AKO 16526 Temperature And Electronic Expansion Controller User Manual

June 13, 2024
AKO

AKO-16526
Temperature and electronic expansion controller for
cold room store
User manual 351652602 Ed. 05

16526 Temperature And Electronic Expansion Controller

AKO Electromecánica thanks you and congratulates you on the purchase of our product, the development and manufacture of which involved the most innovative technologies, as well as rigorous production and quality control processes.
Our commitment to achieving customer satisfaction and our continuous efforts to improve day by day are confirmed by the various quality certificates obtained.
This is a high performance, technologically advanced product. Its operation and the final performance achieved will depend, to a great extent, on correct planning, installation, configuration and commissioning. Please read this manual carefully before proceeding to install it and respect the instructions in the manual at all times.
Only qualified personnel may install the product or provide technical support.
This product has been developed for use in the applications described in the manual. AKO Electromecánica does not guarantee its operation in any use not foreseen in this document and accepts no liability in the case of damage of any type which may result from incorrect use, configuration, installation or commissioning.
Complying with and enforcing the regulations applying to installations where our products are destined to be used is the responsibility of the installer and the customer. AKO Electromecánica accepts no liability for damage which may occur due to failure to comply with these regulations.
Rigorously follow the instructions described in this manual.
In order to extend the lifetime of our products to the maximum, the following points must be observed:
Do not expose electronic equipment to dust, dirt, water, rain, moisture, high temperatures, chemical agents or corrosive substances of any type.
Do not subject equipment to knocks or vibrations or attempt to handle them in any way differently to that indicated in the manual.
Do not under any circumstances exceed the specifications and limitations indicated in the manual.
Respect the indicated environmental conditions for operation and storage at all times.
During installation and on completion of this, avoid the presence of loose, broken or unprotected cables or cables in poor condition.
These may constitute a risk for the equipment and its users.
AKO Electromecánica reserves the right to make any modification to the documentation and the product without prior notification.

Warnings

  • If the device is used without adhering to the manufacturer’s instructions, the device safety requirements could be compromised. Only sensors supplied by AKO must be used for the unit to operate correctly.
  • From -40°C to +20°C, if the NTC sensor is extended to 1000m with at least a 0.5mm cable, the maximum deviation will be 0.25°C (cable for sensor extension ref. AKO-15586. Earth the cable mesh at one end only).
  • The product should be installed in a place protected from vibrations, water and corrosive gases, where the ambient temperature does not exceed the value indicated in the technical data.
  • For the reading to be correct, the sensor should be used in a place without heat influences apart from the temperature you want to measure or control.
  • The IP65 protection degree is only valid with the protection cover closed.
  • The IP65 protection degree is only valid if the cables enter the device using a tube for electric conductions + gland with IP65 or above. The gland should be the right size for the diameter of the tube used.
  • Do not spray the unit directly with high-pressure hoses, as this could damage it.

IMPORTANT:

  • The AUXILIARY relays are programmable, and their operation depends on the configuration.
  • The function of the digital inputs depends on the configuration.
  • The recommended currents and powers are the maximum working currents and powers.

Maintenance

Clean the surface of the unit with a soft cloth, water and soap.
Do not use abrasive detergents, petrol, alcohol or solvents, as this might damage the unit.

Description

Temperature controller with output for electronic expansion valve regulation and evaporator fan speed control.
In addition to regulating the cooling of the cold room, the controller can be configured to control superheating and regulate the speed of the evaporator fans using an inverter or electronic fans.
The different options are:
Temperature Control + Thermostatic Expansion Valv e

Temperature control + EEV controlled by PWM
**Temperature control + EEV controlled by PWM + Evaporator fans regulated***

Temperature control + Stepper EEV **

  • Requires the use of an external frequency inverter controlled by a 0-10 V or 4-20 mA signal or the use of electronic fans (ECFAN).
    **Requires the use of an external driver controlled by a 0-10 V or 4-20 mA signal. For more information on this option, please see the application note available on our website: 351652632

Constant: Stand-By mode activated. Regulation is paused.
Flashing: controlled stop process for the regulation in progress.
Constant: cold room door open.
Flashing: the door has been open for a longer time than defined in parameter A12.
There is an active alarm (no HACCP or temperature).
Constant: HACCP alarm active.
Flashing: HACCP alarm recorded and unconfirmed To acknowledge an HACCP alarm, press the key.
The temperature alarm is active.
Constant: evaporator fans active.
Flashing: the evaporator fans should be active but something is preventing them from activating.
Pulsing: evaporator fans controlled by analogue output.
Constant: the COOL relay is active.
Flashing: the COOL relay should be active but a delay or protection is preventing this.
Pulsing: expansion valve regulated.
Constant: compressor active.
Flashing: the compressor should be active but a delay or protection is preventing this.
Defrosting active.
Continuous cycle mode active.
Cold room light active.
Alarm in progress muted.
Temperature displayed in °Fahrenheit/°Centigrade.
PRG Programming mode active.
K Lower display showing the real time superheating value.
Lower display showing percentage of EEV opening or percentage of evaporator fan power (depending on configuration).
Lower display showing low pressure in psi/bar.

Keypad

| Press and hold for 3 seconds to activate/deactivate the Stand-By mode. In this mode, regulation is paused and the  icon is displayed.
In the programming menu, this key exits the parameter without saving changes and returns to the previous level, or exits programming.
---|---
| Pressing once without holding displays the temperature of sensor S2 for 10 seconds (if it is enabled).
Pressing it for 3 seconds starts/stops the defrost.
In the programming menu, it allows you to scroll through the different levels, or when setting a parameter to change its value.
| Pressing it for 3 seconds activates/deactivates the continuous cycle mode.
In the programming menu, it allows you to scroll through the different levels, or when setting a parameter to change its value.
| Pressing once without holding activates/deactivates the cold room light.
Pressing it for 3 seconds accesses the condensed programming menu.
Pressing it for 6 seconds accesses the expanded programming menu.
In the programming menu, it accesses the level shown on the display or, during the setting of a parameter, accepts the new value.
| Pressing it once without holding it down displays the current effective value of the temperature Set
Point in the upper display and the superheating set point in the lower display, taking into consideration temporary changes due to other parameters.
When an alarm is in progress, pressing once without holding mutes the acoustic alarm.
Pressing for 3 seconds accesses the temperature Set Point setting.

STAND-BY
If the regulation cannot be stopped immediately due to its configuration, a controlled stop process starts and the m icon flashes. To stop the controlled stop process and force Stand-by, press the Stand-by key again for 3 seconds.
Probes

|
---|---
Cold room Probe / Evaporator Probe / 2on evaporator Probe| Superheating probe

Installation

  • Remove the bezels (1).
  • Make a 1/4 turn of the screws (2) anti-clockwise and open the door (3).
  • Install the necessary glands (4/5) by drilling holes in the points indicated on the box.
  • Mark and make the holes in the wall with the aid of the template included.
  • Fix the device to the wall. If it is a brick wall, use the screws and plugs supplied; if the wall is made of sheet metal (cold room store), use the screws provided without plugs (6).
  • Wire the device by following the recommendations indicated on page page 9.
  • Close the cover (3), tighten the screws (2) and replace the bezels (1).

