Product Information

  • Product Name: Presence detector 353-651021
  • Manual: Included
  • Mounting: SnapFit
  • Installation: Flush mounting
  • LED Behavior:
    • Green LED continuous on – Connection OK
    • Green LED flashing – Warming up
    • Red LED continuous on – Error
    • Blue LED flashing – Walk test active
  • Wiring:
    • Secondary: 353-x5xxx1 master
    • Secondary: 353-651021 secondary
    • DALI zone 1
    • DALI zone 2
    • DALI zone 3
  • Product Safety: This product must be secured with a miniature circuit breaker (MCB) of max. 16 A in the electrical cabinet. The MCB rating is limited by national installation rules.
  • Mounting Options:
    • Fixed Ceiling: NOT REMOVABLE
    • Suspended Ceiling: REMOVABLE
  • Dimensions:
    • a: 56.9 mm
    • b: 9.5 mm
    • NL: 44 mm
    • c: 10 – 12 mm
    • d: 45 – 55 mm
  • App Settings: Optional
  • Factory Settings: Sensitivity – High
  • Supported Languages: FR, DE, DK, SE, NO, IT, PL, SK
  • Specifications:
    • Article number: 353-651021
    • Configuration: DALI-2 secondary/BMS
    • Input voltage: via the DALI bus
    • Maximum current consumption: 28.1 mA
    • Maximum startup time DALI: < 1200 ms
    • Maximum PIR detection startup time: 70 s
    • Light intensity range: Not specified
    • Detection angle: Not specified
    • Detection range (PIR): Not specified
    • Ambient temperature: Not specified
    • Mounting method: Flush mounting with SnapFit mounting bracket
    • Mounting height: Not specified
    • Drill diameter: 76 mm
    • Minimum flush mounting depth: 56.9 mm
    • Colour: White (RAL 9010)
    • Dimensions visible (HxWxD): Not specified

Product Usage Instructions

  1. Mounting:
    • For flush mounting, use the SnapFit mounting bracket.
    • If using a fixed ceiling, the product is NOT REMOVABLE.
    • If using a suspended ceiling, the product is REMOVABLE.
    • Ensure the minimum flush mounting depth is 56.9 mm.
    • Drill a hole with a diameter of 76 mm for mounting.
  2. Wiring:
    • Connect the secondary 353-x5xxx1 master and 353-651021 secondary to the DALI zone 1, zone 2, and zone 3.
    • Follow the wiring diagram provided in the manual for proper connection.
  3. LED Behavior:
    • If the green LED is continuously on, it indicates a successful connection.
    • If the green LED is flashing, it means the product is warming up.
    • If the red LED is continuously on, there is an error.
    • If the blue LED is flashing, the walk test is active.
  4. App Settings:
    • The app settings are optional and can be configured according to user preferences.
    • The factory settings have sensitivity set to high.
  5. Additional Information:
    • For more information or troubleshooting, refer to the manual or contact customer support at 5413736374362.

Presence detector P46MR, DALI-2, secondary and BMS, 12-13 m, 360°, SnapFit, for flush mounting

Wiring

Secondaryniko-353-651021-Presence-Detector-01

This product must be secured with a miniature circuit breaker (MCB) of max. 16 A in the electrical cabinet. The MCB rating is limited by national installation rules.

BMS

Dimensions niko-353-651021-Presence-Detector-03

Installation

230 V/DALI power – OFF

App settings 230 V/DALI power – ON

  • App-intelligent

Settings by BMS software

DALI power – ON

Table memory bank 2

Address| Description| Default value| Memory type
0x00| Address and last accessible memory location| 0x03| ROM
0x01| Indicator byte (manufacture definable)| 0x00| any
0x02| Memory bank lock byte (<>0x55 = Read Only else Read/ Write)| 0xFF| RAM
0x03| PIR sensitivity segment A (MR, LR and HC detectors) 4 = MAX 3 = HIGH 2 = LOW 1 = MIN 0 = OFF| 0x03| NVM
0x04| PIR sensitivity segment B (LR and HC detectors)
4 = MAX 3 = HIGH 2 = LOW 1 = MIN 0 = OFF| 0x03| NVM
0x05| PIR sensitivity segment C (LR and HC detectors)
4 = MAX 3 = HIGH 2 = LOW 1 = MIN 0 = OFF| 0x03| NVM
0x06| LUX range

  • 0 = NORMAL 0 – 1023 lux, 10-bit
  • 1 = HIGH 0 – 10360 lux, 14 bit

| 0x00| NVM

LED behaviour

230 V/DALI power – ON

Green LED continuous on| | Connection OK|
---|---|---|---
Green LED flashing| | Warming up| Wait
Red LED continuous on| | Error| More info – >
Blue LED flashing| | Walk test active

Specifications

  • Article number 353-651021
  • Configuration DALI-2 secondary/BMS
  • Input voltage: via the DALI bus
  • Maximum current consumption: 28.1 mA
  • Nominal current consumption (12 V, 25°C): 8.1 mA
  • Maximum startup time DALI: < 1200 ms
  • Maximum PIR detection startup time: 70 s
  • Light intensity range: 0 – 10360 lux (see DALI BMS settings)
  • Detection angle: 360°
  • Detection range (PIR): ø 12 m from a height of 3 m
  • Ambient temperature -25 – +40 °C
  • Mounting method: flush mounting with SnapFit mounting bracket
  • Mounting height: 2 – 3.5 m
  • Drill diameter: 76 mm
  • Minimum flush mounting depth: 56.9 mm
  • Colour: white (RAL 9010)
  • Dimensions visible (HxWxD): 100 x 100 x 9.5 mm
  • Dimensions (HxWxD): 120 x 120 x 66.4 mm
  • Wire capacity: 1.5/2.5 mm²
  • Protection degree: IP20
  • Impact resistance: IK02
  • Modification  o f settingsapp (iOS/Android) and 2-way Bluetooth® communication/BMS software
  • Maximum range Bluetooth® (free field, depending on the device): 50 m
  • Operating frequency:   2.4 GHz
  • Maximum radio frequency power: -2 dBm
  • Halogen-free: yes
  • Marking :CE

Detection area
niko-353-651021-Presence-Detector-16

Troubleshooting

  • Problem: Possible cause
    • Load does not turn on The wiring is not correct
    • Load does not turn off The detector receives false triggers
    • App cannot connect to the detector
    • Bluetooth® has been disabled on your mobile device
  • Proposed solution
    • Check the wiring scheme
    • Check for any objects that may cause false triggering and remove them from the detection range or lower the sensitivity
    • Enable Bluetooth® on your mobile device

Support & contact