Bally B40-BCU-IM-21 Condensing Unit Instruction Manual

June 13, 2024
Bally

B40-BCU-IM-21 Condensing Unit

Product Information: Condensing Unit Installation and

Maintenance

Product Support

Web: www.b-rp.ca/support

This product supports air, water, and remote models. It includes
hermetic, semi-hermetic, and scroll compressors.

General Safety

Only a qualified refrigeration mechanic who is familiar with
refrigeration systems and components, including all controls,
should perform the installation and start-up of the system. To
avoid potential injury, use care when working around coil surfaces
(if applicable) or sharp edges of metal cabinets. All piping and
electrical wiring should be installed in accordance with all
applicable codes, ordinances, and local by-laws.

Important Safety Note

Always disconnect and lock off the main power supply on any
system that will be worked on to avoid accidental start-up of the
equipment.

Inspection

  • Inspect all equipment before unpacking for visible signs of
    damage or loss.

  • Check shipping list against material received to ensure
    shipment is complete.

  • If carton is damaged but damage to equipment is not obvious,
    file a claim for concealed damage with the carrier.

  • If damage or loss during transport is evident, make a claim to
    the carrier as it will be their responsibility, not that of the
    manufacturer.

  • Check the electrical ratings on the unit to make sure they
    correspond to those ordered and to electrical power available at
    the job site.

  • Save all shipping papers, tags, and instruction sheets for
    reference by installer and owner.

Handling, Placement, and Installation

When selecting a location for the condensing unit, consider the
following:

  • Loading capacity of the floor or roof. Check building codes for
    weight distribution requirements.

  • Distance to suitable electrical supply.

  • Distance to the evaporator.

  • Adequate air circulation and ventilation.

  • Close proximity to water source and floor drains (water-cooled
    units).

  • Accessibility for maintenance.

  • Local building codes.

  • Adjacent buildings relative to noise levels.

  • Wishes of the end user / owner.

Once a specific location is chosen, obtain written approval of
this location from the building and/or condensing unit owner to
avoid disagreement and expense later on.

A fully qualified and properly equipped crew with the necessary
tackle and rigging should be engaged to locate the condensing unit
in position. When lifting the unit, spreader bars and chafing gear
should be used to prevent damage. To reduce vibrations that may be
transmitted through the floor structure, install vibration
isolators under the mounting base. These isolators may be rubber,
cork, or similar materials.

®

Bulletin B40-BCU-IM-20 Part # 1068157
PRODUCT SUPPORT web: www.b-rp.ca/support
see inside back cover for more details

scan:

Condensing Unit Installation and Maintenance
Air, Wat e r a nd Re m ot e M ode ls
H e r m e t ic , Se m i-H e r m e t ic a nd Scroll Compressors

!

WARNING: Only a qualified refrigeration mechanic who is familiar with refrigeration systems and
components, including all controls, should perform the installation and start- up of the system.

CONTENTS Page
General Safety …………………………………………………………………………………………………….. 2 Inspection…………………………………………………………………………………………………………….. 2 Handling, Placement and Installation……………………………………………………………………….. 3 Location……………………………………………………………………………………………………………… 4 – 6 Lifting…………………………………………………………………………………………………………………… 7 Electrical Information…………………………………………………………………………………………… 8 – 9 Refrigerant Piping ………………………………………………………………………………………………. 10 – 12 Line Insulation……………………………………………………………………………………………………… 13 Valve Systems…………………………………………………………………………………………………….. 14 Refrigerant Charging …………………………………………………………………………………………… 14 – 19 Weight Of Refrigerants………………………………………………………………………………………….. 20 Compressor Oils…………………………………………………………………………………………………… 21 Water Cooled Condensers……………………………………………………………………………………… 22 Recommended Options…………………………………………………………………………………………. 22 Available Options and Option Information………………………………………………………………. 23 – 26 Leak Testing ……………………………………………………………………………………………………….. 27 Evacuation and Dehydration …………………………………………………………………………………. 27 Dehydration Procedure………………………………………………………………………………………… 28 – 29 System Start-Up Checklist …………………………………………………………………………………….. 29 Pressure Controls ………………………………………………………………………………………………… 30 Low Temperature Room Pull-Down ………………………………………………………………………… 30 Checking Superheat …………………………………………………………………………………………….. 31 Sequence Of Operation…………………………………………………………………………………………. 32 System Operational Checklist ………………………………………………………………………………… 33 System Troubleshooting ………………………………………………………………………………………. 34 – 36 Customer Instructions ………………………………………………………………………………………….. 37 Maintenance Program ………………………………………………………………………………………….. 37 Service Parts Availability………………………………………………………………………………………… 37 Appendix A: Wiring Diagrams………………………………………………………………………………. A1 – A17 Appendix B: Refrigerant Line Sizing Charts…………………………………………………………… B1 – B5 Appendix C: Equipment Start-Up Sheets………………………………………………………………. C1 – C4 Product Support Resources…………………………………………………………………………………. 70 -71 “As Built” Service Parts List………………………………………………………………………………….. BACK
20/04/22

GENERAL SAFETY
IMPORTANT SAFETY NOTE
Only a qualified refrigeration mechanic who is familiar with refrigeration systems and components, including all controls should perform the installation and start-up of the system. To avoid potential injury, use care when working around coil surfaces (if applicable) or sharp edges of metal cabinets. All piping and electrical wiring should be installed in accordance with all applicable codes, ordinances and local by-laws.
WARNING
Always disconnect and lock off the main power supply on any system that will be worked on to avoid accidental start up of the equipment.

INSPECTION

Inspect all equipment before unpacking for visible signs of damage or loss. Check shipping list against material received to ensure shipment is complete.

Should carton be damaged, but damage to equipment is
not obvious, a claim should be filed for “concealed damage” with the carrier.

IMPORTANT: Remember, you, the consignee, must make any claim necessary against the transportation company. Shipping damage or missing parts, when discovered at the outset, will prevent later unnecessary and costly delays. If damage or loss during transport is evident, make claim to carrier, as this will be their responsibility, not that of the manufacturer.

IMPORTANT: Check the electrical ratings on the unit to make sure they correspond to those ordered and to electrical power available at the job site. Save all shipping papers, tags, and instruction sheets for reference by
installer and owner.

B50-BCU-IM-20

– 2 –

20/04/22

HANDLING, PLACEMENT AND INSTALLATION

IMPORTANT: When selecting a location for the condensing unit, consideration should be given to some of the following: (a) Loading capacity of the floor or roof. Check building
codes for weight distribution requirements. (b) Distance to suitable electrical supply. (c) Distance to the evaporator. (d) Adequate air circulation and ventilation. (e) Close proximity to water source and floor drains
(water-cooled units) (f) Accessibility for maintenance. (g) Local building codes. (h) Adjacent buildings relative to noise levels. (i) Wishes of the end user / owner.
When all of the above points have been considered and a specific location chosen, it is advisable to obtain written approval of this location from the building and/or condensing unit owner. This may be a means of avoiding disagreement and expense at a later date.
A fully qualified and properly equipped crew with the necessary tackle and rigging should be engaged to locate the condensing unit in position. When lifting the unit, spreader bars and chafing gear should be used to prevent damage.

be transmitted through the floor structure, vibration isolators should be installed. Isolators should be installed under mounting base and may be rubber or cork or equal.
DO NOT USE THE SHIPPING SKID AS A PERMANENT BASE.
The condensing unit should be positioned to allow adequate space for performing service work.
Indoor and outdoor air-cooled condensing units should be positioned using the guidelines shown below.
Units equipped with spring-mounted compressors have shipping spacers that are designed to hold the compressor rigidly during transit to prevent possible damage. Before operating the unit, it is necessary to remove these spacers. To remove the shipping spacers, follow these steps:
(a) Remove the upper nuts / washers. (b) Discard the shipping spacers. (c) Install the rubber cone washers (located in the
electrical box). (d) Replace the upper mounting nuts / washers. (e) Allow 1/16 inch space between the mounting nuts /
washers and the compressor foot.

The unit should be placed on a base, which is level and
even. Units should be lagged to sleepers or support base.
Place unit where it will not be subject to damage by traffic or flooding. On critical installations where noise is liable to

On units equipped with rigid mounted compressors, check the compressor mounting bolts to insure they have not
vibrated loose during shipping.

B50-BCU-IM-20

– 3 –

20/04/22

LOCATION: Horizontal Air Flow Condensers and Condensing Units

Width of Condensing Unit
Minimum
If placed back to back the minimum spacing is 2 times the tallest Condenser height.
2x Height of Tallest Condenser
Minimum

B50-BCU-IM-20

– 4 –

20/04/22

LOCATION: Vertical Air Flow Condensing Units

B50-BCU-IM-20

– 5 –

20/04/22

LOCATION: Vertical Air Flow Condensing Units (cont’d)

B50-BCU-IM-20

– 6 –

20/04/22

LIFTING INSTRUCTIONS

B50-BCU-IM-20

– 7 –

20/04/22

ELECTRICAL INFORMATION
NOTE: All installers should follow the wiring diagram attached to the equipment electrical compartment cover.

WARNING
All wiring and connections to the unit must be made in accordance with national as well as local electrical codes and by-laws.

Electrical wiring should be sized in accordance with the minimum circuit ampacity (MCA) shown on the unit nameplate and applicable electrical codes. The unit power connections are approved for copper wire only.
Connect the field power supply through a properly sized branch circuit protection disconnect switch. The entering service fuse must not exceed the maximum overcurrent protection (MOP) value on the unit data plate.

All systems should use a liquid line solenoid valve (installed at the evaporator) and should be energized by the room or fixture thermostat. For systems with a defrost time clock, the liquid line solenoid and thermostat should be energized by the time clock. Initially set the defrost time clock (model 8145) as follows:
Air defrost evaporators; 3 per day (every 8 hours) with the time termination at 45 minutes.

Field connected control circuit wires are terminated directly at the control circuit terminal block in accordance with the appropriate wiring diagram.

Voltage at the unit terminals must not vary more than the allowable variation during start-up and while under full load. If the voltage is normal at the supply with the compressor not running and drops considerably when the switch is closed and the motor is trying to start, there is a high resistance due to undersized wires or faulty connections. Voltage drop between inoperative and full load must not exceed 3% of line voltage. In addition, the phase imbalance at the motor terminals should be within 2% on three phase units.

60 Hz Supply

Power

Allowable Variation

115-1-60

103-127 V

208/230-1-60

197-254 V

208/230-3-60

187-254 V

460-3-60

414-506 V

575-3-60

518-632 V

Electric defrost evaporators; 4 per day (every 6 hours) with time termination set (Fail Safe) at 30 minutes. Check that the wiring from the defrost termination thermostat is wired to terminal “X” on the clock and terminates the defrost cycle when the evaporator coil reaches approximately 55 °F. The fan delay thermostat wiring should also be checked for proper operation. This ensures that all water droplets have been refrozen to the coil before the evaporator fan starts back up.
Note: The above settings are guidelines only and must be re-adjusted to suit local field conditions and actual evaporator equipment specifications.
Refer to the evaporator installation manual for further information.
Refer to the following wiring diagrams for typical air defrost and electric defrost wiring arrangements.

50 Hz Supply

Power

Allowable Variation

100-1-50

90-110 V

200/220-1-50

190-242 V

200/220-3-50

180-242 V

380/400-3-50

342-440 V

WARNING

Any deviation or change to the electrical components or wiring as supplied on the original equipment, or noncompliance with the voltage and phase balance requirements without written authorization will void the warranty.

B50-BCU-IM-20

– 8 –

20/04/22

ELECTRICAL INFORMATION (cont’d) Wiring Diagram Cross Reference

Condensing Unit Voltage
208-230/1/60 208-230/3/60 208-230/3/60 208-230/3/60
460/3/60 460/3/60
208-230/1/60

Evaporator Voltage and Type Condensing Unit Type

COPELAND SCROLL

230 Air Defrost Low Profile

Small Scroll

230 Electric Defrost Low Profile

Small Scroll

2x 230 Electric Defrost Low Profile

Small Scroll+ Coresense

2x 230 Electric Defrost Med Profile

Large Scroll+ Coresense

460 Electric Defrost Med Profile

Small Scroll+ Coresense

2x 460 Electric Defrost Med Profile

Large Scroll+ Coresense

COPELAND HERMETIC

230 Air Defrost Low Profile

208-230/3/60

230 Electric Defrost Low Profile

460/3/60 & 575/3/60
208-230/1/60 208-230/3/60 208-230/3/60 460/3/60 & 575/3/60 460/3/60 & 575/3/60

2x 230 Electric Defrost Low Profile
230 Air Defrost Low Profile 230 Electric Defrost Low Profile 2x 230 Electric Defrost Low Profile 460 Electric Defrost Med Profile 2x 460 Electric Defrost Med Profile

SEMI-HERMETIC Copelametic Bitzer Discus Discus
Discus Demand Cooling

Diagram Number
S2A1D T3A1A T3A1D T3C6A T4A6A T4C6A
S2A1A T3A1A T4A1A
S2A1A T3B1A T3L1A T4L1A T4A4A

Page
A2 A3 A5 A6 A9 A10
A1 A3 A8
A1 A4 A7 A12 A11

Diagram Number
KA101 LPE101 LPE201 JE101A JE101A JE201A
KA101 LPE101 JE101A
KA101 LPE101 LPE201 JE101A JE201A

Page
A13 A14 A15 A16 A16 A17
A13 A14 A16
A13 A14 A15 A16 A17

for wiring diagrams, see:
Appendix A: Wiring Diagrams

B50-BCU-IM-20

– 9 –

20/04/22

REFRIGERANT PIPING
WARNING
All local codes must be observed in the installation of refrigerant piping.

IMPORTANT PIPING NOTE
Appropriate line sizing practices must be used throughout the installation of the refrigeration system. Special consideration must be taken when the condensing unit is installed above the evaporator. REFRIGERATION GRADE COPPER TUBING MUST BE USED FOR PIPING SYSTEMS.

Piping practice and line sizing charts as recommended by A.S.H.R.A.E. or other reputable refrigeration standards must be followed to ensure minimum pressure drop and correct oil return. An inert gas such as dry nitrogen should be passed through the piping during welding or brazing operations. This reduces or eliminates oxidation of the copper and formation of scale inside the piping. For specific piping requirements refer to your local distributor or sales representative.
Correct line sizing is most critical because of the several factors involved:
(a) Minimum pressure drop to ensure efficient compressor performance.
(b) Sufficient gas velocity to maintain proper oil return to the compressor under all load conditions.
(c) Elimination of conditions on multiple evaporators whereby oil may log in an idle evaporator.

Suction lines should be sized on the basis of a maximum total pressure drop equivalent to a 2°F (1.1°C) change in saturated temperature.
Horizontal liquid lines should be sized on a basis of a maximum pressure drop equivalent to a 2°F (1.1°C) drop in the sub-cooling temperature. If the lines must travel up vertically then adequate sub-cooling must be provided to overcome the vertical liquid head pressures. A head of two feet of liquid refrigerant is approximately equivalent to 1 psig (6.9 kPa). Liquid line velocities should not exceed 300 fpm (1.52 m/s). This will prevent possible liquid hammering when the solenoid valve closes.

Pressure Loss of Liquid Refrigerant in Liquid Line Risers (Expressed in Pressure Drop PSIG and Subcooling Loss °F)

Refrigerant

10′ PSIG °F

Liquid Line Rise in Feet

15′

20′

25′

PSIG °F PSIG °F PSIG °F

30′ PSIG °F

R134a

4.9

2.0

7.4

2.9

9.8

4.1 12.3 5.2 14.7 6.3

R22

4.8

1.6

7.3

2.3

9.7

3.1 12.1 3.8 14.5 4.7

R404A R507

4.1

1.1

6.1

1.6

8.2

2.1 10.2 2.7 12.2 3.3

R407A R407C R448A

4.3

1.4

6.5

2.1

8.7

2.8 10.8 3.5 12.8 4.1

B50-BCU-IM-20

– 10 –

20/04/22

REFRIGERANT PIPING (cont’d)

At the temperatures encountered in the condenser, receiver and liquid line a certain amount of oil is always being circulated with the refrigerant through the system by the compressor. However, at the evaporator temperature, and with the refrigerant in a vapor state, the oil and refrigerant separate. This oil can only be returned to the compressor by gravity or by entrainment in the suction gas. Roof installations leave no alternative but by entrainment for oil return, so suction gas velocity and correct line sizing to maintain this velocity are imperative. Care must be taken

not to oversize the suction line in the desire for maximum performance.
Gas velocity in vertical suction lines must not be less than 1,000 fpm (5 m/s) and preferably 1,250 to 1,500 fpm (6 to 8 m/s). Important: A suction trap must be installed at the base of all suction risers of four (4) feet or more in order to trap oil and allow entrainment in the suction gas.

TYPICAL SUCTION P-TRAP

IMPORTANT PIPING NOTE
If steps of capacity control are supplied on a compressor, provisions must be made for oil return by sizing suction risers to maintain adequate gas velocities at reduced refrigerant flow.

During the lower capacity running mode (compressor capacity control energized) oil will collect in the elbow or at U-bend below pipe “B”. This will divert the gas and oil to flow up the smaller pipe “A” at a higher velocity.

IMPORTANT: When welding service valves or any components that may be damaged by heat, manufacturer’s installation instructions must be adhered to. Wrapping components with a wet cloth will help to prevent damage from heat.

IMPORTANT: All suction lines outside of the refrigerated space must be insulated.

B50-BCU-IM-20

– 11 –

20/04/22

PIPING

B50-BCU-IM-20

– 12 –

20/04/22

LINE INSULATION

After the final system leak test is complete, it is important that all refrigerant lines exposed to high ambient conditions
must be insulated to reduce the heat pick-up and prevent
the formation of flash gas in the liquid lines. Suction lines should be insulated with 3/4 inch wall insulation,
Armstrong “Armaflex” or equal. To prevent rupture due to condensate re- freezing, all suction vibration eliminators

on low temperature systems MUST BE COMPLETELY INSULATED. Liquid lines exposed to high ambient temperatures should be insulated with 1/2 inch wall insulation or better. Any insulation that is to be located in an outdoor environment should be protected from UV exposure to prevent deterioration of the insulating value.

REFRIGERANT CHARGING

Condensing units must be charged only with the refrigerant for which they were designed. The type of refrigerant to be used is specified on the name plate of the unit. Installing a liquid line drier between the service gauge and the liquid service port when charging a unit will ensure the refrigerant supplied to the system is clean and dry. This is especially important when charging a low

temperature system. Blend type refrigerants (400 series, i.e. R404A) must not be vapor charged unless the cylinder is completely emptied into the system.
Weigh the refrigerant drum before and after charging in order to keep an accurate record of the weight of refrigerant put into the system.

IMPORTANT REFRIGERANT CHARGING NOTE
Overcharging a system can result in poor system performance, personal injury and / or compressor damage. DO NOT charge strictly by the holding capacity of the receiver. DO NOT assume that bubbles in a sight glass, when located at the condensing unit, indicates the system is undercharged.