Wiring

Always disconnect the power supply to do the wiring.
The sensors and their cables must NEVER be installed in a conduit together with power, control or power supply cables.
For disconnection, the power supply circuit must be equipped with at least a 2 A, 230 V switch, located near the device. The power supply cable shall be of the H05VV-F or NYM 1×16/3 type. The section to be used will depend on current local regulations, but should never be less than 1.5mm2.
Cables for relay or contactor outputs should have a section of 2.5mm2, allow working temperatures equal to or over 70ºC, and be installed with as little bending as possible.
The 120/230 V~ wiring area must be kept clear of any other external element.
The wiring setup depends on the options selected in the set-up wizard (See page 11) and on the input and output configurations (See page 34).
Check the enclosed schematic and the defined configuration before wiring.
IMPORTANT:

  • AUXILIARY relays are programmable, and their operation depends on the configuration.
  • The function of the digital inputs depends on the configuration.
  • The recommended currents and powers are the maximum working currents and powers.

Initial configuration

The AKO-16526 controller can be adapted to different types of installation according to the different options chosen in the set-up wizard.
Before completing the wiring, make sure you are familiar with the details of the installation in order to configure it correctly.
It is advisable to note the following points:
Compressor
Whether the controller should switch the compressor on and off (InI=2, 3, 5, 6, 7 or 8) or whether the compressor is switched on and off by the low pressure switch (InI=1 or 4).
Defrost
Defrosting method used:
Electric (InI=1, 2 or 3)
Air (evaporator fans) (InI=4, 5 or 6)
Hot gas valve (condensing unit) (InI=7 or 8)
Solenoid/EEV
Type of solenoid/EEV used:

  • Solenoid + thermostatic expansion valve (u00=0).
  •  PWM-controlled EEV (without liquid solenoid) (u00=1).
  • Stepper-controlled EEV (u00=2). Requires an external controller for the EEV. For more information, please refer to the application note available on our website.

Options u00=1 and u00=2 require the use of a superheating temperature sensor (S5) and an evaporator pressure sensor (S6).
Evaporator fans
If the fan control is ON/OFF (F10=0) or an external frequency inverter is used for ventilation (F10=1).
The second option is only available if a STEPPER-type electronic expansion valve (u00=2) is not used.
Analogue outputs
The analogue output (ANALOG OUT) enables communication between the controller and the external controller of the electronic expansion valve (if u00=2), or with the frequency inverter of the fans (if F10=1), and can be configured as 4-20 mA output (o30=0) or as 0-10 V output (o30=1).
Consult the specifications of the external controller or drive before setting this option.
SET POINT (temperature)
Make a note of the desired set temperature value.
If u00=1 or 2, you must also know:
Type of gas
Type of gas used in the installation.

u02=0| R404A| u02=1| R134A| u02=2| R407A| u02=3| R407F| u02=4| R410A
---|---|---|---|---|---|---|---|---|---
u02=6| R513A| u02=7| R744| u02=8| R449A| u02=9| R290| u02=10| R32
u02=12| R1234ze| u02=13| R23| u02=14| R717| u02=15| R407C| u02=16| 1234yf
u02=18| R454C| u02=19| R455A| u02=20| R507A| u02=21| R515B| u02=22| R452A
u02=24| R454A| | | | | | | |

Pressure sensor type
Type of evaporator pressure sensor installed:
4-20 mA (I61=1)
0-5 V (I61=2)
0.5-4.5 V (I61=3)
0-10 V (I61=4)
1-5 V(I61=5)
Note also the maximum and minimum values of the pressure sensor as well as the units of pressure used (bar or Psi).
Superheating SET POINT
Enter the desired optimum superheating value.

Assistant

The first time the unit receives the power supply, it will enter into ASSISTANT mode.
The display will show the message In{ flashing at 0

** The buttons▲  and ▼ change the value, the SET button accepts the value and moves on to the next step.
Step 1:**
Select the most suitable IN option based on the type of installation to be carried out and press SET.
The available options will be shown in the following table:

In Type of installation Parameters
Control of the compressor Pump Down Defrost
Fans Pd o00
I21 I30 I31
0 Demo mode: it displays the temperature but does not regulate the

temperature
1| No| No| Electric| Yes| 0| 0| | 2| 0| 0| 0| 0| | | 20| 0| 0
2| Yes| Yes| Electric| Yes| 1| 1|
| 2| 7| 1| 0| 0| | | 20| 0| 0
3| Yes| No| Electric| Yes| 0| 1| | 2| 0| 0| 0| 0| | | 20| 0| 0
4| No| No| Air| Yes| 0| 0|
| 1| 0| 0| 0| 0| | | 20| 1| 1
5| Yes| Yes| Air| Yes| 1| 1| | 1| 7| 1| 0| 0| | | 20| 1| 1
6| Yes| No| Air| Yes| 0| 1|
| 1| 0| 0| 0| 0| | | 20| 1| 1
7| Yes| Yes| Hot gas| Yes| 1| 1| | 2| 7| 1| 7| 1| | | 5| 2| 0
8| Yes| No| Hot gas| Yes| 0| 1|
| 2| 0| 0| 7| 1| | | 5| 2| 0

  • If u00=2: o20=3, I30=0, I31=0
    If u00≠ 2: o20=0, I30=9
    ** If options 2, 5, or 7 are chosen, check the configuration of parameter I11 according to the pressure switch type used.
    Step 2:**
    Choose the type of expansion valve to be used:
u00=0 Liquid solenoid valve + thermostatic expansion valve
u00=1 PWM-controlled solenoid valve
u00=2 Electronic expansion valve (requires an external controller for the

EEV. For more information, please refer to the application
note available on our website)

If u00=0 is chosen, steps 4, 5, 6, 7, 8, 9 and 11 are not displayed.
If u00=2 is chosen, step 3 is not displayed.
Step 3:
Define the type of fan control.
F10=0 ON/OFF control
F10=1 Control by external frequency inverter (not included) / electronic fans (ECFAN) If F10=0 is chosen, step 9 is not displayed.
Step 4:
Define the type of refrigerant gas used.

u02=0 R404A u02=1 R134A u02=2 R407A
u02=3 R407F u02=4 R410A u02=5 R450A
u02=9 R290 u02=10 R32 u02=11 R448A
u02=15 R407C u02=16 R1234yf u02=17 R22
u02=21 R515B u02=22 R452A u02=23 R452B
u02=24 R454A

Step 5:
Define the pressure units to be used.
I60=0: Bar
I60=1: Psi
Step 6:
Define the type of pressure sensor used.

I61=0 Deactivated I61=1 4 – 20 mA I61=2 0 – 5 V
I61=3 0.5 – 4.5 V I61=4 0 – 10 V I61=5 1 – 5 V

Step 7:
Define the minimum value of the pressure sensor (I62) (value at 4 mA, 0 V, 0.5 V or 1 V according to I61).
Step 8:
Define the maximum value of the pressure sensor (I63) (value at 20 mA, 5 V, 4.5 V or 10 V according to I61).
Step 9:
Select the analogue output (for EEV control or fan control).
o30=0 4 – 20 mA
o30=1 0 – 10 V
Step 10:
Select the temperature set point.
Step 11:
Select the superheating set point (See page 16).
Step 12:
Set all other parameters to default?
dFP=0 No, the other parameters do not need to be changed
dFP=1 Yes, set all other parameters to their default values
This option only appears if this is not the first time the set-up wizard has been run.
The initial configuration is now complete, and the device will start to regulate the temperature.
**** The configuration wizard will not reactivate. To reactivate it, activate the stand-by mode (by pressing the  key for 3 seconds) and wait until the unit completely halts regulation (the m indicator will light up permanently) and press the▲,▼ SET buttons in this order in sequence, not at the same time.
If the Pump Down function is active, there may be a delay between the initiation of the Stand-by function and the moment the controller stops (See page 17).

