Sonic Driver FIXED-UFM Ultrasonic Flowmeter Instruction Manual

June 12, 2024
Sonic Driver

Sonic Driver FIXED-UFM Ultrasonic Flowmeter

Product Information

  • Product Name: FIXED-UFM Ultrasonic Flowmeter – Modbus RTU Slave Plug-in Module
  • Manufacturer: Sonic Driver Ltd
  • Version: 3.0
  • Date of Release: 13th March 2023
  • Country of Origin: Made in Britain

Introduction

Modbus Slave functionality is implemented in the Sonic Driver TM range of Fixed clamp-on ultrasonic flowmeters (UFM) by means of an optional plug-in board. Modbus settings are fully configurable on the UFM using its User Interface (UI).

Mode
The Modbus RTU protocol is implemented over RS485 hardware. Physical connection to the 2-wire bus is via the screw terminals on the end of the plug-in board. The terminals are labelled ‘A’ and ‘B’, see Figure(1).

Note that some equipment manufacturers label their terminals in other ways, e.g. ‘+’ and ‘-‘ so the exact order that the wires are connected may be reversed. There is also a screw terminal for connection of cable screen. This may be connected at the Master or the Slave UFM if necessary.

Baud rate
The RS485 baud rate can be selected using the UI on the UFM;

  • 9600 (Default)
  • 19200

Parity
The RS485 parity can be selected using the UI on the UFM;

  • None (Default)
  • Even
  • Odd

top Bits
The RS485 stop bits can be selected using the UI on the UFM;

  • 1 (Default)
  • 2

Modbus Address
The Modbus plug-in board Slave address is programmable using the UI on the UFM, from 1 to 247. The default Slave address is set to 1.

Data bits
RS485 serial data is fixed at 8 bit.

Register format
In the Modbus plug-in board each Modbus register is a 16-bit word, consisting of two 8-bit bytes. Register data in Modbus messages are packed as 2 bytes per register. The binary contents are right justified in each byte. For each register the first byte contains the high order bits and the second byte contains the low order bits. A floating-point number is stored as 32 bits using 4 bytes and therefore occupies 2 Modbus registers.

Representation of floating-point values
The micro controller on the Modbus plug-in board stores floating point values in IEEE 754 single precision format.

The bus Master accesses a floating-point value from any one of 4 different register tables. Each register table represents a different byte order .Sonic-Driver-FIXED-UFM-Ultrasonic-Flowmeter-2

By reading the first 2 registers of each table the user can determine which format matches their system when a fixed test value of 1234.0 is received.

Modbus Commands

The Modbus plug-in board implements Modbus commands 03, 04 and 06.

Read Holding Registers 03
This function code is used to read from 1 to 52 contiguous holding registers from the UFM. Registers are addressed starting at zero. Therefore holding registers numbered 1-32 are addressed as 0-31. The Modbus Master specifies a start address and register count.

Read Input Registers 04
This function code is used to read from 1 to 52 contiguous input registers from the flowmeter. Registers are addressed starting at zero. Therefore input registers numbered 1-32 are addressed as 0-31. The Modbus Master specifies a start address and register count.

Write Single Register 06

  • This function code is used to write a single register. This function code is used to reset the Slave UFM internal totals from the Master.
  • The Master specifies an address and 16-bit data value for write.
  • The value is an unsigned 16-bit value. Valid values are in the range 1 to 3 inclusive.
  • Writing a value of 1 to register 60300 will clear the unit’s internal flow metering totals.
  • Writing a value of 2 to register 60300 will clear the unit’s internal energy metering totals.
  • Writing a value of 3 to register 60300 will clear both the unit’s internal flow and energy metering totals.

Broadcast address

The Modbus plug-in board supports broadcast address 0. In broadcast address mode the Modbus master can send a command to all slaves. No response is sent by the slaves.

Communications Soft ware
There are several communications programs available for download online. The Modbus plug in board has been tested using Modbus Poll (for Windows plat form and M odbus Monit or for Android and Windows platforms.

