Sonic Driver Modbus-UFM RTU Slave Meter Instruction Manual
- June 12, 2024
- Sonic Driver
Table of Contents
- Sonic Driver Modbus-UFM RTU Slave Meter Instruction Manual
- Introduction
- Mode
- Figure(1) Mobile and PC connections
- 1.0 Baud rate
- 1.1 Parity
- 1.2 Stop Bits
- 1.3 Modbus Address
- 1.4 Data bits
- 1.5 Register format
- 1.6 Representation of floating-point values
- Modbus Commands
- Read Holding Registers 03 ****
- Read Input Registers 04
- Write Single Register 06
- Write Single Register 16
- Broadcast address
- Communications Software
- Appendix 1: Communication Command Structure
- Text Strings, company name (26 chars), model code (26 chars), serial
- Signal Data Trace Values, as pairs of 8-bit values.
- Read More About This Manual & Download PDF:
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Sonic Driver Modbus-UFM RTU Slave Meter Instruction Manual
Introduction
TM Modbus RTU Slave functionality is implemented on the Sonic Driver on MODBUS
WALL ultrasonic flowmeter (MODBUS WALL-UFM). clamp-
Meter settings are fully configurable on the UFM using a Windows based program
running on a PC or laptop or an Android app running on a mobile phone. In
addition a full range of flow measurements and diagnostics can be read from
the meter.
Once installed and commissioned the computer or mobile can be disconnected and
the meter wired back to a control room PCL or similar.
Mode
The Modbus RTU protocol is implemented over RS485 hardware.
Mobile connection uses a USB-OTG cable and Modbus interface. PC connection
uses a USB A/B cable and a Modbus interface, see figure(1).
Figure(1) Mobile and PC connections
**** Physical connection to the 2-wire bus is via the screw terminals on the UFM board. The terminals are labelled ‘A’ and ‘B’.
Note that some equipment manufacturers label their terminals in other ways,
e.g. ‘+’ and ‘-‘ so the exact order that the wires are connected may be reversed.
There is also a screw terminal for connection of cable screen. This may be connected at either the Master or the Slave UFM if necessary.
1.0 Baud rate
The RS485 baud rate is 19200.
1.1 Parity
The RS485 parity is Even.
1.2 Stop Bits
The RS485 stop bits is 1.
1.3 Modbus Address
The Modbus-UFM Slave address is programmable from 1 to 255. The default Slave address is set to 1.
1.4 Data bits
RS485 serial data is fixed at 8 bits.
1.5 Register format
In the UFM each Modbus register is a 16-bit word, consisting of two 8-bit bytes.
Register data in Modbus messages are packed as 2 bytes per register. The binary contents are right justified in each byte. For each register the first byte contains the high order bits and the second byte contains the low order bits.
A floating-point number is stored as 32 bits using 4 bytes and therefore occupies 2 Modbus registers.
1.6 Representation of floating-point values
The UFM stores floating point values in IEEE 754 single precision format.
The bus Master accesses a floating-point value from any one of 4 different register tables. Each register table represents a different byte order.
Table start | Byte order | Common Description |
---|---|---|
0x0000 | 1,0,3,2 | Floating-point Little-Endian with byte swap (Default) |
0x1000 | 0,1,2,3 | Floating-point Little-Endian Format |
0x2000 | 3,2,1,0 | Floating-point Big-Endian Format |
0x3000 | 2,3,0,1 | Floating point Big-Endian with byte swap |
By reading the first 2 registers of each table the user can determine which format matches their system when a fixed test value of 1234.0 is received.
Modbus Commands
The UFM implements Modbus commands 03, 04, 06 and 16.
Read Holding Registers 03 ****
This function code is used to read from 2 to 110 contiguous holding registers
from the UFM. Registers are addressed starting at zero. Therefore holding
registers numbered 1-110 are addressed as 0-109.
The Modbus Master specifies a start address and register count.
Read Input Registers 04
This function code is used to read from 2 to 110 contiguous input registers
from the flowmeter. Registers are addressed starting at zero. Therefore input
registers numbered 1-110 are addressed as 0-109.
The Modbus Master specifies a start address and register count.
Write Single Register 06
This function code is used to write a single register. This function code is
used to program integer values in the UFM.
The Master specifies an address and 16-bit data value for write.
The value is an unsigned 16-bit value. Valid values are defined for each
register address, see appendix 3
Writing a value of 0x00 to register 60011 will clear the unit’s internal error
log.