Note: To estimate the total system requirement, refer to the manufacturer’s evaporator and condensing unit specifications on typical operating charges and include the amount for the liquid lines (see tables below). Allow an extra 10% to 15% safety factor. Ensure the receiver can handle the required charge during the pump down mode. (Refer to the condensing unit brochure pump down specifications).
Break the vacuum by charging liquid refrigerant into the receiver side only (charge through the receiver outlet valve gauge port with the valve in the open position). Close the valve and then continue to charge through the gauge port feeding the liquid line and evaporator. Start the compressor and continue to charge.

Refrigerant may be added at the compressor through the compressor suction service valve in gas form only. When liquid charging is used, a liquid charging valve must be installed. While charging the system, special attention should be paid to the oil level in the compressor.
If charging to the “bubble” method (observing liquid line sight glass), always use a sight glass located directly before the TXV (thermostatic expansion valve) for the final indicator.
(see next page for details on Valve Systems)

B50-BCU-IM-20

– 13 –

20/04/22

REFRIGERANT CHARGING – VALVE SYSTEMS

DUAL OR ADJUSTABLE LAC VALVE SYSTEMS:
The system employs an adjustable LAC or ORI/ORD valves to regulate system high pressure during low ambient conditions.
The design compressor discharge pressure setting for the valve is 150 psig for medium temperature systems and low temperature systems with hermetic compressors; and 120 psig for other low temperature systems.

All systems are factory set at the above settings; however, the actual compressor discharge pressure at low ambient conditions may differ from the factory settings. If so, the setting needs to be adjusted. Caution: setting the valve higher than the design setting is not permitted.
Exception: If the system is not used for a walk-in, or a walk-in larger than 3000 ft2, or for medical, scientific or research purpose, the above setting requirement does not apply.

Figure 7A: Dual Valve Piping Arrangement

Condenser ORI

ORD-4-20/30 Compressor

Receiver

Figure 7B: Single Valve Piping Arrangement

Condenser

LAC (Adjustable)

Compressor

Receiver

Adjustment:
When an adjustment is needed, a pressure gauge should be connected to the compressor discharge port. Turning the valve stem “clockwise” will increase the pressure setting, while turning the valve stem “counterclockwise” will decrease the pressure setting.

Checking and adjusting the valve setting may only be done properly when the ambient temperature reaches 35F or below
Refer to Sporlan’s installation instructions (bulletins 90-301 and 90-31) for further details.

WARNING
Fans closest to the headers should not be cycled on standard temperature or pressure controls. Dramatic temperature and pressure changes at the headers as a result of fan action can result in possible tube failure.
Fan cycling controls should be adjusted to maintain a minimum of 5 minutes on and 5 minutes off. Short cycling of fans may result in premature failure of motor and/or fan blade.
Compressors operating below +10°F SST must have air flowing over the compressor at all times when the compressor is running.

B50-BCU-IM-20

– 14 –

20/04/22

REFRIGERANT CHARGING (cont’d)

BEH-LINE HERMETIC AIR-COOLED CONDENSING UNIT (WITH HORIZONTAL AIRFLOW CONDENSERS)

Refrigerant Operating Charges (Lbs) (Less Evaporator And Liquid Lines)

UNIT MODEL BEHA006L6 BEHA008L6 B EHA010L6 B EHA015L6 BEHA020L6

BEHA025L6 B EHA030L6

R404A R448A

2.0

2.09

2.8

2.92

5.8

6.1

UNIT MODEL
BEHA006M8 B EHA008M8 B EHA009M8
BEHA010M8 B EHA011M8
BEHA013M8 B EHA015M6 B EHA020M6 B EHA015H7 B
EHA020H7
BEHA025M6 BEHA029M6 BEHA025H7 B EHA029H7
BEHA030M6 BEHA035M6 BEHA030H7 BEHA035H7 B EHA040H7 BEHA050H7

(M6/M8)
R404A
2.0 2.8 4.2
6.0
8.6 –

(M6/M8)
R448A
2.09 2.92 4.3
6.3
8.9 –

(H7)
R407C
2.2 3.0 4.5
6.5
9.3 12

(H7)
R22
2.3 3.2 4.7
6.8
9.7 12

BEZ-LINE SCROLL AIR-COOLED CONDENSING UNIT (WITH HORIZONTAL AIRFLOW CONDENSERS)

Refrigerant Operating Charges (Lbs) (Less Evaporator And Liquid Lines)

UNIT MODEL
BEZA008L8 BEZA010L8
BEZA015L8

BEZA020L8 BEZA025L8 BEZA030L8 BEZA035L8
BEZA045L8
BEZA055L8 BEZA060L8 BEZA075L8 BEZA085L8 BEZA100L8 BEZA130L8 BEZA150L8

R404A R407A R448A

2.0

2.2

2.1

2.8

3.1

2.9

3.9

4.3

4.1

6.0

6.6

6.3

8.6

9.4

8.9

11

12

12

18

20

19

23

25

24

UNIT MODEL
BEZA007H8
BEZA008H8 BEZA009H8 BEZA010H8 BEZA011H8 BEZA015H8 BEZA020H8

BEZA025H8
BEZA030H8 BEZA035H8 BEZA040H8 BEZA045H8 BEZA050H8 BEZA060H8 BEZA061H8 BEZA070H8 BEZA076H8 BEZA085H8 BEZA110H8 BEZA150H8

R404A R407A R448A

2.0

2.2

2.1

2.8

3.1

2.9

R407C
2.2 3.0

4.2

4.5

4.3

4.5

6.0

6.6

6.3

6.5

8.6

9.4

8.9

9.3

11

12

12

12

18

20

19

19

23

25

24

25

39

42

40

41

R22
2.3 3.2
4.7 –
6.8
9.7 13 20 25 43

B50-BCU-IM-20

– 15 –

20/04/22

REFRIGERANT CHARGING (cont’d)

BES-LINE SEMI-HERMETIC AIR-COOLED CONDENSING UNIT (WITH HORIZONTAL AIRFLOW CONDENSERS)

Refrigerant Operating Charges (Lbs) (Less Evaporator And Liquid Lines) – COPELAND

UNIT MODEL
BESA005L8 BESA008L8 B ESA010L8 BESA015L8 BESA020L8 B ESA021L8
BESA030L8 B
ESA032L8 BESA035L6/L8 BESA040L6/L8 BESA060L6/L8 BESA061L6/L8 BESA075L6/L8
BESA090L6/L8 BESA100L6/L8
BESA120L6/L8 BESA130L6/L8 BESA150L6/L8 BESA220L6/L8

(L6)
R404A

(L8)

(L6/L8)

R407A R448A

2.6

3.0

4.5

5.1

8.6

8.8

8.6

9.1

8.8

9.6

10.7

10.2

18

20

19

23

25

24

39

42

40

UNIT MODEL
BESA010M8

BESA020M8
BESA021M8
BESA030M8
BESA050H8 BESA051H8 B ESA075H8 BESA077H8 BESA080H8 B ESA100H8
BESA120H8 ESA150H8 BESA200H8

R404A R407A R448A

2.8

3.1

2.9

R407C
3.0 –

4.5

4.7

5.8

6.1

8.6

8.8

18

20

19

19

23

25

24

25

39

42

40

41

R22
3.2 –
20
25
43

Refrigerant Operating Charges (Lbs) (Less Evaporator And Liquid Lines) – BITZER

UNIT MODEL
BESB010L6/L8 BESB015L6/L8 BESB020L6/L8 BESB025L6/L8 BESB030L6/L8 BESB031L6/L8
BESB039L6/L8
BESB050L6/L8 BESB060L6/L8 BESB080L6/L8 BESB100L6/L8 BESB120L6/L8

(L6)
R404A
3.0 4.4 6.0 8.6

(L8)

(L6/L8)

R407A R448A

3.2

3.1

4.9

4.6

6.6

6.3

9.4

8.9

11

12

12

18

20

19

23

25

24

UNIT MODEL
BESB010H8 BESB015H8 BESB020H8 BESB025H8 BESB029H8 BESB030H8 BESB035H8 BESB040H8 BESB050H8 BESB060H8 BESB076H8 BESB090H8 BESB100H8 BESB121H8 BESB150H8 BESB200H8

R404A
3.5 4.4 6.0 8.6

R407A
3.8 4.9 6.6 9.4

R448A
3.6 4.6 6.3 8.9

11

12

12

18

20

19

R407C
3.8 4.8 6.5 9.3
12
19

23

25

24

25

39

42

40

41

R22
3.9 5.0 6.8 9.7 13 20
25
43

B50-BCU-IM-20

– 16 –

20/04/22

REFRIGERANT CHARGING (cont’d)
BQH-LINE QUIET HERMETIC AIR-COOLED CONDENSING UNIT (WITH HORIZONTAL AIRFLOW CONDENSERS)

Refrigerant Operating Charges (Lbs) (Less Evaporator And Liquid Lines)

UNIT MODEL
BQZA008L8 BQZA010L8 BQZA015L8 BQZA020L8
BQZA025L8 BQZA030L8 BQZA035L8
BQZA045L8 BQZA055L8 BQZA060L8

R404A R407A R448A

3.5

4.2

3.7

3.8

4.2

4.0

4.6

5.0

4.8

5.8

6.4

6.1

7.4

8.1

7.7

UNIT MODEL
BQZA007H8 BQZA008H8 BQZA009H8 BQZA010H8 BQZA011H8
BQZA015H8 BQZA020H8
BQZA025H8
BQZA030H8
BQZA035H8
BQZA040H8 BQZA050H8
BQZA060H8

R404A R407A R448A

3.5

4.2

3.7

3.8

4.2

4.0

5.8

5.0

4.8

5.4

5.9

5.6

5.8

6.4

6.1

7.4

8.1

7.7

9.6

11

10

R407C
4.4
4.1 5.0 5.87 6.4 8.0 10

BQZ-LINE QUIET SCROLL AIR-COOLED CONDENSING UNIT (WITH HORIZONTAL AIRFLOW CONDENSERS)

Refrigerant Operating Charges (Lbs) (Less Evaporator And Liquid Lines)

UNIT MODEL R404A R448A

UNIT MODEL

(E6/M8) (E6/M8)
R404A R448A

(H7)
R407C

(H7)
R22

BQHA006M8

BQHA010L6 BQHA020L6

2.7

2.8

BQHA008M8 BQHA009M8

2.7

2.8

BQHA010M8

BQHA011M8

BQHA013M8

3.5

3.7

3.8

4.0

BQHA015H7

BQHA015E6

BQHA025L6 BQHA030L6

3.9

4.1

BQHA020E6 BQHA025E6 BQHA030E6

3.9

4.1

4.2

4.4

BQHA020H7

BQHA035E6 BQHA035H7

4.5

4.7

5.0

5.1

BQHA025H7 BQHA030H7

6.0

6.2

BQHA040H7 BQHA050H7

7.6

7.9

B50-BCU-IM-20

– 17 –

20/04/22

REFRIGERANT CHARGING (cont’d)

MEDIUM AIR-COOLED CONDENSING UNIT (WITH VERTICAL AIRFLOW CONDENSERS)

Refrigerant Operating Charges (Lbs) (Less Evaporator And Liquid Lines)

Single Compressor UNIT MODEL

RECEIVER

TOTAL UNIT CHARGE R404A (lb)

Copeland

Bitzer

90% Full (lb)

Summer (+10%
receiver)

Winter (+10% receiver)

BMS075L 6/8-A BMS080L 6/8-B 70

BMS090L 6/8-A BMS100L 6/8-B 70

BMS100L 6/8-A BMS120L 6/8-B 82

BMS120L 6/8-A

103

BMS130L 6/8-A BMS130L 6/8-B 103

BMS150L 6/8-A BMS150L 6/8-B 124

BMS220L 6/8-A BMS200L 6/8-B 124

BMS075M8-A BMS060M8-B

70

BMS076M8-A BMS075M8-B

70

BMS080M8-A BMS090M8-B

82

BMS100M8-A BMS100M8-B

103

BMS120M8-A BMS120M8-B

124

BMS150M8-A BMS150M8-B

124

BMS200M8-B

124

BMS075H8-A BMS060H8-B

70

BMS076H8-A BMS075H8-B

70

BMS080H8-A BMS090H8-B

82

BMS100H8-A BMS100H8-B

103

BMS120H8-A BMS120H8-B

124

BMS150H8-A BMS150H8-B

124

BMS200H8-B

124

BMS060L8-Z

50

BMS075L8-Z

50

BMS085L8-Z

50

BMS100L8-Z

50

BMS130L8-Z

60

BMS150L8-Z

70

BMS170L8-Z

82

BMS050M8-Z

50

BMS060M8-Z

50

BMS061M8-Z

60

BMS070M8-Z

60

BMS076M8-Z

70

BMS085M8-Z

82

BMS110M8-Z

103

BMS150M8-Z

103

BMS050H8-Z

50

BMS060H8-Z

50

BMS061H8-Z

60

BMS070H8-Z

60

BMS076H8-Z

70

BMS085H8-Z

82

BMS110H8-Z

103

BMS150H8-Z

103

19.3

37.3

19.3

37.3

20.5

36.8

28.2

54.0

28.2

54.0

30.3

56.1

35.3

69.4

19.3

37.3

19.3

37.3

20.5

36.8

28.2

54.0

33.0

66.5

33.0

66.5

36.7

71.0

18.4

35.6

18.4

35.6

19.9

35.7

25.1

49.4

29.9

61.7

29.9

61.7

33.6

66.3

16.4

34.1

16.4

34.1

17.0

34.9

17.0

34.9

21.4

46.4

22.4

47.4

27.5

60.7

14.9

28.6

15.6

29.4

17.5

31.6

18.3

34.6

21.8

38.9

23.0

40.1

30.9

64.4

30.9

64.4

14.0

27.1

14.0

27.1

16.0

29.3

17.7

33.5

18.7

34.5

19.9

35.7

27.8

59.6

31.5

64.2

Single Compressor UNIT MODEL

RECEIVER

TOTAL UNIT CHARGE R404A (lb)

Copeland

Bitzer

90% Full (lb)

Summer (+10%
receiver)

Winter (+10% receiver)

BMD150L 6/8-A BMD160L 6/8-B 70(2)

38.6

74.5

BMD180L 6/8-A BMD200L 6/8-B 70(2)

38.6

74.5

BMD200L 6/8-A BMD240L 6/8-B 82(2)

41.0

73.6

BMD240L 6/8-A

103(2)

56.4

107.9

BMD260L 6/8-A BMD260L 6/8-B 103(2)

56.4

107.9

BMD300L 6/8-A BMD300L 6/8-B 124(2)

60.6

112.1

BMD440L 6/8-A BMD400L 6/8-B 124(2)

70.6

138.7

BMD150M8-A BMD120M8-B 70(2)

38.6

74.5

BMD151M8-A BMD150M8-B 70(2)

38.6

74.5

BMD160M8-A BMD180M8-B 82(2)

41.0

73.6

BMD200M8-A BMD200M8-B 103(2)

56.4

107.9

BMD240M8-A BMD240M8-B 124(2)

65.9

132.9

BMD300M8-A BMD300M8-B 124(2)

65.9

132.9

BMD400M8-B 124(2)

73.3

142.0

BMS075H8-A BMD120H8-B 70(2)

36.8

71.2

BMS076H8-A BMD150H8-B 70(2)

36.8

71.2

BMS080H8-A BMD180H8-B 82(2)

39.8

71.4

BMS100H8-A BMD200H8-B 103(2)

50.2

98.8

BMS120H8-A BMD240H8-B 124(2)

59.8

123.3

BMS150H8-A BMD300H8-B 124(2)

59.8

123.3

BMD400H8-B 124(2)

67.2

132.6

BMD120L8-Z

50(2)

32.7

68.2

BMD150L8-Z

50(2)

32.7

68.2

BMD170L8-Z

50(2)

33.9

69.8

BMD200L8-Z

50(2)

33.9

69.8

BMD260L8-Z

60(2)

42.8

92.7

BMD300L8-Z

70(2)

44.8

94.7

BMD340L8-Z

82(2)

55.1

121.4

BMD100M8-Z

50(2)

29.9

57.3

BMD120M8-Z

50(2)

31.1

58.8

BMD121M8-Z

60(2)

35.0

63.1

BMD140M8-Z

60(2)

36.6

69.2

BMD151M8-Z

70(2)

43.6

77.7

BMD170M8-Z

82(2)

46.0

80.1

BMD220M8-Z

103(2)

61.7

128.7

BMD300M8-Z

103(2)

61.7

128.7

BMD100H8-Z

50(2)

28.0

54.1

BMD120H8-Z

50(2)

28.0

54.1

BMD121H8-Z

60(2)

32.0

58.5

BMD140H8-Z

60(2)

35.4

67.0

BMD151H8-Z

70(2)

37.4

69.0

BMD170H8-Z

82(2)

39.8

71.4

BMD220H8-Z

103(2)

55.6

119.1

BMD300H8-Z

103(2)

63.0

128.4

NOTE ON ALTERNATE REFRIGERANTS: PUBLISHED RECEIVER CAPACITY IS BASED ON R404A ON MODELS USING “8” AS REFRIGERANT CODE. FOR ALTERNATE
REFRIGERANTS, MULTIPLY R404A VALUE BY THE APPROPRIATE VALUE BELOW:

R407A
1.10

R407C R448A R507

1.10

1.05 1.00

– For R449A, use R448A data.

