AKO 16526 Cold Room Controller User Guide
- June 13, 2024
- AKO
Table of Contents
16526 Cold Room Controller
Product Information: Product Name: AKO-16526 Model Number:
351652611 Ed. 04 Product Usage Instructions: 1. Display and
Keyboard: – The display is labeled as 1 and the keyboard is labeled
as 2. 2. Alarms: – If there is a fixed alarm HACCP active, the
display will show a fixed symbol. – If there is an intermittent
alarm HACCP registered and not confirmed, the display will show an
intermittent symbol. To confirm the alarm, press the keyboard
button. – If there is an active temperature alarm, the display will
show a temperature symbol. 3. Silenced Alarm: – If an alarm is
currently silenced, the display will indicate that. 4. Sondas: –
There is a probe for overheating labeled as “Sonda
sobrecalentamiento”. 5. Asistente: – The display shows the message
“In{ intermitente” with a number 0. – The keys ( and ) can be used
to change the value, and the SET key accepts the value and moves to
the next step. 6. Modo demo: – In demo mode, the display shows the
temperature but does not regulate it. 7. Control Settings: – The
user can choose different control settings for various components
such as valves, solenoids, fans, etc. The manual provides detailed
instructions on how to select and configure these settings. 8.
Desescarche: – The product supports different types of defrosting
methods such as resistances, air/ventilators, and hot gas. The
manual provides instructions on how to configure these settings. 9.
Nivel Settings: – The product has different levels of settings such
as Level 1 and Level 2. The manual provides instructions on how to
configure these settings. 10. Mensajes: – The product displays
different messages related to its operation. The manual provides
information on these messages and their meanings. 11. Valores Min.
Def. Max.: – The product has different configurable values such as
temperature, time, frequency, etc. The manual provides information
on the minimum, default, and maximum values for these settings.
Note: The above information is a summary of the text-extract from
the user manual. For detailed instructions and complete
information, please refer to the user manual provided with the
product.
es en fr
351652611 Ed. 04
AKO-16526
Controlador de temperatura y expansión electrónica para cámara frigorífica
Temperature and electronic expansion controller for cold room store Contrôleur
de température et détendeur électronique pour chambre froide
Guía rápida / User manual / Manuel d’utilisateur
351652611 Ed. 04
Advertencias
-Utilizar el equipo no respetando las instrucciones del fabricante, puede alterar los requisitos de seguridad del aparato. Para el funcionamiento correcto del mismo sólo deberán utilizarse sondas de las suministradas por AKO. -Entre 40 ºC y +20 ºC, si se prolonga la sonda NTC hasta 1.000 m con cable de mínimo 0,5 mm2, la desviación máxima será de 0,25 ºC (Cable para prolongación de sondas ref. AKO-15586. Conectar la malla a tierra sólo en uno de sus extremos). -Debe ser instalado en un sitio protegido de las vibraciones, del agua y de los gases corrosivos, donde la temperatura ambiente no supere el valor reflejado en los datos técnicos. -Para que la lectura sea correcta, la sonda debe ubicarse en un sitio sin influencias térmicas ajenas a la temperatura que se desea medir o controlar. -El grado de protección IP65 solo es válido con la tapa protectora cerrada. -El grado de protección IP65 sólo es válido si la entrada de cables al equipo se realiza mediante tubo para conducciones eléctricas + prensastopas con IP65 o superior. El tamaño de los prensastopas debe ser el adecuado para el diametro de tubo utilizado. -No rociar directamente el equipo con mangueras de alta presión, puede resultar dañado. IMPORTANTE: -Los relés AUXILIARES son programables, su funcionamiento depende de la configuración. -La función de las entradas digitales depende de la configuración. -Las intensidades y potencias indicadas son las máximas de trabajo admitidas.
Mantenimiento
Limpie la superficie del equipo con un paño suave, agua y jabón. No utilice
detergentes abrasivos, gasolina, alcohol o disolventes, el equipo puede
resultar dañado.
Conexionado
Desconectar siempre la alimentación para realizar el conexionado. Las sondas y
sus cables NUNCA deben instalarse en una conducción junto con cables de
potencia,control o alimentación. El circuito de alimentación debe estar
provisto de un interruptor para su desconexión de mínimo 2 A, 230 V, situado
cerca del aparato. El cable de alimentación será del tipo H05VV-F o NYM
1×16/3. La sección a utilizar dependerá de la normativa local vigente, pero
nunca deberá ser inferior a 1.5 mm2. Los cables para las salidas de los relés
o contactor deben tener una sección de 2.5 mm2 , deben admitir temperaturas de
trabajo iguales o superiores a 70 ºC y se deben instalar minimizando su
flexión. La zona de conexión a 120 / 230 V~ debe mantenerse despejada de
cualquier elemento externo. El conexionado a realizar depende de las opciones
escogidas en el asistente inicial de configuración (Ver página 5) y de las
configuraciones de entradas y salidas (Ver página 15). Compruebe el esquema
incluido y la configuración definida antes de realizar el conexionado.
2
351652611 Ed. 04
Descripción
Controlador de temperatura con salida para regulación de valvula de expansión
electronica y control de la velocidad de los ventiladores de evaporador. Puede
configurarse para que, además de regular el frío de la cámara, pueda controlar
el sobrecalentamiento y regular la velocidad de los ventiladores de evaporador
mediante un variador o usando ventiladores electrónicos.
1
2
1: Display; 2: Teclado
Fijo: Modo Stand-By activo, la regulación está detenida. Intermitente: Proceso
de paro controlado de la regulación en curso.
Fijo: Puerta de la cámara abierta. Intermitente: La puerta lleva abierta un
tiempo superior al definido en el parámetro A12.
Hay una alarma activa (No HACCP ni temperatura).
Fijo: Alarma HACCP activa. Intermitente: Alarma de HACCP registrada y sin
confirmar. Para confirmar una alarma HACCP, pulsar la tecla .
Hay una alarma de temperatura activa.
Fijo: Ventiladores de evaporador activos. Intermitente: Los ventiladores de
evaporador deberían estar activos pero algún retardo se lo impide. Pulsante:
Ventiladores de evaporador regulados mediante salida analógica.
Fijo: El relé COOL esta activo. Intermitente: El relé COOL debería estar
activo pero algún retardo o protección se lo impide. Pulsante: Válvula de
expansión regulada.
3
Fijo: Compresor activo. Intermitente: El compresor debería estar activo pero
algún retardo o protección se lo impide. Desescarche activo.
Modo ciclo contínuo activo.
Luz de la cámara activa.
Alarma en curso silenciada.
Temperatura indicada en º Fahrenheit / º Centigrados. Modo de programación
activo.
Display inferior mostrando el valor de sobrecalentamiento en tiempo real.
Display inferior mostrando el porcentaje de apertura de la VEE o porcentaje de
potencia de los ventiladores de evaporador (según configuración) Display
inferior mostrando la presión de baja en psi / bar.
351652611 Ed. 04
Teclado
Pulsando durante 3 segundos,activa / desactiva el modo Stand-By. En este modo
la regulación se detiene y el display muestra el icono m. En el menú de
programación,sale del parámetro sin guardar cambios,retrocede al nivel
anterior o sale de programación.
Una pulsación corta muestra la temperatura de la sonda S2 durante 10 segundos
(Si está habilitada). Pulsando durante 3 segundos,inicia / detiene el
desescarche. En el menú de programación, permite desplazarse por los
diferentes niveles, o, durante el ajuste de un parámetro,variar el valor del
mismo.
Pulsando durante 3 segundos,activa / desactiva el modo ciclo contínuo. En el
menú de programación, permite desplazarse por los diferentes niveles, o,
durante el ajuste de un parámetro,variar el valor del mismo.
Una pulsación corta activa / desactiva la luz de la cámara. Pulsando durante 3
segundos,accede al menú de programación reducido. Pulsando durante 6
segundos,accede al menú de programación extendido. En el menú de programación,
accede al nivel mostrado en pantalla o, durante el ajuste de un parámetro,
acepta el nuevo valor.
Una pulsación corta muestra el valor efectivo actual del Set Point de
temperatura en el display superior, y el Set Point de sobrecalentamiento en el
display inferior, teniendo en cuenta las modificaciones temporales por otros
parámetros. Con una alarma en curso,una pulsación corta silencia la alarma
acústica. Pulsando durante 3 segundos,accede al ajuste del Set Point de
temperatura.
STAND-BY Si la regulación no puede detenerse al instante debido a su
configuración, se inicia un proceso de paro controlado y el icono m parpadea.
Para detener el proceso de paro controlado y forzar el paso a Standby, pulsar
la tecla Stand-by de nuevo durante 3 segundos.
Sondas
Sonda Cámara / Sonda Evaporador / Sonda 2° evaporador
Sonda sobrecalentamiento
4
351652611 Ed. 04
Asistente
Al recibir alimentación por primera vez, el equipo entra en modo ASISTENTE.
El display muestra el mensaje In{ intermitente con 0.
Las teclas y varian el valor, la tecla SET acepta el valor y pasa
1
al siguiente paso.
Paso 1: Seleccionar la opción InI adecuada según el tipo de instalación a realizar y pulsar SET. Las opciones disponibles se muestran en la siguiente tabla:
/ / SET
Tipo de instalación
Parámetros
InI Control del Pump compresor Down
Desescarche
Vent. Evap.
Pd o00 o20 I00 I10 I11 I20 I21 I30 I31 d1 D7
F3
0
Modo demo, muestra temperatura en display pero no regula temperatura
1
No
No
Eléctrico
Si 0 0 2 0 0 0 0 * 20 0 0
2
Si
Si
Eléctrico
Si 1 1 2 7 1 0 0 * 20 0 0
3
Si
No
Eléctrico
Si 0 1 2 0 0 0 0 * 20 0 0
4
No
No
Aire
Si 0 0 1 0 0 0 0 * 20 1 1
5
Si
Si
Aire
Si 1 1 1 7 1 0 0 * 20 1 1
6
Si
No
Aire
Si 0 1 1 0 0 0 0 * 20 1 1
7
Si
Si
Hot gas
Si 1 1 2 7 1 7 1 * 5 2 0
8
Si
No
Hot gas
Si 0 1 2 0 0 7 1 * 5 2 0
- Si u00=2: o20=3, I30=0, I31=0 Si u002: o20=0, I30=9
En caso de escoger las opciones 2, 5 ó 7, revisar la configuración del parámetro I11 en función del
presostato utilizado.
Paso 2: Escoger el tipo de vávula de expansión a utilizar:
2
u00=0
Válvula solenoide de liquido + valvula de expansión termostática
u00=1 Valvula solenoide con control por PWM
Válvula de expansión electronica (Requiere un controlador exu00=2 terno para
la VEE, para más información, consulte la nota de
aplicación disponible en neustra web)
/ / SET
En caso de escoger u00=0, los pasos 4, 5, 6, 7, 8, 9 y 11 no se muestran. En caso de escoger u00=2, el paso 3 no se muestra.
5
Paso 3: Definir el tipo de control de los ventiladores.
F10=0 F10=1
Control ON/OFF
Control por variador de frecuencia externo (No incluido) / ventiladores
electronicos (ECFAN)
En caso de escoger F10=0, el paso 9 no se muestra.
Paso 4: Definir el tipo de gas refrigerante utilizado.
u02=0 u02=1 u02=2 u02=3 u02=4 u02=5 u02=18 u02=21 u02=24
R404A R134A R407A R407F R410A R450A R454C R515B R454A
u02=6 u02=7 u02=8 u02=9 u02=10 u02=11 u02=19 u02=22
R513A R744 R449A R290 R32 R448A R455A R452A
u02=12 u02=13 u02=14 u02=15 u02=16 u02=17 u02=20 u02=23
R1234ze R23 R717
R407C R1234yf
R22 R507A R452B
Paso 5: Definir las unidades de presión a utilizar.
I60=0 Bar I60=1 Psi
Paso 6: Definir el tipo de sensor de presión utilizado.
I61=0 Desactivado I61=1 I61=3 0.5 – 4.5 V I61=4
4 – 20 mA 0 – 10 V
I61=2 I61=5
351652611 Ed. 04
3
/ / SET
4
/ / SET
5
/ / SET
6
0 – 5 V 1 – 5 V
/ / SET
Paso 7: Definir el valor mínimo de la sonda de presión (I62) (Valor a 4 mA, 0 V, 0.5 V ó 1 V según I61).
9 Paso 8:
Definir el valor máximo de la sonda de presión (I63) (Valor a 20 mA, 5 V, 4.5
V ó 10 V según I61).
Paso 9: Elegir el de salida analógica (para control de EEV o control de ventiladores).
o30=0 4 – 20 mA o30=1 0 – 10 V
10
Paso 10: Elección el Set Point de temperatura.
6
/
/
SET
/
/
SET
351652611 Ed. 04
Paso 11: Elección del Set Point de sobrecalentamiento.
11
Paso 12: Configurar el resto de parámetros por defecto?
dFP=0 No, el resto de parámetros no se cambian dFP=1 Si, el resto de parámetros se configuran a su valor por defecto
/ / SET
Esta opción solo aparece si no es la primera vez que se ejecuta el asistente. La configuración inicial ha finalizado, el equipo comienza a regular la temperatura.
El asistente de configuración no vuelve a activarse. Para activarlo de nuevo,
activar el modo Stand-By (pulsando la tecla m durante 3 segundos) y esperar a
que el equipo detenga la regulación completamente (El indicador m se ilumina
de forma permanente) y pulsar en este orden las siguientes teclas (una detrás
de otra, no a la vez) , , SET.
Si la función recogida de gas está activa, puede transcurrir un cierto tiempo
desde que iniciamos la función Stand-by hasta que el controlador se detiene.
Funcionamiento
Mensajes
Error de funcionamiento de la recogida de gas (Paro), se ha superado el tiempo configurado en el parámetro C20. Sólo se muestra en pantalla.
Error de funcionamiento de la recogida de gas (Arranque), se ha superado el tiempo configurado en el parámetro C19. Sólo se muestra en pantalla.
Sonda 1, 2, 3, 4, 5 ó 6 averiada (Circuito abierto, cruzado, o valor fuera de los límites de la sonda). Activa el relé de alarma y la alarma acústica.
Alarma de puerta abierta. Sólo si la puerta permanece abierta un tiempo superior al indicado en el parámetro A12. Activa el relé de alarma y la alarma acústica.
Alarma de temperatura máxima en sonda de control. Se ha alcanzado el valor de temperatura programado en A1. Activa el relé de alarma y la alarma acústica.
Alarma de temperatura mínima en sonda de control. Se ha alcanzado el valor de temperatura programado en A2. Activa el relé de alarma y la alarma acústica.
Alarma externa activada (por entrada digital). Activa el relé de alarma y la alarma acústica.
7
351652611 Ed. 04
Alarma externa severa activada (por entrada digital). Activa el relé de alarma
y la alarma acústica.
Alerta de desescarche finalizado por tiempo, se ha superado el tiempo definido
en d1. Activa el relé de alarma y la alarma acústica.
Alarma HACCP, la temperatura ha alcanzado el valor del parámetro h1 durante un
tiempo superior al definido en h2. Activa el relé de alarma y la alarma
acústica.
Alarma HACCP por fallo en el suministro eléctrico, se ha alcanzado la
temperatura definida en h1 después de un fallo en el suministro eléctrico.
Activa el relé de alarma y la alarma acústica. Alarma de sobrecalentamiento
mínimo, se ha alcanzado el valor definido en A20. Activa el relé de alarma y
la alarma acústica.
Alerta de sobrecalentamiento alto, se ha alcanzado el valor definido en A23.
Sólo se muestra en pantalla.
Alarma de máxima presión de evaporación, se ha alcanzado el valor definido en
A26. Activa el relé de alarma y la alarma acústica.
Alarma de mínima presión de evaporación, se ha alcanzado el valor definido en
A29. Activa el relé de alarma y la alarma acústica.
Indica que se está efectuando un desescarche. Sólo se muestra en pantalla.
Petición de código de acceso (Password). Ver parámetros b10 y PAS. Sólo se
muestra en pantalla.
Mostrados de forma secuencial con la temperatura: El controlador está en modo
demo, la configuración no se ha realizado.
8
351652611 Ed. 04
Configuración
Menu de programación reducido Permite configurar rápidamente los parámetros
más utilizados. Para acceder, pulsar la tecla SET durante 3 segundos.
Parámetros
Nivel 2
Descripción SP Ajuste de temperatura (Set Point) C1 Diferencial de la sonda 1 (Histéresis) d0 Frecuencia de desescarche (Tiempo entre 2 inicios) d1 Duración máxima del desescarche (0=desescarche desactivado) d4 Temperatura final de desescarche (por sonda ) (Si I00 ¹ 1) Sh Set Point de sobrecalentamiento F3 Estado de los ventiladores durante el desescarche 0=Parados 1=En marcha A1 Alarma de máxima en sonda 1 (Debe ser mayor que el SP) A2 Alarma de mínima en sonda 1 (Debe ser menor que el SP)
Valores Min. Def. Max. ºC/ºF -50 0.0 99 ºC/ºF 0.1 2.0 20.0 h. 0 6 96 min. 0 255 ºC/ºF -50 8.0 50 ºK 0.1 8 40 01 ºC/ºF A2 99.0 99.0 ºC/ºF -50 -50 A1
*Según asistente de configuración. 9
351652611 Ed. 04
Menú de programación extendido
Mediante el menú de programación extendido, podrá configurar todos los
parámetros del equipo para adaptarlo a las necesidades de su instalación. Para
acceder, pulsar la tecla SET durante 6 segundos.
IMPORTANTE: Si se ha configurado la función del código de acceso como bloqueo
del teclado (b10=2), o como bloqueo acceso a parámetros (b10=1) al intentar
acceder a cualquiera de las dos funciones, se solicitará la introducción del
código de acceso programado en PAS. Si el código introducido no es correcto,
el equipo volverá a mostrar la temperatura. IMPORTANTE: Determinados
parámetros o menús pueden no ser visibles en función de la configuración del
resto de parámetros y de las opciones escogidas en el asistente inicial.
10
Parámetros
Regulación y control
351652611 Ed. 04
Nivel 2 Nivel 1 rE
Descripción
Valores Min. Def. Max.
SP Ajuste de temperatura (Set Point) C0 Calibración de la sonda 1 (Offset)
ºC/ºF -50 0.0 99 ºC/ºF -20.0 0.0 20.0
C1 Diferencial de la sonda 1 (Histéresis)
ºC/ºF 0.1 2.0 20.0
C2
Bloqueo superior del punto de ajuste (no se podrá fijar por encima de este valor)
ºC/ºF C3 99 99
C3
Bloqueo inferior del punto de ajuste (no se podrá fijar por debajo de este valor)
ºC/ºF -50 -50 C2
Tipo de retardo para protección del compresor: C4 0=Tiempo mínimo del
compresor en OFF
1=Tiempo mínimo del compresor en OFF y en ON en cada ciclo
001
C5
Tiempo de retardo de la protección (Valor de la opción elegida en parámetro C4)
min. 0 0 120
Estado del relé COOL con fallo en sonda 1: C6 0=OFF; 1=ON; 2=Media según
últimas 24h previas al error de sonda;
3=ON-OFF según prog. C7 y C8
023
C7
Tiempo del relé en ON en caso de sonda 1 averiada (Si C7=0 y C8¹0, el relé estará siempre en OFF desconectado)
C8
Tiempo del relé en OFF en caso de sonda 1 averiada (Si C8=0 y C7¹0, el relé estará siempre en ON conectado)
C9 Duración máxima del modo de ciclo contínuo. (0=desactivado)
min. 0 10 120 min. 0 5 120 h. 0 0 48
Variación del punto de ajuste (SP) en modo de ciclo continuo, una vez llegado
C10 a este punto (SP+C10), vuelve al modo normal. (SP+C10 ³ C3).
ºC/ºF
El valor de este parámetro es siempre negativo, excepto si es 0. (0=OFF)
0
-50
C3SP
C12
Variación del punto de ajuste (SP) cuando la función cambio de Set point está activa. (SP+C12£ C2) (0= desactivado)
ºC/ºF
C3SP
0
C2SP
C19
Tiempo máximo para arranque desde recogida de gas (No se aceptan valores entre 1 y 9 segundos) (0=desactivado)
seg. 0 0 120
C20 Tiempo máximo de recogida de gas (0=desactivado) C22 Parar ventiladores y COOL al abrir puerta 0=No 1=Si C23 Retardo de arranque de ventiladores y COOL con puerta abierta EP Salida a nivel 1
min. 0 0 15 001
min. 0 0 999
*Según asistente de configuración. 11
Desescarche
351652611 Ed. 04
Nivel 2 Nivel 1 dEF
Descripción
d0 Frecuencia de desescarche (Tiempo entre 2 inicios)
d1 Duración máxima del desescarche (0=desescarche desactivado)
Tipo de mensaje durante el desescarche: 0=Muestra la temperatura real; d2
1=Muestra la temperatura al inicio del desescarche;
2=Muestra el mensaje dEF
d3
Duración máxima del mensaje (Tiempo añadido al final del proceso de desescarche)
d4 Temperatura final de desescarche (por sonda) (Si I00 ¹ 1)
d5
Desescarche al conectar el equipo: 0=NO Primer desescarche según d0; 1=SI, Primer desescarche según d6
d6 Retardo de inicio del desescarche al conectar el equipo
d7
Tipo de desescarche: 0=Resistencias; 1=Aire / ventiladores 2=Hot gas
d8
Cómputo de tiempo entre períodos de desescarche: 0=Tiempo real total 1 =Suma de tiempo del COOL conectado
d9
Tiempo de goteo al finalizar un desescarche (Paro de COOL y ventiladores)
EP Salida a nivel 1
Ventiladores de evaporador
Valores Min. Def. Max. h. 0 6 96 min. 0 255
022
min. 0 5 255 ºC/ºF -50 8.0 50
001 min. 0 0 255
02
001
min. 0 1 255
Nivel 2 Nivel 1 FAn
Descripción
F0 Temperatura de paro de los ventiladores
F1 Diferencial de la sonda 2 si los ventiladores están parados
F2 Parar ventiladores al parar compresor 0=No 1=Si
F3 Estado de los ventiladores durante el desescarche 0=Parados 1=En marcha
F4
Retardo de arranque después del desescarche (Si F3=0) Solo actúa si es superior a d9
F10 Tipo de regulación de ventiladores 0= ON/OFF 1= Variador de frecuencia
EP Salida a nivel 1
Valores Min. Def. Max. ºC/ºF. -50 45 50 ºC/ºF 0.1 2.0 20.0 001 01
min. 0 2 99
01
*Según asistente de configuración. 12
Válvula de expansión
351652611 Ed. 04
Nivel 2 Nivel 1 EEV
Descripción
Valores Min. Def. Max.
u00
Tipo de válvula: 0=Solenoide + VE termostatica 2=VEE tipo stepper
1=VEE tipo PWM
0*2
Sh Set point de sobrecalentamiento
K 0.1 8 40
Tipo de gas refrigerante: 0= R-404A, 1= R-134A, 2= R-407A, 3= R-407F, 4= R-410A,
u02
5= R-450A, 6= R-513A, 7= R-744, 8= R-449A, 9= R-290, 10= R-32, 11= R-448A, 12=R1234ze, 13=R23, 14=R717, 15=R407C, 16=R1234yf, 17=R22, 18=R454C,
0
19=R455A, 20=R507A, 21=R515B, 22=R452A, 23=R452B, 24=R454A
- 24
u03 Tiempo de ciclo PWM
u04 Valor de la constante proporcional (P)
u05 Valor de la constante integral (I)
u06 Valor de la constante derivativa (D)
u07 Valor de apertura de la válvula de expansión electronica al activarse el frío
u08 Duración de apertura de válvula en demanda de frío
u09
Valor de apertura de válvula con error de sonda S5 ó S6: 0=Apertura fija según u10; 1=Apertura media de las últimas 24 horas
s. 2 6 10 1 10 100 0 10 100 0 0 100
% u13 50 u12 s. 2 5 240
001
u10 Valor de apertura de válvula con error de sonda S5 ó S6 (si u09=0)
% u13 0 u12
u11
Valor de apertura manual de la válvula (0=Deshabilitada), (ciclos según u03) Requiere código de seguridad, ver manual de usuario.
u12 Valor de apertura máxima de válvula
u13 Valor de apertura mínima de válvula
u14
Valor de apertura de válvula después del desescarche (0=Deshabilitado), (duración según u15)
u15 Duración de apertura de válvula después de desescarche
u16 Apertura de la válvula en caso de error LOP (0=válvula cerrada)
% u13 0 u12
% u13 100 100
% 0 0 u12
%
0/ u13
0
u12
s 0 0 240
%
0/ u13
0
u12
EP Salida a nivel 1
*Según asistente de configuración. 13
Alarmas
351652611 Ed. 04
Nivel 2 Nivel 1 AL
Descripción
Valores Min. Def. Max.
A0 Configuración de las alarmas de temperatura 0=Relativa al SP 1=Absoluta A1 Alarma de máxima en sonda 1 (Debe ser mayor que el SP) A2 Alarma de mínima en sonda 1 (Debe ser menor que el SP) A3 Retardo de alarmas de temperatura en la puesta en marcha A4 Retardo de alarmas de temperatura desde que finaliza un desescarche A5 Retardo de alarmas de temperatura desde que se alcanza el valor de A1 o A2
011 ºC/ºF A2 99.0 99.0 ºC/ºF -50 -50 A1 min. 0 0 120 min. 0 0 99 min. 0 30 99
A6
Retardo de alarma externa / Alarma externa severa al recibir señal en entrada digital (I10 ó I20 =2 ó 3)
min.
0
0 120
A7
Retardo de desactivación de alarma externa / Alarma externa severa al desaparecer la señal en entrada digital (I10 ó I20=2 ó 3)
min. 0 0 120
A8 Mostrar aviso si el desescarche finaliza por tiempo máximo 0=No 1=Si
001
A9
Polaridad relé alarma 0= Relé ON en alarma (OFF sin alarma); 1= Relé OFF en alarma (ON sin alarma)
001
A10 Diferencial de alarmas de temperatura (A1 y A2)
ºC/ºF 0.1 1.0 20.0
A12 Retardo de alarma de puerta abierta (Si I10, I20 ó I30=1)
min. 0 10 120
A20 Valor de sobrecalentamiento mínimo para alarma LSH A21 Retraso de la activación de la alarma LSH
K 0 2 Sh seg. 0 30 240
A22 Histéresis alarma LSH
K
0.1
2
ShA20
A23 Valor de sobrecalentamiento máximo para alerta HSH A24 Retraso de la activación del warning HSH
K sh 40 40 s 0 30 240
A25 Histéresis desactivación alarma HSH
K
0.1
2
A23sh
A26 Máxima presión de evaporación (MOP)
bar 0 60 60
A27
Retraso de la activación de la alarma MOP. (Tiempo de retraso para la activación de la alarma una vez superado el umbral)
seg.
0 30 240
A28
Histéresis desactivación alarma MOP (Cuando la presión baja del nivel MOP- histéresis se desactiva la alarma)
bar 0.1 1 60
A29 Mínima presión de evaporación (LOP)
bar -1 0 8
A30
Retraso de la activación de la alarma LOP (Tiempo de retraso para la activación de la alarma una vez a superado el umbral)
seg. 0 30 240
A31
Histéresis desactivación alarma LOP (Cuando la presión sube del nivel LOP + histéresis se desactiva la alarma)
bar 0.1 1
8
EP Salida a nivel 1
14
351652611 Ed. 04
Configuración básica
Nivel 2 Nivel 1 bcn
Descripción
Valores Min. Def. Max.
b00 Retardo de todas las funciones al recibir alimentación eléctrica b01 Temporización luz cámara
min. 0 0 255 min. 0 0 999
b10
Función del código de acceso (Password) 0=Inactivo 1=Bloqueo acceso a parámetros 2=Bloqueo del teclado
002
PAS Código de acceso (Password) b20 Dirección MODBUS
0 0 99 1 1 247
b21
Velocidad de comunicación: 0=9600 bps 1=19200 bps 2=38400 bps 3=57600 bps
bps 0 0 3
b22 Alarma acústica habilitada 0= No 1=Si
011
Función del display inferior: 1=Sonda S2, 2=Sonda S3, 3=Sonda S4, 4=Sonda b23
S5, 5=Sobrecalentamiento, 6=Sonda Presión, 7=% VEE, 8=% eFAN, 9=Carru-
sel, 10 = Apagado
1 * 10
Unt Unidades de trabajo 0=ºC 1=ºF
001
EP Salida a nivel 1
Entradas y salidas
Nivel 2 Nivel 1 InO
Descripción
I00
Sondas conectadas: 1=Sonda 1 (Cámara), 2=Sonda 1 (Cámara) + Sonda 2 (Evaporador)
Valores Min. Def. Max. 122
Configuración entrada D1 / S3: 0=Desactivada, 1=Contacto puerta, 2=Alarma
I10
externa, 3=Alarma externa severa, 4=Cambio de SP, 5=Defrost remoto, 6=Defrost lockout, 7=Presostato de baja, 8=Activación remota modo Standby,
9=Temperatura producto
0*9
I11
Polaridad entrada digital D1: 0= Activa al cerrar contacto, 1= Activa al abrir contacto
001
Configuración entrada D2 / S4: 0=Desactivada, 1=Contacto puerta, 2=Alarma
I20
externa, 3=Alarma externa severa, 4=Cambio de SP, 5=Defrost remoto, 6=Defrost lockout, 7=Presostato de alta para Hot Gas, 8=Activación remota
modo Standby, 9=Temperatura producto, 10=Defrost 2º evaporador
0 * 10
I21
Polaridad entrada digital D2: 0= Activa al cerrar contacto, 1= Activa al abrir contacto
001
Configuración entrada D3 / S5: 0=Desactivada, 1=Contacto puerta, 2=Alarma
I30
externa, 3=Alarma externa severa, 4=Cambio de SP, 5=Defrost remoto, 6=Defrost lockout, 7=Activación remota modo Standby, 8=Temperatura
producto, 9=Temperatura superheating (Sh)
0*9
I31
Polaridad entrada digital D3: 0= Activa al cerrar contacto, 1= Activa al abrir contacto
001
*Según asistente de configuración. 15
351652611 Ed. 04
Entradas y salidas
Nivel 2 Nivel 1 InO
Descripción
I60 Unidades de presión: 0= bar, 1= Psi
I61
Tipo de sensor de presión (S6): 0= Deshabilitado, 1= 4-20 mA, 2= 0-5 V, 3= 0.5-4.5 V, 4= 0-10 V, 5= 1-5 V
I62 Valor mínimo de sonda de presión (4mA, 0V, 0,5V, 1)
I63 Valor máximo de sonda de presión (20mA, 5V, 4,5V, 10V)
I64 Calibración de la sonda de presión (offset)
o00
Configuración del relé AUX1: 0= Desactivado, 1= Compresor/Resistencia carter, 2= Luz, 3= Control virtual, 4= Alarma, 5= Resist. Marco puerta
Valores Min. Def. Max. 01
005
-1 0 I63 I62 12 60 -10 0 10
05
Configuración del relé AUX2: 0= Desactivado, 1= Alarma, 2= Luz, 3= Control o10
virtual, 4= Defrost 2º evaporador, 5= Resist. Marco puerta, 6= Igual estado
solenoide, 7= Igual estado equipo
027
o20
Configuración del relé AUX3: 0= Deshabilitado, 1= Alarma, 2= Luz, 3= ON/OFF controlador externo AO, 4=Defrost 2º evaporador, 5= Resist. Marco puerta
o30 Tipo de salida analógica (AO): 0= 4-20mA, 1= 0-10V
EP Salida a nivel 1
005 001
Alarma HACCP
Nivel 2 Nivel 1 HCP
Descripción
h1 Temperatura máxima para alarma de HACCP
h2
Tiempo máximo admitido para activación de alarma HACCP (0=Alarma HACCP deshabilitada)
EP Salida a nivel 1
Información (Sólo lectura)
Valores Min. Def. Max. ºC/ºF -50 99.0 99.0
h. 0 0 255
Nivel 2 Nivel 1 tid
Descripción InI Opción escogida en el asistente de configuración Pd ¿Recogida
de gas activa? 0= No, 1= Si PU Versión de programa Pr Revisión de programa PSr
Subrevisión de programa bU Versión de bootloader br Revisión de bootloader bSr
Subrevisión de bootloader PAr Revisión de mapa de parámetros EP Salida a nivel
1
*Según asistente de configuración.
16
Valores Min. Def. Max.
351652611 Ed. 04
Especificaciones técnicas
Alimentación…………………………………………………………………………………………………….. 100 – 240 V ~ 50/60 Hz
Potencia máxima absorbida en la maniobra ……………………………………………………………………………………. 8.1 VA
Intensidad máxima nominal…………………………………………………………………………………………………………….15 A
Relé DEF – SPDT – 20 A
NO………………………………………………….(EN 60730-1: 15 (15) A 250 V~ )
NC…………………………………………………..(EN 60730-1: 15 (13) A 250 V~)
Relé FAN – SPST – 16 A……………………………………………………………………………….(EN 60730-1: 12 (9) A 250 V~)
Relé COOL – SPST – SSR 2 A………………………………………………………………………………… Vmax: 275 V~, Imax: 2 A
Relé AUX 1 – SPDT – 20 A
NO…………………………………………………..(EN 60730-1: 15 (15) A 250 V~)
NC…………………………………………………..(EN 60730-1: 15 (13) A 250 V~)
Relé AUX 2 – SPDT – 16 A
NO…………………………………………………….(EN 60730-1: 12 (9) A 250 V~)
NC…………………………………………………….(EN 60730-1: 10 (8) A 250 V~)
Relé AUX 3 – SPST – 16 A
NO…………………………………………………….(EN 60730-1: 12 (9) A 250 V~)
Nº de operaciones de los relés ………………………………………………………………… EN 60730-1:100.000 operaciones
Rango de temperatura de la sonda ………………………………………………………………………………..-50.0 ºC a 99.9 ºC
Resolución, ajuste y diferencial …………………………………………………………………………………………………….. 0.1 ºC
Precisión termométrica …………………………………………………………………………………………………………………±1 ºC
Tolerancia de la sonda NTC a 25 ºC……………………………………………………………………………………………..±0.4 ºC
Entrada para sonda NTC………………………………………………………………………………………………………. AKO-14901
Temperatura ambiente de trabajo ………………………………………………………………………………………-10 ºC a 50 ºC
Temperatura ambiente de almacenaje………………………………………………………………………………….-30 ºC a 60 ºC
Grado de protección…………………………………………………………………………………………………………………….. IP 65
Categoría de instalación………………………………………………………………………………………………… II s/ EN 60730-1
Grado de polución………………………………………………………………………………………………………… II s/ EN 60730-1
Clasificación s/UNE-EN 60730-1: Dispositivo de control incorporado, de característica de funcionamiento automático
acción Tipo 1.B, para utilización en situación limpia, soporte lógico (software) clase A y funcionamiento contínuo.
Grado de contaminación 2.
Aislamiento doble entre alimentación, circuito secundario y salida relé.
Temperatura del ensayo de la bola de presión Partes accesibles…………………………………………………………… 75 ºC
Partes que posicionan elementos activos……………………………………………………………………………………….. 125 ºC
Corriente de ensayo de supresión de radiointerferencias…………………………………………………………………..270 mA
Tensión y corriente declarados por los ensayos de EMC: ……………………………………………………………207 V, 17 mA
Tipo de montaje ………………………………………………………………………………………………………………….. Interior fijo
Dirección MODBUS………………………………………………………………………………………………. Indicada en la etiqueta
Dimensiones …………………………………………………………………………….290 mm (An) x 141 mm (Al) x 84.4 mm (P)
Zumbador interno
Para más información, consulte el manual de usuario disposible en nuestra web:
https://help.ako.com/assets/uploads/351652601.pdf
17
351652611 Ed. 04
Warnings
-If the device is used without adhering to the manufacturer’s instructions, the device safety requirements could be compromised. Only sensors supplied by AKO must be used for the unit to operate correctly. -From -40°C to +20°C, if the NTC sensor is extended to 1000m with at least a 0.5mm2 cable, the maximum deviation will be 0.25°C (cable for sensor extension ref. AKO-15586. Earth the cable mesh at one end only). -The product should be installed in a place protected from vibrations, water and corrosive gases, where the ambient temperature does not exceed the value indicated in the technical data. -For the reading to be correct, the sensor should be used in a place without heat influences apart from the temperature you want to measure or control. -The IP65 protection degree is only valid with the protection cover closed. -The IP65 protection degree is only valid if the cables enter the device using a tube for electric conductions + gland with IP65 or above. The gland should be the right size for the diameter of the tube used. -Do not spray the unit directly with high-pressure hoses, as this could damage it. IMPORTANT: -The AUXILIARY relays are programmable, and their operation depends on the configuration. -The function of the digital inputs depends on the configuration. -The recommended currents and powers are the maximum working currents and powers.
Maintenance
Clean the surface of the unit with a soft cloth, water and soap. Do not use
abrasive detergents, petrol, alcohol or solvents, as this might damage the
unit.
Wiring
Always disconnect the power supply to do the wiring. The sensors and their
cables must NEVER be installed in a conduit together with power, control or
power supply cables. For disconnection, the power supply circuit must be
equipped with at least a 2 A, 230 V switch, located near the device. The power
supply cable shall be of the H05VV-F or NYM 1×16/3 type. The section to be
used will depend on current local regulations, but should never be less than
1.5mm2. Cables for relay or contactor outputs should have a section of 2.5mm2,
allow working temperatures equal to or over 70ºC, and be installed with as
little bending as possible. The 120/230 V~ wiring area must be kept clear of
any other external element. The wiring setup depends on the options selected
in the set-up wizard (See page 21) and on the input and output configurations
(See page 31). Check the enclosed schematic and the defined configuration
before wiring.
18
351652611 Ed. 04
Description
Temperature controller with output for electronic expansion valve regulation
and evaporator fan speed control. In addition to regulating the cooling of the
cold room, the controller can be configured to control superheating and
regulate the speed of the evaporator fans using an inverter or electronic
fans.
1
2
1: Display; 2: Keypad
Constant: Stand-By mode activated. Regulation is paused. Flashing: controlled
stop process for the regulation in progress.
Constant: cold room door open. Flashing: the door has been open for a longer
time than defined in parameter A12.
There is an active alarm (no HACCP or temperature).
Constant: HACCP alarm active. Flashing: HACCP alarm recorded and unconfirmed
To acknowledge an HACCP alarm, press the key.
The temperature alarm is active.
Constant: evaporator fans active. Flashing: the evaporator fans should be
active but something is preventing them from activating. Pulsing: evaporator
fans controlled by analogue output.
Constant: the COOL relay is active. Flashing: the COOL relay should be active
but a delay or protection is preventing this. Pulsing: expansion valve
regulated.
19
Constant: compressor active. Flashing: the compressor should be active but a
delay or protection is preventing this. Defrosting active.
Continuous cycle mode active.
Cold room light active.
Alarm in progress muted.
Temperature displayed in °Fahrenheit / °Centigrade. Programming mode active.
Lower display showing the real time superheating value. Lower display showing
percentage of EEV opening or percentage of evaporator fan power (depending on
configuration). Lower display showing low pressure in psi/bar.
351652611 Ed. 04
Keypad
Press and hold for 3 seconds to activate/deactivate the Stand-By mode. In this
mode, regulation is paused and the m icon is displayed. In the programming
menu, this key exits the parameter without saving changes and returns to the
previous level, or exits programming.
Pressing once without holding displays the temperature of sensor S2 for 10
seconds (if it is enabled). Pressing it for 3 seconds starts/stops the
defrost. In the programming menu, it allows you to scroll through the
different levels, or when setting a parameter to change its value.
Pressing it for 3 seconds activates/deactivates the continuous cycle mode. In
the programming menu, it allows you to scroll through the different levels, or
when setting a parameter to change its value.
Pressing once without holding activates/deactivates the cold room light.
Pressing it for 3 seconds accesses the condensed programming menu. Pressing it
for 6 seconds accesses the expanded programming menu. In the programming menu,
it accesses the level shown on the display or, during the setting of a
parameter, accepts the new value.
Pressing it once without holding it down displays the current effective value
of the temperature Set Point in the upper display and the superheating set
point in the lower display, taking into consideration temporary changes due to
other parameters. When an alarm is in progress, pressing once without holding
mutes the acoustic alarm. Pressing for 3 seconds accesses the temperature Set
Point setting.
STAND-BY If the regulation cannot be stopped immediately due to its
configuration, a controlled stop process starts and the m icon flashes. To
stop the controlled stop process and force Stand-by, press the Stand-by key
again for 3 seconds.
Probes
Cold room Probe / Evaporator Probe / 2on evaporator Probe
Superheating probe
20
351652611 Ed. 04
Wizard
The first time the unit receives the power supply, it will enter into Wizard mode.
The display will show the messageIn{flashing at 0.
The buttons and change the value, the SET button accepts
1
the value and moves on to the next step.
Step 1: Select the most suitable InI option based on the type of installation to be carried out and press SET. The available options will be shown in the following table:
/ / SET
Type of installation
Parameters
InI Control of Pump the compressor Down
Defrost
Evap. Fans
Pd o00 o20 I00 I10 I11 I20 I21 I30 I31
d1
D7
F3
0
Demo mode: it displays the temperature but does not regulate the temperature
1
No
No
Electric
Yes 0 0 2 0 0 0 0 * 20 0 0
2
Yes
Yes
Electric
Yes 1 1 2 7 1 0 0 * 20 0 0
3
Yes
No
Electric
Yes 0 1 2 0 0 0 0 * 20 0 0
4
No
No
Air
Yes 0 0 1 0 0 0 0 * 20 1 1
5
Yes
Yes
Air
Yes 1 1 1 7 1 0 0 * 20 1 1
6
Yes
No
Air
Yes 0 1 1 0 0 0 0 * 20 1 1
7
Yes
Yes
Hot gas
Yes 1 1 2 7 1 7 1 * 5 2 0
8
Yes
No
Hot gas
Yes 0 1 2 0 0 7 1 * 5 2 0
- If u00=2: o20=3, I30=0, I31=0 If u002: o20=0, I30=9
If options 2, 5 or 7 are chosen, check the configuration of parameter I11 according to the pressure switch
type used.
Step 2: Choose the type of expansion valve to be used:
2
u00=0 u00=1 u00=2
Liquid solenoid valve + thermostatic expansion valve
PWM-controlled solenoid valve
Electronic expansion valve (requires an external controller for the EEV. For
more information, please refer to the application note available on our
website)
/ / SET
If u00=0 is chosen, steps 4, 5, 6, 7, 8, 9 and 11 are not displayed. If u00=2 is chosen, step 3 is not displayed.
21
Step 3: Define the type of fan control.
F10=0 F10=1
ON/OFF control
Control by external frequency inverter (not included) / electronic fans
(ECFAN)
If F10=0 is chosen, step 9 is not displayed.
Step 4: Define the type of refrigerant gas used.
u02=0 u02=1 u02=2 u02=3 u02=4 u02=5 u02=18 u02=21 u02=24
R404A R134A R407A R407F R410A R450A R454C R515B R454A
u02=6 u02=7 u02=8 u02=9 u02=10 u02=11 u02=19 u02=22
R513A R744 R449A R290 R32 R448A R455A R452A
u02=12 u02=13 u02=14 u02=15 u02=16 u02=17 u02=20 u02=23
R1234ze R23 R717
R407C R1234yf
R22 R507A R452B
Step 5: Define the pressure units to be used.
I60=0 Bar I60=1 Psi
Step 6: Define the type of pressure sensor used.
I61=0 Deactivated I61=3 0.5 – 4.5 V
I61=1 I61=4
4 – 20 mA 0 – 10 V
I61=2 I61=5
351652611 Ed. 04
3
/ / SET
4
5 6
0 – 5 V 1 – 5 V
/ / SET
/ / SET
/ / SET
Step Define
7: the
minimum
value
of
the
pressure
sensor
(I62)
(value
at
4
mA,
0
V,
0.5
V
or
1
V
according
toI61).
9 Step 8:
Define the maximum value of the pressure sensor (I63) (value at 20 mA, 5 V,
4.5 V or 10 V according to I61).
Step 9: Select the analogue output (for EEV control or fan control).
o30=0 4 – 20 mA o30=1 0 – 10 V
Step 10: Select the temperature set point.
22
/ / SET
10
/ / SET
351652611 Ed. 04
Step 11: Select the superheating set point.
Step 12: Set all other parameters to default?
dFP=0 No, the other parameters do not need to be changed dFP=1 Yes, set all
other parameters to their default values
11
/ / SET
This option only appears if this is not the first time the set-up wizard has been run. The initial configuration is now complete, and the device will start to regulate the temperature.
The configuration wizard will not reactivate. To reactivate it, activate the
stand-by mode (by pressing the m key for 3 seconds) and wait until the unit
completely halts regulation (the m indicator will light up permanently) and
press the , , SET buttons in this order in sequence, not at the same time.
If the Pump Down function is active, there may be a delay between the
initiation of the Stand-by function and the moment the controller stops.
Operation
Messages
Pump down malfunction error (Stop). The time configured in parameter C20 has been exceeded. Only displayed on screen.
Pump down malfunction error (Start). The time configured in parameter C19 has been exceeded. Only displayed on screen.
Sensor 1, 2, 3, 4, 5 or 6 is faulty (open circuit, crossed circuit, or value outside sensor limits). Activates the alarm relay and the audible alarm.
Open door alarm. Only if the door stays open for a longer time than defined in parameter A12. Activates the alarm relay and the audible alarm.
Maximum temperature in control sensor alarm. The temperature value programmed in A1 has been reached. Activates the alarm relay and the audible alarm.
Minimum temperature in control sensor alarm. The temperature value programmed in A2 has been reached. Activates the alarm relay and the audible alarm.
External alarm activated (by digital input). Activates the alarm relay and the audible alarm.
23
351652611 Ed. 04
Severe external alarm activated (by digital input). Activates the alarm relay
and the audible alarm.
Defrost time-out alert. The time set in d1 has been exceeded. Activates the
alarm relay and the audible alarm.
HACCP alarm. The temperature has reached the value of parameter h1 for a
longer period than established in h2. Activates the alarm relay and the
audible alarm.
HACCP alarm due to a fault in the electric supply. The temperature set in h1
has been reached following a fault in the electric supply. Activates the alarm
relay and the audible alarm. Minimum superheat alarm. The value set in A20 has
been reached. Activates the alarm relay and the audible alarm.
Minimum superheat alert. The value defined in A23 has been reached. Only
displayed on screen.
Maximum evaporating pressure alarm. The value defined in A26 has been reached.
Activates the alarm relay and the audible alarm.
Minimum evaporating alarm. The value defined in A29 has been reached.
Activates the alarm relay and the audible alarm.
Indicates that a defrost is being performed. Only displayed on screen.
Password request. See parameters b10 and PAS. Only displayed on screen.
Shown sequentially with the temperature: the controller is in demo mode, the
configuration has not been made.
24
351652611 Ed. 04
Configuration
Condensed programming menu This allows for the most-used parameters to be quickly configured. Press the SET key for 3 seconds to access it.
Condensed programming menu
OUT OF PROGRAMMING
20 sec.
Temperature indication
Parameters
IN PROGRAMMING
Values
Save changes Do not save changes
3 sec.
Change parameter
Change value
20 sec.
Level 2
Parameters
Description SP Temperature setting (Set Point) C1 Sensor 1 differential
(Hysteresis) d0 Defrost frequency (time between 2 starts) d1 Maximum defrost
duration (0=defrost deactivated) d4 Final defrost temperature (by sensor) (If
I00 ¹ 1) SH Superheating set point F3 Status of the fans during the defrost
0=stopped; 1=running A1 Alarm for maximum in sensor 1 (it must be higher than
the SP) A2 Alarm for minimum in sensor 1 (it must be lower than the SP)
Values Min. Def. Max. ºC/ºF -50 0.0 99 ºC/ºF 0.1 2.0 20.0
h. 0 6 96 min. 0 255 ºC/ºF -50 8.0 50 ºK 0.1 8 40
01 ºC/ºF A2 99.0 99.0 ºC/ºF -50 -50 A1
- According to the set-up wizard. 25
351652611 Ed. 04
Extended programming menu
Use the extended programming menu to configure all of the unit’s parameters in
order to adapt it to your installation requirements. Press the SET key for 6
seconds to access it.
IMPORTANT: if the password function has been configured as a keypad lock
(b10=2), or as an access to parameters block (b10=1), you will be requested to
enter the password programmed in PAS when attempting to access either of the
two functions. If the entered password is not correct, the unit will go back
to showing the temperature.
IMPORTANT: certain parameters or menus may not be visible depending on the
configuration of the other parameters and the options chosen during set-up.
Extended programming menu
OUT OF PROGRAMMING
20 sec.
Temperature indication
Level 1 Menus
20 sec.
IN PROGRAMMING
Level 2 Parameters
Level 3 Values
Save changes Do not save changes
6 sec.
Change Menus
Change Parameters
Change Values
20 sec.
26
Parameters
Regulation and control
351652611 Ed. 04
Level 2 Level 1 rE
Description
Values Min. Def. Max.
SP Temperature setting (Set Point) C0 Sensor 1 calibration (Offset)
ºC/ºF -50 0.0 99 ºC/ºF -20.0 0.0 20.0
C1 Sensor 1 differential (Hysteresis)
ºC/ºF 0.1 2.0 20.0
C2
Set point top locking (it cannot be set above this value)
ºC/ºF C3 99 99
C3
Set point bottom locking (it cannot be set under this value)
ºC/ºF -50 -50 C2
Type of delay for the protection of the compressor: C4 0=minimum OFF time of
the compressor
1=minimum OFF and ON time of the compressor in each cycle
001
C5
Protection delay time (value of the option selected in parameter C4)
min. 0 0 120
COOL relay status with fault in sensor 1: C6 0=OFF; 1=ON; 2=average according
to last 24 h before the sensor error;
3=ON-OFF according prog. C7 and C8
023
C7
Time of relay ON if sensor 1 damaged (if C7=0 and C8¹0, the relay will always be OFF when disconnected)
C8
Time of relay OFF if sensor 1 damaged (if C8=0 and C7¹0, the relay will always be ON when connected)
C9 Maximum duration of the continuous cycle mode (0=deactivated)
min. 0 10 120 min. 0 5 120 h. 0 0 48
Variation of the Set Point (SP) in continuous cycle mode. When it reaches this
C10 point (SP+C10), it reverts to the normal mode (SP+C10 ³ C3) The value of
this parameter is always negative, unless it is 0 (0=OFF)
ºC/ºF
0
-50
C3SP
C12
Variation of the set point (SP) when the change set point change function is active (SP+C12£ C2) (0=deactivated)
C19
Maximum time for start-up after gas collection (values between 1 and 9 seconds are not accepted) (0=deactivated)
ºC/ºF
C3SP
0
C2SP
sec. 0 0 120
C20 Maximum time for pump down (0=deactivated) C22 Stop fans and COOL when opening door 0=no 1=yes C23 Start-up delay for fans and COOL when door open EP Output to level 1
min. 0 0 15 001
min. 0 0 999
- According to the set-up wizard. 27
Defrost
351652611 Ed. 04
Level 2 Level 1 dEF
Description
Values Min. Def. Max.
d0 Defrost frequency (time between 2 starts)
h. 0 6 96
d1 Maximum defrost duration (0=defrost deactivated)
min. 0 * 255
Type of message during the defrost: 0=sign of the real temperature; 1=sign of
d2 the temperature at the start of the defrost;
2=sample of the dEF message
022
d3
Maximum message duration (time added at the end of the defrost process)
d4 Final defrost temperature (by sensor) (If I00¹1)
d5
Defrost on connecting the unit: 0=NO, first defrost according to d0; 1=YES, first defrost according to d6
d6 Delay of the defrost start on connecting the unit
d7
Type of defrost: 0=resistors; 1=air/fans 2=hot gas
min. 0 5 255 ºC/ºF -50 8.0 50
001 min. 0 0 255
0*2
d8
Time calculation between defrost periods: 0=total real time 1=sum of COOL time connected
001
d9
Drip time when a defrost finishes (stop COOL and fans)
min. 0 1 255
EP Output to level 1
Evaporator fans
Level 2 Level 1 FAn
Description
F0 Fans stop temperature
F1 Sensor 2 differential if fans are stopped
F2 Stop fans when the compressor stops 0=no 1=yes
F3 Status of the fans during the defrost 0=stopped; 1=running
F4
Start-up delay after defrost (if F3=0) Only actuates if higher than d9
F10 Fan control type 0=ON/OFF 1=frequency inverter
EP Output to level 1
Values Min. Def. Max. ºC/ºF. -50 45 50 ºC/ºF 0.1 2.0 20.0
001 01
min. 0 2 99
01
- According to the set-up wizard. 28
Expansion valve
351652611 Ed. 04
Level 2 Level 1 EEV
Description
Values Min. Def. Max.
u00
Valve type: 0=solenoid + EV thermostat 1= PWM-type EEV 2=Stepper-type EEV
0*2
SH Superheating set point
K 0.1 8 40
Refrigerant gas type: 0= R-404A, 1= R-134A, 2= R-407A, 3= R-407F, 4= R-410A,
u02
5= R-450A, 6= R-513A, 7= R-744, 8= R-449A, 9= R-290, 10= R-32, 11= R-448A, 12=R1234ze, 13=R23, 14=R717, 15=R407C, 16=R1234yf, 17=R22, 18=R454C,
19=R455A, 20=R507A, 21=R515B, 22=R452A, 23=R452B, 24=R454A
0 * 17
u03 PWM cycle time
s. 2 6 10
u04 Proportional constant value (P)
1 10 100
u05 Integral constant value (I)
0 10 100
u06 Derivative constant value (D)
0 0 100
u07 Opening value of the electronic expansion valve when cooling is activated
% u13 50 u12
u08 Duration of valve opening on cooling demand
s. 2 5 240
u09
Valve opening value with sensor error S5 or S6: 0=fixed opening according to u10; 1=average opening over the last 24 hours
001
u10 Valve opening value with sensor error S5 or S6 (if u09=0)
% u13 0 u12
u11
Manual valve opening value (0=disabled), (cycles acc. to u03) Requires safety code. See user manual.
u12 Maximum valve opening value
u13 Minimum valve opening value
u14 Valve opening value after defrost (0=disabled), (duration according to u15)
u15 Duration of valve opening after defrosting
u16 Valve opening in case of LOP error (0=valve closed)
% u13 0 u12
% u13 100 100
% 0 0 u12
%
0/ u13
0
u12
s 0 0 240
%
0/ u13
0
u12
EP Output to level 1
- According to the set-up wizard. 29
Alarms
351652611 Ed. 04
Level 2 Level 1 AL
Description
Values Min. Def. Max.
A0 Configuration of the temperature alarms 0=relative to SP 1=absolute A1 Alarm for maximum in sensor 1 (it must be higher than the SP) A2 Alarm for minimum in sensor 1 (it must be lower than the SP) A3 Delay of temperature alarms in the start-up A4 Delay of temperature alarms from the end of a defrost A5 Delay of temperature alarms from when the A1 or A2 value is reached
011 ºC/ºF A2 99.0 99.0 ºC/ºF -50 -50 A1 min. 0 0 120 min. 0 0 99 min. 0 30 99
A6
Delay of external alarm/severe external alarm on receiving digital input signal (I10 or I20=2 or 3)
min.
0
0 120
A7
External alarm deactivation delay/severe external alarm on disappearance of signal at digital input (I10 or I20=2 or 3)
min. 0 0 120
A8 Show warning if the defrost ends for maximum time 0=no 1=yes
001
A9
Polarity relay alarm 0=relay ON in alarm (OFF without alarm); 1=relay OFF in alarm (ON without alarm)
001
A10 Differential of temperature alarms (A1 and A2)
ºC/ºF 0.1 1.0 20.0
A12 Delay of open door alarm (if I10, I20 or I30=1)
min. 0 10 120
A20 Minimum superheating value for LSH alarm A21 LSH alarm activation delay
K 0 2 SH sec. 0 30 240
A22 LSH alarm hysteresis
K
0.1
2
ShA20
A23 Maximum overheating value for LSH alert A24 Delayed activation of the HSH warning
K sh 40 40 s 0 30 240
A25 HSH alarm deactivation hysteresis
K
0.1
2
A23sh
A26 Maximum evaporating pressure (MOP)
bar 0 60 60
A27
MOP alarm activation delay (delay time for activating alarm after threshold has been exceeded)
sec. 0 30 240
A28
MOP alarm deactivation hysteresis (when the pressure drops below the MOP- hysteresis level the alarm is deactivated)
bar 0.1 1 60
A29 Minimum evaporating pressure (LOP)
bar -1 0 8
A30
LOP alarm activation delay (delay time for activating alarm after threshold has been exceeded)
sec.
0 30 240
A31
LOP alarm deactivation hysteresis (when the pressure exceeds the LOP- hysteresis level the alarm is deactivated)
bar 0.1 1 8
EP Output to level 1
30
351652611 Ed. 04
Basic configuration
Level 2 Level 1 bcn
Description
b00 Delay of all functions on receiving power supply b01 Cold room light timing
b10
Password function 0=inactive 1=parameter access lock 2=keypad lock
PAS Password b20 MODBUS address
b21
Communication speed: 0=9600 bps 1=19200 bps 2=38400 bps 3=57600 bps
b22 Audible alarm enabled 0=no 1=yes
Lower display function: 1=sensor S2, 2=sensor S3, 3=sensor S4, 4=sensor b23
S5, 5=superheating, 6=pressure sensor, 7=% EEV, 8=% eFAN, 9=carousel,
10=off
Unt Working units 0=ºC 1=ºF
EP Output to level 1
Inputs and outputs
Values Min. Def. Max. min. 0 0 255 min. 0 0 999 002 0 0 99 1 1 247 bps 0 0 3
011
1 * 10
001
Level 2 Level 1 InO
Description
Values Min. Def. Max.
I00
Probes connected: 1=sensor 1 (cold room), 2=sensor 1 (cold room) + sensor 2 (evaporator)
122
D1/S3 input configuration: 0=deactivated, 1=door contact, 2=external alarm,
I10
3=severe external alarm, 4=change SP, 5=remote defrost, 6=defrost lockout, 7=low pressure switch, 8=remote activation in Stand-by
mode, 9=product temperature
0*9
I11
Digital input polarity D1: 0=activates on closing, 1=activates on opening contact
001
D2/S4 input configuration: 0=deactivated, 1=door contact, 2=external alarm,
I20
3=severe external alarm, 4=change SP, 5=remote defrost, 6=defrost lockout, 7=high pressure switch for hot gas, 8=remote activation of
Stand-by mode, 9=product temperature, 10=defrost 2nd evaporator
0 * 10
I21
Digital input polarity D2: 0=activates on closing, 1=activates on opening contact
001
D3/S5 input configuration: 0=deactivated, 1=door contact, 2=external alarm,
I30
3=severe external alarm, 4=change SP, 5=remote defrost, 6=defrost lockout, 7=remote activation of Stand-by mode, 8=rroduct temper-
ature, 9=superheating temperature (Sh)
0*9
I31
Digital input polarity D3: 0=activates on closing, 1=activates on opening contact
001
- According to the set-up wizard. 31
351652611 Ed. 04
Inputs and outputs
Level 2 Level 1 InO
Description
Values Min. Def. Max.
I60 Pressure units: 0=bar, 1=Psi
0*1
I61
Pressure sensor type (S6): 0=deactivated, 1=4-20 mA, 2=0-5 V, 3=0.5-4.5 V, 4=0-10 V, 5=1-5 V
005
I62 Minimum pressure sensor value (4 mA, 0 V, 0.5 V, 1 V)
-1 0 I63
I63 Maximum pressure sensor value (20 mA, 5 V, 4.5 V, 10 V)
I62 12 60
I64 Pressure sensor calibration (S2)
-10 0 10
o00
AUX 1 relay configuration: 0=deactivated, 1=compressor/crankcase resistance, 2=light, 3=virtual control, 4= Alarm, 5=resistor. door frame
0*5
AUX 2 relay configuration: 0=deactivated, 1=alarm, 2=light, 3=virtual control,
o10 4=defrost 2nd evaporator, 5=resistor. door frame, 6=equal solenoid status,
7=equal device status
027
o20
AUX 3 relay configuration: 0=deactivated, 1=alarm, 2=light, 3=external AO controller ON/OFF, 4=defrost 2nd evaporator, 5=resistor. door frame
o30 Analogue output type (AO): 0=4-20 mA, 1=0-10 V
EP Output to level 1
005 001
HACCP alarm
Level 2 Level 1 HCP
Description
Values Min. Def. Max.
h1 HACCP alarm maximum temperature
ºC/ºF -50 99.0 99.0
h2
Maximum permitted time for activation of the HACCP alarm (0=HACCP alarm deactivated)
h.
0 0 255
EP Output to level 1
Information (read-only)
Level 2 Level 1 tid
Description
InI Option chosen in the configuration wizard Pd Pump down active? 0=no, 1=yes
PU Software version (Information) Pr Program revision PSr Program Subversion
bU Bootloader version br Bootloader revision bSr Program Subversion PAr
Parameter map revision EP Output to level 1
Values Min. Def. Max.
- According to the set-up wizard. 32
351652611 Ed. 04
Technical specifications
Power supply…………………………………………………………………………………………………….. 100 – 240 V ~ 50/60 Hz
Maximum input power in the operation ………………………………………………………………………………………….8.1 VA
Maximum nominal current………………………………………………………………………………………………………………15 A
DEF relay – SPDT – 20 A NO (EN 60730-1: 15 (15) A 250 V~ )
NC…………………………………………………..(EN 60730-1: 15 (13) A 250 V~)
FAN relay – SPST – 16 A ……………………………………………………………………………..(EN 60730-1: 12 (9) A 250 V~)
Relay COOL – SPST – SSR 2 A ……………………………………………………………………………… Vmax: 275 V~, Imax: 2 A
AUX relay 1 – SPDT – 20 A
NO…………………………………………………..(EN 60730-1: 15 (15) A 250 V~)
NC…………………………………………………..(EN 60730-1: 15 (13) A 250 V~)
AUX relay 2 – SPDT – 16 A
NO…………………………………………………….(EN 60730-1: 12 (9) A 250 V~)
NC…………………………………………………….(EN 60730-1: 10 (8) A 250 V~)
AUX relay 3 – SPST – 16 A
NO…………………………………………………….(EN 60730-1: 12 (9) A 250 V~)
No. of relay operations ……………………………………………………………………………..EN 60730-1:100,000 operations
Sensor temperature range …………………………………………………………………………………………….-50.0ºC to 99.9ºC
Resolution, adjustment and differential…………………………………………………………………………………………… 0.1ºC
Thermometric accuracy ………………………………………………………………………………………………………………….±1ºC
Tolerance of the NTC probe at 25ºC………………………………………………………………………………………………±0.4ºC
Input for NTC probe ……………………………………………………………………………………………………………. AKO-14901
Working ambient temperature ……………………………………………………………………………………………-10ºC to 50ºC
Ambient storage temperature ……………………………………………………………………………………………..-30ºC to 60ºC
Protection degree ……………………………………………………………………………………………………………………….. IP 65
Installation category……………………………………………………………………………………………….. II as per EN 60730-1
Degree of pollution ………………………………………………………………………………………………… II as per EN 60730-1
Grade as per UNE-EN 60730-1: Built-in control device, with Type 1.B automatic action operation feature, for use in
clean situations, logical support (software) class A and continuous operation. Degree of pollution 2.
Double isolation between power supply, secondary circuit and relay output.
Accessible parts pressure ball test temperature ………………………………………………………………………………… 75 °C
Parts positioning active elements …………………………………………………………………………………………………. 125 ºC
Radio interference suppression test current……………………………………………………………………………………270 mA
Voltage and current delayed by the EMC tests:………………………………………………………………………..207 V, 17 mA
Type of mounting ……………………………………………………………………………………………………………… Fixed interior
MODBUS address………………………………………………………………………………………………….. Indicated on the label
Dimensions …………………………………………………………………………………. 290mm (W) x 141mm (H) x 84.4mm (D)
Internal buzzer
For further information, refer to the user manual available on:
https://help.ako.com/assets/uploads/351652602.pdf
33
351652611 Ed. 04
Avertissements
-Le non-respect des instructions du fabricant lors de l’utilisation de l’équipement peut modifier les conditions de sécurité de l’appareil. Pour un fonctionnement correct, n’utilisez que des sondes fournies par AKO. -Entre 40 °C et +20 °C, si la sonde NTC est prolongée jusqu’à 1 000 m avec un câble d’au moins 0,5 mm2, l’écart maximum sera de 0,25 °C (câble pour prolongation de sondes, réf. AKO-15586. Raccorder le treillis à la terre uniquement sur une des extrémités). -Il doit être installé dans un endroit à l’abri des vibrations, de l’eau et des gaz corrosifs, où la température ambiante ne dépasse pas la valeur indiquée dans les indications techniques. -Pour que la lecture soit correcte, la sonde doit être placée dans un endroit à l’abri des influences thermiques autres que la température que vous souhaitez mesurer ou contrôler. -Le degré de protection IP65 n’est valable que lorsque le couvercle de protection est fermé. -Le degré de protection IP65 n’est valable que si l’entrée de câbles dans l’appareil est réalisée au moyen d’un tube pour conduites électrique + presse-étoupes possédant un degré de protection IP65 ou supérieur. Les dimensions des presse-étoupes doivent être adaptées au diamètre du tube utilisé. -Ne pas asperger directement l’appareil avec des tuyaux haute pression pour éviter de l’endommager. IMPORTANT : -Les relais AUXILIAIRES sont programmables, leur fonctionnement dépend de la configuration. -La fonction des entrées numériques dépend de la configuration. -Les intensités et puissances indiquées sont les valeurs maximales de travail autorisées.
Maintenance
Nettoyez la surface de l’appareil avec un chiffon doux, de l’eau et du savon.
N’utilisez ni détergents abrasifs, ni essence, ni alcool ni solvants pour
éviter d’endommager l’appareil.
Câblage
Couper systématiquement l’alimentation avant de procéder au câblage. Les
sondes et leurs câbles ne doivent JAMAIS être installés dans une conduite à
côté de câbles électriques, de commande ou d’alimentation. Le circuit
d’alimentation doit être muni d’un interrupteur de déconnexion situé à
proximité de l’appareil (2 A, 230 V minimum). Le câble d’alimentation doit
être de type H05VV-F ou NYM 1×16/3. La section à utiliser dépend de la
réglementation locale en vigueur. Toutefois, elle ne doit jamais être
inférieure à 1,5 mm2. Les câbles des sorties des relais ou du contacteur
doivent posséder une section de 2,5 mm2, doivent pouvoir être exposés à des
températures de travail supérieures ou égales à 70 ºC et doivent être
installés de manière que leur flexion soit minimisée. La zone de raccordement
à 120/230 V~ doit être maintenue dégagée de tout élément externe. Le
branchement à réaliser dépend des options choisies dans l’assistant initial de
configuration (Consulter page 37) et des configurations pour les entrées et
les sorties (Consulter page 47). Vérifiez le schéma inclus et la configuration
définie avant d’effectuer le branchement.
34
351652611 Ed. 04
Description
Contrôleur de température avec sortie pour la régulation du détendeur
électronique et le contrôle de la vitesse des ventilateurs d’évaporateur. Il
peut être configuré afin que, outre réguler le refroidissement de la chambre,
il puisse contrôler la surchauffe et régler la vitesse des ventilateurs
d’évaporateur à l’aide d’un variateur ou en utilisant des ventilateurs
électroniques.
1
2
Fixe : mode Stand-By actif, le réglage est arrêté. Clignotement : processus
d’arrêt contrôlé du réglage en cours.
Fixe : porte de la chambre ouverte. Clignotement : la porte est ouverte depuis
une durée supérieure à celle définie dans le paramètre A12.
Une alarme est active (pas l’HACCP ni la température).
Fixe : alarme HACCP active. Clignotement : alarme d’HACCP enregistrée et non-
confirmée. Pour confirmer une alarme HACCP, appuyer sur la touche .
Il existe une alarme de température active.
Fixe : ventilateurs d’évaporateur actifs. Clignotement : les ventilateurs
d’évaporateur devraient être actifs mais un retard leur en empêche. Pulsation
: ventilateurs d’évaporateur réglés par une sortie analogique.
Fixe : le relais COOL est actif. Clignotement : le relais COOL devrait être
actif mais un retard ou une protection l’en empêche. Pulsation : détendeur
réglé.
1: Display; 2: Teclado
Fixe : compresseur actif. Clignotement : le compresseur devrait être actif
mais un retard ou une protection l’en empêche. Dégivrage actif.
Mode cycle continu actif.
Lumière de la chambre active.
Alarme en cours en mode muet.
Température indiquée en ° Fahrenheit/° Celsius. Mode de programmation actif.
Écran inférieur affichant la valeur de surchauffe en temps réel. Écran
inférieur affichant le pourcentage d’ouverture du détendeur ou pourcentage de
puissance des ventilateurs d’évaporateur (selon la configuration). Écran
inférieur affichant la basse pression en psi/ bar.
35
351652611 Ed. 04
Clavier
Appuyez pendant 3 secondes pour activer/désactiver le mode Stand-By. Dans ce
mode, le réglage s’arrête et l’écran affiche l’icône m. Dans le menu de
programmation, sortez du paramètre sans enregistrer les changements, revenez
au niveau précédent ou sortez de la programmation.
Un appui court affiche la température de la sonde S2 pendant 10 secondes (si
elle est activée). Appuyez pendant 3 secondes pour démarrer/arrêter le
dégivrage. Dans le menu de programmation, il est possible de se déplacer dans
les différents niveaux ou, pendant le réglage d’un paramètre, de modifier sa
valeur.
Appuyez pendant 3 secondes pour activer/désactiver le mode cycle continu. Dans
le menu de programmation, il est possible de se déplacer dans les différents
niveaux ou, pendant le réglage d’un paramètre, de modifier sa valeur.
Un appui court active/désactive la lumière de la chambre. Appuyez pendant 3
secondes pour accéder au menu de programmation réduit. Appuyez pendant 6
secondes pour accéder au menu de programmation étendu. Dans le menu de
programmation, pour accéder au niveau affiché à l’écran ou, pendant le réglage
d’un paramètre, acceptez la nouvelle valeur.
Un appui court affiche la valeur effective actuelle du Set Point de
température sur l’écran supérieur, et le Set Point de surchauffe sur l’écran
inférieur, en tenant compte des modifications temporaires par d’autres
paramètres. Avec une alarme en cours, un appui court coupe le son de l’alarme
sonore. Appuyez pendant 3 secondes pour accéder au réglage du Set Point de
température.
STAND-BY Si le réglage ne peut pas être arrêté immédiatement en raison de sa
configuration, un processus d’arrêt contrôlé débute et l’icône m clignote.
Pour stopper le processus d’arrêt contrôlé et forcer le passage en Stand-by,
appuyez de nouveau sur la touche Stand-by pendant 3 secondes.
Sondes
Sonde Chambre / Sonde Évaporateur / Sonde 2° évaporateur
Sonde surchauffe
36
351652611 Ed. 04
Assistant
Lorsqu’il est alimenté pour la première fois, l’appareil entre en mode ASSISTANT.
L’écran affiche le messageIn{clignotant avec 0.
Les touches et modifient la valeur, la touche SET accepte la
1
valeur et passe à l’étape suivante.
Étape 1 : Sélectionner l’option InI appropriée en fonction du type d’installation à réaliser et appuyer sur SET. Les options disponibles sont affichées sur le tableau suivant :
/ / SET
Type d’installation
Paramètres
InI Contrôle du Pump compresseur Down
Dégivrage
Vent. Évap.
Pd o00 o20 I00 I10 I11 I20 I21 I30 I31 d1 D7
F3
0
Mode démo, affiche la température sur l’écran mais ne régule pas la température
1
Non
Non Électrique Oui 0 0 2 0 0 0 0 * 20 0 0
2
Oui
Oui
Électrique
Oui 1 1 2 7 1 0 0 * 20 0 0
3
Oui
Non Électrique Oui 0 1 2 0 0 0 0 * 20 0 0
4
Non
Non
Air
Oui 0 0 1 0 0 0 0 * 20 1 1
5
Oui
Oui
Air
Oui 1 1 1 7 1 0 0 * 20 1 1
6
Oui
Non
Air
Oui 0 1 1 0 0 0 0 * 20 1 1
7
Oui
8
Oui
Oui Gaz chaud Oui 1 1 2 7 1 7 1 5 2 0 Non Gaz chaud Oui 0 1 2 0 0 7 1
-
- 5 2 0
-
Si u00 = 2 : o20 = 3, I30 = 0, I31 = 0 Si u00 2 : o20 = 0, I30 = 9
Si les options 2, 5 ou 7 sont choisies, vérifier la configuration du paramètre I11 en fonction du pressostat
utilisé.
Étape 2 : Choisir le type de détendeur à utiliser :
2
u00 = 0 u00 = 1 u00 = 2
Soupape solénoïde de liquide + détendeur thermostatique
Soupape solénoïde avec contrôle par PWM
Détendeur électronique (un contrôleur externe pour le DE est requis. Pour plus
d’informations, consultez la note d’application disponible sur notre site web)
/ / SET
Si vous choisissez u00 = 0, les phases 4, 5, 6, 7, 8, 9 et 11 ne s’affichent pas. Si vous choisissez u00 = 2, la phase 3 ne s’affiche pas.
37
351652611Ed. 04
Étape 3 : Définir le type de contrôle des ventilateurs.
3
F10 = 0 Contrôle ON/OFF
F10 = 1
Contrôle par variateur de fréquence externe (non compris) / ventilateurs électroniques (ECFAN)
Si vous choisissez F10 = 0, la phase 9 ne s’affiche pas. Étape 4 :
4
Définir le type de gaz réfrigérant utilisé.
u02=0 R404A u02 = 6 R513A u02 = 12 R1234ze
u02 = 1 R134A u02 = 7 R744 u02 = 13 R23
u02 = 2 R407A u02 = 8 R449A u02 = 14 R717
u02 = 3 R407F u02 = 9 R290 u02 = 15 R407C
u02 = 4 R410A u02 = 10 R32 u02 = 16 R1234yf
u02 = 5 R450A u02 = 11 R448A u02 = 17 R22
5
u02=18 R454C u02=19 R455A u02=20 R507A
u02=21 R515B u02=22 R452A u02=23 R452B
u02=24 R454A
Étape 5 : Définir les unités de pression à utiliser.
6
I60 = 0 Bar I60 = 1 Psi
Étape 6 : Définir le type de capteur de pression utilisé.
I61 = 0 Désactivé I61 = 1 4 – 20 mA I61 = 2 I61 = 3 0,5 – 4,5 V I61 = 4 0 – 10
V I61 = 5
Étape 7 : Définir la valeur minimale de la sonde de pression (I62) (valeur à 4
mA, 0 V, 0,5 V ou 1 V selon I61).
0 – 5 V 1 – 5 V
9
Étape 8 :
10 Définir la valeur maximale de la sonde de pression (I63) (valeur à 20 mA, 5
V,
4,5 V ou 10 V selon I61).
Étape 9 : Choisir celle de la sortie analogique (pour le contrôle du DE ou des
ventilateurs).
o30 = 0 4 – 20 mA o30 = 1 0 – 10 V
Étape 10 : Choix du Set Point de température.
38
/ / SET
/ / SET
/ / SET
/
/
SET
/
/
SET
/ / SET
351652611 Ed. 04
Étape 11 : Choix du Set Point de surchauffe.
11
Étape 12 : Configurer le reste des paramètres par défaut ?
dFP = 0 Non, les autres paramètres ne se modifient pas dFP = 1 Oui, les autres paramètres se configurent sur leur valeur par défaut
/ / SET
Cette option n’apparaît que si ce n’est pas la première fois que l’assistant est exécuté. La configuration initiale a été réalisée, l’appareil commence à réguler la température.
L’assistant de (en appuyant
configuration sur la touche
ne se réactive pas. Pour l’activer à m pendant 3 secondes) et attendre
nqouuevel’aaup,paarcetiilvearrrlêetemcoodmepSlèttaenmd-eBnyt
la régulation (l’indicateur m reste allumé en permanence) et appuyer dans cet ordre sur les touches
suivantes (une après l’autre, non ensemble) , , SET.
Si la fonction Pump Down est active, un certain temps peut s’écouler entre le moment du démarrage de la fonction Stand-by jusqu’à ce que le contrôleur s’arrête.
Fonctionnement
Messages
Erreur de fonctionnement du Pump Down (arrêt), le temps configuré dans le paramètre C20 a été dépassé. Le message s’affiche uniquement à l’écran.
Erreur de fonctionnement du Pump Down (mise en marche), le temps configuré dans le paramètre C19 a été dépassé. Le message s’affiche uniquement à l’écran.
Sonde 1, 2, 3, 4, 5 ou 6 en panne (circuit ouvert, croisé, ou valeur hors des limites de la sonde). Active le relais d’alarme et l’alarme sonore.
Alarme de porte ouverte. Uniquement si la porte est ouverte depuis une durée
supérieure à celle définie dans le paramètre A12. Active le relais d’alarme et
l’alarme sonore.
Alarme de température maximum dans la sonde de contrôle. La valeur de
température programmée en A1 a été atteinte. Active le relais d’alarme et
l’alarme sonore.
Alarme de température minimum dans la sonde de contrôle. La valeur de
température programmée en A2 a été atteinte. Active le relais d’alarme et
l’alarme sonore.
Alarme externe activée (par entrée numérique). Active le relais d’alarme et
l’alarme sonore.
39
351652611 Ed. 04
Alarme externe sévère activée (par entrée numérique). Active le relais
d’alarme et l’alarme sonore.
Alerte de dégivrage interrompue pour durée écoulée, le temps défini en d1 a
été dépassé. Active le relais d’alarme et l’alarme sonore.
Alarme HACCP, la température a atteint la valeur du paramètre h1 pendant une
durée supérieure à celle définie en h2. Active le relais d’alarme et l’alarme
sonore. Alarme HACCP en raison d’une coupure électrique, la température
définie en h1 après une coupure électrique a été atteinte. Active le relais
d’alarme et l’alarme sonore.
Alarme de surchauffe minimale, la valeur définie en A20 a été atteinte. Active
le relais d’alarme et l’alarme sonore.
Alerte de surchauffe élevée, la valeur définie en A23 a été atteinte. Le
message s’affiche uniquement à l’écran.
Alarme de pression d’évaporation maximale, la valeur définie en A26 a été
atteinte. Active le relais d’alarme et l’alarme sonore.
Alarme de pression d’évaporation minimale, la valeur définie en A29 a été
atteinte. Active le relais d’alarme et l’alarme sonore.
Indique qu’un dégivrage est en cours. Le message s’affiche uniquement à
l’écran.
Demande de mot de passe (password). Voir paramètres b10 et PAS. Le message
s’affiche uniquement à l’écran.
Affichés de manière séquentielle avec la température : le contrôleur est en
mode démo, la configuration n’a pas été effectuée.
40
351652611 Ed. 04
Configuration
Menu de programmation réduit Permet de configurer rapidement les paramètres les plus utilisés. Pour y accéder, appuyer sur la touche SET pendant 3 secondes.
Menu de programmation réduit
HORS DE PROGRAMMATION
20 sec.
EN PROGRAMMATION
Indication température
Paramètres
Valeurs
3 sec.
Modifier le paramètre
Modifier la valeur
Enregistrer les modifications N’enregistre pas les modifications
20 sec.
Niveau 2
Paramètres
Description SP Réglage de température (Set Point) C1 Différentiel de la sonde
1 (hystérésis) d0 Fréquence de dégivrage (délai entre 2 démarrages) d1 Durée
maximale du dégivrage (0 = dégivrage désactivé) d4 Température finale de
dégivrage (par sonde) (si I00 ¹ 1) Sh Set Point de surchauffe F3 État des
ventilateurs lors du dégivrage 0 = arrêtés ; 1 = en marche A1 Alarme de
maximum sur sonde 1 (doit être supérieur au SP) A2 Alarme de minimum sur sonde
1 (doit être inférieur au SP)
Valeurs Min. Déf. Max. ºC/ºF -50 0,0 99 ºC/ºF 0,1 2,0 20,0 h. 0 6 96 min. 0 255 ºC/ºF -50 8,0 50 ºK 0,1 8 40 01 ºC/ºF A2 99,0 99,0 ºC/ºF -50 -50 A1
*Selon l’assistant de configuration. 41
351652611 Ed. 04
Menu de programmation étendu
Dans le menu de programmation étendu, vous pouvez configurer tous les
paramètres de l’appareil pour l’adapter aux besoins de votre installation.
Pour y accéder, appuyer sur la touche SET pendant 6 secondes.
IMPORTANT : si la fonction du mot de passe a été configurée comme blocage du
clavier (b10 = 2), ou comme blocage de l’accès aux paramètres (b10 = 1) lors
d’une tentative d’accès à n’importe laquelle des fonctions, l’introduction du
code d’accès programmé en PAS sera demandée. Si le code introduit est
incorrect, l’appareil affiche de nouveau la température.
IMPORTANT : il est possible que certains paramètres ou menus ne soient pas
visibles en fonction de la configuration du reste des paramètres et des
options choisies dans l’assistant initial.
Menu de programmation étendu
HORS DE PROGRAMMATION
20 sec.
Indication température
Niveau 1 Menus
EN PROGRAMMATION 20 sec.
NNiveau 2 Paramètres
Niveau 3 Valeurs
6 sec.
Changer le menu
Modifier le paramètre
Modifier la valeur
Enregistrer les modifications N’enregistre pas les modifications
20 sec.
42
Paramètres
Réglage et contrôle
351652611 Ed. 04
Niveau 2 Niveau 1 rE
Description
Valeurs Min. Déf. Max.
SP Réglage de température (Set Point) C0 Calibrage de la sonde 1 (offset)
ºC/ºF -50 0,0 99 ºC/ºF -20,0 0,0 20,0
C1 Différentiel de la sonde 1 (hystérésis)
ºC/ºF 0,1 2,0 20,0
C2
Blocage supérieur du point de consigne (impossible de fixer au-delà de cette valeur)
ºC/ºF C3 99 99
C3
Blocage inférieur du point de consigne (impossible de fixer en-deçà de cette valeur)
ºC/ºF -50 -50 C2
Type de retard pour la protection du compresseur : C4 0 = temps minimum du
compresseur sur OFF
1 = temps minimum du compresseur sur OFF et ON au cours de chaque cycle
001
C5
Temps de retard de la protection (valeur de l’option choisie au paramètre C4)
min. 0 0 120
État du relais COOL avec erreur sur sonde 1 : C6 0 = OFF; 1 = ON; 2 = moyenne
selon les dernières 24h avant l’erreur de
sonde ; 3 = ON-OFF selon prog. C7 et C8
023
C7
Temps du relais sur ON si sonde 1 en panne (si C7 = 0 et C8 ¹ 0, le relais sera toujours sur OFF déconnecté)
C8
Temps du relais sur OFF si sonde 1 en panne (si C8 = 0 et C7 ¹ 0, le relais sera toujours sur ON connecté)
C9 Durée maximale du mode de cycle continu. (0 = désactivé)
min. 0 10 120 min. 0 5 120 h. 0 0 48
Variation du point de consigne (SP) en mode de cycle continu, une fois arrivé à
C10 ce point (SP + C10), il revient en mode normal. (SP + C10 ³ C3).
ºC/ºF
La valeur de ce paramètre est toujours négative, sauf si elle est de 0. (0 = OFF)
0
-50
C3SP
C12
Variation du point de consigne (SP) lorsque la fonction changement de Set point est active. (SP + C12 £ C2) (0 = désactivé)
C19
Temps maximal pour démarrage depuis pump down (Les valeurs entre 1 et 9 secondes ne sont pas acceptées) (0 = désactivé)
ºC/ºF
C3SP
0
C2SP
sec. 0 0 120
C20 Temps maximum de Pump Down (0 = désactivé)
min. 0 0 15
C22
Arrêter les ventilateurs et COOL lors de l’ouverture de la porte 0 = non ; 1 = oui
001
C23 Retard de démarrage des ventilateurs et de COOL avec porte ouverte EP Sortir au niveau 1
min. 0 0 999
*Selon l’assistant de configuration. 43
Dégivrage
351652611 Ed. 04
Niveau 2 Niveau 1 dEF
Description
Valeurs Min. Déf. Max.
d0 Fréquence de dégivrage (délai entre 2 démarrages)
h. 0 6 96
d1 Durée maximale du dégivrage (0 = dégivrage désactivé)
min. 0 * 255
Type de message pendant le dégivrage : 0 = affiche la température réelle ; d2
1 = affiche la température au début du dégivrage ;
2 = affiche le message dEF
022
d3
Durée maximale du message (durée ajoutée à la fin du processus de dégivrage)
d4 Température finale de dégivrage (par sonde) (si I00 ¹ 1)
d5
Dégivrage lors de la connexion de l’équipement : 0 = NO, premier dégivrage selon d0 ; 1 = OUI, premier dégivrage selon d6 ;
d6 Retard de démarrage du dégivrage lors de la connexion de l’équipement
d7
Type de dégivrage : 0 = résistances ; 1 = air/ventilateurs 2 = gaz chaud
min. 0 5 255 ºC/ºF -50 8,0 50
001 min. 0 0 255
0*2
d8
Calcul de temps entre périodes de dégivrage : 0 = temps réel total 1 = somme de temps du COOL connecté
001
d9
Temps d’égouttement à la fin d’un dégivrage (arrêt de COOL et des ventilateurs)
min. 0 1 255
EP Sortir au niveau 1
Ventilateurs d’évaporateur
Niveau 2 Niveau 1 FAn
Description
F0 Température d’arrêt des ventilateurs
F1 Différentiel de la sonde 2 si les ventilateurs sont arrêtés
F2 Arrêter les ventilateurs lors de l’arrêt de compresseur 0 = non ; 1 = oui
F3 État des ventilateurs lors du dégivrage 0 = arrêtés ; 1 = en marche
F4
Retard de démarrage après le dégivrage (si F3 = 0) Il n’agit que s’il est supérieur à d9
F10 Type de réglage des ventilateurs 0 = ON/OFF 1 = variateur de fréquence
EP Sortir au niveau 1
Valeurs Min. Déf. Max. ºC/ºF. -50 45 50 ºC/ºF 0,1 2,0 20,0 001 01
min. 0 2 99
01
*Selon l’assistant de configuration. 44
Détendeur
351652611 Ed. 04
Niveau 2 Niveau 1 EEV
Description
Valeurs Min. Déf. Max.
u00
Type de détendeur : 0 = solénoïde + détendeur thermostatique PWM 2 = DE type stepper
1 = DE type
Sh Set Point de surchauffe
0*2 K 0,1 8 40
Type de gaz réfrigérant : 0= R-404A, 1= R-134A, 2= R-407A, 3= R-407F, 4= R-410A,
u02
5= R-450A, 6= R-513A, 7= R-744, 8= R-449A, 9= R-290, 10= R-32, 11= R-448A, 12=R1234ze, 13=R23, 14=R717, 15=R407C, 16=R1234yf, 17=R22, 18=R454C,
0 * 24
19=R455A, 20=R507A, 21=R515B, 22=R452A, 23=R452B, 24=R454A
u03 Temps de cycle PWM u04 Valeur de la constante proportionnelle (P) u05 Valeur de la constante intégrale (I) u06 Valeur de la constante de dérivation (D)
s. 2 6 10 1 10 100 0 10 100 0 0 100
u07
Valeur d’ouverture du détendeur électronique lorsque le refroidissement s’active
% u13 50 u12
u08 Durée d’ouverture du détendeur en demande de refroidissement
u09
Valeur d’ouverture du détendeur avec erreur de sonde S5 ou S6 : 0 = ouverture fixe selon u10 ; 1 = ouverture moyenne des dernières 24 heures
u10 Valeur d’ouverture du détendeur avec erreur de sonde S5 ou S6 (si u09 = 0)
u11
Valeur d’ouverture manuelle du détendeur (0 = désactivé), (cycles selon u03) Nécessite un code de sécurité, voir manuel d’utilisateur.
u12 Valeur d’ouverture maximale du détendeur u13 Valeur d’ouverture minimale du détendeur
u14
Valeur d’ouverture du détendeur après le dégivrage (0 = désactivé), (durée selon u15)
u15 Durée d’ouverture du détendeur après le dégivrage
u16 Ouverture du détendeur en car d’erreur LOP (0 = détendeur fermé)
EP Sortir au niveau 1
s. 2 5 240
001
% u13 0 u12
% u13 0 u12
% u13 100 100
% 0 0 u12
%
0/ u13
0
u12
s 0 0 240
%
0/ u13
0
u12
*Selon l’assistant de configuration. 45
Alarmes
351652611 Ed. 04
Niveau 2 Niveau 1 AL
Description
Valeurs Min. Déf. Max.
A0 Configuration des alarmes de température 0 = relative au SP 1 = absolue
011
A1 Alarme de maximum sur sonde 1 (doit être supérieur au SP)
ºC/ºF A2 99,0 99,0
A2 Alarme de minimum sur sonde 1 (doit être inférieur au SP)
ºC/ºF -50 -50 A1
A3 Retard d’alarmes de température à la mise en marche
min. 0 0 120
A4 Retard d’alarmes de température à compter de la fin d’un dégivrage
min. 0 0 99
A5 Retard d’alarmes de température depuis que la valeur d’A1 ou A2 est atteinte min. 0 30 99
A6
Retard d’alarme externe/alarme externe sévère à la réception d’un signal en entrée numérique (I10 ou I20 = 2 ou 3)
min. 0 0 120
A7
Retard de désactivation d’alarme externe/ alarme externe sévère lors de la disparition du signal en entrée numérique (I10 ou I20 = 2 ou 3)
min. 0 0 120
A8
Afficher un avertissement si le dégivrage est finalisé pour temps maximal 0 = non 1 = oui
001
A9
Polarité relais alarme 0 = relais ON en alarme (OFF sans alarme) ; 1= relais OFF en alarme (ON sans alarme)
001
A10 Différentiel d’alarmes de température (A1 et A2)
ºC/ºF 0,1 1,0 20,0
A12 Retard d’alarme de porte ouverte (si I10, I20 ou I30 = 1)
min. 0 10 120
A20 Valeur de surchauffe minimale pour alarme LSH A21 Retard de l’activation de l’alarme LSH
K 0 2 Sh sec. 0 30 240
A22 Hystérésis alarme LSH
K
0,1
2
ShA20
A23 Valeur de surchauffe maximale pour l’alerte HSH A24 Retard de l’activation de l’avertissement HSH
K sh 40 40 s 0 30 240
A25 Hystérésis désactivation alarme HSH
K
0.1
2
A23sh
A26 Pression d’évaporation maximale (MOP)
bar 0 60 60
A27
Retard de l’activation de l’alarme MOP (temps de retard pour l’activation de l’alarme une fois que le seuil est dépassé)
sec. 0 30 240
A28
Hystérésis désactivation alarme MOP (lorsque la pression descend en dessous du niveau MOP-hystérésis, l’alarme se désactive)
bar
0,1 1
60
A29 Pression d’évaporation minimale (LOP)
bar -1 0 8
A30
Retard de l’activation de l’alarme LOP (temps de retard pour l’activation de l’alarme une fois que le seuil est dépassé)
sec. 0 30 240
A31
Hystérésis désactivation alarme LOP (lorsque la pression monte au-dessus du niveau LOP + hystérésis, l’alarme se désactive)
bar 0,1 1
8
EP Sortir au niveau 1
46
Configuration de base
351652611 Ed. 04
Niveau 2 Niveau 1 bcn
Description
b00 Retard de toutes les fonctions lors de la réception d’alimentation électrique b01 Temporisation éclairage chambre
b10
Fonction du mot de passe (password) 0 = inactif 1 = blocage de l’accès aux paramètres ; 2 = blocage du clavier
PAS Mot de passe (password) b20 Adresse MODBUS
b21
Vitesse de communication : 0 = 9 600 bps 1 = 19 200 bps 2 = 38 400 bps 3 = 57 600 bps
b22 Alarme sonore activée 0 = non 1 = oui
Fonction de l’écran inférieur : 1 = sonde S2, 2 = sonde S3, 3 = sonde S4, b23
4 = sonde S5, 5 = surchauffe, 6 = sonde pression, 7 = % DE, 8 = % eFAN,
9 = sarrousel, 10 = arrêt
Unt Unités de travail 0 = ºC 1 = ºF EP Sortir au niveau 1
Entrées et sorties
Valeurs Min. Déf. Max. min. 0 0 255 min. 0 0 999 002 0 0 99 1 1 247 bps 0 0 3
011
1 * 10
001
Niveau 2 Niveau 1 InO
Description
Valeurs Min. Déf. Max.
I00
Sondes connectées : 1 = sonde 1 (chambre), 2 = sonde 1 (chambre) + sonde 2 (évaporateur)
122
Configuration entrée D1/S3 : 0 = désactivée, 1 = contact porte, 2 = alarme
I10
externe, 3 = alarme externe sévère, 4 = changement de SP, 5 = dégivrage à distance, 6 = verrouillage du dégivrage, 7 = pressostat basse pression, 8 = ac-
tivation à distance en mode Stand-by, 9 = température produit
0*9
I11
Polarité entrée numérique D1 : 0 = active à la fermeture du contact, 1 = active à l’ouverture du contact
001
Configuration entrée D2/S4 : 0 = désactivée, 1 = contact porte, 2 = alarme externe, 3 = alarme externe sévère, 4 = changement de SP, 5 = dégivrage à I20 distance, 6 = verrouillage du dégivrage, 7 = pressostat haute pression pour gaz chaud, 8 = activation à distance en mode Stand-by, 9 = température produit, 10 = dégivrage 2e évaporateur
0 * 10
I21
Polarité entrée numérique D2 : 0 = active à la fermeture du contact, 1 = active à l’ouverture du contact
001
Configuration entrée D3/S5 : 0 = désactivée, 1 = contact porte, 2 = alarme
I30
externe, 3 = alarme externe sévère, 4 = changement de SP, 5 = dégivrage à distance, 6 = verrouillage du dégivrage, 7 = activation à distance en mode
Stand-by, 8 = température produit, 9 = température surchauffe (Sh)
0*9
I31
Polarité entrée numérique D3 : 0 = active à la fermeture du contact, 1 = active à l’ouverture du contact
001
*Selon l’assistant de configuration.
47
Entrées et sorties
351652611 Ed. 04
Niveau 2 Niveau 1 InO
Description
I60 Unités de pression : 0 = bar, 1 = Psi
I61
Type de capteur de pression (S6) : 0 = désactivé, 1 = 4-20 mA, 2 = 0-5 V, 3 = 0,5-4,5 V, 4 = 0-10 V, 5 = 1-5 V
I62 Valeur minimale de la sonde de pression (4 mA, 0 V, 0,5 V, 1 V) I63 Valeur maximale de la sonde de pression (20 mA, 5 V, 4,5 V, 10 V) I64 Calibrage de la sonde de pression (offset)
o00
Configuration du relais AUX1 : 0 = désactivé, 1 = compresseur/résistance carter, 2 = lumière, 3 = contrôle virtuel
Configuration du relais AUX2 : 0 = désactivé, 1 = alarme, 2 = lumière, o10 3 =
contrôle virtuel, 4 = dégivrage 2e évaporateur, 5 = résist. cadre porte,
6 = état du solénoïde identique, 7 = état de l’appareil identique
o20
Configuration du relais AUX3 : 0 = désactivé, 1 = alarme, 2 = lumière, 3 = ON/OFF contrôleur externe AO, 4 = dégivrage 2e évaporateur
o30 Type de sortie analogique (AO) : 0 = 4-20 mA, 1 = 0-10 V
EP Sortir au niveau 1
Alarme HACCP
Valeurs Min. Déf. Max. 01 005 -1 0 I63 I62 12 60 -10 0 10 03
027
004 001
Niveau 2 Niveau 1 HCP
Description
h1 Température maximale pour l’alarme HACCP
h2
Temps maximum autorisé pour l’activation de l’alarme HACCP (0 = alarme HACCP désactivée)
EP Sortir au niveau 1
Informations (lecture seule)
Valeurs Min. Déf. Max. ºC/ºF -50 99,0 99,0
h. 0 0 255
Niveau 2 Niveau 1 tid
Description InI Option choisie dans l’assistant de configuration Pd Pump down
actif ? 0 = non, 1 = oui PU Version du logiciel (informations) Pr Révision du
logiciel PSr Sous-version de programme bU Version du bootloader br Révision du
bootloader bSr Sous-version du bootloader PAr Révision du plan de paramètres
EP Sortir au niveau 1
*Selon l’assistant de configuration.
48
Valeurs Min. Déf. Max.
351652611 Ed. 04
Spécifications techniques
Alimentation …………………………………………………………………………………………………….. 100 – 240 V ~ 50/60 Hz
Puissance maximale absorbée dans la manoeuvre …………………………………………………………………………….8,1 VA
Intensité maximale nominale …………………………………………………………………………………………………………..15 A
Relais DEF – SPDT – 20 A
NO…………………………………………………(EN 60730-1 : 15 (15) A 250 V~ )
NC…………………………………………………..(EN 60730-1: 15 (13) A 250 V~)
Relais FAN – SPST – 16 A…………………………………………………………………………….(EN 60730-1 : 12 (9) A 250 V~)
Relais COOL – SPST – SSR 2 A ……………………………………………………………………………. Vmax : 275 V~, Imax : 2 A
Relais AUX 1 – SPDT – 20 A
NO………………………………………………….(EN 60730-1 : 15 (15) A 250 V~)
NC…………………………………………………..(EN 60730-1: 15 (13) A 250 V~)
Relais AUX 2 – SPDT – 16 A
NO……………………………………………………(EN 60730-1 : 12 (9) A 250 V~)
NC…………………………………………………….(EN 60730-1: 10 (8) A 250 V~)
Relais AUX 3 – SPST – 16 A
NO……………………………………………………(EN 60730-1 : 12 (9) A 250 V~)
Nbre d’opérations des relais …………………………………………………………………….EN 60730-1 : 100 000 opérations
Plage de température de la sonde …………………………………………………………………………………-50,0 ºC à 99,9 ºC
Résolution, réglage et différentiel ………………………………………………………………………………………………….. 0,1ºC
Précision thermométrique…………………………………………………………………………………………………………….± 1 ºC
Tolérance de la sonde NTC à 25 ºC……………………………………………………………………………………………..± 0,4 ºC
Entrée pour sonde NTC ……………………………………………………………………………………………………….. AKO-14901
Température ambiante de travail……………………………………………………………………………………………. -10 à 40 ºC
Température ambiante de stockage …………………………………………………………………………………….-30 ºC à 60 ºC
Degré de protection……………………………………………………………………………………………………………………… IP 65
Catégorie d’installation …………………………………………………………………………………………………. II s/ EN 60730-1
Niveau de pollution ………………………………………………………………………………………………………. II s/ EN 60730-1
Classification selon la norme UNE-EN 60730-1 : dispositif à commande intégrée, type de fonctionnement auto-
matique pour une action de type 1.B, à utiliser dans une ambiance propre, support logique (logiciel) de classe A et
fonctionnement en continu. Niveau de pollution 2.
Double isolation entre alimentation, circuit secondaire et sortie relais.
Température de l’essai à la bille de pression parties accessibles …………………………………………………………… 75 ºC
Parties qui positionnent les éléments actifs ……………………………………………………………………………………. 125 ºC
Courant d’essai de suppression d’interférences radio……………………………………………………………………….270 mA
Tension et courant déclarés par les essais d’EMC :……………………………………………………………………207 V, 17 mA
Type de montage……………………………………………………………………………………………………………….. Intérieur fixe
Adresse MODBUS………………………………………………………………………………………………… Indiquée sur l’étiquette
Dimensions …………………………………………………………………………………. 290 mm (l) x 141 mm (h) x 84,4 mm (P)
Vibreur interne
Pour plus d’informations, consultez le manuel d’utilisateur disponible sur:
https://help.ako.com/assets/uploads/351652603.pdf
49
351652611 Ed. 04 50
351652611 Ed. 04 51
351652611 Rev. 03 2023
AKO ELECTROMECÁNICA , S.A.L. Avda. Roquetes, 30-38 08812 · Sant Pere de Ribes.
Barcelona · Spain www.ako.com
Nos reservamos el derecho de suministrar materiales que pudieran diferir
levemente de los descritos en nuestras Hojas Técnicas. Información actualizada
en nuestra web. We reserve the right to supply materials that might vary
slightly to those described in our Technical Sheets. Updated information is
available on our website. Nous nous réservons le droit de fournir des produits
qui peuvent légèrement différer de ceux décrits dans nos Fiches techniques.
Informations actualisées sur notre site Web .