Write Single Register 16
This function code is used to write multiple registers. This function code is
used to program 32-bit floating-point values in the UFM.
The Master specifies an address and 32-bit data value for write.
The value is a pair of unsigned 16-bit values. Valid values are defined for
each register address, see appendix 3.
Broadcast address
The UFM supports broadcast address 0.
In broadcast address mode the Modbus master can send a command to all slaves.
No response is sent by the slaves.
Communications Software
There are several communications programs available for download online.
The UFM has been tested using Modbus Poll (for Windows platform) and Modbus
Monitor (for Android and Windows platforms).
Appendix 1: Communication Command Structure
Read holding registers| |
---|---|---
| Slave ID| (1 byte)
| Function| (1 byte=03H)
| Start Address| (2 bytes)
| No. of Registers R| (2 bytes)
| CRC code| (2 bytes)
Reply| |
| Slave ID| (1 byte)
| Function| (1 byte)
N = 2R| Byte Count N| (1 byte)
| Hex Data| (N bytes)
| CRC code| (2 bytes)
Read input registers| |
| Slave ID| (1 byte)
| Function| (1 byte=04H)
| Start Address| (2 bytes)
| No. of Registers R| (2 bytes)
| CRC code| (2 bytes)
Reply| |
| Slave ID| (1 byte)
| Function| (1 byte)
N = 2R| Byte Count N| (1 byte)
| Hex Data| (N bytes)
| CRC code| (2 bytes)
Write single register| Slave ID| (1 byte)
| Function| (1 byte=06H)
| Start Address| (2 bytes)
| Hex Data| (2 bytes)
| CRC code| (2 bytes)
Write multiple registers| Slave ID| (1 byte)
| Function| (1 byte=10H)
| Start Address| (2 bytes)
| No. of Registers R| (2 bytes)
N = 2R| Hex Data| (N bytes)
| CRC Code| (2 bytes)
Appendix 2: Command 03 and 04 UFM Register Map
Modbus Address | Measurement/Variable | Bytes | Format |
---|---|---|---|
40001 | Fixed test pattern 1234.0 | 4 | IEEE |
40002 | |||
40003 | Flow Velocity (m/s) | 4 | IEEE |
40004 | |||
40005 | Flow Rate Volumetric (l/min) | 4 | IEEE |
40006 | |||
40007 | Flow Rate Mass (kg/min) | 4 | IEEE |
40008 | |||
40009 | Flow Rate Heat (KJ/s) | 4 | IEEE |
40010 | |||
40011 | Amplifier gain (dB) | 4 | IEEE |
40012 | |||
40013 | Signal Amplitude (dB) | 4 | IEEE |
40014 | |||
40015 | Signal Noise (dB) | 4 | IEEE |
40016 | |||
40017 | SNR (dB) | 4 | IEEE |
40018 | |||
40019 | Delta Time Difference (ns) | 4 | IEEE |
40020 | |||
40021 | Upstream Transit Time (us) | 4 | IEEE |
40022 | |||
40023 | Downstream Transit Time (us) | 4 | IEEE |
40024 | |||
40025 | Arrival Bin | 4 | IEEE |
40026 | |||
40027 | Signal Diagnostic 1 (us) | 4 | IEEE |
40028 | |||
40029 | Signal Diagnostic 2 (ADU) | 4 | IEEE |
40030 | |||
40031 | Meter Error Code | 4 | IEEE |
40032 | |||
40033 | Transducer Type (List) | 4 | IEEE |
40034 | |||
40035 | Transducer Wedge Angle (deg) | 4 | IEEE |
40036 | |||
40037 | Transducer SOS at 20 deg C (m/s) | 4 | IEEE |
40038 | |||
40039 | Transducer SOS at 60 deg C (m/s) | 4 | IEEE |
40040 | |||
40041 | Transducer Crystal Offset (m) | 4 | IEEE |
40042 | |||
40043 | Transducer Spacing Offset (m) | 4 | IEEE |
40044 | |||