R22 1.15

B50-BCU-IM-20

– 18 –

20/04/22

REFRIGERANT CHARGING (cont’d)
LARGE AIR-COOLED CONDENSING UNIT (WITH VERTICAL AIRFLOW CONDENSERS)

Refrigerant Operating Charges (Lbs) (Less Evaporator And Liquid Lines)

Single Compressor UNIT MODEL

RECEIVER

TOTAL UNIT CHARGE R404A (lb)

Copeland

Bitzer

90% Full (lb)

Summer (+10%
receiver)

Winter (+10% receiver)

BVS010L 6/8-A BVS012L 6/8-B

70

BVS015L 6/8-A BVS015L 6/8-B

82

BVS022L 6/8-A BVS020L 6/8-B 103

BVS027L 6/8-A BVS025L 6/8-B 124

BVS030L 6/8-A BVS030L 6/8-B 124

BVS040L 6/8-A BVS040L 6/8-B 157

BVS015M8-A BVS015M8-B

103

BVS020M8-A BVS020M8-B

103

BVS022M8-A

103

BVS025M8-A BVS025M8-B

124

BVS030M8-A BVS030M8-B

157

BVS035M8-A BVS035M8-B

189

BVS040M8-A BVS040M8-B

189

BVS050M8-A BVS050M8-B

254

BVS015H8-A BVS015H8-B

103

BVS022H8-A BVS020H8-B

103

BVS025H8-A BVS025H8-B

124

BVS030H8-A BVS030H8-B

157

BVS035H8-A BVS035H8-B

189

BVS040H8-A BVS040H8-B

189

BVS011L 6/8-A BVS013L 6/8-B

82

BVS016L 6/8-A BVS016L 6/8-B 103

BVS023L 6/8-A BVS021L 6/8-B 124

BVS028L 6/8-A BVS026L 6/8-B 157

BVS031L 6/8-A BVS031L 6/8-B 157

BVS041L 6/8-A BVS041L 6/8-B 189

BVS016M8-A BVS016M8-B

124

BVS021M8-A BVS021M8-B

124

BVS023M8-A

124

BVS026M8-A BVS026M8-B

157

BVS031M8-A BVS031M8-B

189

BVS036M8-A BVS036M8-B

254

BVS041M8-A BVS041M8-B

254

BVS051M8-A BVS051M8-B

254

BVS016H8-A BVS016H8-B

124

BVS021H8-A BVS021H8-B

124

BVS026H8-A BVS026H8-B

157

BVS031H8-A BVS031H8-B

189

BVS036H8-A BVS036H8-B

254

BVS041H8-A BVS041H8-B

254

BVS051H8-A BVS051H8-B

254

BVS008V6-B

70

BVS012V6-B

82

BVS016V6-B

82

BVS020V6-B

124

BVS025V6-B

124

BVS030V6-B

124

19.0 23.8 27.9 37.7 37.7 46.1 25.5 32.9 35.6 37.7 43.8 50.9 58.1 64.6 23.6 32.3 34.4 40.5 47.6 56.5
21.9 29.1 33.6 43.8 43.8 51.3 31.2 37.8 40.5 45.8
53.9
78.7 93.0 93.0 31.7 37.2 42.6 50.7 77.8 91.5 91.5 19.0 23.8 23.8 33.6 33.6 36.4

34.6 44.8 47.9 68.6 68.6 85.1 45.0 63.0 66.5 68.6 82.3 95.1 116.3 122.8 42.1 61.5 63.6 77.2 89.9 112.8
42.2 58.4 63.4 82.3 82.3 95.8 60.5 75.4 79.0 89.8
111.4
181.2 228.9 228.9 60.2 73.9 84.5 105.6 177.5 223.6 223.6 34.2 44.0 44.0 62.5 62.5 72.8

Double Compressor UNIT MODEL

RECEIVER

TOTAL UNIT CHARGE R404A (lb)

Copeland

Bitzer

90% Full (lb)

Summer (+10%
receiver)

Winter (+10% receiver)

BVD020L 6/8-A BVD024L 6/8-B BVD030L 6/8-A BVD030L 6/8-B BVD044L 6/8-A BVD040L 6/8-B BVD054L 6/8-A BVD050L 6/8-B BVD060L 6/8-A BVD060L 6/8-B BVD080L 6/8-A BVD080L 6/8-B BVD030M8-A BVD030M8-B BVD040M8-A BVD040M8-B BVD044M8-A BVD050M8-A BVD050M8-B BVD060M8-A BVD060M8-B BVD070M8-A BVD070M8-B BVD080M8-A BVD080M8-B BVD100M8-A BVD100M8-B BVD030H8-A BVD030H8-B BVD044H8-A BVD040H8-B BVD050H8-A BVD050H8-B BVD060H8-A BVD060H8-B BVD070H8-A BVD070H8-B BVD080H8-A BVD080H8-B
BVD021L 6/8-A BVD025L 6/8-B BVD031L 6/8-A BVD031L 6/8-B BVD045L 6/8-A BVD041L 6/8-B BVD055L 6/8-A BVD051L 6/8-B BVD061L 6/8-A BVD061L 6/8-B BVD081L 6/8-A BVD081L 6/8-B BVD031M8-A BVD031M8-B BVD041M8-A BVD041M8-B BVD045M8-A BVD051M8-A BVD051M8-B
BVD061M8-A BVD061M8-B
BVD071M8-A BVD071M8-B BVD081M8-A BVD081M8-B BVD101M8-A BVD101M8-B BVD031H8-A BVD031H8-B BVD041H8-A BVD041H8-B BVD051H8-A BVD051H8-B BVD061H8-A BVD061H8-B BVD071H8-A BVD071H8-B BVD081H8-A BVD081H8-B BVD101H8-A BVD101H8-B
BVD016V 6/8-B BVD024V 6/8-B BVD032V 6/8-B BVD040V 6/8-B BVD050V 6/8-B BVD060V 6/8-B

70(2) 82(2) 103(2) 124(2) 124(2) 157(2) 103(2) 103(2) 103(2) 124(2) 157(2) 189(2) 189(2) 254(2) 103(2) 103(2) 124(2) 157(2) 189(2) 189(2)
82(2) 103(2) 124(2) 157(2) 157(2) 189(2) 124(2) 124(2) 124(2) 157(2)
189(2)
254(2) 254(2) 254(2) 124(2) 124(2) 157(2) 189(2) 254(2) 254(2) 254(2) 70(2) 82(2) 82(2) 124(2) 124(2) 124(2)

38.1 47.7 55.7 75.4 75.4 92.2 51.0 65.8 71.2 75.4 87.6 101.8 116.2 129.2 47.2 64.7 68.9 81.1 95.3 113.1
43.9 58.2 67.1 87.6 87.6 102.7 62.4 75.6 81.0 91.7
107.9
157.4 186.1 186.1 63.3 74.5 85.2 101.4 155.5 183.0 183.0 38.1 47.7 47.7 67.1 67.1 72.7

69.3 89.5 95.8 137.2 137.2 170.2 89.9 125.9 133.0 137.2 164.6 190.3 232.6 245.6 84.2 122.9 127.1 154.4 179.9 225.6
84.5 116.7 126.8 164.6 164.6 191.6 120.9 150.9 158.0 179.6
222.7
362.3 457.8 457.8 120.3 147.8 169.0 211.3 355.0 447.2 447.2 68.5 88.0 88.0 125.0 125.0 145.7

NOTE ON ALTERNATE REFRIGERANTS: PUBLISHED RECEIVER CAPACITY IS BASED ON R404A ON MODELS USING “8” AS REFRIGERANT CODE. FOR ALTERNATE REFRIGERANTS, MULTIPLY R404A VALUE
BY THE APPROPRIATE VALUE AT RIGHT:

R407A
1.10

R407C R448A R507

1.10

1.05 1.00

– For R449A, use R448A data.

R22 1.15

B50-BCU-IM-20

– 19 –

20/04/22

WEIGHT OF REFRIGERANT

Weight of Refrigerant in Copper Tubing (Lbs)

Pipe O.D. Cubic ft.

in

per

inches 100 ft.

3/8 1/2 5/8 7/8 1- 1/8 1- 3/8 1- 5/8 2- 1/8 2- 5/8 3- 1/8 3- 5/8 4- 1/8 5-1/8 6-1/8

0.054 0.101 0.162 0.336 0.573 0.873 1.235 2.149 3.314 4.731 6.398 8.317 12.98 18.63

R404A

L

V

65.51 3.94

3.5

0.2

6.6

0.4

10.6

0.6

22.0

1.3

37.5

2.3

57.2

3.4

80.9

4.9

140.8

8.5

217.1 13.1

309.9 18.6

419.1 25.2

544.8 32.8

850.3 51.1

1220 73.4

Note: – L = Liquid, V = Vapor – For R507 use R404A – For 449A use R448A.

R407A

R407C

R448A

R22

Lbs per 100 feet of type L tubing – Weight at 75°F/28.89°C

L

V

L

V

L

V

L

V

71.8

3

71.31 2.64

68.5

2.93

74.6

2.68

3.9

0.2

3.9

0.1

3.7

0.2

4.0

0.1

7.3

0.3

7.2

0.3

6.9

0.3

7.5

0.3

11.6

0.5

11.6

0.4

11.1

0.5

12.1

0.4

24.1

1.0

24.0

0.9

23.0

1.0

25.1

0.9

41.1

1.7

40.9

1.5

39.3

1.7

42.7

1.5

62.7

2.6

62.3

2.3

59.8

2.6

65.1

2.3

88.7

3.7

88.1

3.3

84.6

3.6

92.1

3.3

154.3

6.4

153.2

5.7

147.2

6.3

160.3

5.8

237.9

9.9

236.3

8.7

227.0

9.7

247.2

8.9

339.7 14.2 337.4 12.5 324.1 13.9 352.9 12.7

459.4 19.2 456.2 16.9 438.3 18.7 477.3 17.1

597.2 25.0 593.1 22.0 569.7 24.4 620.4 22.3

932.0 38.9 925.6 34.3 889.1 38.0 968.3 34.8

1338

55.9

1329

49.2

1276

54.6

1390

49.9

R134a

L

V

75.59 1.95

4.1

0.1

7.6

0.2

12.2

0.3

25.4

0.7

43.3

1.1

66.0

1.7

93.4

2.4

162.4

4.2

250.5

6.5

357.6

9.2

483.6 12.5

628.7 16.2

981.2 25.3

1408 36.3

B50-BCU-IM-20

– 20 –

20/04/22

COMPRESSOR OILS

Copeland Compressors

REFRIGERANT
HCFC R401A HCFC R-401B HCFC R-402A HCFC R-402 HCFC R-408A HCFC R-409A

LUBRICANT CHOICES

PREFERRED *

ALTERNATE 1 ALTERNATE 2

AB & MIN

POE-32 & MIN

POE-32

HFC R134a

HFC R404A

HFC R507

HFC R407A

POE-32

n/a

n/a

HFC R407C

HFC R448A

HFC R-407F

  • LEGEND:

MIN: Mineral Oil (Copeland® 46BWMO, Sonneborn Suniso 3GS), Chevron/Texaco Capella WF32 )

Mineral oils are interchangeable for `top off’ purpose

AB:

Alkyl Benzene Oil (Copeland® Ultra 200, Shrieve Zerol 200 TD, Sonneborn Suniso AKB200A,

Shell 2212)

POE 32: Polyolester Oil (Copeland® Ultra 32-3MAF, National NL PE32-3MAF, Lubrizol Emkarate RL32-3MAF,

Parker EMKARATE, RL32-3MAF/ (Virginia) LE323MAF, Nu Calgon 4314-66 (EMKARATE RL32-3MAF)

Spectronics AR-GLO 4/E Fluorescent Leak Detection Dye is approved for HFC/POE and HCFC/Mineral Oil

usage at the manufacturer’s recommended concentrations

Bitzer Semi-Hermetic Reciprocating Compressors: 2KC-05.2(Y) to 6F-50.2(Y)

Lubricant Type

(H)CFC R22
Interim Blends R-401A, R-401B, R-402A,
R-408A, R-409A, (MP-39, MP-66, HP-80, FX-10, FX56)

HFC’s R134a R404A R507 R407C R407A R448A

ICI (Virgina KMP) Emkarate RL32S

A*

P

Polyol Ester

Mobil EAL Arctic 32

A*

P

Castrol Icematic SW32

A*

P

Suniso 3GS

A

Suniso 4GS

A

Mineral Oils

Capella Oil WF32

A

Not Acceptable

Capella Oil WF68

A

Esso Zerice R68

A

Zerol 150

P

Zerol 300

P

Alkyl Benzene

Icematic 2284

P

Not Acceptable

Esso Zerice S46

P

Esso Zerice S68

P

A/B M/O Mix

Shell Clavus SD 2212 Esso Zerice R46

P Not Acceptable
A

B50-BCU-IM-20

Legend: P = Preferred

A= Acceptable Alternative

– Compressor with “Y” designation are factory charged with polyolester oil * NOTE: When operating (H)CFC with ester oils the quantity of refrigerant dissolved in the oil is more than doubled as compared with conventional lubricants. Special care should be taken. Refer to Bitzer Technical Bulletin KT-510-2, section 5 for additional information.
– 21 –

20/04/22

WATER-COOLED CONDENSERS
WARNING
All water and drain connections to the unit must be made in accordance with national as well as local plumbing codes and by-laws.

All water-cooled condensers require a water regulating
valve that must be installed upstream of the condenser.
The water-regulating valve is adjustable and is set
to provide the desired condensing pressure. As the
condensing pressure rises, the valve will open and allow more water to flow. As the condensing pressure lowers, the valve will start to close to reduce the amount of water flow into the condenser. Typical condensing temperatures normally range between 90 to 110 °F. The actual water inlet temperature and water supply flow capacity available at the site determines the suitable
condensing temperature. Lower inlet water temperatures
(40°F to 70 °F) allow the condensing unit to run at a lower
condensing temperature (70°F to 90°F). Higher water
inlet temperatures (above 85°F) require the condensing
temperature to be higher (105° to 120°F). The capacity of
the water-cooled condensing unit varies with condensing temperature. Refer to the water flow rate chart in the Product Data and Specifications brochure that comes with the condensing unit to estimate the required flow rate in GPM. If water supply pressure is excessive, a pressure-
reducing valve must be used since the allowable working
pressure of water valves and condensers is normally 150
psig (1136 kPa).

Care should be exercised in locating the condensing unit so that the condenser will never be exposed to temperatures below freezing.
Excessive water velocities or cavitation on the waterside of the condenser tubes may damage a water-cooled condenser. In order to prevent operating difficulties, care should be taken to follow the instructions outlined below:
(a) Water velocities through the condenser should not exceed 7 fps (2.13 m/s). Higher velocities can result in “impingement corrosion”. In order to maintain water velocities at an acceptable level, parallel circuiting of the condenser may be necessary when high water flow is required. (b) If a water-circulating pump is used, it should be installed so that the condenser is fed from the discharge side of the pump. (c) If the condenser is installed more than 5 ft (1.52 m) higher than the outlet drain point of the condenser, a vacuum breaker or open vent line should be provided to prevent the outlet line from creating a partial vacuum condition.

RECOMMENDED OPTIONS

Low Temperature Systems (-10°F Freezers) · Suction Accumulator with Heat Exchanger · Oil Separator · Suction Filter
Medium Temperature Systems (+35°F Coolers) · Suction Accumulator with Heat Exchanger · Oil Separator · Suction Filter
Long Piping Runs (>100-150 ft) · Suction Accumulator
with Heat Exchanger · Oil Separator · Oversized Receiver · Liquid / Suction Heat Exchanger · Suction Filter

Capacity Control (Expected Periods of Low Load / Oversized Equipment to Daily Load Requirements / Tight Temperature Control)
· Hot Gas Bypass to Evaporator (for use with 1 evaporator) Add Aux Sideport Connector to evaporator (required) HG Bypass to Evaporator Kit (required)
· Hot Gas Bypass to Suction (for use with multiple evaporators or where bypass to evaporator is not accessible/realistic) Add Suction Accumulator (required) HG Bypass to Suction Line Kit (required)

  • Highly recommended

B50-BCU-IM-20

– 22 –

20/04/22

AVAILABLE OPTIONS & OPTION INFORMATION

HOT GAS BYPASS
Purpose: To maintain a constant evaporating pressure during periods of low load either to prevent coil icing or to avoid operating the condensing unit at a lower suction pressure than it was designed to operate. Application: Hot gas bypass is a method of compressor capacity control that eliminates the on-off control of the compressor allowing for greater control of temperature, humidity and load matching. Common uses are in wine rooms, fur storage and biotech; anywhere critical temperature and or humidity applications exist. How it Works: The discharge bypass valve is located in a branch line off the discharge line close to the compressor. The bypassed hot gas can enter the low side at the inlet of the evaporator or at the suction line. The hot gas bypass valve is adjustable to maintain the desired evaporating or suction pressure. Maintaining a constant evaporating pressure regulated by the modulating hot gas will allow for a constant coil temperature resulting in a constant room temperature regardless of room load.
Bypass to Inlet of the evaporator is the preferred method because the TXV will provide the correct amount of liquid refrigerant for desuperheating. In addition, the evaporator allows for proper mixing of liquid and hot gas ensuring dry super-heated refrigerant returns to the compressor.
Bypass to the suction line is used with long line runs and with multiple evaporators. The addition of a specific desuperheating TXV is required to prevent overloading (overheating) of the compressor due to high return gas temperatures caused by bypassed hot gas close to the compressor. A suction accumulator is also recommended, as this will ensure proper mixing of the hot gas and liquid refrigerant prior to it reaching the compressor.
CRANKCASE PRESSURE REGULATOR (CPR)
Purpose: Prevents overloading of the compressor motor by limiting the suction pressure at the compressor during normal operation, during or after defrost, or after a lengthy shutdown period. Application: Required on any application where the potential for the compressor running at a suction temperature or pressure higher than what is allowed by the compressor manufacturer (i.e. running the compressor outside its operating envelope) for an extended period of time. This can be seen on low temperature systems using hot gas defrost. High suction pressure and temperatures will overload the compressor motor causing the internal motor overload to open, stopping the compressor until it cools down. How it works A crankcase pressure regulator is a valve that closes on a rise of outlet pressure. The valve set point is the corresponding pressure of the maximum saturated suction

temperature the compressor manufacturer allows for the specific compressor. If the suction pressure upstream of the valve exceeds the set point, it begins to close modulating and maintaining a constant pressure for the compressor.
Please note that the use of a CPR valve introduces a large pressure drop in the suction line. Even under normal operating conditions a full 2°F drop may occur across the valve; reducing the refrigeration system capacity. A CPR valve set point lower than the maximum saturated suction temperature will prolong the pull-down period after a defrost has completed.
HEATED AND INSULATED RECEIVER
Purpose: Heated and Insulated Receivers are used to maintain a minimum receiver pressure. Application: Applicable for outdoor units where mild to low ambient temperatures combined with extended off cycles (low product load) are experienced. How it works: Heated and insulated receivers help maintain a higher pressure that would normally correspond to the cold ambient/low pressure in the receiver. Without a heated and insulated receiver the pressure in the receiver would drop to the corresponding ambient temperature during off cycles (low product load conditions) upon a call for cooling the receiver pressure will be too low to feed the expansion valve. This would result in short cycling on the low pressure switch which could eventually lead to oil loss and compressor damage.
REPLACEABLE SUCTION FILTER
Purpose: To pick up and remove system contaminants such as metal particles, rust, oxides, dirt, and any other solid contaminants. The suction filter protects compressors from materials becoming imbedded in the motor windings where the natural flexing of windings during start up can cause particles to scrape the motor insulation and result in motor burnout. Also used with desiccant cores (filter-drier) to collect and remove acid, moisture and sludge.
Application: Required for field built up systems where cutting and/or brazing of lines occurs or additionally any system where contamination could or could have occurred.
Desiccant core suction filter-driers can be used to clean the system (removing corrosive acids) after mild hermetic motor burnouts. Filter-driers are also used to remove system moisture as system moisture could freeze TX valves and ultimately lead to liquid flood back and compressor damage.

B50-BCU-IM-20

– 23 –

20/04/22

AVAILABLE OPTIONS & OPTION INFORMATION (cont’d)

REPLACEABLE SUCTION FILTER (cont’d)
How it works: The suction filter (filter-drier) is simply a shell with pleated or felt element used to collect contaminants. The suction filter is installed in the suction line and the filter core itself can be of sealed type or replaceable type where it can be removed and have a replaceable core. The core itself can be combined with or made out of a desiccant material for moisture removal.
REPLACEABLE LIQUID FILTER/DRIER
Same application as suction line filter/drier but installed in the liquid line. See Replaceable Suction Filter.
SUCTION ACCUMULATOR w/ HEAT EXCHANGER
Purpose: To prevent liquid refrigerant from flooding back to the compressor as liquid flood back can result in liquid slugging, loss of oil from the crankcase or bearing washout. Note: liquid flood back is considered one of the major causes of compressor failure.
The addition of a heat exchanger raises the temperature of the return gas in the suction line and lowers the temperature of the refrigerant in the liquid line. This prevents the formation of flash gas in the liquid line, provides additional superheat to the suction gas helping to prevent liquid refrigerant from flooding back to the compressor and increasing system capacity. Application: Suction accumulators are used for any instances were liquid flood back could occur. Commonly used in low temperature systems where flood back is an increased issue. How it works: Suction accumulators are installed in the suction line close to the compressor. The accumulator is vertical container with top inlet and outlet connections. An internal U-tube connected only to the outlet reaches down near the bottom of the container and draws refrigerant in from the top. This allows the accumulator to almost completely fill with liquid refrigerant before flood back can occur. A small diameter hole is drilled in the U-tube near the lowest point. This small hole allows for controlled metering of liquid refrigerant or oil back to the compressor by a siphoning action.
ADJUSTABLE FLOODED HEAD PRESSURE CONTROL

condenser reducing condenser area, which in turn increases condensing pressure. At the same time hot discharge gas can be bypassed around the condenser by means of the ORD (open on rise of differential) raising the liquid pressure in the receiver allowing the system to operate properly. The ORI (Open on Rise of Inlet pressure) is adjustable; its set point will maintain the condensing pressure in low ambient conditions. The ORD opens when the pressure drop between the inlet of the condenser and the outlet of the ORI exceeds approximately 20 PSI. The function of the ORD is to maintain receiver pressure to allow for adequate differential pressure across the TXV for proper operation of the TXV.
DISCHARGE LINE CHECK VALVE
Purpose: To prevent the migration of liquid refrigerant from the condenser back to the compressor during the off cycle. Application: During long off cycle periods and combined with cold ambient temperatures, liquid refrigerant in the condenser may migrate to the compressor. The compressor may not be able to overcome the initial static head if liquid refrigerant is in the discharge line or worse if backed up right to the discharge valves. The valves in the head of the compressor may also leak the liquid into the crankcase causing a flooded start when the compressor eventually starts up. When the scroll compressor stops, high and low side equalize within the compressor. The discharge check valve will maintain the high/low side differential pressure during the compressor off cycle. How it Works: A check valve allows flow in one direction only. A discharge check valve will allow refrigerant to pass from the compressor to the condenser. It will not allow refrigerant to flow back through the valve from the condenser to the compressor.
EXTENDED LEG KIT
Purpose: To raise the condensing unit off the ground by 8 inches Application: Leg kits are required in locations with high snow accumulation, areas common to flooding etc. Used where a requirement exists to keep the base of the condensing unit off the ground. This may prevent damage to components within the cabinet.

Purpose: To maintain the minimum required condensing pressure during periods of low ambient temperatures. Application: Any air cooled condenser exposed to ambient temperatures that fall below 65°F. How it Works: Liquid refrigerant is restricted from leaving the condenser to the receiver. This backs up liquid refrigerant into the

B50-BCU-IM-20

– 24 –

20/04/22

AVAILABLE OPTIONS & OPTION INFORMATION (cont’d)

OIL SEPARATOR W/ OIL RETURN SOLENOID

DISCONNECT SWITCH

Purpose: Oil Separators are used to return oil to the compressor. Application: Used on refrigeration systems where it’s difficult to return oil to the compressor. Commonly used in low temperature systems where oil return is an increased issue. How it Works: Oil separators are installed in the compressor(s) discharge line. They are usually a vertical container with the discharge gas connections at the top and an oil return port at the bottom. Internal to the oil separator is a form of baffles (usually screen meshing) which removes oil by a means of velocity reduction. Most of the oil is removed from the refrigerant and returned to the compressor by means of a ball float valve
PUMP DOWN TOGGLE SWITCH

Purpose: To externally disconnect power to the system/unit Application: A disconnect switch is used such power can easily be accessed and removed from the unit. How it Works: Disconnect switch is available with and without fusing and is a manual throw switch.
CONTROL CIRCUIT TRANSFORMER
Purpose: Control circuit transformers are used to convert the unit supply voltage to a lesser voltage for use in the control circuit. Application: Used when supply voltage is large and a lower voltage is required or to allow for smaller electrical components.

Purpose: The purpose of the pump down cycle toggle switch is to force a pump down state. A pump down state prevents liquid migration to the compressor during off cycles which can lead to compressor oil loss and flooded starts. Application: Installed in systems where user controlled off cycles are used, common, or frequent. How it Works: The pump down switch is installed in series with the thermostat. When the pump down switch is thrown the power to the liquid line solenoid valve is lost and the solenoid goes into its powerless state of normally closed. With the liquid line solenoid valve closed the refrigerant flow to the evaporator is stopped and the compressor continues to run pumping refrigerant into the condenser and receiver until the low pressure control cuts out and the compressor contactor opens (stopping the compressor). The system will stay in a state of pump down that is the compressor running as required to pump down any refrigerant that might leak through the closed solenoid valve until the pump down switch is switched back.
PHASE/VOLTAGE MONITOR

COMPRESSOR CIRCUIT BREAKER
Purpose: To disconnect power and provide branch circuit protection to the compressor Application: A compressor circuit breaker is used to provide branch circuit protection disconnect power from the compressor.
GOLD COAT FINS
Purpose: To protect the aluminum fins from corrosion in specific environmental applications. Application: Any aluminum fin coil exposed to a sodium rich environment such as fish coolers & freezers and salt water coast lines. How it Works: This is an aluminum fin that has a gold coloured coating applied at the aluminum manufactures facility. The micro thin coating is adhered to the aluminum fin protecting the aluminum from corrosion and material degradation from airborne contaminants that accumulate on the coil surface during the units operating cycle.

Purpose: Used to protect the compressor from voltage and/or phase imbalances. Application: Installed in areas where phase and voltage fluctuation is common or could occur. How it Works: Phase voltage monitor is installed to sense voltage and phase imbalance across the compressor contactor. Disconnects the power supplied to the compressor upon voltage and/or phase imbalance. Has a built in field adjustable restart delay (normally factory preset to 2 seconds).

HERESITE COATING
Purpose: To protect from exposure to corrosive atmospheres with the exception of strong alkalies, strong oxidizers and wet bromine, chlorine and fluorine in concentrations greater than 100 ppm Application: For both fins and units in corrosive atmospheres How it Works: This is a Heresite baked phenolic compound coating and is offered as a service to the customer. As standard the Heresite coating is applied to the coil and manifold only for additional protection.

B50-BCU-IM-20

– 25 –

20/04/22

AVAILABLE OPTIONS & OPTION INFORMATION (cont’d)

A419 ELECTRONIC THERMOSTAT

EC MOTORS (Electronically Commutating Motors)

Purpose: To provide users with an easy to read, easy to access, and single point reliable solid-state control thermostat. Application: The digital thermostat can be used where a thermostat is required separate of the evaporator(s). It is often used in circumstances having multiple evaporators in order to provide single point control from an easy to access location that can be either inside or outside the space. The digital thermostat with LCD display is used to more accurately set, read and control system temperatures and offers a tighter range differential. How it Works: This is a single stage, electronic temperature control with a single pole double throw output relay. Has LCD display with adjustable set point, differential and adjustable anti- short cycle delay. A419 is available in 120/240 VAC. Is wired in series with the liquid line solenoid valve(s) such that upon satisfying the cooling load the thermostat cuts out (de-energizing/closing the liquid solenoid valve) and pumping down the system. The electronic thermostat also offers a tighter range of control as the differential setting can be as low as 1°F (standard mechanical Saginomiya thermosat has a minimum differential of 3.6°F).
ELECTRONIC THERMOSTAT
Purpose: To provide users with an easy to read, easy to access, and single point reliable solid-state control thermostat. Application: The digital thermostat can be used where a thermostat is required separate of the evaporator(s). It is often used in circumstances having multiple evaporators in order to provide single point control from an easy to access location that can be either inside or outside the space. The digital thermostat with LCD display is used to more accurately set, read and control system temperatures and offers a tighter range differential. How it Works: This is a single stage, electronic temperature control with a single pole double throw output relay. Has LCD display with adjustable set point, differential and adjustable anti- short cycle delay. Most electronic thermostats are available in 120/240 VAC. Is wired in series with the liquid line solenoid valve(s) such that upon satisfying the cooling load the thermostat cuts out (de-energizing/closing the liquid solenoid valve) and pumping down the system. The electronic thermostat also offers a tighter range of control as the differential setting can be as low as 1°F.

Purpose: To comply with regional regulatory code as well as provide increased energy efficiency and decreased operational costs Application: EC Motors are required in most regions by local codes and regulations. Used to provide increased energy efficiency and as such lower operating cost (compared to Shaded Pole or PSC motors). How it Works: An EC motor is made up of two components, the motor and the motor control module. Input AC voltage is supplied and converted to DC voltage by the motor control module. This DC voltage is used in the brushless operation of the motor. The motor controller energizes the motor phases at the appropriate time for optimum operation and speed. The motor controller can be programmed to provide specific speed based on a 0-10V input signal. Note: our standard EC evaporator motors are set up for 1 speed or 2 speed operation with SmartSpeed. EC motors due to brushless commutation and internal controller are significantly more efficient then standard motors. Installed PSC motor efficiencies are typically in the range of 12-45% whereas EC motors maintain an efficiency of 65-72% at all speeds. In addition to EC motor efficiency; these motors operate at low temperatures requiring less energy to offset motor heat gain in the refrigeration system.
FOR DETAILS ON EC MOTOR APPLICATION REFER TO EC MOTOR APPLICATION GUIDE
COMPRESSOR TIME DELAY (Delay on Break)
Purpose: To provide a specified amount of time for the compressor to remain off after pump down and prevent short cycling. Application: Installed on condensing units to prevent short cycling and protect the compressor. (Factory setting 3-minutes) How It Works: Immediately upon application of power, the Delay on Break timer enables circuit operation. Once power is interrupted, the circuit opens for the time set on the dial. After the time period elapses, the circuit closes, allowing the protected motor or compressor to start.

B50-BCU-IM-20

– 26 –

20/04/22

LEAK TESTING
IMPORTANT: All system piping, including the condensing unit and accessories should be thoroughly tested for leaks prior to start up and charging. The system should be initially pressurized to a maximum of 150 psig (1136 kPa) with dry nitrogen to ensure that the system is free of major leaks. With the system free of major leaks, a more detailed leak check should be performed. Discharge the initial dry nitrogen charge and add enough refrigerant to raise the system pressure up to 10 psig (170 kPa) (tracer amount). Add dry nitrogen to increase the system pressure to a maximum of 150 psig (1136 kPa). It is recommended that an electronic leak detector be used when checking for leaks because of its greater sensitivity to small leaks. As a further check it is recommended that this pressure be held for a minimum of 12 hours and then rechecked. The system must be leak free for satisfactory operation.
WARNING
HFC-134a has been shown to be combustible at pressures as low as 5.5 psig (140 kPa) at 350 °F (176.7 °C) when mixed with air at concentrations more than 60% air by volume. At lower temperature, higher pressures are required to support combustion. Therefore, air should never be mixed with HFC-134a for leak detection.
IMPORTANT ENVIRONMENTAL NOTE
When conventional leak detection methods are employed using HCFC or CFC tracer gas, all of the tracer gas must be reclaimed and disposed of in a proper manner.
EVACUATION AND DEHYDRATION
When the system is completely free of refrigerant leaks, an evacuation of the entire system should be completed by using a “high vacuum” pump. This evacuation, if completed correctly, will ensure long life for the system as well as elimination of moisture and non-condensable gas problems. Moisture problems causing compressor failure will void warranty. Follow the recommended procedure carefully.
CAU T I ON
Do not use the refrigeration compressor to evacuate the system. Never start the compressor or perform a megger insulation test while the system is in a vacuum.
DEHYDRATION PROCEDURE
1. Use larger size (3/8 or 1/2) hoses or copper lines. 2. Perform oil change on vacuum pump at the beginning of each evacuation 3. Always check vacuum pump, manifold, and hose assembly that it will pull below 250 microns. 4. Evacuate system from 4 access points (if available) on the system. These points are: (Refer to piping schematic below)
i. Liquid receiver service valve (VL1) ii. Compressor Suction service valve (VL2) iii. Compressor Discharge service valve (VL3) iv. ¼ fitting on Discharge line before the condenser (VL4) 5. Ensure that all solenoids in the system are open (energized) during evacuation. 6. Ensure that all ball valves in the system are open and all service valves are appropriately cracked or back- seated during evacuation. 7. Perform “Deep Vacuum Method”.

B50-BCU-IM-20

– 27 –

20/04/22

DEHYDRATION PROCEDURE (cont’d)

Deep Vacuum Method: 1. Ensure that the vacuum pump used is capable of pulling a 250 micron vacuum. 2. Connect hoses to the appropriate locations on the system and other ends to the manifold. Then connect the manifold
to the vacuum pump. 3. Connect an electronic vacuum gauge at a point on the system furthest away from the vacuum pump. 4. Turn on the vacuum pump and proceed with opening the high and low side valves on the gauge manifold first then
proceed with opening the shut off valves or service valves which gives access to the system. 5. Evacuate until the vacuum gauge reads 500 microns or less. 6. Close the valves to the vacuum pump and shut pump off. Wait 30 minutes. 7. If the vacuum gauge reads below 1000 microns the system can be considered dry and leak free and can proceed with
refrigerant charging. 8. If the vacuum gauge reads between 1000-2000 microns then some moisture is still present.
Sweep with Nitrogen and repeat steps 4­7.
Refer to graph below as a guideline when using the Deep Vacuum Method.

B50-BCU-IM-20

Microns

5000

4500

4000

3500 3000

Leak in System

2500

2000

50 ppm H 0 Vacuum tight too wet 2
1500

1000
< 10 ppm H 0 Tight dry system 2
500

0

0

1

2

3

4

5

6

7

Time – Hours
– 28 –

20/04/22

SYSTEM START-UP CHECK LIST
I M PORTAN T START-U P N OT E
Only a qualified refrigeration mechanic who is familiar with compressor performance and the function and adjustment of all controls and components should start up the compressor. Finishing up work on the installations should be planned so that a qualified mechanic is on the job for at least the first full day that the unit is in operation.
Before any refrigeration system is started, the following items should be checked:
(1) Check that all electrical and refrigeration connections are tight. (2) Check compressor crankcase oil level (if equipped with sight glass). It should be from 1/8 to 1/2 full in the sight
glass. (3) Insure that compressor shipping spacers (spring mounted compressors) or hold down nut (solid mounted
compressors) are properly in place. (4) Check that the compressor discharge and suction shut-off valves are open. (5) Ensure that the high and low pressure controls pressure regulating valves, oil pressure safety controls,
Compressor Time Delay and any other safety controls are adjusted properly. (6) Check that the room thermostat is set for normal operation and adjust if required. (7) Check all motors, fans and pump bearings in the condenser and evaporator. If they are the type that require
oil or grease, make sure that this is attended to in accordance with the tag, which will be attached. Fan blades and pumps should be checked for correct rotation, tightness and alignment. Air should draw air through the condenser (air cooled condensing unit models). (8) Electric and hot gas evaporator fan motors should be temporarily wired for continuous operation until the room temperature has stabilized. (9) Observe the system pressures during the charging and initial operation process. DO NOT add oil while the system is low on refrigerant charge unless the oil level is dangerously low. (10) Continue to charge the system until it has enough charge for proper operation. DO NOT OVERCHARGE THE SYSTEM. Note that bubbles in the sight glass may not necessarily mean a shortage of refrigerant. (11) DO NOT leave the system unattended until the system has reached its normal operating condition and the oil charge has properly adjusted itself to maintain the proper level in the sight glass. (12) Compressor performance, and that of all of the moving components should be watched carefully throughout the first operating cycle and then checked periodically during the first day of operation. Careful attention to details at this time will pay dividends in trouble-free performance of the entire system. (13) Check that the wiring diagrams, instructions bulletins etc. are read and attached to the unit for future reference.

WARNING
Three phase scroll compressors must be checked for correct rotation. During the initial start up, observe the suction and discharge gauges to ensure the suction pressure drops and the discharge pressure rises.

B50-BCU-IM-20

– 29 –

20/04/22

PRESSURE CONTROLS

Encapsulated Pressure Switches
Encapsulated pressure switches are commonly installed on many condensing units. These switches set with fixed set points (non-adjustable) and are auto reset.

·

High Pressure Switch: R22 Cut-out @ 350 PSIG, Cut-in @ 250 PSIG

R404A/R507/R448A/R407A/R407C Cut-out @ 400 PSIG, Cut-in @ 300 PSIG

Adjustable Pressure Controls

Adjustable Low Pressure Control Settings **

Minimum Temperature
°F *
50 40 30 20 10 0 -10 -20 -30

R134a

Cut-in
(PSIG)
35 25 17 12 7 5 –

Cut-out
(PSIG)
5 5 5 0 0 0 –

R22

Cut-in
(PSIG)
70 55 40 30 20 15 15 10 10

Cut-out
(PSIG)
20 20 20 10 0 0 0 0 0

  • The coldest Temperature of either the fixture or outdoor ambient. ** Compressor Time Delay Setting: 3 Minutes

R404A R507

R448A R407A R407C

Cut-in
(PSIG)
85 70 50 40 30 20 15 10 6

Cut-out
(PSIG)
30 30 30 20 10 5 0 0 0

Cut-in
(PSIG)
65 50 35 25 15 10 10 7 7

Cut-out
(PSIG)
20 20 20 5 0 0 0 0 0

Adjustable High Pressure Control Settings

Refrigerant
R134a R22

Maximum Cut-out (PSIG)

Air-Cooled Units

Water Cooled Units

250

200

350

315

R404A R448A R407A R407C

400

315

LOW TEMPERATURE ROOM PULL-DOWN

It can take up to two weeks to properly start-up and pulldown a large freezer. Large freezers should be pull-down to temperature in stages. Too fast a pull- down can cause structural problems in pre-fabricated rooms and will damage (crack) concrete floors. Reduce room temperature by 10 to 15°F (5.6 to 8.4°C) per day. Hold this temperature for 24 to 48 hours at 35°F (1.7 °C) and again at 25°F (-3.9 °C). Monitor the amount of defrost water during this pull down stage.

Once the room is pulled down to temperature, expect frost on the compressor end bell and any exposed suction line. A lack of frost in these areas probably indicates too high of suction superheat. Reduce defrost frequency to 30 minutes every 6 hours if possible. Adjust the defrost termination (and time clock) so that the coil and drain pan are COMPLETELY free of frost / ice at termination. Too short of a defrost cycle will allow residual ice to grow. Too long of a defrost will allow the coil(s) to steam at the end of the cycle. The steam will condense and freeze fans, fan guards and create frosting on the ceiling of the room. The evaporator fan delay must allow any condensate left on the coil surface to refreeze before the fans start.