Operation

Messages

| Pump down malfunction error (Stop). The time configured in parameter C20 has been exceeded (See page 17). Only displayed on screen.
---|---
| Pump down malfunction error (Start). The time configured in parameter C19 has been exceeded (See page 17). Only displayed on screen.
| Sensor 1, 2, 3, 4, 5 or 6 is faulty (open circuit, crossed circuit, or value outside sensor limits). Activates the alarm relay and the audible alarm.
| Open door alarm. Only if the door stays open for a longer time than defined in parameter A12 (See page 25). Activates the alarm relay and the audible alarm.
| Maximum temperature in control sensor alarm. The temperature value programmed in A1 has been reached (See page 24). Activates the alarm relay and the audible alarm.
| Minimum temperature in control sensor alarm. The temperature value programmed in A2 has been reached (See page 24). Activates the alarm relay and the audible alarm.
| External alarm activated (by digital input) (See page 24). Activates the alarm relay and the audible alarm.
| Severe external alarm activated (by digital input) (See page 24). Activates the alarm relay and the audible alarm.
| Defrost time-out alert. The time set in d1 has been exceeded (See page 26). Activates the alarm relay and the audible alarm.
| HACCP alarm. The temperature has reached the value of parameter h1 for a longer period than established in h2 (See page 25). Activates the alarm relay and the audible alarm.
| HACCP alarm due to a fault in the electric supply. The temperature set in h1 has been reached following a fault in the electric supply. Activates the alarm relay and the audible alarm.
| Minimum superheat alarm. The value set in A20 has been reached (See page 25). Activates the alarm relay and the audible alarm.
| Minimum superheat alert. The value defined in A23 has been reached (See page 26). Only displayed on screen.
| Maximum evaporating pressure alarm. The value defined in A26 has been reached (See page 25). Activates the alarm relay and the audible alarm.
| Minimum evaporating alarm. The value defined in A29 has been reached (See page 25). Activates the alarm relay and the audible alarm.
| Indicates that a defrost is being performed (See page 20). Only displayed on screen.
| Password request. See parameters b10 and PAS (See page 27). Only displayed on screen.
| Shown sequentially with the temperature: the controller is in demo mode, the configuration has not been made.

Cold regulation

Solenoid control (COOL relay)
If u00=0 is selected in the wizard, coolant production is regulated by opening/closing the solenoid valve, which sends liquid to the thermostatic expansion valve.
If u00=1 is selected in the wizard, coolant production is regulated by controlling the opening and closing of the expansion valve (PWM control).
If u00=2 is selected in the wizard, coolant production is regulated by controlling the opening degree of the expansion valve (stepper control).
For more information on this type of regulation, please consult the application note available on our website.

When the temperature in sensor S1 reaches the set point value (SP) plus the sensor differential (C1), coolant production is activated and the temperature drops. Once the set point (SP) value is reached, the solenoid closes.
Compressor control (AUX 1 relay)
With Pump Down (Inl: 2, 5, 7)
Requires the connection of a low pressure switch in digital input 1.
When the temperature in sensor S1 reaches the set point (SP) value plus the sensor’s differential (C1), the solenoid opens, causing the pressure in the evaporator to increase and, therefore, the low pressure switch deactivates and the compressor starts up.
Once the set point (SP) value is reached, the solenoid closes, causing the pressure in the evaporator to decrease, triggering the low pressure switch and stopping the compressor.
For further details of the process, see the next page.
Without Pump Down (Inl: 3, 6, 8)
The compressor operates simultaneously with the solenoid valve, starting up when the latter opens and stopping when it closes.
Operation in the event of a fault in sensor S1
If sensor S1 fails (fault, disconnection, etc. ), compressor behavior will depend on parameter C6, with one of 3 options available:
C6=0: the compressor is stopped until sensor S1 begins to operate again.
C6=1: the compressor is started-up until sensor S1 begins to operate again
C6=2: the compressor operates in line with the average operation during the 24 hours prior to the error, taking into account the number of start-ups and stops and the average time in each state (stop-start). If 24 hours have not elapsed without a sensor error, the device moves to C6=3 mode.
C6=3: the compressor operates according to the times programmed in C7 (ON) and C8 (OFF).

Control of superheating
Superheating (SH) is the temperature difference between the temperature at the evaporator outlet and the evaporating temperature. To obtain the SH value, sensors S5 (evaporator outlet temperature) and S6 (pressure sensor) are required. The pressure is converted to temperature according to the refrigerant gas used, so that the SH is obtained as:
SH (K) = S5 temperature – S6 temperature
A low superheat allows for better evaporator efficiency, but too low a value may cause liquid to enter the compressors because the liquid in the evaporator is not completely evaporated.
The AKO-16526 provides stable superheat regulation and a fast response to pressure or load fluctuations, thus ensuring a high level of system safety.
** When the EEV is regulating, the cold icon on the display performs a dimming sequence, indicating that the expansion regulation is electronic and is therefore constantly being adjusted.
The superheat value is shown on the bottom line of the display by default. Parameter b23 defines which value is displayed on that line.
When there is no cooling required, the superheat value is not updated, as the regulation is stopped.
When the controller does not generate coolant, the display shows the last superheat value reached before cooling was required, for the user’s information.
IMPORTANT
Install sensors S5 and S6 at the evaporator outlet.
The parameters must be set correctly in the set-up wizard to ensure correct regulation of superheating. Incorrect configuration can lead to problems in the refrigeration system.
Manual opening of the electronic expansion valve (EEV)**
By using parameter U11, a fixed opening value can be set for the EEV. The equipment performs ON/OFF cycles according to U03 but always with the selected opening %.
This function should only be used by qualified personnel and in exceptional circumstances.

  • Access parameter U11. The equipment will ask for a security code.
  • Enter the code 63
  • Enter the opening % and press SET

** The equipment will not readjust the opening of the valve until U11=0 is configured again (manual opening disabled).
While there is no demand for cooling, the valve will remain closed.
Pump down function
This function foresees problems in the compressor caused by movements of coolant, using a stop/start technique for the installation, controlled via the liquid solenoid, the low pressure switch and the compressor itself.
This function is only available for In 2, 5 and 7 and requires the connection of a low pressure switch in digital input 1 (I10=7).
STOP
When the temperature in sensor S1 reaches the set point (SP) value, the COOL relay deactivates, closing the solenoid valve.
Because the compressor continues to operate, pressure in the evaporator quickly drops. Upon reaching a given value, the low pressure switch activates, changing the status of digital input 1, which stops the compressor (AUX 1 relay).
This maneuver isolates all of the coolant in the high-pressure line, far from the compressor crankcase, preventing serious faults upon start-up.
Should the low pressure switch fail, the controller stops the compressor once the safety interval defined in C20 has elapsed, displaying the message “Pd” (an informative message that does not affect the unit’s operation).
If C20 time is 0 (default value), the compressor will not stop until the low pressure switch is activated, but it will display the “Pd” message after 15 minutes.
START
When the temperature in sensor S1 reaches the set point value plus the differential (SP+C1), the COOL relay activates, opening the liquid solenoid.
This increases the pressure in the evaporator, deactivating the low pressure switch, which turns the compressor on. If, some time (determined by C19) after the liquid solenoid is opened (COOL relay set to ON), the low pressure switch does not deactivate, the controller will once again close the solenoid (COOL relay set to OFF) and the “LP” message will be displayed.
This maneuver will be repeated every 2 minutes, indefinitely, until the pressure switch is deactivated and the installation reverts to its normal operation. If C19 time is 0 (default value), the solenoid will remain open until the low pressure switch deactivates, but  t will display the “LP” message after 5 minutes.
STAND-BY**
If the pump down function is active, there may be a delay between starting the Stand-by function and the controller stopping; this is because certain installation control phases cannot be interrupted.
To force the stop of the controller, press the Stand-by key again for 3 seconds.

