ELRO FZ5010R Wireless Linkable Smoke Detector Instruction Manual

June 12, 2024
ELRO

ELRO FZ5010R Wireless Linkable Smoke Detector

ELRO-FZ5010R-Wireless-Linkable-Smoke-Detector-
product

Product Information

  • Product Name: FZ5010R Smoke Detector
  • Product Type: Wireless Connected Smoke Alarm
  • Model Number: FZ5010R_MN_V4
  • Power Supply: Optical Sealed battery 3V DC (10 years battery lifetime)
  • Detection Method: Optical Sensor
  • Alarm Volume: Not specified
  • Monitored Area: Residential buildings, apartments, and rooms with residential-like use
  • Operating Temperature: Not specified
  • Operating Humidity: Not specified
  • Date of Replacement: 10 years after activation
  • Individual Alarm Indicator: Yes
  • Alarm Silence Facility: Yes
  • Low Battery Warning: Yes
  • Low Battery Silence Facility: Yes
  • Installation in Leisure Accommodation Vehicles: Not specified
  • Mounting Location: Ceiling (between 30 and 50 centimeters)
  • Interconnectable: Yes
  • Wireless Frequency: Not specified
  • Wireless Distance: Not specified

Product Usage Instructions

To ensure proper usage of the FZ5010R Smoke Detector, please follow the instructions below:

Where to Install a Smoke Alarm:

  • The smoke alarm should be installed on the ceiling, between 30  and 50 centimeters from the ceiling.

Where to Install a Smoke Alarm in Rooms with Special Geometries:

  • Please consider the instructions provided in the manual for proper installation in rooms with special geometries.

Where Not to Install a Smoke Alarm:

  • Avoid installing the smoke alarm near sources of steam, dust, or exhaust fumes, as they may cause false alarms.
  • Do not install the smoke alarm in kitchens, bathrooms, or near cooking appliances or machinery.

Activation:

  • To activate the smoke detector, set the switch on the mounting plate to the B = ON position.
  • Replace the smoke detector after 10 years of activation. If the test signal is not heard during testing, do not use the smoke detector.

Connecting Smoke Alarms:

  1. Choose one smoke alarm as the master smoke alarm.
  2. Turn the master smoke alarm into connect mode by quickly pressing the test button 3 times.
  3. The red LED will light up, followed by the blue LED, indicating that the smoke alarm is in connect mode for 30 seconds.
  4. Turn the next smoke alarm into learn mode by quickly pressing the test button 3 times.
  5. The red LED will light up, followed by the green LED, indicating that the smoke alarms are connected to each other.
  6. Repeat steps 1-5 for connecting more smoke alarms. Always use the same master smoke alarm.
  7. To test if the smoke alarms are connected successfully, press the test button of a random device until it beeps. The red LED of all connected devices will flash twice per second for five minutes. Stop the alarms by pressing the test button of each alarm.

Resetting Connection:

  1. Disconnect the smoke alarm you want to reset by removing it
    from the mounting plate or pushing the activation switch to the A position with a screwdriver.

  2. Press and hold the test button and activate the smoke alarm again by pushing the activation switch to the B = ON position.

  3. Hold the test button while the LED lights up red and release it when the LED turns off.

  4. When the LED lights up again, press the test button.

  5. The LED will start flashing to indicate that the network is being cleared.

  6. When the LED turns off, the connection is successfully cleared.

  7. Repeat steps 1-6 for disconnecting more smoke alarms.

ELRO-FZ5010R-Wireless-Linkable-Smoke-Detector-fig-
\(1\)

Thank you for purchasing our smoke alarm!
Please read these instructions carefully and store them in a safe place where you can access them easily.

Product description and intended use
This is a smoke alarm with radio link function with an optical sensor for installation in residential buildings, apartments and rooms with residential- like use. Smoke alarms are designed to provide an early warning of fire smoke and fires to persons present, so that these persons can react appropriately to the hazardous event. Always consult local regulations for smoke alarms.