B50-BCU-IM-20

– 30 –

20/04/22

CHECKING SUPERHEAT
IMPORTANT SYSTEM BALANCING NOTE
To obtain maximum system capacity and insure trouble free operation it is necessary to check both the compressor and evaporator superheat.
Compressor Superheat
Compressor suction superheat must be checked. To check the superheat at the compressor the following steps should be followed:
(1) Measure the suction pressure at the suction service valve of the compressor. Determine the saturated temperature corresponding to this pressure from a “Pressure- Temperature” chart.
(2) Measure the suction temperature of the suction line about 6 inches (15 cm) back from the compressor suction valve using an accurate thermometer.
(3) Subtract the saturated temperature (from step 1) from the actual suction line temperature (from step 2). This difference is the actual superheat at the compressor.
System capacity decreases as the suction superheat increases. For maximum system capacity, the suction superheat should be kept as low as is practical. The superheat at the compressor should range within 20 to 45 °F (11.2 to 25.2 °C) Superheat.
NOTE: Too low of a suction superheat can result in liquid being returned to the compressor. This can cause dilution of
the oil and eventually cause failure of the bearings and rings through wash out as well as liquid slugging.
NOTE: Too high of a suction superheat will cause excessive discharge temperatures which cause a break down of the
oil and will result in piston ring wear, piston and cylinder wall damage.
If adjustment to the suction superheat is required, it should be done either by adjusting the thermostatic expansion valve at the evaporator, the use of liquid to suction heat exchanger or suitable use of suction line insulation.
Evaporator Superheat
Once the refrigerated space is at its design temperature or close to design temperature, the evaporator superheat must be checked. To check the suction superheat at the evaporator the following steps should be followed:
(1) Measure the suction pressure in the suction line at the bulb location by either, (a) A gauge in the external equalizer line will indicate the pressure directly and accurately. (b) A gauge directly in the suction line near the evaporator or directly in the suction header will suffice.
(2) Measure the temperature of the suction line at the point where the thermostatic expansion valve bulb is clamped to the suction line.
(3) Convert the pressure obtained in step 1 above to a saturated evaporator temperature from a “PressureTemperature” chart.
(4) Subtract the saturated temperature (from step 1) from the actual suction line temperature (from step 2). This difference is the actual superheat at the evaporator.
The superheat at the evaporator should be a minimum of 6 to 10 °F (3.4 to 5.6 °C) for systems with a 10 °F (5.6 °C) design TD (temperature difference) to a maximum of 12 to 15 °F (6.7 to 8.4 °C) for systems with a higher operating TD.
Low temperature applications (freezers) should be set at superheats of 4 to 6 °F (2.2 to 3.4 °C).
TD = Box temperature ­ evaporating temperature.

B50-BCU-IM-20

– 31 –

20/04/22

SEQUENCE OF OPERATION

Recycling Pump Down System

Power is generally supplied to the thermostat and liquid line solenoid circuit from the evaporator fan terminals

“4” & “F” (off time defrost) or from the time clock (timed air or electric defrost) terminals “4” and “N”.

The room thermostat switch closes when the temperature rises above the desired set point.

The liquid line solenoid coil is energized causing the valve to open, allowing liquid refrigerant into the evaporator

coil.

The low pressure control closes when the suction pressure rises above the cut- in setting of the control.

The compressor contactor coil is energized causing the contactor to close. The compressor and the condenser

fan closest to the discharge header start at the same time. Additional fans will come on after the discharge

pressure rises above the cut-in set point of the fan cycle control.

Once the thermostat set point has been reached, the thermostat opens and the liquid line solenoid coil is de-

energized. The solenoid valve closes stopping the refrigerant flow to the evaporator.

The compressor continues to run reducing the suction pressure until it drops below the cut-out setting indicated

on the low pressure control. The compressor contactor coil is de-energized, the contactor opens and the

compressor and condenser fan stop running. The Compressor Time Delay opens for the recommended

3-minute setting to prevent short cycling.

The system remains off until the temperature rises above the desired set point again.

Electric Defrost Cycle ­ Using 8145 time clock or equivalent

During refrigeration the “4” terminal on the time clock is powered supplying voltage to the thermostat and

solenoid circuit. It also supplies voltage to the evaporator fans directly or to a contactor coil whose contactor

contacts directly power the evaporator fan motors.

During defrost the “3” terminal on the time clock is powered supplying voltage to the defrost heater circuit.

The defrost cycle starts automatically via the time clock at predetermined times as defined by the installing

contractor by manipulating the pins on the clock face. Three (3) to four (4) defrost cycles are generally sufficient

however variations in loads due to usage and infiltration may require additional adjustments, defrost cycles of

alternative defrost methods

When it’s time for a defrost cycle to start, terminal “4” is de-energized, the liquid line solenoid coil is de-

energized. The solenoid valve closes stopping the refrigerant flow to the evaporator allowing the compressor to

pump down and shut off on the low pressure control. At the same time the evaporator fan motors stop running.

From the time clock terminal “3” is powered, however a normally closed auxiliary contact mounted on the side of

the compressor contactor holds the off the power to the heater circuit until the compressor has finished pumping

down.

Once the compressor contactor opens, the auxiliary switch closes supplying voltage to the defrost heaters

directly or to a contactor coil whose contactor contacts directly power the defrost heaters.

Once powered, the defrost heaters increase the coil temperature melting the frost that had accumulated during

the refrigeration cycle.

A defrost termination thermostat measures the coil temperature. Once the coil reaches 55°F +/-5°F the switch

closes powering the “X” terminal on the evaporator which is field wired to the “X” terminal on the time clock. The

time clock switches back into refrigeration mode, de-energizing terminal “3” and re-energizing terminal “4”.

Assuming the room thermostat is closed, the liquid line solenoid coil is energized causing the valve to open

allowing liquid refrigerant into the evaporator coil. The low pressure control closes when the suction pressure

rises above the cut-in setting of the control. The compressor contactor coil is energized causing the contactor to

close. The compressor and the condenser fan(s) start at the same time.

As the compressor runs the coil temperature will drop, the fan delay thermostat measures the coil temperature.

The contacts of the fan delay thermostat will close completing the evaporator fan motor circuit back to “N” on the

time clock causing the fans to start running again.

The system will now operate in the refrigeration cycle until another defrost period is initiated by the time clock.

B50-BCU-IM-20

– 32 –

20/04/22

SYSTEM OPERATIONAL CHECK LIST
When the system has been running trouble free for an extended time (two weeks or more) and design conditions are satisfied, the following check list should be followed:
(1) Check that compressor discharge and suction pressures are operating within the allowable design limits for the compressor. If not, take the necessary corrective action.
(2) Check the liquid line sight glass and expansion valve operation. If there is an indication that the system is low on refrigerant, thoroughly check the system for leaks before adding refrigerant.
(3) Check the level of the oil in the compressor sight glass (if so equipped). Add oil as necessary. (4) The thermostatic expansion valve must be checked for proper superheat settings. The sensing bulb must have
positive contact with the suction line and should be insulated. Valves operating at a high superheat setting results in low refrigeration capacity. Low superheat settings can cause liquid slugging and compressor bearing washout. (Refer to the section on compressor and evaporator superheats) (5) Check the voltage and amperage readings at the compressor terminals. Voltage reading must be within the recommended guidelines. Normal operating amperages can be much lower than the compressor nameplate values. (6) To check the high pressure control setting it is necessary to build up the head pressure to the cut-out point of the control. This can be done by stopping the condenser fan(s) (air cooled condensing units) or pump and watching the pressure rise on a high pressure gauge to make sure the high pressure control is operating at the setting. (7) Check the low pressure settings by throttling the compressor shut-off valve and allowing the compressor to pump down. This operation must be done with extreme caution to avoid too sudden a reduction in crankcase pressure, which will cause oil slugging and possible damage to the compressor valves. Close the valve a turn a a time while watching the compound gauge for change and allowing time for the crankcase pressure to equalize with the pressure control bellows pressure. The slower the pressure is reduced, the more accurate will be the check on the pressure control setting. (8) Recheck all safety and operating controls for proper operation and adjust as necessary. (9) Check defrost controls for initiation and termination settings, and the length of defrost period. Set the fail safe on the time clock at the length of defrost plus 25 %. (10) If the system is equipped with winter head pressure controls (fan cycling or flooded valves), check for operation. See details on page 14 for flooded valves. (11) Fill in the Service Log in the back of this Installation Manual.

B50-BCU-IM-20

– 33 –

20/04/22

SYSTEM TROUBLESHOOTING

The following System Troubleshooting Guide lists the most common types of malfunctions encountered with refrigeration systems. These simple troubleshooting techniques can save time and money minimizing unnecessary downtime and end-user dissatisfaction.

Contact the factory or your local sales representative for further information or assistance.

System Troubleshooting Guide

Condensing Unit Problem

Possible Causes

Compressor will not run. Does not try to start.

1. Main power switch open.

2. Fuse blown or tripped circuit breaker.

3. Thermal overloads tripped.

4. Defective contactor or coil.

5. System shut down by safety devices.

6. Open thermostat or control. No cooling required.

7. Liquid line solenoid will not open.

Compressor hums, but will not start.

8. Loose wiring. 1. Improperly wired.

2. Low line voltage.

3. Loose wiring.

4. Defective start or run capacitor.

5. Defective start relay.

6. Motor windings damaged.

Compressor starts, but trips on overload protector.

7. Internal compressor mechanical damage. 1. Improperly wired.

2. Low line voltage.

3. Loose wiring.

4. Defective start or run capacitor.

5. Defective start relay.

6. Excessive suction or discharge pressure.

7. Tight bearings or mechanical damage in compressor.

8. Defective overload protector.

9. Motor windings damaged.

10. Overcharged system.

11. Shortage of refrigerant.

12. Suction or discharge pressure too high.

13. Inadequate ventilation.

Compressor short cycles.

14. Operating system beyond design conditions.
1. Low pressure control differential set too low. 2. Shortage of refrigerant.

3. Low airflow at evaporator(s). 4. Discharge pressure too high.

5. Compressor internal discharge valves leaking.

Start relay burns out.

6. Incorrect unit selection (oversized). 7. Check Compressor Time Delay Setting (3-Minutes recommended)
1. Improperly wired.

2. Low or high line voltage.

3. Short cycling.

4. Improper mounting of relay.

5. Incorrect start or run capacitor.

Contact welded stuck on start relay

6. Incorrect relay. 1. Short cycling.

Start capacitor burns out

2. No bleed resistor on start capacitor. 1. Improperly wired.

2. Short cycling.

3. Low line voltage.

4. Relay contacts sticking.

5. Incorrect capacitor.

6. Start winding remaining in circuit for prolonged period.

B50-BCU-IM-20

– 34 –

20/04/22

SYSTEM TROUBLESHOOTING (cont’d)

System Troubleshooting Guide Continued

Condensing Unit Problem

Possible Causes

Compressor noisy or vibrating.

1. Flood back of refrigerant.

2. Improper piping support on the suction or discharge lines.

3. Broken or worn internal compressor parts.

4. Incorrect oil level.

5. Scroll compressor rotating in reverse (three phase).

Discharge pressure too high.

6. Improper mounting on unit base. 1. Non-condensables in the system.

2. System overcharged with refrigerant.

3. Discharge service valve partially closed.

4. Condenser fan not running.

5. Dirty condenser coil.(air-cooled condensers)

6. Dirty tubes. .(water-cooled condensers)

7. Defective or improperly set water regulating valve. (water-cooled condensers)

Discharge pressure too low.

8. Defective or improperly set flooded head pressure control. 1. Low suction pressure.

2. Cold ambient air.

3. Suction service valve partially closed.

4. Shortage of refrigerant.

5. Defective or improperly set water regulating valve. (water-cooled condensers)

Suction pressure too high.

6. Defective or improperly set flooded head pressure control. 1. Excessive load.

2. Compressor internal valves broken.

3. Incorrect unit selection (undersized).

Suction pressure too low.

4. Improper TXV bulb charge. 1. Shortage of refrigerant.

2. Evaporator dirty or iced up.

3. Clogged liquid line filter drier.

4. Clogged suction line filter or compressor suction strainers.

5. Expansion valve malfunctioning.

6. Condensing temperature too low.

7. Improper TX valve selection.

Low or no oil pressure.

8. Evaporator distributor feed problems. 1. Low oil level. (trapped oil in evaporator or suction line)

2. Clogged suction oil strainer.

3. Excessive liquid refrigerant in the crankcase.

4. Worn oil pump.

5. Oil pump reversing gear sticking in the wrong position.

6. Worn bearings.

7. Loose fitting on oil line.

Compressor loses oil.

8. Pump housing gasket leaking. 1. Refrigerant leak.

2. Short cycling.

3. Excessive compressor ring blowby.

4. Refrigerant flood back.

5. Improper piping or traps.

Compressor runs continuously

6. Trapped oil in evaporator. 1. Excessive load.

2. Too low of a system thermostat setting or defective thermostat.

3. Shortage of refrigerant.

4. Leaking compressor internal valves.

5. Malfunctioning liquid line solenoid.

6. Incorrect unit selection (undersized).

B50-BCU-IM-20

– 35 –

20/04/22

SYSTEM TROUBLESHOOTING (cont’d)

System Troubleshooting Guide Continued

Condensing Unit Problem

Possible Causes

Room temperature too high.

1. Defective room thermostat or improper differential / setting.

2. Malfunctioning liquid line solenoid valve. 3. Insufficient air across evaporator coil (iced up coil, product

blocking evaporator, fan blade / motor problem). 4. Improper evaporator superheat (low refrigerant charge,

plugged TXV strainer, poor TXV bulb contact, incorrect

TXV setting).

Room temperature too low.

5. Malfunctioning condensing unit. 1. Defective room thermostat or improper differential / setting.

Ice accumulating on ceiling.

2. Malfunctioning liquid line solenoid valve. 1. Defrost on too long (improper setting / defective termination

thermostat, improper setting / defective time clock). 2. Too many defrosts per day. 3. Fans not delayed after defrost (improper setting / defective

Evaporator coil not clear of ice after defrost.

fan delay thermostat). 1. Defrost on too short (improper setting / defective

termination thermostat, improper setting / defective time

clock).

2. Electric heaters defective / miswired / low voltage.

3. Not enough defrosts per day.

4. Air defrost evaporator operating at too low of temperature

(require electric defrost). 5. Defective / miswired interlock at compressor contactor.

Ice building up in drain pan.

6. Defective defrost contactor or coil. 1. Improper slope in pan.

2. Blocked drain line (unheated , not insulated). 3. Electric heater in drain pan defective / miswired / low

voltage). 4. Not enough defrosts per day.

5. Lack of or improper P-trap in drain line.

Evaporator fans will not operate.

1. Main power switch open.

2. Fuse blown or tripped circuit breaker.

3. Defective contactor or coil.

4. Room temperature too high (fan delay thermostat open).

5. Fan delay thermostat improper setting / defective. 6. Defective fan motor (low voltage / tripped on thermal

overload). 7. Defective time clock. 8. Normal mode during defrost cycle (electric defrost type

evaporator).

IMPORTANT TROUBLESHOOTING NOTE
Before any components are changed on the refrigeration system, the cause of the failure must be identified. Further problems will exist unless the true cause or problem is identified and corrected.

B50-BCU-IM-20

– 36 –

20/04/22

CUSTOMER INSTRUCTIONS
Completely fill in System Start-Up Worksheets located in Appendix C at the back of this Installation and Maintenance Manual. This document should be left with the equipment for future reference.
Give the owner / end user instructions on normal operation of the system. Explain electrical characteristics, location of disconnect switches as well as other safety precautions. Advise on keeping equipment area clean and free of debris. If system has operational features, point these out to the operator.
MAINTENANCE PROGRAM
In order to ensure that the refrigeration system runs trouble free for many years, a follow-up maintenance program (consisting of a minimum of two inspections per year) should be set up. A qualified refrigeration service mechanic should carry out this semi-annual inspection. The main power supply must be disconnected and locked off to avoid accidental start up of the equipment.
(1) Check electrical components and tighten any loose connections. (2) Check all wiring and electrical insulators. (3) Check contactors to ensure proper operation and contact point for wear. (4) Check that fan motors (if applicable) are operational, ensure fan blades are tight and all mounting bolts are tight. (5) Check oil and refrigerant levels in the system. (6) Ensure that the condenser surface (if applicable) is cleaned and free of dirt and debris. (7) Check the operation of the control system. Make certain that all of the safety controls are operational and
functioning properly. (8) Check all refrigeration piping. Make sure that all mechanical joints and flare nuts are tight.
SERVICE PARTS AVAILABILITY
Genuine replacement service parts should be used whenever possible. Refer to the Service Parts List on the back cover of this Installation and Maintenance Manual or attached to the unit. Parts may be obtained by contacting your local sales representative or authorized distributor.

B50-BCU-IM-20

– 37 –

20/04/22

NOTES

B50-BCU-IM-20

– 38 –

20/04/22

Appendix A: Wiring Diagrams

Wiring Diagram Cross Reference

Condensing Unit Voltage

Condensing Unit Type

Diagram Number

Page

Evaporator Voltage and Type

Diagram Number

208-230/1/60 208-230/3/60 208-230/3/60 208-230/3/60
460/3/60 460/3/60

Small Scroll Small Scroll Small Scroll+ Coresense Large Scroll+ Coresense Small Scroll+ Coresense Large Scroll+ Coresense

208-230/1/60 208-230/3/60 460/3/60 & 575/3/60

208-230/1/60 208-230/3/60 208-230/3/60 460/3/60 & 575/3/60 460/3/60 & 575/3/60

Copelametic Bitzer Discus Discus
Discus Demand Cooling

COPELAND SCROLL

S2A1D T3A1A T3A1D T3C6A T4A6A T4C6A

A2

230 Air Defrost Low Profile

A3

230 Electric Defrost Low Profile

A5 2x 230 Electric Defrost Low Profile

A6 2x 230 Electric Defrost Med Profile

A9

460 Electric Defrost Med Profile

A10 2x 460 Electric Defrost Med Profile

COPELAND HERMETIC

S2A1A T3A1A T4A1A

A1

230 Air Defrost Low Profile

A3

230 Electric Defrost Low Profile

A8 2x 230 Electric Defrost Low Profile

SEMI-HERMETIC

KA101 LPE101 LPE201 JE101A JE101A JE201A
KA101 LPE101 JE101A

S2A1A T3B1A T3L1A T4L1A T4A4A

A1

230 Air Defrost Low Profile

KA101

A4

230 Electric Defrost Low Profile LPE101

A7 2x 230 Electric Defrost Low Profile LPE201

A12 460 Electric Defrost Med Profile JE101A

A11 2x 460 Electric Defrost Med Profile JE201A

Page
A13 A14 A15 A16 A16 A17
A13 A14 A16
A13 A14 A15 A16 A17

B50-BCU-IM-20

– 39 –

20/04/22

Condensing Unit Wiring Diagram ­ S2A1A

B50-BCU-IM-20

– 40 –

20/04/22

Condensing Unit Wiring Diagram ­ S2A1D

B50-BCU-IM-20

– 41 –

20/04/22

Condensing Unit Wiring Diagram ­ T3A1A

B50-BCU-IM-20

– 42 –

20/04/22

Condensing Unit Wiring Diagram ­ T3B1A (Bitzer)

B50-BCU-IM-20

– 43 –

20/04/22

Condensing Unit Wiring Diagram ­ T3A1D

B50-BCU-IM-20

– 44 –

20/04/22

Condensing Unit Wiring Diagram ­ T3C6A

B50-BCU-IM-20

– 45 –

20/04/22

Condensing Unit Wiring Diagram ­ T3L1A

B50-BCU-IM-20

– 46 –

20/04/22

Condensing Unit Wiring Diagram ­ T4A1A

B50-BCU-IM-20

– 47 –

20/04/22

Condensing Unit Wiring Diagram ­ T4A6A

B50-BCU-IM-20

– 48 –

20/04/22

Condensing Unit Wiring Diagram ­ T4C6A

B50-BCU-IM-20

– 49 –

20/04/22

Condensing Unit Wiring Diagram ­ T4A4A

B50-BCU-IM-20

– 50 –

20/04/22

Condensing Unit Wiring Diagram ­ T4L1A

B50-BCU-IM-20

– 51 –

20/04/22

Evaporator Wiring Diagram ­ KA101

B50-BCU-IM-20

– 52 –

20/04/22

Evaporator Wiring Diagram ­ LPE101

B50-BCU-IM-20

– 53 –

20/04/22

Evaporator Wiring Diagram ­ LPE201

B50-BCU-IM-20

– 54 –

20/04/22

Evaporator Wiring Diagram ­ JE101A

B50-BCU-IM-20

– 55 –

20/04/22

Evaporator Wiring Diagram ­ JE201A

B50-BCU-IM-20

– 56 –

20/04/22

Appendix B: Refrigerant Line Sizing Charts

B50-BCU-IM-20

– B1 –

20/04/22

REFRIGERANT LINE SIZING CHARTS
R134a

Capacity BTU/Hr.

+45°F SST Equivalent Length

R134a

Suction Line Size from Evaporator to Compressor R134a

+25°F SST Equivalent Length

+0°F SST Equivalent Length

-20°F SST Equivalent Length

-40°F SST Equivalent Length

Liquid Line Size
Receiver to TXV Equivalent Length

25′ 50′ 75′ 100′ 150′ 25′ 50′ 75′ 100′ 150′ 25′ 50′ 75′ 100′ 150′ 25′ 50′ 75 100′ 150′ 25′ 50′ 75′ 100′ 150′ 25′ 50′ 75′ 100′ 150′

2000 3/8 3/8 3/8 1/2 1/2 3/8 1/2 1/2 1/2 1/2 1/2 1/2 5/8 5/8 5/8 5/8 7/8 7/8 7/8 7/8 7/8 3/8 7/8 7/8 1-1/8 5/16 5/16 5/16 5/16 5/16

3000 3/8 1/2 1/2 1/2 1/2 1/2 1/2 1/2 5/8 5/8 1/2 5/8 5/8 7/8 7/8 5/8 7/8 7/8 7/8 7/8 1/8 7/8 1-1/8 1-1/8 1-1/8 5/16 5/16 5/16 5/16 5/16

4000 1/2 1/2 1/2 1/2 5/8 1/2 5/8 5/8 5/8 5/8 5/8 5/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 1-1/8 7/8 1-1/8 1-1/8 1-1/8 1-1/8 5/16 5/16 5/16 5/16 5/16

6000 1/2 5/8 5/8 5/8 5/8 5/8 5/8 7/8 7/8 7/8 5/8 7/8 7/8 7/8 1-1/8 7/8 7/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-3/8 1-3/8 1-3/8 5/16 5/16 5/16 5/16 5/16

9000 5/8 5/8 5/8 7/8 7/8 5/8 7/8 7/8 7/8 7/8 7/8 7/8 1-1/8 1-1/8 1-1/8 7/8 1-1/8 1-1/8 1-1/8 1-3/8 1-1/8 1-3/8 1-3/8 1-5/8 1-5/8 5/16 5/16 5/16 5/16 3/8

12000 5/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 1-1/8 7/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-3/8 1-3/8 1-3/8 1-3/8 1-3/8 1-3/8 1-5/8 1-5/8 2-1/8 3/8 3/8 3/8 3/8 3/8

15000 5/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 1-1/8 1-1/8 7/8 1-1/8 1-1/8 1-1/8 1-3/8 1-1/8 1-3/8 1-3/8 1-3/8 1-5/8 1-3/8 1-5/8 1-5/8 2-1/8 2-1/8 3/8 3/8 3/8 3/8 1/2

18000 7/8 7/8 7/8 7/8 1-1/8 7/8 7/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-3/8 1-3/8 1-3/8 1-1/8 1-3/8 1-3/8 1-5/8 1-5/8 1-3/8 1-5/8 2-1/8 2-1/8 2-1/8 3/8 3/8 3/8 1/2 1/2

24000 7/8 7/8 1-1/8 1-1/8 1-1/8 7/8 1-1/8 1-1/8 1-1/8 1-3/8 1-1/8 1-3/8 1-3/8 1-3/8 1-5/8 1-3/8 1-5/8 1-5/8 1-5/8 2-1/8 1-5/8 1-5/8 2-1/8 2-1/8 2-1/8 3/8 3/8 1/2 1/2 1/2

30000 7/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-3/8 1-3/8 1-1/8 1-3/8 1-3/8 1-5/8 1-5/8 1-3/8 1-5/8 2-1/8 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8 2-5/8 2-5/8 1/2 1/2 1/2 1/2 1/2

36000 7/8 1-1/8 1-1/8 1-1/8 1-3/8 1-1/8 1-1/8 1-3/8 1-3/8 1-3/8 1-3/8 1-3/8 1-5/8 1-5/8 2-1/8 1-5/8 1-5/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-5/8 2-5/8 2-5/8 1/2 1/2 1/2 1/2 5/8

48000 1-1/8 1-1/8 1-1/8 1-3/8 1-3/8 1-1/8 1-3/8 1-3/8 1-5/8 1-5/8 1-3/8 1-5/8 1-5/8 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-5/8 2-1/8 2-5/8 2-5/8 2-5/8 3-1/8 1/2 1/2 1/2 5/8 5/8

54000 1-1/8 1-1/8 1-3/8 1-3/8 1-3/8 1-1/8 1-3/8 1-3/8 1-5/8 1-5/8 1-3/8 1-5/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-5/8 2-5/8 2-1/8 2-5/8 2-5/8 3-1/8 3-1/8 1/2 1/2 5/8 5/8 5/8

60000 1-1/8 1-3/8 1-3/8 1-3/8 1-5/8 1-3/8 1-3/8 1-5/8 1-5/8 1-5/8 1-5/8 1-5/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-5/8 2-5/8 2-1/8 2-5/8 2-5/8 3-1/8 3-1/8 1/2 1/2 5/8 5/8 5/8

66000 1-1/8 1-3/8 1-3/8 1-3/8 1-5/8 1-3/8 1-3/8 1-5/8 1-5/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-5/8 2-5/8 2-5/8 2-5/8 2-5/8 3-1/8 3-1/8 3-1/8 1/2 5/8 5/8 5/8 7/8

72000 1-1/8 1-3/8 1-3/8 1-5/8 1-5/8 1-3/8 1-5/8 1-5/8 1-5/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-5/8 2-1/8 2-1/8 2-5/8 2-5/8 2-5/8 2-5/8 2-5/8 3-1/8 3-1/8 3-5/8 1/2 5/8 5/8 5/8 7/8

78000 1-1/8 1-3/8 1-3/8 1-5/8 1-5/8 1-3/8 1-5/8 1-5/8 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-5/8 2-1/8 2-5/8 2-5/8 2-5/8 3-1/8 2-5/8 3-1/8 3-1/8 3-1/8 3-5/8 1/2 5/8 5/8 5/8 7/8

84000 1-1/8 1-3/8 1-5/8 1-5/8 1-5/8 1-3/8 1-5/8 1-5/8 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-5/8 2-1/8 2-5/8 2-5/8 2-5/8 3-1/8 2-5/8 3-1/8 3-1/8 3-5/8 3-5/8 1/2 5/8 5/8 7/8 7/8

90000 1-3/8 1-3/8 1-5/8 1-5/8 1-5/8 1-3/8 1-5/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-5/8 2-5/8 2-1/8 2-5/8 2-5/8 2-5/8 3-1/8 2-5/8 3-1/8 3-1/8 3-5/8 3-5/8 1/2 5/8 5/8 7/8 7/8

120000 1-3/8 1-5/8 1-5/8 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-5/8 2-5/8 2-5/8 2-5/8 2-5/8 3-1/8 3-1/8 3-5/8 3-1/8 3-1/8 3-5/8 3-5/8 4-1/8 5/8 7/8 7/8 7/8 7/8

150000 1-3/8 1-5/8 2-1/8 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-5/8 2-1/8 2-5/8 2-5/8 2-5/8 3-1/8 2-5/8 3-1/8 3-1/8 3-5/8 3-5/8 3-1/8 3-5/8 4-1/8 4-1/8 5-1/8 5/8 7/8 7/8 7/8 7/8

180000 1-5/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-5/8 2-5/8 2-1/8 2-5/8 2-5/8 3-1/8 3-1/8 2-5/8 3-1/8 3-5/8 3-5/8 4-1/8 3-5/8 3-5/8 4-1/8 5-1/8 5-1/8 7/8 7/8 7/8 7/8 1-1/8

210000 1-5/8 2-1/8 2-1/8 2-1/8 2-5/8 2-1/8 2-1/8 2-5/8 2-5/8 2-5/8 2-5/8 2-5/8 3-1/8 3-1/8 3-5/8 3-1/8 3-1/8 3-5/8 3-5/8 4-1/8 3-5/8 4-1/8 5-1/8 5-1/8 5-1/8 7/8 7/8 7/8 7/8 1-1/8

240000 2-1/8 2-1/8 2-1/8 2-5/8 2-5/8 2-1/8 2-5/8 2-5/8 2-5/8 3-1/8 2-5/8 3-1/8 3-1/8 3-1/8 3-5/8 3-1/8 3-5/8 3-5/8 4-1/8 4-1/8 3-5/8 4-1/8 5-1/8 5-1/8 5-1/8 7/8 7/8 7/8 1-1/8 1-1/8

300000 2-1/8 2-1/8 2-5/8 2-5/8 2-5/8 2-1/8 2-5/8 2-5/8 3-1/8 3-1/8 2-5/8 3-1/8 3-5/8 3-5/8 4-1/8 3-1/8 3-5/8 4-1/8 4-1/8 5-1/8 4-1/8 5-1/8 5-1/8 5-1/8 6-1/8 7/8 7/8 1-1/8 1-1/8 1-1/8

360000 2-1/8 2-5/8 2-5/8 2-5/8 3-1/8 2-5/8 2-5/8 3-1/8 3-1/8 3-5/8 3-1/8 3-1/8 3-5/8 3-5/8 4-1/8 3-5/8 4-1/8 4-1/8 5-1/8 5-1/8 4-1/8 5-1/8 5-1/8 6-1/8 6-1/8 7/8 1-1/8 1-1/8 1-1/8 1-3/8

480000 2-1/8 2-5/8 2-5/8 3-1/8 3-1/8 2-5/8 3-1/8 3-1/8 3-5/8 3-5/8 3-1/8 3-5/8 4-1/8 4-1/8 5-1/8 4-1/8 5-1/8 5-1/8 5-1/8 6-1/8 5-1/8 6-1/8 6-1/8 6-1/8 8-1/8 1-1/8 1-1/8 1-1/8 1-3/8 1-3/8

600000 2-5/8 3-1/8 3-1/8 3-1/8 3-5/8 3-1/8 3-1/8 3-5/8 3-5/8 4-1/8 3-5/8 4-1/8 4-1/8 5-1/8 5-1/8 4-1/8 5-1/8 5-1/8 6-1/8 6-1/8 5-1/8 6-1/8 8-1/8 8-1/8 8-1/8 1-1/8 1-1/8 1-3/8 1-3/8 1-3/8

Notes: – Line sizes are calculated at 100% system capacity – Suction lines sized based on a maximum total pressure drop equivalent to 2°F – Sizing is based on 65°F return gas at compressor with a liquid temperature of 100°F – Line sizes are O.D. using type `L’ copper tubing. – Follow proper piping practices to ensure proper oil return, including proper slopes, traps and supporting. – Double suction risers might be necessary with cylinder unloading. Consult factory if unsure.

B50-BCU-IM-20

– B2 –

20/04/22

REFRIGERANT LINE SIZING CHARTS

R404A R507

Capacity BTU/Hr.

+45°F SST Equivalent Length

R404A R507 Suction Line Size from Evaporator to Compressor R404A R507

+25°F SST Equivalent Length

+0°F SST Equivalent Length

-20°F SST Equivalent Length

-40°F SST Equivalent Length

Liquid Line Size
Receiver to TXV Equivalent Length

25′ 50′ 75′ 100′ 150′ 25′ 50′ 75′ 100′ 150′ 25′ 50′ 75′ 100′ 150′ 25′ 50′ 75 100′ 150′ 25′ 50′ 75′ 100′ 150′ 25′ 50′ 75′ 100′ 150′

2000 5/16 3/8 3/8 3/8 3/8 3/8 3/8 3/8 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 5/8 5/8 5/8 5/8 5/8 5/8 7/8 7/8 3/8 3/8 3/8 3/8 3/8

3000 5/16 3/8 3/8 3/8 1/2 3/8 3/8 1/2 1/2 1/2 1/2 1/2 5/8 5/8 5/8 1/2 5/8 5/8 7/8 7/8 5/8 7/8 7/8 7/8 7/8 3/8 3/8 3/8 3/8 3/8

4000 5/16 3/8 1/2 1/2 1/2 1/2 1/2 1/2 1/2 5/8 1/2 5/8 5/8 5/8 7/8 5/8 5/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 1-1/8 3/8 3/8 3/8 3/8 3/8

6000 1/2 1/2 1/2 1/2 5/8 1/2 1/2 5/8 5/8 5/8 5/8 5/8 7/8 7/8 7/8 5/8 7/8 7/8 7/8 7/8 7/8 7/8 1-1/8 1-1/8 1-1/8 3/8 3/8 3/8 3/8 3/8

9000 1/2 1/2 5/8 5/8 5/8 5/8 5/8 5/8 7/8 7/8 5/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 1-1/8 1-1/8 7/8 1-1/8 1-1/8 1-1/8 1-3/8 3/8 3/8 3/8 3/8 3/8

12000 1/5 5/8 5/8 5/8 7/8 5/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 1-1/8 7/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-3/8 1-3/8 1-3/8 3/8 3/8 3/8 3/8 3/8

15000 5/8 5/8 7/8 7/8 7/8 5/8 7/8 7/8 7/8 7/8 7/8 7/8 1-1/8 1-1/8 1-1/8 7/8 1-1/8 1-1/8 1-1/8 1-3/8 1/1/8 1-3/8 1-3/8 1-3/8 1-5/8 3/8 3/8 3/8 3/8 1/2

18000 5/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 1-1/8 7/8 7/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-3/8 1-3/8 1-1/8 1-3/8 1-3/8 1-5/8 1-5/8 3/8 1/2 1/2 1/2 1/2

24000 5/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 1-1/8 1-1/8 7/8 1-1/8 1-1/8 1-1/8 1-3/8 1-1/8 1-3/8 1-3/8 1-3/8 1-5/8 1-3/8 1-5/8 1-5/8 1-5/8 2-1/8 1/2 1/2 1/2 1/2 1/2

30000 7/8 7/8 7/8 7/8 1-1/8 7/8 7/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-3/8 1-3/8 1-3/8 1-1/8 1-3/8 1-3/8 1-5/8 1-5/8 1-3/8 1-5/8 1-5/8 2-1/8 2-1/8 1/2 1/2 1/2 1/2 1/2

36000 7/8 7/8 1-1/8 1-1/8 1-1/8 7/8 1-1/8 1-1/8 1-1/8 1-3/8 1-1/8 1-1/8 1-3/8 1-3/8 1-5/8 1-3/8 1-3/8 1-5/8 1-5/8 2-1/8 1-5/8 1-5/8 2-1/8 2-1/8 2-1/8 1/2 1/2 1/2 1/2 5/8

48000 7/8 1-1/8 1-1/8 1-1/8 1-/18 1-1/8 1-1/8 1-1/8 1-3/8 1-3/8 1-1/8 1-3/8 1-3/8 1-5/8 1-5/8 1-3/8 1-5/8 1-5/8 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-5/8 1/2 1/2 5/8 5/8 5/8

54000 7/8 1-1/8 1-1/8 1-1/8 1-3/8 1-1/8 1-1/8 1-3/8 1-3/8 1-3/8 1-3/8 1-3/8 1-5/8 1-5/8 1-5/8 1-3/8 1-5/8 2-1/8 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-5/8 1/2 1/2 5/8 5/8 5/8

60000 1-1/8 1-1/8 1-1/8 1-1/8 1-3/8 1-1/8 1-1/8 1-3/8 1-3/8 1-5/8 1-3/8 1-3/8 1-5/8 1-5/8 2-1/8 1-5/8 1-5/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-5/8 2-5/8 1/2 5/8 5/8 5/8 5/8

66000 1-1/8 1-1/8 1-1/8 1-3/8 1-3/8 1-1/8 1-3/8 1-3/8 1-3/8 1-5/8 1-3/8 1-5/8 1-5/8 1-5/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-5/8 2-5/8 2-5/8 1/2 5/8 5/8 5/8 7/8

72000 1-1/8 1-1/8 1-1/8 1-3/8 1-3/8 1-1/8 1-3/8 1-3/8 1-3/8 1-5/8 1-3/8 1-5/8 1-5/8 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-5/8 2-5/8 2-5/8 1/2 5/8 5/8 5/8 7/8

78000 1-1/8 1-1/8 1-3/8 1-3/8 1-3/8 1-1/8 1-3/8 1-3/8 1-5/8 1-5/8 1-3/8 1-5/8 1-5/8 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-5/8 2-1/8 2-1/8 2-5/8 2-5/8 3-1/8 1/2 5/8 5/8 7/8 7/8

84000 1-1/8 1-1/8 1-3/8 1-3/8 1-3/8 1-1/8 1-3/8 1-3/8 1-5/8 1-5/8 1-3/8 1-5/8 2-1/8 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-5/8 2-1/8 2-5/8 2-5/8 2-5/8 3-1/8 1/2 5/8 5/8 7/8 7/8

90000 1-3/8 1-3/8 1-3/8 1-3/8 1-5/8 1-3/8 1-3/8 1-5/8 1-5/8 1-5/8 1-3/8 1-5/8 2-1/8 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-5/8 2-1/8 2-5/8 2-5/8 2-5/8 3-1/8 5/8 5/8 7/8 7/8 7/8

120000 1-3/8 1-3/8 1-3/8 1-5/8 1-5/8 1-3/8 1-5/8 1-5/8 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-5/8 2-1/8 2-1/8 2-5/8 2-5/8 2-5/8 2-5/8 2-5/8 3-1/8 3-1/8 3-1/8 5/8 7/8 7/8 7/8 7/8

150000 1-5/8 1-5/8 1-5/8 2-1/8 2-1/8 1-3/8 1-5/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-5/8 2-5/8 2-1/8 2-5/8 2-5/8 2-5/8 3-1/8 2-5/8 3-1/8 3-1/8 3-1/8 3-5/8 5/8 7/8 7/8 7/8 7/8

180000 1-5/8 1-5/8 2-1/8 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-5/8 2-5/8 2-5/8 2-1/8 2-5/8 2-5/8 3-1/8 3-1/8 2-5/8 3-1/8 3-5/8 3-5/8 3-5/8 7/8 7/8 7/8 7/8 1/1/8

210000 1-5/8 2-1/8 2-1/8 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-5/8 2-1/8 2-5/8 2-5/8 2-5/8 3-1/8 2-5/8 2-5/8 3-1/8 3-1/8 3-5/8 3-1/8 3-1/8 3-5/8 3-5/8 4-1/8 7/8 7/8 7/8 1-1/8 1-1/8

240000 1-5/8 2-1/8 2-1/8 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-5/8 2-1/8 2-5/8 2-5/8 2-5/8 3-1/8 2-5/8 3-1/8 3-1/8 3-1/8 3-5/8 3-1/8 3-5/8 3-5/8 4-1/8 4-1/8 7/8 7/8 1-1/8 1/1/8 1/1/8

300000 2-1/8 2-1/8 2-1/8 2-5/8 2-5/8 2-1/8 2-1/8 2-5/8 2-5/8 2-5/8 2-1/8 2-5/8 3-1/8 3-1/8 3-1/8 2-5/8 3-1/8 3-5/8 3-5/8 3-5/8 3-1/8 3-5/8 4-1/8 4-1/8 5-1/8 7/8 1-1/8 1-1/8 1-1/8 1-1/8

360000 2-1/8 2-1/8 2-5/8 2-5/8 3-1/8 2-1/8 2-5/8 2-5/8 2-5/8 3-1/8 2-5/8 2-5/8 3-1/8 3-1/8 3-5/8 3-1/8 3-1/8 3-5/8 3-5/8 4-1/8 3-5/8 4-1/8 4-1/8 5-1/8 5-1/8 7/8 1-1/8 1-1/8 1-1/8 1-3/8

480000 2-1/8 2-1/8 2-5/8 2-5/8 2-5/8 2-1/8 2-5/8 2-5/8 3-1/8 3-1/8 2-5/8 3-1/8 3-5/8 3-5/8 3-5/8 3-1/8 3-5/8 4-1/8 4-1/8 5-1/8 4-1/8 5-1/8 5-1/8 5-1/8 6-1/8 1-1/8 1-1/8 1-3/8 1-3/8 1-3/8

600000 2-1/8 2/5/8 2-5/8 2-5/8 3-1/8 2-5/8 2-5/8 3-1/8 3-1/8 3/5/8 3-1/8 3-5/8 3-5/8 3-5/8 4-1/8 3-5/8 4-1/8 4-1/8 5-1/8 5-1/8 4-1/8 5-1/8 5-1/8 6-1/8 6-1/8 1-1/8 1-3/8 1-3/8 1-3/8 1-3/8

Notes: – Line sizes are calculated at 100% system capacity – Suction lines sized based on a maximum total pressure drop equivalent to 2°F – Sizing is based on 65°F return gas at compressor with a liquid temperature of 100°F – Line sizes are O.D. using type `L’ copper tubing. – Follow proper piping practices to ensure proper oil return, including proper slopes, traps and supporting. – Double suction risers might be necessary with cylinder unloading. Consult factory if unsure.

B50-BCU-IM-20

– B3 –

20/04/22

REFRIGERANT LINE SIZING CHARTS
R407A R407C R4 0 7 F

Capacity BTU/Hr.

R407A
+45°F SST Equivalent Length

R407C R4 0 7 F Suction Line Size from Evaporator to Compressor R407A R407C R4 0 7 F

+25°F SST Equivalent Length

+0°F SST Equivalent Length

-20°F SST Equivalent Length

-40°F SST Equivalent Length

Liquid Line Size
Receiver to TXV Equivalent Length

25′ 50′ 75′ 100′ 150′ 25′ 50′ 75′ 100′ 150′ 25′ 50′ 75′ 100′ 150′ 25′ 50′ 75 100′ 150′ 25′ 50′ 75′ 100′ 150′ 25′ 50′ 75′ 100′ 150′

2000 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 1/2 1/2 3/8 1/2 1/2 1/2 5/8 1/2 1/2 5/8 5/8 5/8 5/8 5/8 7/8 7/8 7/8 3/8 3/8 3/8 3/8 3/8

3000 3/8 1/2 1/2 1/2 1/2 3/8 1/2 1/2 1/2 1/2 1/2 1/2 5/8 5/8 5/8 5/8 5/8 5/8 7/8 7/8 5/8 7/8 7/8 7/8 7/8 3/8 3/8 3/8 3/8 3/8

4000 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 5/8 1/2 5/8 5/8 5/8 7/8 5/8 5/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 1-1/8 3/8 3/8 3/8 3/8 3/8

6000 1/2 1/2 1/2 1/2 5/8 1/2 1/2 5/8 5/8 5/8 5/8 5/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 1-1/8 1-1/8 1-1/8 3/8 3/8 3/8 3/8 3/8

9000 1/2 1/2 5/8 5/8 5/8 1/2 5/8 5/8 7/8 7/8 5/8 7/8 7/8 7/8 7/8 7/8 7/8 1-1/8 1-1/8 1-1/8 7/8 1-1/8 1-1/8 1-3/8 1-3/8 3/8 3/8 3/8 3/8 3/8

12000 1/2 5/8 5/8 5/8 7/8 5/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 1-1/8 7/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-3/8 1-3/8 1-3/8 3/8 3/8 3/8 3/8 3/8

15000 5/8 5/8 7/8 7/8 7/8 5/8 7/8 7/8 7/8 7/8 7/8 7/8 1-1/8 1-1/8 1-1/8 7/8 1-1/8 1-1/8 1-1/8 1-3/8 1-1/8 1-1/8 1-3/8 1-3/8 1-5/8 3/8 3/8 3/8 3/8 3/8

18000 5/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 1-1/8 7/8 7/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-3/8 1-3/8 1-3/8 1-1/8 1-3/8 1-3/8 1-5/8 1-5/8 3/8 3/8 3/8 3/8 3/8

24000 5/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 1-1/8 1-1/8 7/8 1-1/8 1-1/8 1-1/8 1-3/8 1-1/8 1-3/8 1-3/8 1-3/8 1-5/8 1-3/8 1-5/8 1-5/8 1-5/8 2-1/8 3/8 3/8 3/8 1/2 1/2

30000 7/8 7/8 7/8 7/8 1-1/8 7/8 7/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-3/8 1-3/8 1-3/8 1-1/8 1-3/8 1-3/8 1-5/8 1-5/8 1-3/8 1-5/8 2-1/8 2-1/8 2-1/8 3/8 3/8 1/2 1/2 1/2

36000 7/8 7/8 7/8 1-1/8 1-1/8 7/8 1-1/8 1-1/8 1-1/8 1-3/8 1-1/8 1-1/8 1-3/8 1-3/8 1-5/8 1-3/8 1-3/8 1-5/8 1-5/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-1/8 3/8 1/2 1/2 1/2 1/2

48000 7/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-3/8 1-3/8 1-1/8 1-3/8 1-3/8 1-5/8 1-5/8 1-3/8 1-5/8 1-5/8 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-5/8 1/2 1/2 1/2 5/8 5/8

54000 7/8 1-1/8 1-1/8 1-1/8 1-3/8 1-1/8 1-1/8 1-3/8 1-3/8 1-3/8 1-3/8 1-3/8 1-5/8 1-5/8 1-5/8 1-3/8 1-5/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-5/8 2-5/8 1/2 1/2 1/2 5/8 5/8

60000 7/8 1-1/8 1-1/8 1-1/8 1-3/8 1-1/8 1-1/8 1-1/8 1-3/8 1-3/8 1-3/8 1-3/8 1-5/8 1-5/8 2-1/8 1-5/8 1-5/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-5/8 2-5/8 1/2 1/2 1/2 5/8 5/8

66000 7/8 1-1/8 1-1/8 1-3/8 1-3/8 1-1/8 1-1/8 1-3/8 1-3/8 1-5/8 1-3/8 1-5/8 1-5/8 1-5/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-5/8 2-5/8 2-5/8 1/2 1/2 5/8 5/8 5/8

72000 1-1/8 1-1/8 1/1/8 1-3/8 1-3/8 1-1/8 1-3/8 1-3/8 1-3/8 1-5/8 1-3/8 1-5/8 1-5/8 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-5/8 2-1/8 2-1/8 2-5/8 2-5/8 2-5/8 1/2 1/2 5/8 5/8 5/8

78000 1-1/8 1-1/8 1-3/8 1-3/8 1-3/8 1-1/8 1-3/8 1-3/8 1-5/8 1-5/8 1-3/8 1-5/8 1-5/8 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-5/8 2-1/8 2-5/8 2-5/8 2-5/8 3-1/8 1/2 1/2 5/8 5/8 5/8

84000 1-1/8 1-1/8 1-3/8 1-3/8 1-3/8 1-2/8 1-3/8 1-3/8 1-5/8 1-5/8 1-3/8 1-5/8 2-1/8 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-5/8 2-1/8 2-5/8 2-5/8 2-5/8 3-1/8 1/2 5/8 5/8 5/8 7/8

90000 1-1/8 1-1/8 1-3/8 1-3/8 1-5/8 1-1/8 1-3/8 1-5/8 1-5/8 1-5/8 1-3/8 1-5/8 2-1/8 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8 2-5/8 2-5/8 2-1/8 2-5/8 2-5/8 2-5/8 3-1/8 1/2 5/8 5/8 5/8 7/8

120000 1-1/8 1-3/8 1-3/8 1-5/8 1-5/8 1-3/8 1-5/8 1-5/8 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-5/8 2-1/8 2-1/8 2-5/8 2-5/8 2-5/8 2-5/8 2-5/8 3-1/8 3-1/8 3-5/8 5/8 5/8 7/8 7/8 7/8

150000 1-3/8 1-3/8 1-5/8 1-5/8 2-1/8 1-3/8 1-5/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-5/8 2-5/8 2-1/8 2-5/8 2-5/8 2-5/8 3-1/8 2-5/8 3-1/8 3-1/8 3-5/8 3-5/8 5/8 7/8 7/8 7/8 7/8

180000 1-3/8 1-5/8 1-5/8 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-5/8 2-5/8 2-5/8 2-1/8 2-5/8 2-5/8 3-1/8 3-1/8 2-5/8 3-1/8 3-5/8 3-5/8 4-1/8 5/8 7/8 7/8 7/8 7/8

210000 1-3/8 1-5/8 2-1/8 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-5/8 2-1/8 2-5/8 2-5/8 2-5/8 3-1/8 2-5/8 2-5/8 3-1/8 3-1/8 3-5/8 3-1/8 3-1/8 3-5/8 3-5/8 4-1/8 5/8 7/8 7/8 7/8 7/8

240000 1-5/8 1-5/8 2-1/8 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-5/8 2-1/8 2-5/8 2-5/8 2-5/8 3-1/8 2-5/8 3-1/8 3-1/8 3-1/8 3-5/8 3-1/8 3-5/8 3-5/8 4-1/8 4-1/8 7/8 7/8 7/8 7/8 1-1/8

300000 1-5/8 2-1/8 2-1/8 2-1/8 2-5/8 2-1/8 2-1/8 2-5/8 2-5/8 2-5/8 2-1/8 2-5/8 3-1/8 3-1/8 3-1/8 2-5/8 3-1/8 3-5/8 3-3/8 4-1/8 3-1/8 3-5/8 4-1/8 4-1/8 5-1/8 7/8 7/8 7/8 1-1/8 1-1/8

360000 1-5/8 2-1/8 2-1/8 2-1/8 2-5/8 2-1/8 2-5/8 2-5/8 2-5/8 3-1/8 2-5/8 2-5/8 3-1/8 3-1/8 3-5/8 3-1/8 3-1/8 3-5/8 3-5/8 4-1/8 3-5/8 4-1/8 5-1/8 5-1/8 5-1/8 7/8 7/8 1-1/8 1-1/8 1-1/8

480000 2-1/8 2-1/8 2-5/8 2-5/8 2-5/8 2-1/8 2-5/8 2-5/8 3-1/8 3-1/8 2-5/8 3-1/8 3-5/8 3-5/8 3-5/8 3-1/8 3-5/8 4-1/8 4-1/8 5-1/8 4-1/8 5-1/8 5-1/8 5-1/8 6-1/8 7/8 1-1/8 1-1/8 1-1/8 1-3/8

600000 2-1/8 2-1/8 2-5/8 2-5/8 3-1/8 2-5/8 2-5/8 3-1/8 3-1/8 3-5/8 3-5/8 3-5/8 3-5/8 3-5/8 4-1/8 3-5/8 4-1/8 4-1/8 5-1/8 5-1/8 4-1/8 5-1/8 5-1/8 6-1/8 6-1/8 1-1/8 1-1/8 1-1/8 1-3/8 1-3/8

Notes: – Line sizes are calculated at 100% system capacity – Suction lines sized based on a maximum total pressure drop equivalent to 2°F – Sizing is based on 65°F return gas at compressor with a liquid temperature of 100°F – Line sizes are O.D. using type `L’ copper tubing. – Follow proper piping practices to ensure proper oil return, including proper slopes, traps and supporting. – Double suction risers might be necessary with cylinder unloading. Consult factory if unsure.

B50-BCU-IM-20

– B4 –

20/04/22

REFRIGERANT LINE SIZING CHARTS
R448A

Capacity BTU/Hr.

+45°F SST Equivalent Length

R448A

Suction Line Size from Evaporator to Compressor R 4 4 8 A

+25°F SST Equivalent Length

+0°F SST Equivalent Length

-20°F SST Equivalent Length

-40°F SST Equivalent Length

Liquid Line Size
Receiver to TXV Equivalent Length

25′ 50′ 75′ 100′ 150′ 25′ 50′ 75′ 100′ 150′ 25′ 50′ 75′ 100′ 150′ 25′ 50′ 75 100′ 150′ 25′ 50′ 75′ 100′ 150′ 25′ 50′ 75′ 100′ 150′

2000 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 5/8 5/8 5/8 5/8 5/8 5/8 7/8 7/8 3/8 3/8 3/8 3/8 3/8

3000 3/8 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 5/8 5/8 1/2 5/8 5/8 5/8 7/8 5/8 7/8 7/8 7/8 7/8 3/8 3/8 3/8 3/8 3/8

4000 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 5/8 1/2 5/8 5/8 5/8 7/8 7/8 5/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 1-1/8 3/8 3/8 3/8 3/8 3/8

6000 1/2 1/2 1/2 1/2 5/8 1/2 1/2 5/8 5/8 5/8 5/8 5/8 7/8 7/8 7/8 5/8 7/8 7/8 7/8 7/8 7/8 7/8 1-1/8 1-1/8 1-1/8 3/8 3/8 3/8 3/8 3/8

9000 1/2 1/2 5/8 5/8 5/8 1/2 5/8 5/8 7/8 7/8 5/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 1-1/8 1-1/8 7/8 1-1/8 1-1/8 1-1/8 1-3/8 3/8 3/8 3/8 3/8 3/8

12000 1/2 5/8 5/8 5/8 7/8 5/8 5/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 1-1/8 7/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-3/8 1-3/8 1-3/8 3/8 3/8 3/8 3/8 3/8

15000 5/8 5/8 7/8 7/8 7/8 5/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 1-1/8 1-1/8 7/8 1-1/8 1-1/8 1-1/8 1-3/8 1-1/8 1-3/8 1-3/8 1-3/8 1-5/8 3/8 3/8 3/8 3/8 3/8

18000 5/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 1-1/8 7/8 7/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-3/8 1-3/8 1-1/8 1-3/8 1-3/8 1-5/8 1-5/8 3/8 3/8 3/8 3/8 1/2

24000 5/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 1-1/8 1-1/8 7/8 1-1/8 1-1/8 1-1/8 1-3/8 1-1/8 1-3/8 1-3/8 1-3/8 1-5/8 1-3/8 1-3/8 1-5/8 1-5/8 2-1/8 3/8 3/8 3/8 3/8 1/2

30000 7/8 7/8 7/8 7/8 1-1/8 7/8 7/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-3/8 1-3/8 1-1/8 1-3/8 1-3/8 1-5/8 1-5/8 1-3/8 1-5/8 1-5/8 2-1/8 2-1/8 3/8 3/8 1/2 1/2 1/2

36000 7/8 7/8 7/8 1-1/8 1-1/8 7/8 1-1/8 1-1/8 1-1/8 1-3/8 1-1/8 1-1/8 1-3/8 1-3/8 1-3/8 1-3/8 1-3/8 1-5/8 1-5/8 2-1/8 1-5/8 1-5/8 2-1/8 2-1/8 2-1/8 3/8 1/2 1/2 1/2 1/2

48000 7/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-3/8 1-3/8 1-1/8 1-3/8 1-3/8 1-5/8 1-5/8 1-3/8 1-5/8 1-5/8 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-5/8 3/8 1/2 1/2 1/2 5/8

54000 7/8 1-1/8 1-1/8 1-1/8 1-3/8 1-1/8 1-1/8 1-3/8 1-3/8 1-3/8 1-1/8 1-3/8 1-5/8 1-5/8 1-5/8 1-3/8 1-5/8 2-1/8 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-5/8 1/2 1/2 1/2 1/2 5/8

60000 7/8 1-1/8 1-1/8 1-1/8 1-3/8 1-1/8 1-1/8 1-3/8 1-3/8 1-3/8 1-3/8 1-3/8 1-5/8 1-5/8 2-1/8 1-3/8 1-5/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-5/8 2-5/8 1/2 1/2 1/2 5/8 5/8

66000 7/8 1-1/8 1-1/8 1-3/8 1-3/8 1-1/8 1-3/8 1-3/8 1-3/8 1-5/8 1-3/8 1-3/8 1-5/8 1-5/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-5/8 2-5/8 2-5/8 1/2 1/2 5/8 5/8 5/8

72000 1-1/8 1-1/8 1-1/8 1-3/8 1-3/8 1-1/8 1-3/8 1-3/8 1-3/8 1-5/8 1-3/8 1-5/8 1-5/8 1-5/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-5/8 2-5/8 2-5/8 1/2 1/2 5/8 5/8 5/8

78000 7/8 1-1/8 1-3/8 1-3/8 1-3/8 1-1/8 1-3/8 1-3/8 1-5/8 1-5/8 1-3/8 1-5/8 1-5/8 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-5/8 2-1/8 2-1/8 2-5/8 2-5/8 3-1/8 1/2 1/2 5/8 5/8 5/8

84000 1-1/8 1-1/8 1-3/8 1-3/8 1-3/8 1-1/8 1-3/8 1-3/8 1-5/8 1-5/8 1-3/8 1-5/8 1-5/8 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-5/8 2-1/8 2-5/8 2-5/8 2-5/8 3-1/8 1/2 5/8 5/8 5/8 7/8

90000 1-1/8 1-1/8 1-3/8 1-3/8 1-3/8 1-1/8 1-3/8 1-3/8 1-5/8 1-5/8 1-3/8 1-5/8 2-1/8 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-5/8 2-1/8 2-5/8 2-5/8 2-5/8 3-1/8 5/8 5/8 5/8 5/8 7/8

120000 1-1/8 1-3/8 1-3/8 1-5/8 1-5/8 1-3/8 1-5/8 1-5/8 1-5/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-5/8 2-5/8 2-5/8 2-5/8 2-5/8 3-1/8 3-1/8 3-1/8 5/8 5/8 5/8 7/8 7/8

150000 1-3/8 1-3/8 1-5/8 1-5/8 2-1/8 1-3/8 1-5/8 2-1/8 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-5/8 2-1/8 2-5/8 2-5/8 2-5/8 3-1/8 2-5/8 3-1/8 3-1/8 3-1/8 3-5/8 5/8 7/8 7/8 7/8 7/8

