure to purge the PVB assembly with pressurized air.
(See Figure 2)
- Close the main shutoff valve.
- Open the upstream drain, test cocks, and isolation ball valves to depressurize the line.
- Purge with pressurized line.
- Leave test cocks and isolation ball valve handles at 45°angle to drain ball valves and prevent casting damage.
Typical Installation
The TWS hydrant is usually included in the PVB installation to provide outside
access to a building water supply for start-up, winterizing, and servicing of
irrigation sprinkler systems. (See Figure 3) The hydrant is connected to
the PVB assembly and installed through the structure wall to connect to the
water supply.
Servicing and Maintenance
Internal parts can be removed, repaired, or inspected without removing the valve from the piping.
Routine Service
- In cold climates, open the test cocks to drain if operated only seasonally.
- Replace rubber goods every 5 years.
Vacuum Breaker Disassembly
- Shut off the supply pressure and drain the valve.
- Remove the two hood screws and the hood.
- Place a wrench on the parallel flats of the bonnet and stem assembly. Turn counterclockwise and remove.
- Remove the vent assembly.
- Press down on the spring retainer and disengage it from the retaining lugs. Then turn 90 degrees and remove.
- Remove the spring retainer and spring. The large diameter of the spring is down on the guide assembly.
- Remove the check disc holder and guide assembly.
- Disassemble the check disc holder assembly.
- Remove the seat (if required) by turning counterclockwise.
Vacuum Breaker Reassembly
Use the procedure above in reverse order to reassemble the vacuum breaker with
new parts from the repair kit.
Add-on/Retrofit Sensor Connection Kit for Building/Irrigation Management Systems
ORDERING CODE | ADD-ON/RETROFIT KIT | DESCRIPTION |
---|---|---|
88009429 | ![Watts-800M4-Series-Pressure-Vacuum-Breaker-Assemblies- |
FIG-4](https://manuals.plus/wp-content/uploads/2023/09/Watts-800M4-Series- Pressure-Vacuum-Breaker-Assemblies-FIG-4.png)
FP-BF-BMS/IMS-FZ
BMS/IMS Freeze Sensor Connection Kit Series 800M4FR, LF800M4FR, 800M4QT, LF800M4QT
Sizes 1″ to 2″
| Includes freeze sensor in the mounting clip, activation module with mounting hardware, wire nuts (2), and power adapter. Use this kit to add an indicator of the freeze threshold for PVB assemblies in a BMS/IMS configuration.
Limited Warranty:
Watts (the “Company”) warrants each product to be free from defects in
material and workmanship under normal usage for a period of one year from the
date of original shipment. In the event of such defects within the warranty
period, the Company will, at its option, replace or recondition the product
without charge.
THE WARRANTY SET FORTH HEREIN IS GIVEN EXPRESSLY AND IS THE ONLY WARRANTY GIVEN BY THE COMPANY WITH RESPECT TO THE PRODUCT. THE COMPANY MAKES NO OTHER WARRANTIES, EXPRESS OR IMPLIED. THE COMPANY HEREBY SPECIFICALLY DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
The remedy described in the first paragraph of this warranty shall constitute the sole and exclusive remedy for breach of warranty, and the Company shall not be responsible for any incidental, special or consequential damages, including without limitation, lost profits or the cost of repairing or replacing other property which is damaged if this product does not work properly, other costs resulting from labor charges, delays, vandalism, negligence, fouling caused by foreign material, damage from adverse water conditions, chemical, or any other circumstances over which the Company has no control. This warranty shall be invalidated by any abuse, misuse, misapplication, improper installation or improper maintenance or alteration of the product.
Some States do not allow limitations on how long an implied warranty lasts, and some States do not allow the exclusion or limitation of incidental or consequential damages. Therefore the above limitations may not apply to you. This Limited Warranty gives you specific legal rights, and you may have other rights that vary from State to State. You should consult applicable state laws to determine your rights. SO FAR AS IS CONSISTENT WITH APPLICABLE STATE LAW, ANY
IMPLIED WARRANTIES THAT MAY NOT BE DISCLAIMED, INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE LIMITED IN DURATION TO ONE YEAR FROM THE DATE OF ORIGINAL SHIPMENT.
- USA: T: 978-689-6066 • Watts.com
- Canada: T: 888-208-8927 • Watts.ca
- Latin America: T: (52) 55-4122-0138 • Watts.com
RP/IS-FZ-800M4 2317
1923067
© 2023 Watts
References
- Watts | Plumbing, Heating and Water Quality Solutions
- Watts | Plumbing, Heating and Water Quality Solutions
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>