Product specifications

  • Detection method: Optical
  • Power supply: Sealed battery 3V DC
  • Battery lifetime: 10 years
  • Alarm volume: ≥ 85 dB (A) at 3 meters
  • Monitored area: 40 m²
  • Operating temperature  : 0 °C – 45 °C
  • Operating humidity: < 93 %
  • Date of replacement: See product label
  • Individual alarm indicator: Yes
  • Alarm silence facility: Yes | Hush time: 5-15 minutes
  • Low battery warning: Yes
  • Low battery silence facility: Yes | Hush time: 10 hours Installation in leisure accommodation vehicles : Yes
  • Mounting location: Ceiling or wall
  • Interconnectable: Yes | max. 40 devices
  • Wireless frequency: 868.3 MHz
  • Wireless distance: 35 meters (100 meters open space)

Warnings

  • To prevent injury, this apparatus must be securely attached to the ceiling/wall in accordance with the installation
  • Batteries should not be exposed to excessive heat such as sunshine, fire or the
  • Do not paint or cover the smoke

Where to install a smoke alarm

  • Smoke alarms must be installed in such a way that they can be reached unhindered by the fire smoke so that fires can be reliably detected during the development
  • Install at least in sleeping areas (especially children’s rooms).
  • Install at least in escape
  • In the middle of the ceiling of a
  • At least 50 cm away from the wall and other
  • Maximum installation height of 6
  • If ceiling installation is not possible, the smoke alarm can be installed on the The distance to the ceiling should be between 30 and 50 centimeters.

Where to install a smoke alarm in rooms with special geometries

  • Corridors with a maximum width of 3m: 15m between 2 smoke alarms. Max. 7,5m to the front side of the gallery and smoke alarms at edges/crossings of corridors.
  • Rooms with sloping ceilings:
  • If the ceiling inclination is > 20° to the horizontal: Smoke alarms must be installed at least 5 m and at most 1 m from ceiling top.
  • Partial roof slopes: If the flat ceiling is ≤ 1m wide, consider as ceiling inclination is of > 20°. If the flat ceiling is >1m wide, consider as flat ceiling.
  • Rooms with subdivided ceilings:
  • Height of the subdivisions is ≤ 2 m: Beams without consideration; smoke alarm may be installed on the beams as well as on ceiling.
  • Height of subdivisions is > 2 m and area of ceiling panels > 36 m²: Smoke alarm should be installed in each ceiling panel.
  • Height of subdivisions > 2 m and area of ceiling panels ≤ 36 m²: Individual ceiling without consideration.

Where not to install a smoke alarm

  • In an environment with a high risk of drought (e.g., close to air conditioning, fans and ventilation outlets). The movement of air can impair the penetration of fire smoke into the smoke
  • Areas where combustions regularly occur, such as
  • Areas with high humidity such as bathrooms, or close to devices such as dishwashers or washing

Activation (view page 1_A-B)

  • Before using the smoke detector, it is important to activate and test
  • Use a screwdriver to push the activation switch to “B = ON”, on the front side a red LED will light up very
  • Test the correct activation of your smoke detector by pressing the test button for a few seconds, you will hear the test signal, the smoke detector is functioning as it
  • Then return the switch to the “A”
  • The smoke detector is automatically reactivated by placing it on the mounting plate and turning it to the left, 2 plastic hooks on the mounting plate set the switch to the “B = ON”

Warning

  • Replace 10 years after activation:
  • If the test signal is not heard, the smoke detector must not be used!

Connect your smoke alarms

  1. Choose one smoke alarm as the master smoke
  2. Turn your master smoke alarm into the connect mode by quickly pressing the test button 3
  3. The red LED (front side) will light up, followed by the blue LED (backside). This indicates that the smoke alarm turned into the connect mode in which it remains for 30
  4. Turn the next smoke alarm into the learn mode by quickly pressing the test button 3
  5. The red LED (front side) will light up, followed by the green LED (backside). This indicates that the smoke alarms are connected to each
  6. Repeat step 1 to 5 for connecting more smoke Make sure that you always use the same master smoke alarm!
  7. Test if your smoke alarm were connected successfully by pressing the test button of a random device until it The red LED of all connected devices will flash twice per second for five minutes. Stop these alarms by pressing the test button of each alarm.

Reset connection

  1. Disconnect the smoke alarm you want to reset by removing it from the mounting plate, or by pushing the activation switch to the “A” position with a
  2. Press and hold the test button and activate the smoke alarm again by pushing the activation switch to the “B = ON” position.
  3. Hold the test button while the LED lights up red and release it when the LED turns
  4. When the LED lights up again, press the test
  5. The LED will start flashing to indicate that it the network is being
  6. When the LED turns off, the connection is successfully
  7. Repeat step 1 to 6 for disconnecting more smoke

Mounting (view page 1_C-D-E)

  • Place the mounting plate on the desired installation location and mark where the holes should be
  • Drill two holes with a diameter of 5
  • Push the plastic plugs into the
  • Insert the screws into the mounting plate and tighten them firmly into the
  • Place the smoke alarm on the mounting bracket and secure it by turning it
  • Test the correct operation of your smoke alarm by pressing the test If no sound is generated, the smoke alarm is not functioning properly and should not be used!

Alarm silence facility
When the smoke alarm has detected smoke and turns into the alarm mode, you can mute the alarm for a minimum of 5 minutes and a maximum 15 minutes by pressing the test button. After that, the smoke alarm automatically resets and returns into the normal operation mode. If there are still particles of combustion in the air, the smoke alarm will turn into the alarm mode again. WARNING: Before using the alarm silence facility, always identify the cause of the alarm and make sure that the circumstances are safe.

Low battery mode
When the battery is running low, the smoke alarm will indicate this with a repetitive beep and flash for approximately 30 days.

WARNING : This smoke alarm is equipped with a non-replaceable battery. When this warning occurs, replace the device as soon as possible! The acoustic low battery warning signal can be muted for ten hours by pressing the test button. The smoke alarm is still functioning and able to detect smoke when it’s in this mode.

Fault warning mode
When the smoke alarm is not functioning properly, it will turn into the fault warning mode. Try cleaning the smoke alarm (see paragraph maintenance) or replace the smoke alarm

Maintenance

  • Test this smoke alarm weekly for correct operation using the test If the smoke alarm functions correctly, it will generate a loud beep. Due to the loudness of the alarm, make sure that you always stand at arm’s length distance from the unit when you are testing. If the smoke alarm does not generate an acoustic signal, the smoke alarm must be replaced immediately!
  • Clean the smoke alarm at least once per month to remove dirt, dust or Use a vacuum cleaner with a soft brush and vacuum all sides and covers of the smoke alarm. Do not remove the top cover of the smoke alarm to clean it inside.
  • Do not attempt to repair this smoke If the smoke alarm shows a damage related to its functionality, it must be replaced!
  • Troubleshooting : False alarm is often caused by dust or steam.
    Operating mode| Visual (red flash)| Acoustic (beep)| Description mode
    ---|---|---|---
    Normal| 1 x per 40 seconds| None| Device is functioning properly
    Test| 1 x per second (3 x) / pause of 1,5 seconds| 1 x per second (3 x) / pause of 1,5 seconds| Device is being tested
    Alarm| 1 x per second (3 x) / pause of 1,5 seconds| 1 x per second (3 x) / pause of 1,5 seconds| Device has detected smoke
    Wireless alarm| None| 2 x per seconds| Connected device detected smoke
    Alarm silence| 1 x per 8 seconds| None| Smoke alarm is muted
    Low battery warning| 1 x per 40 seconds| 1 x per 40 seconds| Battery is running low
    Connected low battery warning| 1 x per 3 hours| 1 x per 3 hours| Battery of connected device is running low
    Low battery warning silence| None| None| Low battery warning is muted
    Fault warning| None| 1 x per 40 seconds| Device is not functioning properly

Recycling and disposal
The WEEE symbol means that this product and batteries must be disposed of separately from other household waste. When they reach their end of life, take them to a designated waste collection point in your area to guarantee a safe disposal or recycling. Protect the environment, human health and natural resources!

1116 DoP: FZ5010R-01 22 FZ5010R Fire Safety EN 14604:2005 + AC:2008 By affixing the CE marking on a product, the manufacturer declares that the product complies with all legal requirements for CE marking and can be sold throughout the EEA.

Service and contact
To ensure that we can provide our customers with the best possible service as quickly as possible, we ask you to consider the following:

Go to www.elro.eu to receive a quick answer to your question. Here you will find answers to frequently asked questions, detailed installation videos and the most recent version of a product manual. Can’t resolve your question using the website? Leave a question via the product page or send an email to info@elro.eu we will help you as soon as possible. For the warranty conditions applicable to this product, please visit  www.elro.eu