Continuous cycle mode
This is used to quickly cool the cold room stores before products are loaded and is activated by pressing the key for 3 seconds.
Upon activating this mode, the compressor begins to operate until the temperature in sensor S1 reaches the set point value, minus the variation indicated in parameter C10.
The value of C10 is always negative, unless it is 0.
The unit will immediately return to normal operation.
Should it not be possible to reach this point, the device will return to normal operation once the time configured in C9 has elapsed, or by pressing the key again for 5 seconds.

Set Point change mode
This allows for quick alternation between two working temperatures in the cold room store, modifying the Set Point in line with the value indicated in parameter C12. The aforementioned value may be negative or positive, which allows for the Set Point to be reduced or increased. If it is configured in 0, the mode is disabled.
It is activated in three possible ways:
By means of an external switch connected to one of the digital inputs. The digital input should be configured as “Set Point change” (I10 or I20=4). Activation through this method cancels any other activation and can only be deactivated using the same method.
By means of the AKONet application. This requires the device to be connected to a Modbus network (See page 36).
By means of the CAMM module and the AKO CAMM tool application.
EXAMPLE:

Calibration of sensor 1
Parameter C0 allows for correction of the temperature detected by sensor 1; this is particularly useful when the sensor cannot be located in the ideal place.
Set Point locking
Parameters C2 and C3 allow for an upper and lower limit to be established for the set point (SP), to protect the product or installation from Set Point manipulation.

Compressor protection timing

Parameter C4 allows for selection of the type of timing to be applied to protect the compressor. These delays prevent continuous compressor starts and stops.
These timings affect the COOL and AUX 1 relays (if o00=1).
OFF-ON (C4=0): minimum time in OFF mode before each start-up.
OFF-ON/ON-OFF (C4=1): minimum time in ON and OFF mode for each cycle.
The delay time is defined by means of parameter C5; if C5=0, timing is disabled.

Door management
Door management allows for the installation’s behavior to be controlled, should the cold room door open through parameters C22 and C23.
Parameter C22 defines whether cold production should be stopped if the door opens. If C22=1, when the door opens, the fans stop and, 15 seconds later, the solenoid closes (COOL relay).
Parameter C23 defines the maximum time, in minutes, that the installation can remain without producing cold whilst the door is open. If C23=0, cold is not produced with the door open.

Management of door frame resistor

If the Set Point is equal to or below -4°C and the AUX 2 relay has been configured as “door frame resistor” (o10=5), the resistor is activated (relay ON) when the temperature of the cold room drops below -3°C, and is deactivated (relay OFF) when 0°C is reached.
Defrost
Types of defrost
There are 5 possible defrost types, depending on the option selected in the wizard (Inl):
Electric (InI=1, 2 and 3) (d7=0)
Defrost is performed through electrical resistors, supplying the evaporator with heat. The operation of fans in this mode depends on parameter F3; the compressor and solenoid are stopped.
By air (InI=4, 5 and 6) (d7=1)
Usually used in positive cold rooms (> 3°C), since the inside temperature of the cold room is sufficient to melt evaporator ice. By default, the fans are activated so that air may circulate through the evaporator; to stop them, change parameter F3 to 0. The compressor and solenoid are stopped.
Hot gas (InI=7 and 8) (d7=2)
The hot gas from compressor discharge is used to melt evaporator ice and, to this end, two valves are necessary: one at the condenser input (A) and another between the compressor output and the evaporator input (B). During the process, the liquid solenoid valve (C) and the condenser input valve (A) are closed and the evaporator input valve is opened (B), forcing hot gas to pass through the latter and melting the ice.
Optionally, a high pressure switch (D) can be added to control the solenoid valve (digital input D2, l20=7) during the defrost process using hot gas. If the pressure decreases, the solenoid opens to allow liquid into the tank; when the pressure rises again, the solenoid closes.

Defrost control

Defrost start
Defrost will start if:

  • The time programmed in parameter d0 has elapsed since the start of the last defrost.
  • Press the key for 3 seconds.
  • By means of an external push-button (I10 / I11=5).
  • Through the app or through Alkanet.

Defrost completion
Defrost will complete if:

  • The temperature programmed in parameter d4 has been reached in sensor 2. This requires a 2 sensor (l00=2) to be available, located in the evaporator.
  • The time configured in parameter d1 has elapsed (maximum defrost duration).
  • Press the key for 5 seconds.
  • By means of an external push-button (I10/I20=5).
  • Through the app or through Anent.

Drip time
It is set by parameter d9 and defines the time added at the end of defrost to allow the evacuation of the remaining defrost water from the evaporator, during which time there is no cooling regulation.
Fan start-up delay
This is established through parameter F4 and allows for the possible drops left in the evaporator to freeze before the fans activate, preventing them from being projected into the cold room. It also prevents heat being supplied to the cold room due to defrost in the evaporator.
** If defrost is cancelled before 1 minute has elapsed, the drip time (d9) is not applied and the fans are activated without taking into account the start-up delay (F4).
If defrost is by air or is static, the drip time (d9) and fan start-up delay (F4) are deactivated.
Message displayed during defrost
This is established using parameter d2, and you can choose between displaying the real temperature captured by sensor 1 (d2=0), showing the temperature captured by sensor 1 at the start of the defrost (d2=1), or displaying the dEF (d2=2) message. Parameter d3 defines the time during which the aforementioned message will be displayed once the drip time (d9) and fan stop time (F4) are complete.
Remote defrost
This function allows defrost of the unit to be activated using an external key, connecting it to one of the digital inputs that must be configured as remote defrost (I10 or I20=5).
Defrost locking
This prevents defrost starting at unusual points by means of an external switch, which may be useful for ensuring that the installation’s load does not excessively increase, exceeding the permitted limits.
The external switch must be connected to one of the digital inputs, which should be configured as “Defrost locking” (I10 or I20=6).
Defrosting in a second evaporator
This function allows for defrost to be controlled in a second evaporator, provided that defrost is by electric heat, by air or is static. The same type of defrost should be used for the first and second evaporators. This requires configuration of input D2/S4 as a 2nd
evaporator sensor (l120=10). In the event of an error in the 2nd evaporator sensor, defrost completes once the time defined in d1 has elapsed.
Electric defrosting
This requires configuration of the AUX 2 relay as 2nd evaporator defrost (o10=4). Defrost begins simultaneously in both evaporators. When the sensor of evaporator 1 reaches the temperature defined in d4, the DEF relay deactivates, completing defrost of evaporator 1. Defrost of evaporator 2 is completed when the evaporator 2 sensor reaches the temperature defined in d4. Drip time begins when both defrosts are complete.
Defrost by air
The fans of both evaporators are connected in parallel to the FAN relay. Defrost begins simultaneously in both evaporators and does not complete until both sensors reach the temperature defined in d4. Drip time subsequently begins.
Static defrost
Defrost begins simultaneously in both evaporators and does not complete until both probes reach the temperature defined in d4. Drip time subsequently begins.
Other parameters
Using parameter d5, you can configure whether the unit performs a defrost (d5=1) or not (d5=0) when it receives power (first start-up or after a power supply failure). Should the option YES (d5=1) be selected, defrost will begin once the delay time defined in d6 has elapsed.
Using parameter d8, we define the time tally established in d0, choosing between total time elapsed (d8=0) or the sum of compressor operation time (d8=1).
REMARK:** If parameter d1 is configured to 0, no defrosts are performed.

