Rheem Endeavor Line Classic Plus Series iM Heat Pumps User Guide

June 12, 2024
Rheem

The new degree of comfort.
Endeavor™ Line Classic Plus® Series iM Heat Pumps

RP16AZ
Cooling Efficiency: 17.0 SEER2/10.4 EER2
Heating Efficiency: 8.1 HSPF2
Nominal Sizes: 2 to 5 Ton [7.0 TO 17.6 kW] Cooling Capacities 22.8 to 55.0 kBTU [6.7 to 16.1 kW]Rheem Endeavor Line Classic Plus Series iM Heat Pumps -
iso

A.F.U.E. (Annual Fuel Utilization Efficiency) calculated in accordance with Department of Energy test procedures.

Features and Benefits

  • EcoNet® Enabled: Automatic system configuration and optimization

  • PlusOne® Diagnostics & Bluetooth Connectivity: With the Rheem Contractor & EcoNet® Apps, built-in technology makes advanced set-up, monitoring, troubleshooting, and repairing the product easier than ever before

  • PlusOne® Variable Speed Twin Rotary Compressor & Inverter Drive:
    — Features variable speed operation from 40 to 70% capacity, or 100% capacity via line voltage, with the EcoNet® Smart Thermostat
    — 3-speed operation when installed with a 24V two-stage thermostat
    — Provides precise temperature control, advanced humidity control and greater efficiency

  • Brushless DC Condenser Motors (BLDC): Enhances reliability and allows for easier serviceability

  • Swept Wing Fan Technology: Features quieter operation and improved unit acoustics

  • 7 mm Condenser Copper Coil1: Requires less refrigerant allowing for a smaller and lighter footprint while enhancing reliability

  • Inverted Reversing Valve: Allows for faster heat transfer with gravity assist shifting and reduced joint stress for increased reliability

  • PlusOne® Expanded Value Space: 3 in. – 4 in. – 5 in. service valve space – provides a minimum working area of 27-square inches for easier access

  • PlusOne® Triple Service Access: 15 in. wide, industry leading corner service access, two fastener, removeable corner and individual louver panels – makes repairs easier and faster

Heat Pumps

Rheem Endeavor Line Classic Plus Series iM Heat Pumps -
pum

[ ] Designates Metric Conversions

AVAILABLE MODELS DESCRIPTION
RP16AZ24AJ3CA Endeavor™ Line Classic Plus®  2 ton 16 SEER2 Variable Speed iM

Heat Pump-208/230/1/60
RP16AZ36AJ3CA| Endeavor™ Line Classic Plus®  3 ton 16 SEER2 Variable Speed iM Heat Pump-208/230/1/60
RP16AZ48AJ3CA| Endeavor™ Line Classic Plus®  4 ton 16 SEER2 Variable Speed iM Heat Pump-208/230/1/60
RP16AZ60AJ3CA| Endeavor™ Line Classic Plus®  5 ton 16 SEER2 Variable Speed iM Heat Pump-208/230/1/60

STANDARD EQUIPMENT

R-410A Refrigerant

Twin Rotary Compressor
Compressor Sound Blanket
Field Installed Filter Drier
Front Seating Service Valves
Internal Thermal Overload
Long Line capability
Low Ambient capability
3-4-5 Expanded Valve Space
Composite Basepan
15″ Access to Internal Components
Quick release louver panel design
No fasteners to remove along bottom
Optimized Venturi Airflow
Single row condenser coil
Powder coated paint
Rust resistant screws
OR code
External gauge ports
Service trays
General Data

Model No.| RP16AZ24AJ3| RP16AZ36AJ3| RP16AZ48AJ3| RP16AZ60AJ3
Nominal Tonnage| 2| 3| 4| 5
Valve Connections|
Liquid Line O.D. — in.| 3/8| 3/8| 3/8| 3/8
Suction Line O.D. — in.| 3/4| 3/4| 7/8| 7/8
Refrigerant (R410A) furnished oz.’| 118| 135| 164| 256
Compressor Type| Twin Rotary
Outdoor Coil|
Net face area — Outer Coil| 14.| 20.| 20.| 24.
Net face area — Inner Coil| —| —| —| —
Tube diameter — in.| 0.276| 0.276| 0.276| 0.276
Number of rows| 1| 1| 1| 1
Fins per inch| 22| 24| 22| 20
Outdoor Fan|
Diameter — in.| 20| 24| 24| 26
Number of blades| 3| 3| 3| 3
Motor hp| 1/5| 1/5| 1/3| 1/2
CFM| 2754| 4560| 4567| 5477
RPM| 1075| 1000| 1000| 925
Watts| 165| 277| 252| 283
Shipping weight — lbs.| 167| 239| 244| 279
Operating weight — lbs.| 160| 232| 237| 272
Electrical Data

Line Voltage Data (Volts-Phase-Hz)| 208/230-1-60| 208/230-1-60| 208/230-1-60| 208/230-1-60
Maximum overcurrent protection (amps)2| 20| 35| 40| 50
Minimum circuit ampacity3| 12| 21| 25| 30
Compressor
Rated load amps| 9| 13| 18| 22
Locked rotor amps| 65| 68| 96| 119

¹Refrigerant charge sufficient for 15 ft. length of refrigerant lines. For longer line set requirements see the installation instructions for information about set length and additional refrigerant charge required.
²HACR type circuit breaker of fuse.
³Refer to National Electrical Code manual to determine wire, fuse and disconnect size requirements.

Accessories

MODEL NO.| RP16AZ24AJ3| RP16AZ36AJ3| RP16AZ48AJ3| RP16AZ60AJ3
---|---|---|---|---
EcoNet® Smart Thermostat| RETST800SYS| RETST800SYS| RETST800SYS| RETST800SYS
Heat Pump Riser 6 in.| 686020| 686020| 686020| 686020
Supply/Return Sensor| RXHT-A02| RXHT-A02| RXHT-A02| RXHT-A02

Weighted Sound Power Level (dBA)

UNIT SIZE –
VOLTAGE. SERIES| STANDARD RATING (dBA) HIGH STAGE LOW STAGE| TYPICAL OCTAVE BAND SPECTRUM (dBA WITHOUT TONE ADJUSTMENT)
---|---|---
125| 250| 500| 1000| 2000| 4000| 8000
RP16AZ24AJ3| 72.| 44.| 57.| 64.| 61.| 59.0| 58.| 48.
64.| 38.| 49.| 55.| 53.| 50.| 52.| 42.
RP16AZ36AJ3| 73.| 49.| 61.| 65.| 60.| 61.| 59.| 47.
60.| 36.| 45.| 52.| 50.| 47.| 45.| 42.
RP16AZ48AJ3| – COMING SOON –
RP16AZ60AJ3| 71.| 46.| 56.0| 64.| 60.| 57.| 55.| 48.
62.| 31.| 45.| 53.| 49.| 50.| 49.| 42.

NOTE: Tested in accordance with AHRI Standard 270-08 (not listed in AHRI)

Unit Dimensions

MODEL
NO.| OPERATING| SHIPPING
---|---|---
H (Height)| L (Length)| W (Width)| H (Height)| L (Length)| W (Width)
INCHES| mm| INCHES| mm| INCHES| mm| INCHES| mm| INCHES| mm| INCHES| mm
RP16AZ24AJ3CA| 45.| 1147| 36.| 918| 36.| 918| 48.| 1224| 39.| 1000| 40.| 1007
RP16AZ36AJ3CA| 51.| 1300| 36.| 918| 36.| 918| 54.| 1360| 39.| 1000| 40.| 1007
RP16AZ48AJ3CA| 51.| 1300| 36.| 918| 36.| 918| 54.| 1360| 39.| 1000| 40.| 1007
RP16AZ60AJ3CA| 51.| 1300| 36.| 918| 36.| 918| 54.| 1360| 39.| 1000| 40.| 1007

Rheem Endeavor Line Classic Plus Series iM Heat Pumps -
Dimensions

[ ] Designates Metric Conversions

Clearances

RP16AZRheem Endeavor Line Classic Plus Series iM Heat Pumps -
CLEARANCES

Control Wiring

Application Guidelines

  1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01-in. wc.
  2. Minimum outdoor operation air temperature for cooling mode without low-ambient operation accessory is 55°F (12.8°C).
  3. Maximum outdoor operating air temperature is 125°F (51.7°C).
  4. For reliable operation, unit should be level in all horizontal planes.
  5. Use only copper wire for electric connections at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided.
  6. Do not apply capillary tube indoor coils to these units.
  7. Factory-supplied filter drier must be installed.

Refrigerant Line Size Information

16 SEER2 VARIABLE SPEED HEAT PUMPS

UNIT SIZE| ALLOWABLE
LIQUID
LINE SIZE| ALLOWABLE
VAPOR
LINE SIZE| OUTDOOR UNIT ABOVE OR BELOW INDOOR UNIT
EQUIVALENT LENGTH (FEET)
< 25| 26-50| 51-75| 76-100| 101-125| 126-150
MAXIMUM VERTICAL SEPARATION/CAPACITY MULTIPLIER
2.0 TON
*SEE
NOTE 3| 1/4″| 5/8′| 25/1.00| 50/0.99| 33/0.98| 60/0.97| NR| NR
5/16″| 5/8′| 25/1.00| 50/0.99| 50/0.98| 50/0.97| 50/0.96| 50/0.95
3/8″| 5/8″| 25/1.00| 50/0.99| 50/0.98| 50/0.97| 50/0.96| 50/0.95
1/4″| 3/4″| 25/1.00| 50/1.00| 33/0.99| 60/0.99| NR| NR
5/16″| 3/4″| 25/1.00| 50/1.00| 50/0.99| 50/0.99| 50/0.99| 50/0.98
3/8″| 3/4″| 25/1.00| 50/1.00| 50/0.99| 50/0.99| 50/0.99| 50/0.98
3 TON| 5/16″| 5/8″| 25/0.99| 50/0.97| 50/0.95| 50/0.93| 36/0.91| NR
3/8″| 5/8″| 25/0.99| 50/0.97| 50/0.95| 50/0.93| 50/0.91| NR
5/16″| 3/4″| 25/1.00| 50/0.99| 50/0.99| 50/0.98| 36/0.97| 20/0.96
3/8″| 3/4″| 25/1.00| 50/0.99| 50/0.99| 50/0.98| 50/0.97| 50/0.96
1/2″| 3/4″| 25/1.00| 50/0.99| 50/0.99| 50/0.98| 50/0.97| 50/0.96
4 TON| 3/8″| 3/4″| 25/0.99| 50/0.98| 50/0.96| 50/0.95| 50/0.93| 50/0.92
1/2″| 3/4″| 25/0.99| 50/0.98| 50/0.96| 50/0.95| 50/0.93| 50/0.92
3/8″| 7/8″| 25/1.00| 50/0.99| 50/0.99| 50/0.98| 50/0.98| 50/0.97
1/2″| 7/8″| 25/1.00| 50/0.99| 50/0.99| 50/0.98| 50/0.98| 50/0.97
5 TON| 3/8″| 3/4′| 25/0.98| 50/0.97| 50/0.95| 50/0.93| 46/0.91| NR
1/2″| 3/4″| 25/0.98| 50/0.97| 50/0.95| 50/0.93| 50/0.91| NR
3/8″| 7/8″| 25/0.99| 50/0.99| 50/0.98| 50/0.97| 50/0.96| 38/0.95
1/2″| 7/8″| 25/0.99| 50/0.99| 50/0.98| 50/0.97| 50/0.96| 50/0.95
3/8″| 1-1/8″”| 25/1.00| 50/1.00| 50/1.00| 50/0.99| 50/0.99| 38/0.99
1/2″| 1-1/8″• “| 25/1.00| 50/1.00| 50/1.00| 50/0.99| 50/0.99| 50/0.99

NOTES:

  1. Do not exceed 150 ft linear line length.
  2. Do not exceed 50 ft vertical separation between indoor and outdoor units.
  3. *3/4″ vapor line should only be used for 2 ton systems if outdoor unit is below or at same level as indoor unit to assure proper oil return.
  4. **1-1/8″ vapor line should only be used for 5 ton systems if outdoor unit is below or at same level as indoor unit to assure proper oil return.
  5. Always use the smallest liquid line allowable to minimize refrigerant charge.
  6. Applications shaded in light gray indicate capacity multipliers between 0.90 and 0.96 which are not recommended, but are allowed.
  7. Applications shaded in dark gray are not recommended due to excessive liquid or suction pressure drop.

16 SEER2 VARIABLE SPEED HEAT PUMPS

UNIT SIZE| ALLOWABLE
LIQUID
LINE SIZE| ALLOWABLE
VAPOR
LINE SIZE| OUTDOOR UNIT ABOVE OR BELOW INDOOR UNIT
EQUIVALENT LENGTH (METERS)
<8| 8-15| 16-23| 24-30| 31-38| 39-46
MAXIMUM VERTICAL SEPARATION/CAPACITY MULTIPLIER
7.0 kW
[2.0 TON] *SEE
NOTE 3| 6.35 [1/4]| 15.88 [5/8]| 8/1/00| 15/0.99| 10/0.98| 20/0.97| NR| NR
7.94 [5/16]| 15.88 [5/8]| 8/1/00| 15/0.99| 15/0.98| 15/0.97| 15/0.96| 15/0.95
9.53 [3/8]| 15.88 [5/8]| 8/1/00| 15/0.99| 15/0.98| 15/0.97| 15/0.96| 15/0.95
6.35 [1/4]| 19.05 [3/4]| 8/1/00| 15/0.99| 10/0.99| 20/0.99| NR| NR
7.94 [5/16]| 19.05 [3/4]| 8/1/00| 15/0.99| 15/0.99| 15/0.99| 15.0.99| 15.0.98
9.53 [3/8]| 19.05 [3/4]| 8/1/00| 15/0.99| 15/0.99| 15/0.99| 15/0.99| 15/0.98
10.6 kW
[3 TON]| 7.94 [5/16]| 15.88 [5/8]| 8/0.99| 15/0.97| 15/0.95| 15/0.93| 11/0.91| NR
9.53 [3/8]| 15.88 [5/8]| 8/0.99| 15/0.97| 15/0.95| 15/0.93| 15/0.91| NR
7.94 [5/16]| 19.05 [3/4]| 8/1/00| 15/0.99| 15/0.99| 15/0.98| 11/0.97| 6/0.96
9.53 [3/8]| 19.05 [3/4]| 8/1/00| 15/0.99| 15/0.99| 15/0.98| 15/0.97| 15/0.96
12.70 [1/2]| 19.05 [3/4]| 8/1/00| 15/0.99| 15/0.99| 15/0.98| 15/0.97| 15/0.96
14.1 kW
[4 TON]| 9.53 [3/8]| 19.05 [3/4]| 8/0.99| 15/0.98| 15/0.96| 15/0.95| 15/0.93| 15/0.92
12.70 [1/2]| 19.05 [3/4]| 8/0.99| 15/0.98| 15/0.96| 15/0.95| 15/0.93| 15/0.92
9.53 [3/8]| 22.23 [7/8]| 8/1/00| 15/0.99| 15/0.99| 15/0.98| 15/0.98| 15/0.97
12.70 [1/2]| 22.23 [7/8]| 8/1/00| 15/0.99| 15/0.99| 15/0.98| 15/0.98| 15:0.97
17.6 kW
[5 TON]| 9.53 [3/8]| 19.05 [3/4]| 8/0.98| 15/0.97| 15/0.95| 15/0.93| 14/0.91| NR
12.70 [1/2]| 19.05 [3/4]| 8/0.98| 15/0.97| 15/0.95| 15/0.93| 15/0.91| NR
9.53 [3/8]| 22.23 [7/8]| 8/0.99| 15/0.99| 15/0.98| 15/0.97| 15/0.96| 12/0.95
12.70 [1/2]| 22.23 [7/8]| 8/0.99| 15/0.99| 15/0.98| 15/0.97| 15/0.96| 15/0.95
9.53 [3/8]| 28.58 [1-1/8]”| 8/1/00| 15/0.99| 15/0.99| 15/0.99| 15/0.99| 12/0.99
12.70 [1/2]| 28.58 [1-1/8]”| 8/1/00| 15/0.99| 15/0.99| 15/0.99| 15/0.99| 15/0.99

NOTES:

  1. Do not exceed 46 meters linear line length.
  2. Do not exceed 15 meters vertical separation between indoor and outdoor units.
  3. *19.05 mm [3/4 in.] vapor line should only be used for 2 ton systems if outdoor unit is below or at same level as indoor unit to assure proper oil return.
  4. **28.58 mm [1-1/8 in.] vapor line should only be used for 5 ton systems if outdoor unit is below or at same level as indoor unit to assure proper oil return.
  5. Always use the smallest liquid line allowable to minimize refrigerant charge.
  6. Applications shaded in light gray indicate capacity multipliers between 0.90 and 0.96 which are not recommended, but are allowed.
  7. Applications shaded in dark gray are not recommended due to excessive liquid or suction pressure drop.

Performance Data @ AHRI Standard Conditions – Cooling

Designated Tested Combination (DTC)

Outdoor Unit| Air Handler| Total
Capacity
BTU/H [kW]| Net
Sensible
BTU/H [kW]| Net
Latent
BTU/H [kW]| SEER2| EER2| Indoor
CFM
[Lis]| 47 Degree
Heating
Capacity
BTU/H [kW]| 47
Degree
COP| 17 Degree
Heating
Capacity
BTU/H [kW]| 17
Degree
COP| Region
IV
HSPF2
RP16AZ24AJ3| RH3VZ2417STACN| 22600 [6.6]| 17300 [5.1]| 5300 [1.6]| 16.0| 10.| 750 [354.0]| 22800 [6.7]| 3.50| 13800 [4.0]| 2.40| 8.0
RP16AZ36AJ3| RH3VZ3617STACN| 34200 [10.0]| 26200 [7.7]| 8000 [2.3]| 16.0| 10.| 1100 [519.1]| 34500 [10.1]| 3.20| 21600 [6.3]| 2.30| 8.0
RP16AZ48AJ3| RH3VZ4821STACN| 45500 [13.3]| 34900 [10.2]| 10600 [3.1]| 16.0| 10.| 1475 [696.1]| 45500 [13.3]| 3.40| 28500 [8.4]| 2.40| 8.0
RP16AZ60AJ3| RH3VZ6024STACN| 55000 [16.1]| 42200 [12.4]| 12800 [3.8]| 16.0| 10.| 1725 [814.1]| 57000 [16.7]| 3.20| 35500 [10.4]| 2.40| 8.0

NOTE: This data includes DTC (Designated Test Combination) ratings and is for reference purposes only. A full listing of official ratings and system match-ups, along with downloadable certificates, can be accessed from the AHRI website: www.ahridirectory.org.
[ ] Designates Metric Conversions

**GENERAL TERMS OF LIMITED WARRANTY**
Rheem will furnish a replacement for any part of this product which fails in normal use and service within the applicable period stated, in accordance with the terms of the limited warranty.
For complete details of the Limited and Conditional Warranties, including applicable terms and conditions, contact your local contractor or the Manufacturer for a copy of the product warranty certificate.

Conditional Unit Replacement
(Registration Required) ……………………………Ten (10) Years
Parts ……………………………………………………….. Ten (10) Years

Before proceeding with installation, refer to installation instructions packaged with each model, as well as complying with all Federal, State, Provincial, and Local codes, regulations, and practices.
© 2022 Rheem Manufacturing Company. Rheem trademarks owned by Rheem Manufacturing Company.
In keeping with its policy of continuous progress and product improvement, Rheem reserves the right to make changes without notice.

Rheem Heating, Cooling & Water Heating
5600 Old Greenwood Road
Fort Smith, Arkansas 72908
www.rheem.com 
Rheem Canada Ltd.
125 Edgeware Road, Unit 1
Brampton, Ontario
L6Y 0P5
rheem.ca.com