180000 1-3/8 1-5/8 1-5/8 1-5/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-5/8 2-5/8 2-5/8 2-1/8 2-5/8 2-5/8 3-1/8 3-1/8 2-5/8 3-1/8 3-1/8 3-5/8 3-5/8 5/8 7/8 7/8 7/8 7/8

210000 1-3/8 1-5/8 1-5/8 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-5/8 2-1/8 2-1/8 2-5/8 2-5/8 2-5/8 2-5/8 2-5/8 3-1/8 3-1/8 3-1/8 3-1/8 3-1/8 3-5/8 3-5/8 4-1/8 5/8 7/8 7/8 7/8 7/8

240000 1-5/8 1-5/8 2-1/8 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-5/8 2-1/8 2-5/8 2-5/8 2-5/8 3-1/8 2-5/8 3-1/8 3-1/8 3-1/8 3-5/8 3-1/8 3-5/8 3-5/8 4-1/8 4-1/8 7/8 7/8 7/8 7/8 1-1/8

300000 1-5/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-5/8 2-5/8 2-5/8 2-1/8 2-5/8 2-5/8 3-1/8 3-1/8 2-5/8 3-1/8 3-1/8 3-5/8 3-5/8 3-1/8 3-5/8 1-1/8 4-1/8 5-1/8 7/8 7/8 7/8 1-1/8 1-1/8

360000 1-5/8 2-1/8 2-1/8 2-1/8 2-5/8 2-1/8 2-1/8 2-5/8 2-5/8 2-5/8 2-5/8 2-5/8 3-1/8 3-1/8 3-5/8 3-1/8 3-1/8 3-5/8 3-5/8 4-1/8 3-5/8 4-1/8 4-1/8 5-1/8 5-1/8 7/8 1-1/8 1-1/8 1-1/8 1-1/8

480000 2-1/8 2-1/8 2-5/8 2-5/8 2-5/8 2-1/8 2-5/8 2-5/8 3-1/8 3-1/8 2-5/8 3-1/8 3-1/8 3-5/8 3-5/8 3-1/8 3-5/8 4-1/8 4-1/8 5-1/8 3-5/8 5-1/8 5-1/8 5-1/8 6-1/8 7/8 1-1/8 1-1/8 1-3/8 1-3/8

600000 2-5/8 2-5/8 3-1/8 3-1/8 3-5/8 2-5/8 2-5/8 3-1/8 3-1/8 3-5/8 3-1/8 3-1/8 3-5/8 3-5/8 4-1/8 3-5/8 4-1/8 4-1/8 5-1/8 5-1/8 4-1/8 5-1/8 5-1/8 6-1/8 6-1/8 1-1/8 1-1/8 1-3/8 1-3/8 1-3/8

Notes: – Line sizes are calculated at 100% system capacity – Suction lines sized based on a maximum total pressure drop equivalent to 2°F – Sizing is based on 65°F return gas at compressor with a liquid temperature of 100°F – Line sizes are O.D. using type `L’ copper tubing. – Follow proper piping practices to ensure proper oil return, including proper slopes, traps and supporting. – Double suction risers might be necessary with cylinder unloading. Consult factory if unsure.

B50-BCU-IM-20

– B5 –

20/04/22

REFRIGERANT LINE SIZING CHARTS

R22

Capacity BTU/Hr.

+45°F SST Equivalent Length

R22 Suction Line Size from Evaporator to Compressor R22

+25°F SST Equivalent Length

+0°F SST Equivalent Length

-20°F SST Equivalent Length

-40°F SST Equivalent Length

Liquid Line Size
Receiver to TXV Equivalent Length

25′ 50′ 75′ 100′ 150′ 25′ 50′ 75′ 100′ 150′ 25′ 50′ 75′ 100′ 150′ 25′ 50′ 75 100′ 150′ 25′ 50′ 75′ 100′ 150′ 25′ 50′ 75′ 100′ 150′

2000 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 1/2 1/2 3/8 1/2 1/2 1/2 1/2 1/2 1/2 1/2 5/8 5/8 1/2 5/8 5/8 5/8 7/8 3/8 3/8 3/8 3/8 3/8

3000 3/8 3/8 1/2 1/2 1/2 3/8 1/2 1/2 1/2 1/2 1/2 1/2 1/2 5/8 5/8 1/2 5/8 5/8 5/8 7/8 5/8 5/8 7/8 7/8 7/8 3/8 3/8 3/8 3/8 3/8

4000 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 5/8 1/2 1/2 5/8 5/8 5/8 5/8 5/8 7/8 7/8 7/8 5/8 7/8 7/8 7/8 7/8 3/8 3/8 3/8 3/8 3/8

6000 1/2 1/2 1/2 1/2 5/8 1/2 1/2 5/8 5/8 5/8 1/2 5/8 5/8 7/8 7/8 5/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 1-1/8 1-1/8 3/8 3/8 3/8 3/8 3/8

9000 1/2 1/2 1/2 5/8 5/8 1/2 5/8 5/8 7/8 7/8 5/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 1-1/8 1-1/8 7/8 1-1/8 1-1/8 1-1/8 1-3/8 3/8 3/8 3/8 3/8 3/8

12000 1/2 5/8 5/8 5/8 7/8 5/8 5/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 1-1/8 7/8 7/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-3/8 1-3/8 3/8 3/8 3/8 3/8 3/8

15000 5/8 5/8 7/8 7/8 7/8 5/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 1-1/8 1-1/8 7/8 1-1/8 1-1/8 1-1/8 1-3/8 1-1/8 1-1/8 1-3/8 1-3/8 1-3/8 3/8 3/8 3/8 3/8 3/8

18000 5/8 5/8 7/8 7/8 7/8 5/8 7/8 7/8 7/8 7/8 7/8 7/8 1-1/8 1-1/8 1-1/8 7/8 1-1/8 1-1/8 1-1/8 1-3/8 1-1/8 1-3/8 1-3/8 1-3/8 1-5/8 3/8 3/8 3/8 3/8 3/8

24000 5/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 1-1/8 1-1/8 7/8 1-1/8 1-1/8 1-1/8 1-3/8 1-1/8 1-1/8 1-3/8 1-3/8 1-3/8 1-3/8 1-3/8 1-5/8 1-5/8 1-5/8 3/8 3/8 2/8 1/2 1/2

30000 7/8 7/8 7/8 7/8 1-1/8 7/8 7/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-3/8 1-3/8 1-1/8 1-3/8 1-3/8 1-3/8 1-5/8 1-3/8 1-5/8 1-5/8 1-5/8 2-1/8 1/2 1/2 1/2 1/2 1/2

36000 7/8 7/8 7/8 1-1/8 1-1/8 7/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-3/8 1-3/8 1-3/8 1-1/8 1-3/8 1-3/8 1-5/8 1-5/8 1-3/8 1-5/8 1-5/8 2-1/8 2-1/8 1/2 1/2 1/2 1/2 1/2

48000 7/8 1-1/8 1-1/8 1-1/8 1-1/8 7/8 1-1/8 1-1/8 1-3/8 1-3/8 1-1/8 1-3/8 1-3/8 1-3/8 1-5/8 1-3/8 1-5/8 1-5/8 1-5/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-1/8 1/2 1/2 1/2 1/2 5/8

54000 7/8 1-1/8 1-1/8 1-1/8 1-3/8 1-1/8 1-1/8 1-1/8 1-3/8 1-3/8 1-1/8 1-3/8 1-3/8 1-5/8 1-5/8 1-3/8 1-3/8 1-5/8 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-5/8 1/2 1/2 1/2 1/2 5/8

60000 7/8 1-1/8 1-1/8 1-1/8 1-3/8 1-1/8 1-1/8 1-3/8 1-3/8 1-3/8 1-1/8 1-3/8 1-5/8 1-5/8 1-5/8 1-3/8 1-5/8 2-1/8 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-5/8 1/2 1/2 1/2 5/8 5/8

66000 1-1/8 1-1/8 1-1/8 1-1/8 1-3/8 1-1/8 1-1/8 1-3/8 1-3/8 1-5/8 1-3/8 1-3/8 1-5/8 1-5/8 2-1/8 1-3/8 1-5/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-5/8 2-5/8 1/2 1/2 1/2 5/8 5/8

72000 1-1/8 1-1/8 1-1/8 1-3/8 1-3/8 1-1/8 1-3/8 1-3/8 1-3/8 1-5/8 1-3/8 1-3/8 1-5/8 1-5/8 2-1/8 1-5/8 1-5/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-5/8 2-5/8 1/2 1/2 5/8 5/8 5/8

78000 1-1/8 1-1/8 1-3/8 1-3/8 1-3/8 1-1/8 1-3/8 1-3/8 1-3/8 1-5/8 1-3/8 1-5/8 1-5/8 1-5/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-5/8 2-5/8 2-5/8 1/2 1/2 5/8 5/8 5/8

84000 1-1/8 1-1/8 1-3/8 1-3/8 1-3/8 1-1/8 1-3/8 1-3/8 1-5/8 1-5/8 1-3/8 1-5/8 1-5/8 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-5/8 2-5/8 2-5/8 1/2 5/8 5/8 5/8 5/8

90000 1-1/8 1-1/8 1-3/8 1-3/8 1-3/8 1-1/8 1-3/8 1-3/8 1-5/8 1-5/8 1-3/8 1-5/8 1-5/8 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-5/8 2-1/8 2-1/8 2-5/8 2-5/8 2-5/8 1/2 5/8 5/8 5/8 7/8

120000 1-1/8 1-3/8 1-3/8 1-5/8 1-5/8 1-3/8 1-5/8 1-5/8 1-5/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-5/8 2-5/8 2-1/8 2-5/8 2-5/8 3-1/8 3-1/8 1/2 5/8 5/8 7/8 7/8

150000 1-3/8 1-3/8 1-5/8 1-5/8 2-1/8 1-3/8 1-5/8 2-1/8 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-5/8 2-1/8 2-1/8 2-5/8 2-5/8 2-5/8 2-5/8 2-5/8 3-1/8 3-1/8 3-5/8 5/8 5/8 7/8 7/8 7/8

180000 1-3/8 1-5/8 1-5/8 1-5/8 2-1/8 1-5/8 1-5/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-5/8 2-5/8 2-1/8 2-5/8 2-5/8 2-5/8 3-1/8 2-5/8 3-1/8 3-1/8 3-1/8 3-5/8 5/8 7/8 7/8 7/8 7/8

210000 1-3/8 1-5/8 1-5/8 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-5/8 2-5/8 2-5/8 2-1/8 2-5/8 2-5/8 3-1/8 3-1/8 2-5/8 3-1/8 3-1/8 3-5/8 3-5/8 5/8 7/8 7/8 7/8 7/8

240000 1-3/8 1-5/8 2-1/8 2-1/8 2-1/8 1-5/8 2-1/8 2-1/8 2-1/8 2-5/8 2-1/8 2-5/8 2-5/8 2-5/8 3-1/8 2-5/8 2-5/8 3-1/8 3-1/8 3-5/8 2-5/8 3-1/8 3-5/8 3-5/8 4-1/8 7/8 7/8 7/8 7/8 1-1/8

300000 1-5/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-1/8 2-5/8 2-5/8 2-1/8 2-5/8 2-5/8 3-1/8 3-1/8 2-5/8 3-1/8 3-1/8 3-5/8 3-5/8 3-1/8 3-5/8 3-5/8 4-1/8 4-1/8 7/8 7/8 7/8 1-1/8 1-1/8

360000 1-5/8 2-1/8 2-1/8 2-1/8 2-5/8 2-1/8 2-1/8 2-5/8 2-5/8 2-5/8 2-5/8 2-5/8 3-1/8 3-1/8 3-1/8 2-5/8 3-1/8 3-5/8 3-5/8 4-1/8 3-1/8 3-5/8 4-1/8 4-1/8 5-1/8 7/8 7/8 1-1/8 1-1/8 1-1/8

480000 2-1/8 2-1/8 2-5/8 2-5/8 2-5/8 2-1/8 2-5/8 2-5/8 3-1/8 3-1/8 2-5/8 3-1/8 3-1/8 3-5/8 3-5/8 3-1/8 3-5/8 3-5/8 4-1/8 4-1/8 3-5/8 4-1/8 5-1/8 5-1/8 5-1/8 7/8 1-1/8 1-1/8 1-1/8 1-3/8

600000 2-1/8 2-5/8 2/5/8 2-5/8 3-1/8 2-5/8 2-5/8 3-1/8 3-1/8 3-1/8 2-5/8 3-1/8 3-5/8 3-5/8 4-1/8 3-1/8 3-5/8 4-1/8 4-1/8 5-1/8 4-1/8 5-1/8 5-1/8 5-1/8 6-1/8 1-1/8 1-1/8 1-1/8 1-3/8 1-3/8

Notes: – Line sizes are calculated at 100% system capacity – Suction lines sized based on a maximum total pressure drop equivalent to 2°F – Sizing is based on 65°F return gas at compressor with a liquid temperature of 100°F – Line sizes are O.D. using type `L’ copper tubing. – Follow proper piping practices to ensure proper oil return, including proper slopes, traps and supporting. – Double suction risers might be necessary with cylinder unloading. Consult factory if unsure.

B50-BCU-IM-20

– B6 –

20/04/22

Appendix C: Equipment Start-Up Sheets

B50-BCU-IM-20

– C1 –

20/04/22

Company/Location:
Condensing Unit Model: Evaporator Unit Model: Compressor model number Original System start-up date: Refrigerant Type : System evacuation; # of times: Expansion valve – Model Number:

Condensing Unit Serial:

Evaporator Unit Serial:

Compressor serial number

Today’s Date:

Total Charge:

LBS

Final micron:

ALL READINGS SHOULD BE MADE WITH PROPERLY CALIBRATED MEASURING EQUIPMENT ALL REQUIRED INFORMATION MUST BE SUPPLIED FOR AN ACCURATE DIAGNOSIS

System Conditions (Record after system has been running for a minimum of 4 hours or when lowest possible temperature has been reached)

Designed Box Temperature: Operating Box Temperature: Thermostat Setting: Cut- In Thermostat Setting: Cut-Out Thermostat Differential Setting: Ambient Temperature Around Box Exterior: Ambient Temperature @ Condensing Unit: Discharge Pressure: Discharge Temperature @ Service Valve: Suction Pressure @ Service Valve: Suction Line Temperature @ Service Valve: Condensate Line Temperature: Liquid Line Temp Leaving Receiver: Liquid Line Temp Leaving Condensing Unit: Liquid Line Temp Entering TXV: Suction Pressure Leaving Evaporator: Suction Line Temp @ TXV Bulb: Evaporator Superheat: Compressor Superheat: CPR Setting: Pressure upstream of CPR: Pressure downstream of CPR: Oil Pressure: Oil Level in Compressor Sightglass :
(Also, make note if bubbles are seen)

ºF ºF ºF ºF ºF ºF Show different temperatures if required and note on ºF drawing. PSIG ºF 6″ away from discharge valve. PSIG ºF 6″ away from suction service valve. ºF Line between the condenser and receiver. ºF ºF ºF PSIG If available by schrader access. ºF ºF ºF PSIG If applicable. PSIG If applicable. PSIG If applicable. PSIG 1/4, 1/2, 3/4 During refrigeration.
1/4, 1/2, 3/4 During pump down. 1/4, 1/2, 3/4 During start-up after defrost.

Air Temperature Entering Evaporator: Supply Air Temperature Leaving Evaporator:
B50-BCU-IM-20

ºF ºF
– C2 –

20/04/22

Water Cooled Condenser GPM: PSIG: Pres-Drop: Water Valve Size: Water Valve Model:

Water Inlet: Water Outlet: Closed Loop: City Water:

Verify Inlet / Outlet Water Connection:

Electrical Data (Record while system is running at conditions on page one (C1))

Condensing Unit Condensing unit electrical: Voltage at compressor terminals: Amperage at compressor:

Volts L1-L2 L1

Phase L2-L3 L2

Evaporator Unit Evaporator unit electrical: Voltage at motor terminals: Amperage at motor:
Evaporator Defrost Settings Defrost Settings – Number per day Defrost Termination : Fan Delay Setting:

Volts L1-L2 L1
ºF ºF

Phase L2-L3 L2

HZ L1-L3 L3
HZ L1-L3 L3

SYSTEM LAYOUT

In the space below, provide piping schematic showing details on pipe size, line run length and P-trap locations

Suction Line Size OD :

Liquid Line Size OD:

Suction Riser Size OD:

B50-BCU-IM-20

– C3 –

20/04/22

EQUIPMENT AND BOX LAYOUT
In the space below, please provide sketch showing box location, unit cooler location, condensing unit location complete with accurate dimensions.
A complete layout is required to visualize the job location and equipment setup.

Outside Box Dimensions (Feet) : Box Wall Thickness (Inches) : Glass Door Dimensions (Inches) : Glass Door Construction : Number of Glass Doors :

Length Inches Length

Width Width

Height Height

BOX LOADING DETAIL

Room Heat Load from Motors or Machinery:

BTUH or Watts (Circle One)

Description of any and all objects inside the box (required for product load)

Lighting

B50-BCU-IM-20

– C4 –

20/04/22

MISCELLANEOUS Describe (in detail) frost pattern on distributor feeds:

Describe (in detail) frost pattern evaporator coil surface:

Is the TXV Bulb Insulated ? Describe location of TXV Bulb : (vertical or horizontal)

Yes / No

Is the Suction Line Insulated ?

Yes / No

Please make note of any other items that may have bearing on system performance and box temperature below:

B50-BCU-IM-20

– C5 –

20/04/22

NOTES

B50-BCU-IM-20

– C6 –

20/04/22

NOTES

B50-BCU-IM-20

– C7 –

20/04/22

PRODUCT SUPPORT RESOURCES
FOR SMALL CONDENSING UNITS (BEH, BEZ, BES, BQH, BQZ)
web: www.b-rp.ca/support email: smcu@b-rp.ca
call: 1-844-893-3222 x521
FOR MEDIUM AND LARGE CONDENSING UNITS (BMS/BMD, BVS/BVD) web: www.b-rp.ca/support email: mdcu_lgcu@b-rp.ca call: 1-844-893-3222 x522
FOR REMOTE & WATER COOLED CONDENSING UNITS (RB, BX, BW)
web: www.b-rp.ca/support email: rcu-wccu@b-rp.ca call: 1-844-893-3222 x523

B50-BCU-IM-20

– 70 –

20/04/22

PRODUCT SUPPORT RESOURCES
email: troubleshooting@b-rp.ca call: 1-844-893-3222 x529
web: www.b-rp.ca/parts
email: parts@b-rp.ca call: 1-844-893-3222 x504
web: www.b-rp.ca/warranty email: warranty@b-rp.ca call: 1-844-893-3222 x507
email: orders@b-rp.ca call: 1-844-893-3222 x501
email: shipping@b-rp.ca call: 1-844-893-3222 x503

B50-BCU-IM-20

– 71 –

20/04/22

“AS BUILT” SERVICE PARTS LIST
Ser vice Par ts List Label
To Be Attached HERE

DISTRIBUTED BY:

Bally Refrigeration Morehead City, NC · Brantford, ON · Longview, TX 1-800-242-2559 ballysales@ballyrefboxes.com www.ballyrefboxes.com
Due to the manufacturer’s policy of continuous product improvement, we reserve the right to make changes without notice.

20/04/22

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals