Schneider Electric BMENUA0100 OPC UA Module Instruction Manual

June 4, 2024
Schneider Electric

How to Install BMENUA0100 Firmware
Using EcoStruxure Automation Device Maintenance
Instruction Manual

Firmware Updates – Unsecured Mode

Pre-Requisites

  • If the card is already configured, take a backup of the module configuration and reset the module to Factory Default.

  • Once RESET select Standard (Unsecured) Mode and wait until it is in standard mode (see the LED pattern).

  • Use either the default IP address of the control port or the configured IP address (i.e. 192.164.10.1).
    The default is 10.10.@MAC5.@MAC6.
    Example: @MAC 00.80.F4.01.F0.61
    Default @IP will be: 10.10.240.97

  • If the control port is disabled, use the backplane port IP address.

  • Check communication with the module using Ping.

The positions on the rotary switch are:

Schneider Electric BMENUA0100 OPC UA Module - User Management
The BMENUA0100 module provides role-based access control (RBAC). All users are assigned a role and can perform only those tasks associated with that role.
The following roles and permissions are supported:

Role Permissions
Cybersecurity Configuration Firmware Upgrade
Web Page Access OPC UA Protocol Access
SECADM Update, Read, Delete
OPERATOR
ENGINEER
INSTALLER

Each BMENUA0100 module supports a maximum of 15 simultaneous users. No custom roles or custom permission sets can be configured.
No IP address-based access control whitelist can be configured.

  • Open the web page: e.g. https://192.164.10.1
  • Enter the login and password:
  • Login: installer
  • Password: Inst@ller
  • Confirm access to the web page of the module.
  • If the password does not open the unit, repeat the first step and ensure the module has been reset to factory default.
  • Only the “installer” profile can upgrade the firmware.

Schneider Electric BMENUA0100 OPC UA Module - 1

Open EcoStruxure Automation Device Maintenance (EADM)

Setup EADM – this step can be bypassed but is useful if updating the CPU

Schneider Electric BMENUA0100 OPC UA Module - 2

Acquire firmware and load this into the package folder
Modicon M580 BMENUA0100 Firmware SV01.10 | Schneider Electric (se.com)

Schneider Electric BMENUA0100 OPC UA Module - 3

EcoStruxure Automation Device Maintenance (EADM)

Discover and Manually Add a Device

Schneider Electric BMENUA0100 OPC UA Module - 4Select the firmware and trust the Connection

Schneider Electric BMENUA0100 OPC UA Module - 5

Enter the Password and Connect

Schneider Electric BMENUA0100 OPC UA Module - 6

Select the device, then update the firmware and confirm the update

Schneider Electric BMENUA0100 OPC UA Module - 7

Monitor the update, verify completion and check the summary

Schneider Electric BMENUA0100 OPC UA Module - 8

Pre-Requisites

  • If the card is already configured, take a backup of the module configuration and reset the module to Factory Default.

  • Once RESET select Standard (Unsecured) Mode and wait until it is in standard mode (see the LED pattern).

  • Use either the default IP address of the control port or the configured IP address (i.e. 192.164.10.1).
    The default is 10.10.@MAC5.@MAC6.
    Example: @MAC 00.80.F4.01.F0.61
    Default @IP will be: 10.10.240.97

  • If the control port is disabled, use the backplane port IP address.

  • Check communication with the module using Ping.

The positions on the rotary switch are:

Schneider Electric BMENUA0100 OPC UA Module - User Management
The BMENUA0100 module provides role-based access control (RBAC). All users are assigned a role and can perform only those tasks associated with that role.
The following roles and permissions are supported:

Role Permissions
Cybersecurity Configuration Firmware Upgrade
Web Page Access OPC UA Protocol Access
SECADM Update, Read, Delete
OPERATOR
ENGINEER
INSTALLER

Each BMENUA0100 module supports a maximum of 15 simultaneous users. No custom roles or custom permission sets can be configured.
No IP address-based access control whitelist can be configured.

Access Web page

  • https://192.164.10.1 – (i.e via the appropriate IPV4 address.

  • Login – first with the default setting

  • Login: admin Password: password

  • Change to a new password as required – suggestion:
    Login: admin
    Password: A@dmin_01

  • Remove the errors

Schneider Electric BMENUA0100 OPC UA Module - 9

Configure an installer

  • Needed to update the firmware
  • Under user management, create a New User.
  • Suggestion: user: Installer pswd: Inst@ller_01 role: Installer
  • Once submitted make sure the configuration is applied to the device.

Schneider Electric BMENUA0100 OPC UA Module - 10

Connect using EcoStruxure Automation Device Maintenance (EADM)
Refer to Firmware Updates – Standard
Mode for more detail

  1. Open EADM

  2. Make sure the firmware is in the
    Data Packages folder

  3. Add a manual device

  4. Select the BMENUA0100 firmware

  5. Trust the certificate

  6. Enter the password and connect.

  7. Select the device

  8. Update firmware

  9. Confirm success via the summary

Schneider Electric BMENUA0100 OPC UA Module - 11

Confidential Property of Schneider Electric

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Schneider Electric User Manuals

Related Manuals