Appendix

Appendix 1: Communication Command Structure

Read holding registers| |
---|---|---
| Slave ID| (1 byte)
| Function| (1 byte=03H)
| Start Address| (2 bytes)
| No. of Registers R| (2 bytes)
| CRC code| (2 bytes)
Reply| |
| Slave ID| (1 byte)
| Function| (1 byte)
N = 2R| Byte Count N| (1 byte)
| Hex Data| (N bytes)
| CRC code| (2 bytes)
| |
| |
Read input registers| |
| Slave ID| (1 byte)
| Function| (1 byte=04H)
| Start Address| (2 bytes)
| No. of Registers R| (2 bytes)
| CRC code| (2 bytes)
Reply| |
| Slave ID| (1 byte)
| Function| (1 byte)
N = 2R| Byte Count N| (1 byte)
| Hex Data| (N bytes)
| CRC code| (2 bytes)
| |
| |
Write single register| Slave ID| (1 byte)
| Function| (1 byte=06H)
| Start Address| (2 bytes)
| Hex Data| (2 bytes)
| CRC code| (2 bytes)
| |

Appendix 2: UFM Register Map

Modbus Address Measurement Variable Bytes Format
40001 Fixed test pattern 1234.0 4 IEEE
40002
40003 Flow Velocity (m/s) 4 IEEE
40004
40005 Flow Rate 4 IEEE
40006
40007 Flow Positive Total 4 IEEE
40008
40009 Flow Negative Total 4 IEEE
40010
40011 Flow Net Total 4 IEEE
40012
40013 Energy Rate 4 IEEE
40014
40015 Energy Positive Total 4 IEEE
40016
40017 Energy Negative Total 4 IEEE
40018
40019 Energy Net Total 4 IEEE
40020
40021 Delta Time Difference (ns) 4 IEEE
40022
40023 Upstream Transit Time (us) 4 IEEE
40024
40025 Signal Amplitude (dB) 4 IEEE
40026
40027 Signal Noise (dB) 4 IEEE
40028
40029 Amplifier gain (dB) 4 IEEE
40030
40031 SNR (dB) 4 IEEE
40032
40033 Signal Quality 1 (us) 4 IEEE
--- --- --- ---
40034
40035 Signal Quality 2 (ADU) 4 IEEE
40036
40037 Signal Quality 3 (ADU) 4 IEEE
40038
40039 CU Temperature (degC) 4 IEEE
40040
40041 Inlet Temperature (degC) 4 IEEE
40042
40043 Outlet Temperature (degC) 4 IEEE
40044
40045 Fluid Temperature (degC) 4 IEEE
40046
40047 ATA/ETA (%) 4 IEEE
40048
40049 Fluid Density (kg/m3) 4 IEEE
40050
40051 Fluid Specific Heat Capacity (J/K.degC) 4 IEEE
Modbus Address Text Strings Bytes Format
--- --- --- ---
Model Code
40101 Mo 2 WORD
40102 de 2 WORD
40103 l< > 2 WORD
40104 Co 2 WORD
40105 de 2 WORD
40106 < >< > 2 WORD
40107 < >< > 2 WORD
40108 < >< > 2 WORD
40109 < >< > 2 WORD
40110 < >< > 2 WORD
40111 < >< > 2 WORD
40112 < >< > 2 WORD
40113 < >< > 2 WORD
Serial Number
40114 88 2 WORD
40115 88 2 WORD
40116 88 2 WORD
40117 88 2 WORD
Tag
40118 Ta 2 WORD
40119 g< > 2 WORD
40120 < >< > 2 WORD
40121 < >< > 2 WORD
40122 < >< > 2 WORD
Ident
40123 Id 2 WORD
40124 en 2 WORD
40125 t< > 2 WORD
40126 < >< > 2 WORD
40127 < >< > 2 WORD
Flow rate units
40128 m/ 2 WORD
40129 s< > 2 WORD
40130 < >< > 2 WORD
40131 < >< > 2 WORD
Flow net total units
40132 l/ 2 WORD
40133 m< > 2 WORD
40134 < >< > 2 WORD
40135 < >< > 2 WORD
Energy rate units
40136 GJ 2 WORD
40137 /s 2 WORD
40138 < >< > 2 WORD
40139 < >< > 2 WORD
--- --- --- ---
Energy net total units
40140 GJ 2 WORD
40141 < >< > 2 WORD
40142 < >< > 2 WORD
40143 < >< > 2 WORD

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Sonic Driver User Manuals

Related Manuals