How to Install BMENUA0100 Firmware
Using EcoStruxure Automation Device Maintenance
Instruction Manual

Firmware Updates – Unsecured Mode

Pre-Requisites

  • If the card is already configured, take a backup of the module configuration and reset the module to Factory Default.

  • Once RESET select Standard (Unsecured) Mode and wait until it is in standard mode (see the LED pattern).

  • Use either the default IP address of the control port or the configured IP address (i.e. 192.164.10.1).
    The default is 10.10.@MAC5.@MAC6.
    Example: @MAC 00.80.F4.01.F0.61
    Default @IP will be: 10.10.240.97

  • If the control port is disabled, use the backplane port IP address.

  • Check communication with the module using Ping.

The positions on the rotary switch are:

Schneider Electric BMENUA0100 OPC UA Module - User Management
The BMENUA0100 module provides role-based access control (RBAC). All users are assigned a role and can perform only those tasks associated with that role.
The following roles and permissions are supported:

Role Permissions
Cybersecurity Configuration Firmware Upgrade
Web Page Access OPC UA Protocol Access
SECADM Update, Read, Delete
OPERATOR
ENGINEER
INSTALLER

Each BMENUA0100 module supports a maximum of 15 simultaneous users. No custom roles or custom permission sets can be configured.
No IP address-based access control whitelist can be configured.

  • Open the web page: e.g. https://192.164.10.1
  • Enter the login and password:
  • Login: installer
  • Password: Inst@ller
  • Confirm access to the web page of the module.
  • If the password does not open the unit, repeat the first step and ensure the module has been reset to factory default.
  • Only the “installer” profile can upgrade the firmware.

Schneider Electric BMENUA0100 OPC UA Module - 1

Open EcoStruxure Automation Device Maintenance (EADM)

Setup EADM – this step can be bypassed but is useful if updating the CPU

Schneider Electric BMENUA0100 OPC UA Module - 2

Acquire firmware and load this into the package folder
Modicon M580 BMENUA0100 Firmware SV01.10 | Schneider Electric (se.com)

Schneider Electric BMENUA0100 OPC UA Module - 3

EcoStruxure Automation Device Maintenance (EADM)

Discover and Manually Add a Device

Schneider Electric BMENUA0100 OPC UA Module - 4Select the firmware and trust the Connection

Schneider Electric BMENUA0100 OPC UA Module - 5

Enter the Password and Connect

Schneider Electric BMENUA0100 OPC UA Module - 6

Select the device, then update the firmware and confirm the update

Schneider Electric BMENUA0100 OPC UA Module - 7

Monitor the update, verify completion and check the summary

Schneider Electric BMENUA0100 OPC UA Module - 8

Pre-Requisites

  • If the card is already configured, take a backup of the module configuration and reset the module to Factory Default.

  • Once RESET select Standard (Unsecured) Mode and wait until it is in standard mode (see the LED pattern).

  • Use either the default IP address of the control port or the configured IP address (i.e. 192.164.10.1).
    The default is 10.10.@MAC5.@MAC6.
    Example: @MAC 00.80.F4.01.F0.61
    Default @IP will be: 10.10.240.97

  • If the control port is disabled, use the backplane port IP address.

  • Check communication with the module using Ping.

The positions on the rotary switch are:

Schneider Electric BMENUA0100 OPC UA Module - User Management
The BMENUA0100 module provides role-based access control (RBAC). All users are assigned a role and can perform only those tasks associated with that role.
The following roles and permissions are supported:

Role Permissions
Cybersecurity Configuration Firmware Upgrade
Web Page Access OPC UA Protocol Access
SECADM Update, Read, Delete
OPERATOR
ENGINEER
INSTALLER

Each BMENUA0100 module supports a maximum of 15 simultaneous users. No custom roles or custom permission sets can be configured.
No IP address-based access control whitelist can be configured.

Access Web page

  • https://192.164.10.1 – (i.e via the appropriate IPV4 address.

  • Login – first with the default setting

  • Login: admin Password: password

  • Change to a new password as required – suggestion:
    Login: admin
    Password: A@dmin_01

  • Remove the errors

Schneider Electric BMENUA0100 OPC UA Module - 9

Configure an installer

  • Needed to update the firmware
  • Under user management, create a New User.
  • Suggestion: user: Installer pswd: Inst@ller_01 role: Installer
  • Once submitted make sure the configuration is applied to the device.

Schneider Electric BMENUA0100 OPC UA Module - 10

Connect using EcoStruxure Automation Device Maintenance (EADM)
Refer to Firmware Updates – Standard
Mode for more detail

  1. Open EADM

  2. Make sure the firmware is in the
    Data Packages folder

  3. Add a manual device

  4. Select the BMENUA0100 firmware

  5. Trust the certificate

  6. Enter the password and connect.

  7. Select the device

  8. Update firmware

  9. Confirm success via the summary