Fan control

Fans are controlled through sensor 2 (evaporator), and parameters F0 (stop temperature) and F1 (sensor differential).
If sensor S2 is not connected or an error in the sensor (E2) is detected, the fans continuously operate without taking into account parameters F0 and F1, but taking the remaining parameters (F2 to F4) into account.
Using parameter F2, the status of the fans during compressor stops is defined.
Using parameter F3, the status of the fans during defrost is defined.
Parameter F4 defines the fan start-up delay time after defrost (See page 20).
Parameter C22 defines whether fans stop when the door is opened.
ON/OFF control (F10=0)
This type of control starts or stops the fans depending on the temperature at sensor S2. If F2=0 the fans start when the temperature falls below the value defined in F0 minus the differential F1, and stop when the value of F0 is reached.
If F2=1 the fans stop when the compressor stops or when the temperature defined in F0 is reached, and start if the temperature drops below F0 minus F1, as long as the compressor is running.
Control via frequency inverter or electronic fans (F10=1)
This function regulates the fan speed via the AO output according to the temperature at sensor S1. The fan speed decreases as the temperature approaches SP and increases as it approaches SP + C1.

Alarms
When the criteria programmed in the parameters are met, the device warns the user through an on-screen message, activation of a relay (only 5-relay devices if o10=1 or 4-relay devices if o00=4) and an audible alarm.
Maximum/minimum temperature alarm
It shows the message “AK” or “AL” when the temperature in sensor 1 reaches the value configured in parameters A1 (maximum temperature) and A2 (minimum temperature). This value may be:

  • Absolute (A0=1): the temperature at which the alarm should activate must be indicated in A1/A2.
  • Relative to the SP (A0=0): the increase or decrease in the number of degrees necessary for the alarm to activate, in relation to the set point, must be indicated in A1/A2. This option enables us to change the set point without having to reset the maximum and minimum alarms.

Parameter A10 establishes the differential of both parameters (Hysteresis).
Example
We configure the following parameters in a controller: SP=2, A1=10, A10=2

  • If A0=0 (relative to the SP), the maximum temperature alarm will activate when 12 degrees are reached in sensor 1, and will deactivate when 10 degrees are reached.
  • If A0=1 (absolute), the maximum temperature alarm will activate when 10 degrees are reached in sensor 1, and will deactivate when 8 degrees are reached.

External alarm/severe external alarm
The message EA (external alarm) or SEA (severe external alarm) is displayed when the digital input configured as external alarm or severe external alarm is activated.
The severe external alarm also deactivates all the loads and, therefore, temperature regulation stops.
When this alarm disappears, the device returns to its normal operation.
At least one of the digital inputs must be configured as an external alarm (l10 or l20=2) or as a severe external alarm (l10 or l20=2).
Evaporator sensor error alarm due to moisture ingress
If, at the start of defrost, the temperature in sensor S2 is 20°C higher than the temperature in sensor S1, the defrost ignores sensor S2 and completes due to time-out.
The display shows the message E2, activates the alarm relay and audible alarm.
The alarm can be silenced, but alarm icon  will not disappear until:

  • The controller is switched off and then on again.
  • Defrost without error is started in sensor S2.

If the 2nd evaporator sensor (l20=10) has been enabled, it will behave in the same way, but displaying the message E3.
HACCP alarm
The alarm is activated should situations be detected which could endanger the integrity of the products stored in the cold room.
If the temperature of the cold room is higher than that defined in parameter h1 for a length of time exceeding that defined in parameter h2, the alarm activates, displaying the message HCP on screen.
Upon pressing the mute key, the sound alarm switches off, but the alarm remains.
Once the temperature drops below parameter h1, if the mute key has been pressed, the alarm disappears. If the mute key has not been pressed, the audible alarm deactivates but the HACCP indicator remains in flashing mode, indicating than a non-confirmed HACCP alarm has occurred.
Press the mute key to confirm an HACCP alarm.
Sensor error alarm
If one of the enabled sensors is crossed, open circuit, or out of range, the message E1, E2, E3, E4, E5 or E6 is displayed depending on whether it is sensor S1, S2, S3, S4, S5 or S6.

Open door alarm
The door has been open for a longer time than defined in parameter A12, the open door alarm is activated.
In order to detect the open door, configuration is required of one of the digital inputs as “door contact” (l10, l20 or l30=1).
Activates alarm relay and audible alarm.
Minimum superheat alarm
If the superheat value falls below the value defined in parameter A20, the alarm is activated and the display shows the message LSH.
The alarm disappears when the value A20 + differential A22 is reached.
Parameter A21 allows a delay in the activation of this alarm to be defined.
Activates the alarm relay and the audible alarm.
Maximum evaporating pressure alarm
If the evaporating pressure exceeds the value defined in parameter A26, the alarm is activated and the display shows the message MOP.
The alarm disappears when the value A26 + differential A28 is reached.
Parameter A27 allows a delay in the activation of this alarm to be defined.
Activates the alarm relay and the audible alarm.
Minimum evaporating pressure alarm
If the evaporating pressure falls below the value defined in parameter A29, the alarm is activated and the display shows the message LOP.
The alarm disappears when the value A29 – A31 is reached.
Parameter A30 allows a delay in the activation of this alarm to be defined.
Activates the alarm relay and the audible alarm.
Alarm delays
These delays prevent certain alarms from being shown, to allow the installation to recover its normal operation after certain events.

  • Delays in start-up (A3): this delays the activation of the temperature alarms upon receiving power (at startup or after a power supply failure) or when exiting Stand-by mode. This allows for the installation to start up avoiding alarms.
  • Delay after a defrost (A4): this delays the activation of the temperature alarms when a defrost completes.
  • Maximum and minimum temperature alarm delay (A5): this delays the activation of the maximum (A1) and minimum (A2) temperature alarms, from when the temperature in sensor 1 reaches the programmed value.
  • Delay to activation of external alarm (A6): this delays the activation of the external alarm, from when the digital input becomes active.
  • Delay to deactivation of external alarm (A7): this delays the deactivation of the external alarm, from when the digital input becomes active.

Delay to open door alarm (A12): this delays the activation of the alarm upon detecting that the door is open.
Alarm relay configuration
Should any relay have been configured as an alarm relay, parameter A9 allows for the relay status to be defined when an alarm is triggered:
A9=0 Relay active (ON) in the event of an alarm (OFF without alarm)
A9=1 Relay inactive (OFF) in the event of an alarm (ON without alarm)
Alerts
The device alerts the user through an on-screen message when an event occurs which requires his/her attention.
However, it does not activate the sound alarm or the alarm relay (if active).
Defrost time-out alert
The message Add is displayed when a defrost has completed due to time-out, if parameter A8=1. Pump down malfunction error (stop)
The message Pdc is displayed if a malfunction is detected when the installation is stopped using the pump down maneuver (See page 17). Pump down malfunction error (start-up)
Displays the LP message if a malfunction is detected when the installation is started up using the pump down maneuver (See page 17).