40045 | Transducer Frequency Code (List) | 4 | IEEE |
--- | --- | --- | --- |
40046 | |||
40047 | Transducer Delta Time Offset(ns) | 4 | IEEE |
40048 | |||
40049 | Transducer K Factor | 4 | IEEE |
40050 | |||
40051 | Pipe Type (List) | 4 | IEEE |
40052 | |||
40053 | Pipe SOS (m/s) | 4 | IEEE |
40054 | |||
40055 | Pipe Outer Diameter (m) | 4 | IEEE |
40056 | |||
40057 | Pipe Wall Thickness (m) | 4 | IEEE |
40058 | |||
40059 | Pipe Inner Wall Roughness (m) | 4 | IEEE |
40060 | |||
40061 | Fluid Type (List) | 4 | IEEE |
40062 | |||
40063 | Fluid Temperature (deg C) | 4 | IEEE |
40064 | |||
40065 | Fluid SOS (m/s) | 4 | IEEE |
40066 | |||
40067 | Fluid Density (kg/m3) | 4 | IEEE |
40068 | |||
40069 | Fluid Kinematic (cSt) | 4 | IEEE |
40070 | |||
40071 | Fluid SHC (J/(kg.K)) | 4 | IEEE |
40072 | |||
40073 | Flow Minimum Cut-off (m/s) | 4 | IEEE |
40074 | |||
40075 | Flow Damping (s) | 4 | IEEE |
40076 | |||
40077 | Modbus Address | 4 | IEEE |
40078 | |||
40079 | Corrected SOS (m/s) | 4 | IEEE |
40080 | |||
40081 | Window Delay (us) | 4 | IEEE |
40082 | |||
40083 | Zero Tracking (On/Off) | 4 | IEEE |
40084 | |||
40085 | Zero Calibration (On/Off) | 4 | IEEE |
40086 | |||
40087 | Dynamic Temperature (On/Off) | 4 | IEEE |
40088 | |||
40089 | Inlet Temperature (deg C) | 4 | IEEE |
40090 | |||
40091 | Outlet Temperature (deg C) | 4 | IEEE |
40092 | |||
--- | --- | --- | --- |
40093 | Flow Profile K Factor | 4 | IEEE |
40094 | |||
40095 | Reynolds Number | 4 | IEEE |
40096 | |||
40097 | Number of Passes | 4 | IEEE |
40098 | |||
40099 | Tup Method | 4 | IEEE |
40100 | |||
40101 | Transducer Spacing (m) | 4 | IEEE |
40102 | |||
40103 | ATA/ETA (%) | 4 | IEEE |
40104 | |||
40105 | Iout Minimum Value (l/min) | 4 | IEEE |
40106 | |||
40107 | Iout Maximum Value (l/min) | 4 | IEEE |
40108 | |||
40109 | Relay Alarm Value (l/min) | 4 | IEEE |
40110 |
Text Strings, company name (26 chars), model code (26 chars), serial
number (8 chars), HW/SW version (6 chars)
Modbus Address | Text Strings, 2 chars | Bytes | Format |
---|---|---|---|
40300 | So | 2 | Word |
40301 | ni | 2 | Word |
40302 | c< > | 2 | Word |
40303 | Dr | 2 | Word |
40304 | Iv | 2 | Word |
40305 | er | 2 | Word |
40306 | < >< > | 2 | Word |
40307 | < >< > | 2 | Word |
40308 | < >< > | 2 | Word |
40309 | < >< > | 2 | Word |
40310 | < >< > | 2 | Word |
40311 | < >< > | 2 | Word |
40312 | < >< > | 2 | Word |
40313 | MO | 2 | Word |
40314 | DB | 2 | Word |
40315 | US | 2 | Word |
40316 | < >W | 2 | Word |
40317 | AL | 2 | Word |
40318 | L- | 2 | Word |
40319 | UF | 2 | Word |
40320 | M< > | 2 | Word |
40321 | ST | 2 | Word |
40322 | D< > | 2 | Word |
40323 | < >< > | 2 | Word |
--- | --- | --- | --- |
40324 | < >< > | 2 | Word |
40325 | < >< > | 2 | Word |
40326 | 10 | 2 | Word |
40327 | 00 | 2 | Word |
40328 | 00 | 2 | Word |
40329 | 00 | 2 | Word |
40330 | 20 | 2 | Word |
40331 | 02 | 2 | Word |
40332 | 00 | 2 | Word |
Serial number in the example is 1000000, HW and SW versions are 2.00 and 2.00.
Signal Data Trace Values, as pairs of 8-bit values.
