Sonic Driver Modbus-UFM RTU Slave Meter Instruction Manual

June 12, 2024
Sonic Driver

Sonic Driver Modbus-UFM RTU Slave Meter Instruction Manual

Introduction

TM Modbus RTU Slave functionality is implemented on the Sonic Driver on MODBUS WALL ultrasonic flowmeter (MODBUS WALL-UFM). clamp-
Meter settings are fully configurable on the UFM using a Windows based program running on a PC or laptop or an Android app running on a mobile phone. In addition a full range of flow measurements and diagnostics can be read from the meter.
Once installed and commissioned the computer or mobile can be disconnected and the meter wired back to a control room PCL or similar.

Mode

The Modbus RTU protocol is implemented over RS485 hardware.
Mobile connection uses a USB-OTG cable and Modbus interface. PC connection uses a USB A/B cable and a Modbus interface, see figure(1).

Figure(1) Mobile and PC connections

**** Physical connection to the 2-wire bus is via the screw terminals on the UFM board. The terminals are labelled ‘A’ and ‘B’.

Note that some equipment manufacturers label their terminals in other ways,

e.g. ‘+’ and ‘-‘ so the exact order that the wires are connected may be reversed.

There is also a screw terminal for connection of cable screen. This may be connected at either the Master or the Slave UFM if necessary.

1.0  Baud rate


The RS485 baud rate is 19200.

1.1  Parity


The RS485 parity is Even.

1.2  Stop Bits


The RS485 stop bits is 1.

1.3  Modbus Address


The Modbus-UFM Slave address is programmable from 1 to 255. The default Slave address is set to 1.

1.4  Data bits


RS485 serial data is fixed at 8 bits.

1.5  Register format


In the UFM each Modbus register is a 16-bit word, consisting of two 8-bit bytes.

Register data in Modbus messages are packed as 2 bytes per register. The binary contents are right justified in each byte. For each register the first byte contains the high order bits and the second byte contains the low order bits.

A floating-point number is stored as 32 bits using 4 bytes and therefore occupies 2 Modbus registers.

1.6  Representation of floating-point values


The UFM stores floating point values in IEEE 754 single precision format.

The bus Master accesses a floating-point value from any one of 4 different register tables. Each register table represents a different byte order.

Table start Byte order Common Description
0x0000 1,0,3,2 Floating-point Little-Endian with byte swap (Default)
0x1000 0,1,2,3 Floating-point Little-Endian Format
0x2000 3,2,1,0 Floating-point Big-Endian Format
0x3000 2,3,0,1 Floating point Big-Endian with byte swap

By reading the first 2 registers of each table the user can determine which format matches their system when a fixed test value of 1234.0 is received.

Modbus Commands

The UFM implements Modbus commands 03, 04, 06 and 16.

Read Holding Registers 03 ****

This function code is used to read from 2 to 110 contiguous holding registers from the UFM. Registers are addressed starting at zero. Therefore holding registers numbered 1-110 are addressed as 0-109.
The Modbus Master specifies a start address and register count.

Read Input Registers 04

This function code is used to read from 2 to 110 contiguous input registers from the flowmeter. Registers are addressed starting at zero. Therefore input registers numbered 1-110 are addressed as 0-109.
The Modbus Master specifies a start address and register count.

Write Single Register 06

This function code is used to write a single register. This function code is used to program integer values in the UFM.
The Master specifies an address and 16-bit data value for write.
The value is an unsigned 16-bit value. Valid values are defined for each register address, see appendix 3
Writing a value of 0x00 to register 60011 will clear the unit’s internal error log.

Write Single Register 16

This function code is used to write multiple registers. This function code is used to program 32-bit floating-point values in the UFM.
The Master specifies an address and 32-bit data value for write.
The value is a pair of unsigned 16-bit values. Valid values are defined for each register address, see appendix 3.

Broadcast address

The UFM supports broadcast address 0.
In broadcast address mode the Modbus master can send a command to all slaves.
No response is sent by the slaves.

Communications Software

There are several communications programs available for download online.
The UFM has been tested using Modbus Poll (for Windows platform) and Modbus Monitor (for Android and Windows platforms).

Appendix 1: Communication Command Structure

Read holding registers|  |
---|---|---
 | Slave ID| (1 byte)
 | Function| (1 byte=03H)
 | Start Address| (2 bytes)
 | No. of Registers R| (2 bytes)
 | CRC code| (2 bytes)
Reply|  |
 | Slave ID| (1 byte)
 | Function| (1 byte)
N = 2R| Byte Count N| (1 byte)
 | Hex Data| (N bytes)
 | CRC code| (2 bytes)

Read input registers|  |
 | Slave ID| (1 byte)
 | Function| (1 byte=04H)
 | Start Address| (2 bytes)
 | No. of Registers R| (2 bytes)
 | CRC code| (2 bytes)
Reply|  |
 | Slave ID| (1 byte)
 | Function| (1 byte)
N = 2R| Byte Count N| (1 byte)
 | Hex Data| (N bytes)
 | CRC code| (2 bytes)

Write single register| Slave ID| (1 byte)
 | Function| (1 byte=06H)
 | Start Address| (2 bytes)
 | Hex Data| (2 bytes)
 | CRC code| (2 bytes)

Write multiple registers| Slave ID| (1 byte)
 | Function| (1 byte=10H)
 | Start Address| (2 bytes)
 | No. of Registers R| (2 bytes)
N = 2R| Hex Data| (N bytes)
 | CRC Code| (2 bytes)

Appendix 2: Command 03 and 04 UFM Register Map

Modbus Address Measurement/Variable Bytes Format
40001 Fixed test pattern 1234.0 4 IEEE
40002    
40003 Flow Velocity (m/s) 4 IEEE
40004    
40005 Flow Rate Volumetric (l/min) 4 IEEE
40006    
40007 Flow Rate Mass (kg/min) 4 IEEE
40008    
40009 Flow Rate Heat (KJ/s) 4 IEEE
40010    
40011 Amplifier gain (dB) 4 IEEE
40012    
40013 Signal Amplitude (dB) 4 IEEE
40014    
40015 Signal Noise (dB) 4 IEEE
40016    
40017 SNR (dB) 4 IEEE
40018    
40019 Delta Time Difference (ns) 4 IEEE
40020    
40021 Upstream Transit Time (us) 4 IEEE
40022    
40023 Downstream Transit Time (us) 4 IEEE
40024    
40025 Arrival Bin 4 IEEE
40026    
40027 Signal Diagnostic 1 (us) 4 IEEE
40028    
40029 Signal Diagnostic 2 (ADU) 4 IEEE
40030    
40031 Meter Error Code 4 IEEE
40032    
40033 Transducer Type (List) 4 IEEE
40034    
40035 Transducer Wedge Angle (deg) 4 IEEE
40036    
40037 Transducer SOS at 20 deg C (m/s) 4 IEEE
40038    
40039 Transducer SOS at 60 deg C (m/s) 4 IEEE
40040    
40041 Transducer Crystal Offset (m) 4 IEEE
40042    
40043 Transducer Spacing Offset (m) 4 IEEE
40044    
40045 Transducer Frequency Code (List) 4 IEEE
--- --- --- ---
40046    
40047 Transducer Delta Time Offset(ns) 4 IEEE
40048    
40049 Transducer K Factor 4 IEEE
40050    
40051 Pipe Type (List) 4 IEEE
40052    
40053 Pipe SOS (m/s) 4 IEEE
40054    
40055 Pipe Outer Diameter (m) 4 IEEE
40056    
40057 Pipe Wall Thickness (m) 4 IEEE
40058    
40059 Pipe Inner Wall Roughness (m) 4 IEEE
40060    
40061 Fluid Type (List) 4 IEEE
40062    
40063 Fluid Temperature (deg C) 4 IEEE
40064    
40065 Fluid SOS (m/s) 4 IEEE
40066    
40067 Fluid Density (kg/m3) 4 IEEE
40068    
40069 Fluid Kinematic (cSt) 4 IEEE
40070    
40071 Fluid SHC (J/(kg.K)) 4 IEEE
40072    
40073 Flow Minimum Cut-off (m/s) 4 IEEE
40074    
40075 Flow Damping (s) 4 IEEE
40076    
40077 Modbus Address 4 IEEE
40078    
40079 Corrected SOS (m/s) 4 IEEE
40080    
40081 Window Delay (us) 4 IEEE
40082    
40083 Zero Tracking (On/Off) 4 IEEE
40084    
40085 Zero Calibration (On/Off) 4 IEEE
40086    
40087 Dynamic Temperature (On/Off) 4 IEEE
40088    
40089 Inlet Temperature (deg C) 4 IEEE
40090    
40091 Outlet Temperature (deg C) 4 IEEE
40092    
--- --- --- ---
40093 Flow Profile K Factor 4 IEEE
40094    
40095 Reynolds Number 4 IEEE
40096    
40097 Number of Passes 4 IEEE
40098    
40099 Tup Method 4 IEEE
40100    
40101 Transducer Spacing (m) 4 IEEE
40102    
40103 ATA/ETA (%) 4 IEEE
40104    
40105 Iout Minimum Value (l/min) 4 IEEE
40106    
40107 Iout Maximum Value (l/min) 4 IEEE
40108    
40109 Relay Alarm Value (l/min) 4 IEEE
40110    

Text Strings, company name (26 chars), model code (26 chars), serial

number (8 chars), HW/SW version (6 chars)

Modbus Address Text Strings, 2 chars Bytes Format
40300 So 2 Word
40301 ni 2 Word
40302 c< > 2 Word
40303 Dr 2 Word
40304 Iv 2 Word
40305 er 2 Word
40306 < >< > 2 Word
40307 < >< > 2 Word
40308 < >< > 2 Word
40309 < >< > 2 Word
40310 < >< > 2 Word
40311 < >< > 2 Word
40312 < >< > 2 Word
40313 MO 2 Word
40314 DB 2 Word
40315 US 2 Word
40316 < >W 2 Word
40317 AL 2 Word
40318 L- 2 Word
40319 UF 2 Word
40320 M< > 2 Word
40321 ST 2 Word
40322 D< > 2 Word
40323 < >< > 2 Word
--- --- --- ---
40324 < >< > 2 Word
40325 < >< > 2 Word
40326 10 2 Word
40327 00 2 Word
40328 00 2 Word
40329 00 2 Word
40330 20 2 Word
40331 02 2 Word
40332 00 2 Word

Serial number in the example is 1000000, HW and SW versions are 2.00 and 2.00.

Signal Data Trace Values, as pairs of 8-bit values.

Modbus Address| Signal Data Trace Value Pairs| Bytes| Format
---|---|---|---
 |  |  |
40401| 8-bit data point 0, 8-bit data point 1| 2| WORD
40402| 8-bit data point 2, 8-bit data point 3| 2| WORD
40403| 8-bit data point 4, 8-bit data point 5| 2| WORD
40404| 8-bit data point 6, 8-bit data point 7| 2| WORD
40405| 8-bit data point 8, 8-bit data point 9| 2| WORD
40406| 8-bit data point 10, 8-bit data point 11| 2| WORD
..| …,…| ..| …
..| …,…| ..| …
40649| 8-bit data point 496, 8-bit data point 497| 2| WORD
40650| 8-bit data point 498, 8-bit data point 499| 2| WORD

Appendix 3: Command 06 and 16 Definitions

 | Write Single| Write Multiple| 16/32 bit Write| Value| Default| Minimum| Maximum| SI Unit|
---|---|---|---|---|---|---|---|---|---
Value| CMD 06| CMD 16|  |  |  |  |  |  |
Transducer Type| 0|  | 16| 1| 1| 0| 3| List| DN40/DM10/DM20/DS10
Transducer Wedge Angle|  | 0| 32| 40.000| 40.000| 1.000| 90.000| deg|
Transducer SOS at 20degC|  | 2| 32| 2522.000| 2522.000| 500.000| 7000.000| m/s|
Transducer SOS at 60degC|  | 4| 32| 2522.000| 2522.000| 500.000| 7000.000| m/s|
Transducer Crystal Offset|  | 6| 32| 0.012| 0.012| 0.001| 0.100| m|
Transducer Spacing Offset|  | 8| 32| 0.030| 0.030| 0.001| 0.100| m|
Transducer Transmit Code| 1|  | 16| 1| 1| 0| 2|  | 4/1/2 MHz
Transducer Delta Transit Time Offset|  | 10| 32| 0| 0| -2.00E-08| 2.00E-08| s|
Transducer K Factor|  | 12| 32| 1.000| 1.000| 0.001| 1000.000|  |
Pipe Type| 2|  | 16| 0| 0| 0| 3| List| Carbon Steel/Stainless Steel/Copper/PVC
Pipe SOS|  | 14| 32| 3230.0| 3230.0| 500.0| 7000.0| m/s|
Pipe Outer Diameter|  | 16| 32| 0.0606| 0.0606| 0.01| 6.50| m|
Pipe Wall Thickness|  | 18| 32| 0.0032| 0.0032| 0.0005| 0.1| m|
Pipe Inner Wall Roughness|  | 20| 32| 0.00001| 0.00001| 0.000001| 0.002| m|
Fluid Type| 3|  | 16| 0| 0| 0| 3| List| Water/Petrol/Diesel/Glycol-Water
Fluid Temperature|  | 22| 32| 18.000| 18.000| 0.000| 150.000| deg C|
Fluid SOS|  | 24| 32| 1475.000| 1475.000| 50.000| 3000.000| m/s|
Fluid Density|  | 26| 32| 998.520| 998.520| 50.000| 3000.000| kg/m2|
Fluid Kinematic|  | 28| 32| 1.080| 1.080| 0.001| 40000.000| cSt|
Fluid Specific Heat Capacity|  | 30| 32| 4184.000| 4184.000| 10.000| 10000.000| J/(g.K)|
Minimum Flow Cut Off|  | 32| 32| 0.025| 0.025| 0.000| 1.000| m/s|
Flow damping| 4|  | 16| 10| 10| 0| 255| s|
---|---|---|---|---|---|---|---|---|---
Modbus Address| 5|  | 16| 1| 1| 1| 255|  |
Transducer Wedge Corrected SOS|  | 34| 32| 2522.000| 2522.000| 500.000| 7000.000| m/s|
Sampling Window delay| 6|  | 16| 169| 169| 11| 65535| us|
Zero Tracking On/Off| 7|  | 16| 1| 1| 0| 1| On/Off
Zero calibration On/Off| 8|  | 16| 0| 0| 0| 1| On/Off
Dynamic Temperature On/Off| 9|  | 16| 0| 0| 0| 1| On/Off
Number of Passes| 10|  | 16| 4| 4| 1| 16|  |
Tup Method| 12|  | 16| 3| 3| 0| 4| List| Method 0, 1, 2, 3, 4
Iout Minimum Value|  | 36| 32| 0| 0| -1000000.0| 1000000.0| l/min|
Iout Maximum Value|  | 38| 32| 160.0| 160.0| -1000000.0| 1000000.0| l/min|
Relay Alarm Value|  | 40| 32| 40.0| 40.0| -1000000.0| 1000000.0| l/min|

Read More About This Manual & Download PDF:

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Sonic Driver User Manuals

Related Manuals