Maximum overheating alert
If the superheat value falls below the value defined in parameter A23, the and the display shows the message HSH.
The alert disappears when the value A23 – A25 is reached.
Parameter A23 allows a delay in the activation of this alarm to be defined.

Light control

The AUX 1 or AUX 2 relay must be configured as “Light” (o00, o10 or o20=2).
Switching the lights on or off is controlled using:

  • The LIGHT push-button: one press switches the lights on or off.
  • The cold room door: when the door is opened, the lights remain on for the time defined by parameter b01.

If the value is 0, when the door closes the lights go out. (One of the digital inputs must be configured as door contact (I10, I20 or I30=1). The control even occurs with the equipment in Stand-by.

Password

Allows the configuration of the equipment to be protected by a 2-digit code.
If it is active a code is requested when you try to access the programming menu. This menu cannot be accessed if a wrong value is entered. The code is set via the PAS parameter.
Parameter b10 defines the operation of this code.

Remote Stand-by mode

This allows activating Stand-by mode using a switch connected to one of the digital inputs.
Said digital input must be set to Stand-by remote activation (I10=8 or I20=8).

Operation of the auxiliary relays

Depending on the controller model, it may have 1 or 2 auxiliary relays. The function of these relays is configurable via the parameter menu.

AUX 1 relay

  • Deactivated (o00=0): does not carry out any function.
  • Compressors/crankcase resistor (o00=1): controls compressor operation. When the compressor is not in operation, it powers the crankcase resistor. This function can only be selected via the initial wizard (In{).
  • Light (o00=2): this regulates the operation of cold room light (See page 26).
  • Virtual control (o00=3): the relay can be remotely activated and deactivated by means of Alkanet software.

AUX 2 relay

  • Deactivated (o10=0): does not carry out any function.
  • Alarm (o10=1): this activates the relay every time that an alarm occurs (See page 24).
  • Light (o10=2): this regulates the operation of cold room light (See page 26).
  • Virtual control (o10=3): the relay can be remotely activated and deactivated by means of Alkanet software.
  • Defrost 2nd evaporator (o10=4): this controls the defrost resistors of a second evaporator (See page 22).
  • Door frame resistor (o10=5): this controls the operation of the cold room’s door frame resistor (See page 19).
  • Same as solenoid status (o10=6): imitates solenoid status: active if the solenoid is in ON mode, inactive if the solenoid is in OFF mode.
  • Same as unit status (o10=7): indicates the unit’s status: active if the unit is in ON mode, inactive if the unit is in Stand-by mode.

AUX 3 relay

  • Deactivated (o20=0): does not carry out any function.
  • Alarm (o20=1): this activates the relay every time an alarm occurs (See page 24)
  • Light (o20=2): this regulates the operation of cold room light (See page 26).
  • ON/OFF external control (o20=3): sends the ON/OFF signal to the external frequency inverter (if F10=1) or to the EVV driver (if u00=2).
  • Defrost 2nd evaporator (o20=4): this controls the defrost resistors of a second evaporator (See page 22).

Configuration

Condensed programming menu
This allows for the most-used parameters to be quickly configured. Press the SET key for 3 seconds to access it.
Condensed programming menu

Parameters

Level 2 Description Values Min. Def. Max.
SP Temperature setting (Set Point) ºC/ºF -50 0.0 99
C1 Sensor 1 differential (Hysteresis) ºC/ºF 0.1 2.0 20.0
d0 Defrost frequency (time between 2 starts) h. 0 6 96
d1 Maximum defrost duration (0=defrost deactivated) min. 0 * 255
d4 Final defrost temperature (by sensor) (If I00 ¹ 1) ºC/ºF -50 8.0

50
SH| Superheating set point| ºK| 0.1| 8| 40
F3| Status of the fans during the defrost 0=stopped; 1=running| | 0| *| 1
A1| Alarm for maximum in sensor 1 (it must be higher than the SP)| ºC/ºF| A2| 99.0| 99.0
A2| Alarm for minimum in sensor 1 (it must be lower than the SP)| ºC/ºF| -50| -50| A1

  • According to the set-up wizard.

Extended programming menu

Use the extended programming menu to configure all of the unit’s parameters in order to adapt it to your installation requirements. Press the SET key for 6 seconds to access it.
IMPORTANT: if the password function has been configured as a keypad lock (b10=2), or as an access to parameters block (b10=1), you will be requested to enter the password programmed in PAS when attempting to access either of the two functions. If the entered password is not correct, the unit will go back to showing the temperature.
IMPORTANT: certain parameters or menus may not be visible depending on the configuration of the other parameters and the options chosen during set- up.
Extended programming menu

Regulation and control

Level 1| Level 2| Description| Values| Min.| Def.| Max.
---|---|---|---|---|---|---
rE| SP| Temperature setting (Set Point)| ºC/ºF| -50| 0.0 99|
C0| Sensor 1 calibration (Offset)| ºC/ºF| -20.0| 0.0| 20.0
C1| Sensor 1 differential (Hysteresis)| ºC/ºF| 0.1| 2.0 20.0|
C2| Set point top locking| ºC/ºF| C3| 99| 99
(it cannot be set above this value)
C3| Set point bottom locking| ºC/ºF| -50| -50 C2|
(it cannot be set under this value)| | | |
| Type of delay for the protection of the compressor:| | | |
C4| 0=minimum OFF time of the compressor| | 0| 0| 1
| 1=minimum OFF and ON time of the compressor in each cycle| | | |
C5| Protection delay time| min.| 0| 0 120|
| (value of the option selected in parameter C4)| | | |
| COOL relay status with fault in sensor 1:| | | |
C6| 0=OFF; 1=ON; 2=average according to last 24 h before the sensor error;| | 0| 2| 3
| 3=ON-OFF according prog. C7 and C8| | | |
C7| Time of relay ON if sensor 1 damaged| min.| 0| 10 120|
(if C7=0 and C8¹0, the relay will always be OFF when disconnected)| | | |
C8| Time of relay OFF if sensor 1 damaged| min.| 0| 5| 120
(if C8=0 and C7¹0, the relay will always be ON when connected)
C9| Maximum duration of the continuous cycle mode (0=deactivated)| h.| 0| 0| 48
C10| Variation of the Set Point (SP) in continuous cycle mode. When it reaches this point (SP+C10), it reverts to the normal mode (SP+C10 ³ C3)
The value of this parameter is always negative, unless it is 0 (0=OFF)| ºC/ºF| 0|  -50| C3- SP
C12| Variation of the set point (SP) when the change set point change function is| ºC/ºF| C3-| 0 C2-|
active (SP+C12£ C2) (0=deactivated)| | SP| | SP
C19| Maximum time for start-up after gas collection| sec.| 0| 0| 120
(values between 1 and 9 seconds are not accepted) (0=deactivated)
C20| Maximum time for pump down (0=deactivated)| min.| 0| 0| 15
C22| Stop fans and COOL when opening door 0=no 1=yes| | 0| 0| 1
C23| Start-up delay for fans and COOL when door open| min.| 0| 0 999|
EP| Output to level 1| | | |