Modbus Address| Signal Data Trace Value Pairs| Bytes|
Format
---|---|---|---
| | |
40401| 8-bit data point 0, 8-bit data point 1| 2| WORD
40402| 8-bit data point 2, 8-bit data point 3| 2| WORD
40403| 8-bit data point 4, 8-bit data point 5| 2| WORD
40404| 8-bit data point 6, 8-bit data point 7| 2| WORD
40405| 8-bit data point 8, 8-bit data point 9| 2| WORD
40406| 8-bit data point 10, 8-bit data point 11| 2| WORD
..| …,…| ..| …
..| …,…| ..| …
40649| 8-bit data point 496, 8-bit data point 497| 2| WORD
40650| 8-bit data point 498, 8-bit data point 499| 2| WORD
Appendix 3: Command 06 and 16 Definitions
| Write Single| Write Multiple| 16/32 bit Write| Value| Default| Minimum|
Maximum| SI Unit|
---|---|---|---|---|---|---|---|---|---
Value| CMD 06| CMD 16| | | | | | |
Transducer Type| 0| | 16| 1| 1| 0| 3| List| DN40/DM10/DM20/DS10
Transducer Wedge Angle| | 0| 32| 40.000| 40.000| 1.000| 90.000| deg|
Transducer SOS at 20degC| | 2| 32| 2522.000| 2522.000| 500.000| 7000.000|
m/s|
Transducer SOS at 60degC| | 4| 32| 2522.000| 2522.000| 500.000| 7000.000|
m/s|
Transducer Crystal Offset| | 6| 32| 0.012| 0.012| 0.001| 0.100| m|
Transducer Spacing Offset| | 8| 32| 0.030| 0.030| 0.001| 0.100| m|
Transducer Transmit Code| 1| | 16| 1| 1| 0| 2| | 4/1/2 MHz
Transducer Delta Transit Time Offset| | 10| 32| 0| 0| -2.00E-08| 2.00E-08| s|
Transducer K Factor| | 12| 32| 1.000| 1.000| 0.001| 1000.000| |
Pipe Type| 2| | 16| 0| 0| 0| 3| List| Carbon Steel/Stainless Steel/Copper/PVC
Pipe SOS| | 14| 32| 3230.0| 3230.0| 500.0| 7000.0| m/s|
Pipe Outer Diameter| | 16| 32| 0.0606| 0.0606| 0.01| 6.50| m|
Pipe Wall Thickness| | 18| 32| 0.0032| 0.0032| 0.0005| 0.1| m|
Pipe Inner Wall Roughness| | 20| 32| 0.00001| 0.00001| 0.000001| 0.002| m|
Fluid Type| 3| | 16| 0| 0| 0| 3| List| Water/Petrol/Diesel/Glycol-Water
Fluid Temperature| | 22| 32| 18.000| 18.000| 0.000| 150.000| deg C|
Fluid SOS| | 24| 32| 1475.000| 1475.000| 50.000| 3000.000| m/s|
Fluid Density| | 26| 32| 998.520| 998.520| 50.000| 3000.000| kg/m2|
Fluid Kinematic| | 28| 32| 1.080| 1.080| 0.001| 40000.000| cSt|
Fluid Specific Heat Capacity| | 30| 32| 4184.000| 4184.000| 10.000|
10000.000| J/(g.K)|
Minimum Flow Cut Off| | 32| 32| 0.025| 0.025| 0.000| 1.000| m/s|
Flow damping| 4| | 16| 10| 10| 0| 255| s|
---|---|---|---|---|---|---|---|---|---
Modbus Address| 5| | 16| 1| 1| 1| 255| |
Transducer Wedge Corrected SOS| | 34| 32| 2522.000| 2522.000| 500.000|
7000.000| m/s|
Sampling Window delay| 6| | 16| 169| 169| 11| 65535| us|
Zero Tracking On/Off| 7| | 16| 1| 1| 0| 1| On/Off
Zero calibration On/Off| 8| | 16| 0| 0| 0| 1| On/Off
Dynamic Temperature On/Off| 9| | 16| 0| 0| 0| 1| On/Off
Number of Passes| 10| | 16| 4| 4| 1| 16| |
Tup Method| 12| | 16| 3| 3| 0| 4| List| Method 0, 1, 2, 3, 4
Iout Minimum Value| | 36| 32| 0| 0| -1000000.0| 1000000.0| l/min|
Iout Maximum Value| | 38| 32| 160.0| 160.0| -1000000.0| 1000000.0| l/min|
Relay Alarm Value| | 40| 32| 40.0| 40.0| -1000000.0| 1000000.0| l/min|
Read More About This Manual & Download PDF:
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>