Defrost

Level 1| Level 2|
---|---|---
Description| Values| Min.| Def.| Max.
def.| d0| Defrost frequency (time between 2 starts)| h.| 0| 6| 96
d1| Maximum defrost duration (0=defrost deactivated)| min.| 0| | 255
d2| Type of message during the defrost: 0=sign of the real temperature; 1=sign of| | | |
the temperature at the start of the defrost;| | 0| 2| 2
2=sample of the dEF message| | | |
d3| Maximum message duration| min.| 0| 5| 255
(time added at the end of the defrost process)
d4| Final defrost temperature (by sensor) (If I00¹1)| ºC/ºF| -50| 8.0| 50
d5| Defrost on connecting the unit: 0=NO, first defrost according to d0;| | 0| 0| 1
1=YES, first defrost according to d6
d6| Delay of the defrost start on connecting the unit| min.| 0| 0| 255
d7| Type of defrost: 0=resistors; 1=air/fans| | 0|
| 2
2=hot gas
d8| Time calculation between defrost periods:| | 0| 0| 1
0=total real time 1=sum of COOL time connected| | | |
d9| Drip time when a defrost finishes| min.| 0| 1| 255
(stop COOL and fans)
EP| Output to level 1

Evaporator fans

Level 1| Level 2| Description| Values| Min.| Def.| Max.
---|---|---|---|---|---|---
Fang| F0| Fans stop temperature| ºC/ºF.| -50| 45| 50
F1| Sensor 2 differential if fans are stopped| ºC/ºF| 0.1| 2.0| 20.0
F2| Stop fans when the compressor stops 0=no 1=yes| | 0| 0| 1
F3| Status of the fans during the defrost 0=stopped; 1=running| | 0| | 1
F4| Start-up delay after defrost (if F3=0)
Only actuates if higher than d9| min.| 0| 2| 99
F10| Fan control type 0=ON/OFF 1=frequency inverter| | 0|
| 1
EP| Output to level 1

  • According to the set-up wizard.
    Expansion valve

Level 1| Level 2| Description| Values| Min.| Def.| Max.
---|---|---|---|---|---|---
EEV| u00| Valve type: 0=solenoid + EV thermostat 1= PWM-type EEV  2 =Stepper-type EEV| | 0| | 2
SH| Superheating set point| K| 0.1| 8| 40
u02| Refrigerant gas type: 0= R-404A, 1= R-134A, 2= R-407A, 3= R-407F, 4= R-410A, 5= R-450A, 6= R-513A, 7= R-744, 8= R-449A, 9= R-290, 10= R-32, 11= R-448A, 12=R1234ze, 13=R23, 14=R717, 15=R407C, 16=R1234yf, 17=R22, 18=R454C, 19=R455A, 20=R507A, 21=R515B, 22=R452A, 23=R452B, 24=R454A| |   0|  
| 24
u03| PWM cycle time| s.| 2| 6| 10
u04| Proportional constant value (P)| | 1| 10| 100
u05| Integral constant value (I)| | 0| 10| 100
u06| Derivative constant value (D)| | | | 100
u07| Opening value of the electronic expansion valve when cooling is activated| %| u13| 50| u12
u08| Duration of valve opening on cooling demand| %| 2| 5| 240
u09| Valve opening value with sensor error S5 or S6: 0=fixed opening according to u10; 1=average opening over the last 24 hours| %| 0| 0| 1
u10| Valve opening value with sensor error S5 or S6 (if u09=0)| %|  u13| 0| u12
u11| Manual valve opening value (0=disabled), (cycles acc. to u03) (See page 16)| %| u13| 0| u12
u12| Maximum valve opening value| %| u13| 100| 100
u13| Minimum valve opening value| %| 0| 0| u12
u14| Valve opening value after defrost (0=disabled), (duration according to u15)   u13| %| 0/| 0| u12
u15| Duration of valve opening after defrosting| %| 0| 0| 240
u16| Valve opening in case of LOP error (0=valve closed)
EP| Output to level 1

Alarms

Level 1| Level 2|
---|---|---
Description| Values| Min.| Def.| Max.
AL| A0| Configuration of the temperature alarms 0=relative to SP 1=absolute| | 0| 1| 1
A1| Alarm for maximum in sensor 1 (it must be higher than the SP)| ºC/ºF| A2| 99.0| 99.0
| A2| Alarm for minimum in sensor 1 (it must be lower than the SP)| ºC/ºF| -50|    -50| A1
A3| Delay of temperature alarms in the start-up| min.| 0| 0| 120
A4| Delay of temperature alarms from the end of a defrost| min.| 0|  0| 99
A5| Delay of temperature alarms from when the A1 or A2 value is reached| min.| 0| 30| 99
A6| Delay of external alarm/severe external alarm on receiving digital input signal (I10 or I20=2 or 3)|  min.| 0| 0|  120
A7| External alarm deactivation delay/severe external alarm on disappearance of signal at digital input (I10 or I20=2 or 3)| min.| 0| 0| 120
A8| Show warning if the defrost ends for maximum time 0=no 1=yes| | 0| 0|  1
A9| Polarity relay alarm 0=relay ON in alarm (OFF without alarm); 1=relay OFF in alarm (ON without alarm)| | 0| 0| 1
A10| Differential of temperature alarms (A1 and A2)| ºC/ºF| 0.1| 1.0| 20.0
A12| Delay of open door alarm (if I10, I20 or I30=1)| min.| 0| 10| 120
A20| Minimum superheating value for LSH alarm| K| 0| 2| SH
A21| LSH alarm activation delay| sec.| 0| 30| 240
A22| LSH alarm hysteresis| K|  0.1|  2| Sh- A20
A23| Maximum overheating value for LSH alert| K| sh| 40| 40
A24| Delayed activation of the HSH warning| s| 0| 30| 240
A25| HSH alarm deactivation hysteresis| K| 0.1| 2| A23- sh
A26| Maximum evaporating pressure (MOP)|  bar| 0|  60| 60
A27| MOP alarm activation delay (delay time for activating alarm after threshold has been exceeded)| sec.| 0| 30| 240
A28| MOP alarm deactivation hysteresis (when the pressure drops below the MOP-hysteresis level the alarm is deactivated)|  bar| 0.1|  1| 60
A29| Minimum evaporating pressure (LOP)| bar| -1| 0| 8
A30| LOP alarm activation delay (delay time for activating alarm after threshold has been exceeded)| sec.|  0| 30| 240
A31| LOP alarm deactivation hysteresis (when the pressure exceeds the LOP-hysteresis level the alarm is deactivated)| bar| 0.1| 1| 8
EP| Output to level 1|

Basic configuration

Level 1| Level 2|
---|---|---
Description| Values| Min.| Def.| Max.
bcn| b00| Delay of all functions on receiving power supply| min.| 0| 0| 255
b01| Cold room light timing| min.| 0| 0| 999
b10| Password function 0=inactive
1=parameter access lock 2=keypad lock| | 0|  0|  2
PAS| Password| | 0| 0| 99
b20| MODBUS address| | 1| 1| 247
b21| Communication speed: 0=9600 bps 1=19200 bps
2=38400 bps 3=57600 bps| bps| 0| 0| 3
b22| Audible alarm enabled 0=no 1=yes| | 0| 1|  1

b23

| Lower display function: 1=sensor S2, 2=sensor S3, 3=sensor S4, 4=sensor S5, 5=superheating, 6=pressure sensor, 7=% EEV, 8=% eFAN, 9=carousel, 10=off| | 1| *| 10
Unt| Working units 0=ºC 1=ºF| | 0| 0| 1
EP| Output to level 1|

Inputs and outputs

Level 1| Level 2|
---|---|---
Description| Values| Min.| Def.| Max.
InO| I00| Probes connected: 1=sensor 1 (cold room), 2=sensor 1 (cold room) + sensor 2 (evaporator)| |  1| 2| 2

I10

| D1/S3 input configuration: 0=deactivated, 1=door contact, 2=external alarm, 3=severe external alarm, 4=change SP, 5=remote defrost, 6=defrost lockout, 7=low pressure switch, 8=remote activation in Stand-by mode, 9=product temperature| | 0| | 9
I11| Digital input polarity D1: 0=activates on closing, 1=activates on opening contact| | 0| 0|   1
I20| D2/S4 input configuration: 0=deactivated, 1=door contact, 2=external alarm, 3=severe external alarm, 4=change SP, 5=remote defrost,
6=defrost lockout, 7=high pressure switch for hot gas, 8=remote activation of Stand-by mode, 9=product temperature, 10=defrost 2nd evaporator| | 0|
| 10
I21| Digital input polarity D2: 0=activates on closing, 1=activates on opening contact| |  0| 0|  1
I30| D3/S5 input configuration: 0=deactivated, 1=door contact, 2=external alarm, 3=severe external alarm, 4=change SP, 5=remote defrost,
6=defrost lockout, 7=remote activation of Stand-by mode, 8=rroduct temper- ature, 9=superheating temperature (Sh)| | 0| | 9
I31| Digital input polarity D3: 0=activates on closing, 1=activates on opening contact| | 0| 0| 1
Level 1| Level 2|
---|---|---
Description| Values| Min.| Def.| Max.
InO| I60| Pressure units: 0=bar, 1=Psi| | 0|
| 1
I61| Pressure sensor type (S6): 0=deactivated, 1=4-20 mA, 2=0-5 V, 3=0.5-4.5 V,           4=0-10 V, 5=1-5 V| | 0| 0|  5
I62| Minimum pressure sensor value (4 mA, 0 V, 0.5 V, 1 V)| | -1| 0|
I63| Maximum pressure sensor value (20 mA, 5 V, 4.5 V, 10 V)| | 12| 60| I62
I64| Pressure sensor calibration (S2)| | -10| 0| 10
o00| AUX 1 relay configuration: 0=deactivated, 1=compressor/crankcase resistance, 2=light, 3=virtual control, 4= alarm, 5=resistor door frame| | 0| *| 5
o10| AUX 2 relay configuration: 0=deactivated, 1=alarm, 2=light, 3=virtual control, 4=defrost 2nd evaporator, 5=resistor. door frame, 6=equal solenoid status, 7=equal device status| | 0| 2| 7
o20| AUX 3 relay configuration: 0=deactivated, 1=alarm, 2=light, 3=external AO  controller ON/OFF, 4=defrost 2nd evaporator, 5=resistor. door frame| | 0| 0| 5
o30| Analogue output type (AO): 0=4-20 mA, 1=0-10 V| | 0| 0| 1
EP| Output to level 1

HACCP alarm

Level 1| Level 2|
---|---|---
Description| Values| Min.| Def.| Max.
HCP| h1| HACCP alarm maximum temperature| ºC/ºF|  -50| 99.0|  99.0
h2| Maximum permitted time for activation of the HACCP alarm (0=HACCP alarm deactivated)| h.| 0| 0| 255
EP| Output to level 1

Information (read-only)

Level 1| Level 2|
---|---|---
Description| Values| Min.| Def.| Max.
tid| InI| Option chosen in the configuration wizard
Pd| Pump down active? 0=no, 1=yes| | | |
PU| Software version (Information)
Pr| Program revision| | | |
PSr| Program Subversion
bU| Bootloader version| | | |
br| Bootloader revision
bSr| Program Subversion| | | |
PAr| Parameter map revision
EP| Output to level 1

Connectivity

The controllers are equipped with a port for connection of RS485 (MODBUS) data, which allows for remote management of these using an AKO-5012 web- server.
The MODBUS address is factory-set and is indicated on the rating plate located on the left side of the controller.
This address must be different for each unit within the same network.
The address can be changed using parameter b20. Once modified, the old address indicated on the plate will not be valid.

Technical specifications

Power supply …………………………………………………………….. 100 – 240 V ~ 50/60 Hz
Maximum input power in the operation …………………………………………….8.1 VA
Maximum nominal current …………………………………………………..15 A
DEF relay – SPDT – 20 A NO (EN 60730-1: 15 (15) A 250 V~ )
NC …………………………………………………..(EN 60730-1: 15 (13) A 250 V~)
FAN relay – SPST – 16 A ……………………………………………(EN 60730-1: 12 (9) A 250 V~)
Relay COOL – SPST – SSR 2 A …………………………………….. Vmax: 275 V~, Imax: 2 A
AUX relay 1 – SPDT – 20 A
NO …………………………………………………..(EN 60730-1: 15 (15) A 250 V~)
NC …………………………………………………..(EN 60730-1: 15 (13) A 250 V~)
AUX relay 2 – SPDT – 16 A
NO …………………………………………………….(EN 60730-1: 12 (9) A 250 V~)
NC …………………………………………………….(EN 60730-1: 10 (8) A 250 V~)
AUX relay 3 – SPST – 16 A
NO …………………………………………………….(EN 60730-1: 12 (9) A 250 V~)
No. of relay operations ………………………………………EN 60730-1:100,000 operations
Sensor temperature range ……………………………………………………-50.0ºC to 99.9ºC
Resolution, adjustment and differential …………………………………………… 0.1ºC
Thermometric accuracy …………………………………………… ±1ºC
Tolerance of the NTC probe at 25ºC ………………………………………….. ±0.4ºC
Input for NTC probe ……………………………………………………… AKO-14901
Working ambient temperature ………………………………….-10ºC to 50ºC
Ambient storage temperature ……………………………………-30ºC to 60ºC
Protection degree …………………………………………………….. IP 65
Installation category ………………………………………… II as per EN 60730-1
Degree of pollution ………………………………………….. II as per EN 60730-1

Grade as per UNE-EN 60730-1: Built-in control device, with Type 1.B automatic action operation feature, for use in clean situations, logical support (software) class A and continuous operation. Degree of pollution 2.
Double isolation between power supply, secondary circuit and relay output.
Accessible parts pressure ball test temperature …………………………………………………………….. 75 °C
Parts positioning active elements ………………………………………………………………………………… 125 ºC
Radio interference suppression test current …………………………………………………………270 mA
Voltage and current delayed by the EMC tests: ………………………………………………..207 V, 17 mA
Type of mounting …………………………………………………………………………… Fixed interior
MODBUS address ……………………………………………………………… Indicated on the label
Dimensions ………………………………………… 290mm (W) x 141mm (H) x 84.4mm (D)
Internal buzzer

AKO ELECTROMECÁNICA, S.A.L.
Avda. Roquetes, 30-38
08812 • Sant Pere de Ribes.
Barcelona • Spain
www.ako.com
We reserve the right to supply materials slightly different to those described in our data sheets. Updated information on our website.
351652602 Rev. 04 2023

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals