Rheem 6N0325M0 Storage Tank
Specifications
- Model: 6N0325M0
- Manufacturer: Rheem Australia Pty Ltd
- Insulation Requirement: Suitable for the application and capable of withstanding the temperature of the water
- Warranty: Terms apply to storage tanks manufactured from August 1, 2018
Product Usage Instructions
Installation Guidelines
This storage tank must be installed and serviced by a qualified person. Follow
the installation instructions provided in the Owner’s Guide and Installation
Instructions manual.
Insulation Requirements
The insulation used must be suitable for the application and capable of
withstanding the temperature of the water generated by the primary water
heating source. Insulation helps reduce heat losses and prevents accidental
contact with high-temperature water.
Freeze Protection
Proper insulation is essential for freeze protection. Failure to insulate the
pipes may lead to freeze damage. Ensure that all pipes, including solar hot
and cold pipes, are insulated according to the installation instructions to
avoid warranty issues.
Maintenance
Regular maintenance of the storage tank is recommended to ensure optimal
performance and longevity. Refer to the Owner’s Guide for maintenance
guidelines.
FAQ
Q: Can I install the storage tank myself?
A: It is recommended to have the storage tank installed and serviced by a
qualified person to ensure proper installation and warranty coverage.
Q: What should I do if I encounter freeze damage?
A: If you suspect freeze damage, contact the service number provided for
assistance. Proper insulation can help prevent freeze damage.
This storage tank must be installed and serviced by a qualified person.
Please leave this guide with the householder
WARNING: Plumber – Be Aware
-
The primary flow and return pipes between the storage tank(s) and the primary water heating source, including the solar hot and solar cold pipes between the solar storage tank(s) and the solar collectors, MUST BE of copper. All compression fittings must use brass or copper olives.
-
The full length of the primary flow and return pipes MUST BE insulated.
The insulation must:-
be of a type suitable for the application and capable of withstanding the temperature of the water generated by the primary water heating source
The specification of the chosen insulation material should be checked with the insulation manufacturer prior to installation as different materials may vary in temperature tolerance. Closed cell type or equivalent insulation used between the storage tank(s) and solar collectors, if this storage tank is part of a solar water heater installation, must be able to withstand the temperature of the water generated by the solar collectors under stagnation conditions. Refer to the installation instructions provided with the solar controller for full details on the insulation requirements of the solar hot and solar cold pipes. -
be at least 13 mm thick, however thicker insulation may be required to comply with the requirements of AS/NZS 3500.4
-
be weatherproof and UV resistant if exposed
-
be fitted up to and cover the connections on both the storage tank(s) and the primary heating source.
-
The insulation will reduce pipe heat losses and also assist in avoiding accidental contact with the pipe work as high temperature water can flow from the primary heating source and the storage tank(s).
- In addition, the insulation on the solar hot and solar cold pipes must also:
- extend through any penetrations in the eaves, ceiling and roof
- cover valves and fittings in the solar hot and solar cold pipe work
Note: Failure to observe these requirements also increases the risk of
freeze damage.
The insulation is essential to assist in providing freeze protection and will
offer protection to a metal roof against corrosion due to water running off
the copper pipes.
Uninsulated pipe work, including concealed in cavities and roof spaces or
where it may be in contact with a metal roof, may lead to freeze damage. The
system has NO WARRANTY for freeze damage if the solar hot and solar cold pipes
are not insulated in accordance with the installation instructions.
An electronic copy of these Owner’s Guide and Installation Instructions can be downloaded from rheem.com.au and rheem.co.nz.
PATENTS
This storage tank may be protected by one or more patents or registered
designs in the name of Rheem Australia Pty Ltd.
TRADEMARKS
® Registered trademark of Rheem Australia Pty Ltd.
TM Trademark of Rheem Australia Pty Ltd.
Note: Every care has been taken to ensure the accuracy in preparation of
this publication.
No liability can be accepted for any consequences, which may arise as a result
of its publication.
RESPONSIBLE OFFICER
This booklet contains important information about your new water heater,
including terms of the Rheem warranty.
We recommend you read pages 7 to 17, and the terms of the Rheem warranty on pages 4 to 6.
The other pages are intended for the installer but may be of interest.
WARRANTY
RHEEM MAINS PRESSURE STORAGE TANK WARRANTY
– AUSTRALIA AND NEW ZEALAND ONLY –
STORAGE TANK MODEL 6N0325M0
THE RHEEM WARRANTY – GENERAL
- This warranty is given in Australia by Rheem Australia Pty Limited ABN 21 098 823 511 of 1 Alan Street, Rydalmere New South Wales, and in New Zealand by Rheem New Zealand Limited of 475 Rosebank Road Avondale Auckland 1026.
- Rheem offer a trained and qualified national service network who will repair or replace components at the address of the storage tank subject to the terms of the Rheem warranty. Rheem Service, in addition can provide preventative maintenance and advice on the operation of your storage tank. The Rheem Service contact number in Australia is 131031, with Contact Centre personnel available 24 hours, 7 days a week to take your call and if necessary to arrange a service call for during normal working hours Monday to Friday (hours subject to change) or in New Zealand on 0800 657 335.
- For details about this warranty, you can contact us in Australia on 131031 or by email at warrantyenquiry@rheem.com.au (not for service bookings), or in New Zealand on 0800 657 335 or by email at rheem@rheem.co.nz (not for service bookings).
- The terms of this warranty and what is covered by it are set out in sections 2 and 3 and apply to storage tanks manufactured from the 1st August 2018.
- If a subsequent version of this warranty is published, the terms of that warranty and what is covered by it will apply to storage tanks manufactured after the date specified in the subsequent version.
TERMS OF THE RHEEM WARRANTY AND EXCLUSIONS TO IT
- The decision of whether to repair or replace a faulty component is at Rheem’s sole discretion.
- If you require a call out and we find that the fault is not covered by the Rheem warranty, you are responsible for our standard call out charge. If you wish to have the relevant component repaired or replaced by Rheem, that service will be at your cost.
- Where a failed component or cylinder is replaced under this warranty, the balance of the original warranty period will remain effective. The replacement does not carry a new Rheem warranty.
- Where the storage tank is installed outside the boundaries of a metropolitan area as defined by Rheem or further than 25 km from either a regional Rheem branch office or an Accredited Rheem Service Agent’s / Centre’s office, the cost of transport, insurance and travelling between the nearest branch office or Rheem Accredited Service Agent’s / Centre’s office and the installed site shall be the owner’s responsibility.
- Where the storage tank is installed in a position that does not allow safe or ready access, the cost of that access, including the cost of additional materials handling and/or safety equipment, shall be the owner’s responsibility. In other words, the cost of dismantling or removing cupboards, doors or walls and the cost of any special equipment to bring the storage tank to floor or ground level or to a serviceable position is not covered by this warranty.
- This warranty only applies to the original and genuine Rheem storage tank in its original installed location and any genuine Rheem replacement parts.
- The Rheem warranty does not cover faults that are a result of:
- Accidental damage to the storage tank or any component (for example: (i) Acts of God such as floods, storms, fires, lightning strikes and the like; and (ii) third party acts or omissions).
- Misuse or abnormal use of the storage tank.
- Installation not in accordance with the Owner’s Guide and Installation Instructions or with relevant statutory and local requirements in the State or Territory in which the storage tank is installed.
- Connection at any time to a water supply that does not comply with the water supply guidelines as outlined in the Owner’s Guide and Installation Instructions.
- Repairs, attempts to repair or modifications to the storage tank by a person other than Rheem Service or a Rheem Accredited Service Agent / Centre.
- Faulty plumbing or faulty power supply.
- Failure to maintain the storage tank in accordance with the Owner’s Guide and Installation Instructions.
- Transport damage.
- Fair wear and tear from adverse conditions (for example, corrosion).
- Cosmetic defects.
- Subject to any statutory provisions to the contrary, this warranty excludes any and all claims for damage to furniture, carpet, walls, foundations or any other consequential loss either directly or indirectly due to leakage from the storage tank, or due to leakage from fittings and/ or pipe work of metal, plastic or other materials caused by water temperature, workmanship or other modes of failure.
- If the storage tank is not sized to supply the hot water demand in accordance with the guidelines in the Rheem storage tank literature, any resultant fault will not be covered by the Rheem warranty.
- In New Zealand this warranty excludes to the extent permissible all implied warranties set out in the Sale of Goods Act 1908 (New Zealand) and all guarantees set out in the Consumers Guarantees Act 1993 (New Zealand) to the extent that the goods are acquired for the purpose of resupply in trade consumption in the course of a process of production or manufacture or repairing or treating in trade other goods or fixtures on land.
- Rheem may reject a claim under this warranty in its sole discretion if a third party solar diverter is connected to the water heater.
WHAT IS COVERED BY THE RHEEM WARRANTY
FOR THE STORAGE TANKS DETAILED IN THIS DOCUMENT
Rheem will repair or replace a faulty component of your storage tank if it fails to operate in accordance with its specifications as follows:
What components are covered
| The period from the date of installation in which the fault must appear in order to be covered|
What coverage you receive
---|---|---
MODEL 6N0325M0
All components| Year 1| Repair and/or replacement of the faulty
component, free of charge, including labour.
The cylinder
(if the water heater is installed in a single-family domestic dwelling with a thermostat setting below 76°C)
| Years 2 & 3| Repair and / or replacement of the cylinder, free of charge,
including labour.
Years 4 to 12| Replacement cylinder, free of charge. Installation and repair
labour costs are the responsibility of the owner.
The cylinder
(if the water heater is not installed in a single-family domestic dwelling with a thermostat setting below 76°C)
| Years 2 to 8| Replacement cylinder, free of charge. Installation and repair labour costs are the responsibility of the owner.
ENTITLEMENT TO MAKE A CLAIM UNDER THIS WARRANTY
- To be entitled to make a claim under this warranty you need to:
- Be the owner of the storage tank or have consent of the owner to act on their behalf.
- Contact Rheem Service without undue delay after detection of the defect and, in any event, within the applicable warranty period.
- You are not entitled to make a claim under this warranty if your storage tank:
- Does not have its original serial numbers or rating labels.
- Is not installed in Australia or New Zealand.
HOW TO MAKE A CLAIM UNDER THIS WARRANTY
- If you wish to make a claim under this warranty, you need to:
- Contact Rheem on 131031 in Australia or 0800 657 335 in New Zealand and provide owner’s details, address of the storage tank, a contact number and date of installation of the storage tank or if that’s unavailable, the date of manufacture and serial number (from the rating label on the storage tank).
- Rheem will arrange for the storage tank to be tested and assessed on-site.
- If Rheem determines that you have a valid warranty claim, Rheem will repair or replace the storage tank in accordance with this warranty.
- Any expenses incurred in the making of a claim under this warranty will be borne by you.
THE AUSTRALIAN CONSUMER LAW
Our goods come with guarantees that cannot be excluded under the Australian
Consumer Law. You are entitled to a replacement or refund for a major failure
and for compensation for any other reasonably foreseeable loss or damage. You
are also entitled to have the goods repaired or replaced if the goods fail to
be of acceptable quality and the failure does not amount to a major failure.
The Rheem warranty (set out above) is in addition to any rights and remedies
that you may have under the Australian Consumer Law.
THE CONSUMER GUARANTEES ACT 1993 (NEW ZEALAND)
- Our goods come with guarantees that cannot be excluded under the Consumer Guarantees Act 1993 (New Zealand). If the goods fail to comply with the applicable guarantees set out under the Consumer Guarantees Act 1993 (New Zealand) being the guarantee as to acceptable quality, the guarantee as to correspondence with description or the guarantee as to repair and parts, or if the goods fail to comply with any express guarantee given by Rheem, then you are entitled to a replacement or refund and for compensation for any other reasonably foreseeable loss or damage.
- The Rheem warranty (set out above) is in addition to any rights and remedies that you may have under the Consumer Guarantees Act 1993 (New Zealand).
SAFETY, WARNINGS, INSTALLATION NOTES
It is important you read the following safety and warnings information.
SAFETY AND WARNINGS
-
This storage tank is only intended to be operated by persons who have the experience or the knowledge and the capabilities to do so.
-
This storage tank is not intended to be operated by persons with reduced physical, sensory or mental capabilities i.e. the infirm, or by children. Children should be supervised to ensure they do not interfere with the water heater.
-
If a remote thermostat (Tankstat) is fitted to the storage tank and the electrical conduit is damaged, it must be replaced by a qualified person in order to avoid a hazard. Phone Rheem Service or their nearest Accredited Service Agent / Centre to arrange for an inspection.
-
This storage tank is supplied with a combination temperature pressure relief valve. This valve has a rating of 46 kW. If the primary heating source has an output exceeding this valve, additional relief valves are required. The valve(s) must not be tampered with or removed. The storage tank and its primary heating source must not be operated unless each of these devices is fitted and is in working order.
The Rheem warranty may not cover faults if relief valves or other safety devices are tampered with or if the installation is not in accordance with these instructions. -
The storage tank can store water up to a water temperature of 60°C to 75°C, depending upon the type of water heating system and the setting of the thermostats and control system.
Refer to “How Hot Should The Water Be?” on page 10. -
The lever on the temperature pressure relief valve and expansion control valve (if fitted) requires to be operated every six (6) months to clear any deposits and to ensure the valve and its drain line are not blocked.
Refer to “Relief Valves” on page 8 and “Minor Maintenance Every Six Months” on page 12. -
For continued safety of this water heating system it must be installed, operated and maintained in accordance with the Owner’s Guide and Installation Instructions.
-
Servicing of a storage tank must only be carried out by qualified personnel. Phone Rheem Service or their nearest Accredited Service Agent / Centre.
-
Only a person qualified to install or service a water heater can drain the storage tank, if this is required.
-
Do not modify this storage tank.
RELIEF VALVES
Temperature Pressure Relief Valve
This storage tank incorporates a temperature pressure relief valve located
near the top of the tank. This valve is essential for the storage tank’s safe
operation.
It is possible for the valve to discharge a quantity of water through the drain line during each heating period. This quantity should be equal to approximately 1/50 of the hot water used, as water expands by this volume when heated.
Expansion Control Valve
In many areas, including South Australia, Western Australia, New Zealand and
scaling water areas, it is mandatory an expansion control valve is fitted to
the cold water line to the storage tank.
The expansion control valve will discharge the quantity of water from its
drain line during the heating period instead of the temperature pressure
relief valve as it has a lower pressure rating.
Valve Operation
Continuous leakage of water from either valve and its drain line may indicate
a problem with the water heater. Refer to “Temperature Pressure Relief Valve
or Expansion Control Valve Running” on page 17.
Warning: Never block the outlet of either valve or their drain lines for any
reason. A relief valve drain must be left open to atmosphere, and be installed
in a continuously downward direction.
In locations where water pipes are prone to freezing, the relief valve drain
line must be insulated and not exceed 300 mm in length before discharging into
a tundish through an air gap.
Operate the easing lever on the temperature pressure relief valve and expansion control valve once every six (6) months to clear any deposits and ensure the valve and its drain line are not blocked. It is very important the lever is raised and lowered gently. Refer to “Minor Maintenance Every Six Months” on page 12.
Warning: Water discharged from the temperature pressure relief valve drain line will be hot. Exercise care to avoid any splashing of water by standing clear of the drain line’s point of discharge when operating either valve’s easing lever.
Warning: Failure to operate the easing lever on the relief valve once every six (6) months may result in the water heater cylinder failing.
If water does not flow freely from the drain line when the lever is lifted,
then the water heater must be checked. Phone Rheem Service or their nearest
Accredited Service Agent / Centre to arrange for an inspection.
The temperature pressure relief valve should be replaced at intervals not
exceeding five (5) years and the expansion control valve should be checked for
performance or replaced at intervals not exceeding five (5) years. The
checking of the valves performance or replacement should occur more frequently
in areas where there is a high incidence of water deposits. Refer to “Water
Supplies” on page 13.
INSTALLATION NOTES
This storage tank must be installed:
- by a qualified person,
- in accordance with the installation instructions,
- in compliance with the Plumbing Code of Australia (PCA) and Plumbing Standard AS/NZS 3500.4,
- This storage tank is designed for either indoor or outdoor installation.
- This storage tank is intended to be permanently connected to the water mains and not connected by a hose-set. A braided flexible hose or semi-flexible connector may be used for connection to the water heater, where permitted by AS/NZS 3500.4.
- in compliance with all local codes and regulatory authority requirements.
- in New Zealand also conforming to Clauses G12 and H1 of the New Zealand Building Code.
Installation and commissioning requirements and details for the installing plumber are contained on pages 18 to 33.
Mains pressure water supply
The storage tank is designed to operate at mains pressure by connecting
directly to the mains water supply.
The storage tank is supplied with a temperature pressure relief valve with a
pressure rating of 1000 kPa. If an expansion control valve has been installed
on the cold water line to the storage tank, this should have a pressure rating
of 850 kPa.
The maximum mains water supply pressure for the storage tank is 800 kPa if an
expansion control valve is not installed, or 680 kPa if an expansion control
valve is installed. If the mains supply pressure in your area exceeds these
values, a pressure limiting valve must be installed.
The supply pressure should be greater than 350 kPa for true mains pressure operation to be achieved.
ABOUT YOUR STORAGE TANK
STORAGE TANK APPLICATION
This storage tank is designed for the purpose of storing heated potable water.
Its use in an application other than this may shorten its life.
MODEL TYPE
The Rheem Induro® Commercial hot water storage tank you have chosen can be
installed indoor or outdoor and is 315 litre.
Water is stored in a stainless steel cylinder and heated by an external
primary heating source. The temperature is controlled by the thermostat(s) on
the primary heating source. Automatic safety controls must be fitted to the
primary heating source to provide safe and efficient operation.
HOW HOT SHOULD THE WATER BE?
The storage tank is designed for a maximum recommended water temperature of
75°C. Refer to the installation instructions supplied with the primary heating
source plant for further information on water temperatures.
If this storage tank is installed as part of a solar water heater, to maximise
solar contribution it is recommended the thermostats of the in-series booster
water heaters are set at 60°C if a dead leg system is installed or 65°C if a
circulated flow and return system is installed, unless sanitising temperatures
are required.
Note: Australian Standard AS 3498 and New Zealand Building Code Clause
G12 requires that a water heater provides the means to inhibit the growth of
Legionella bacteria in potable water.
If this storage tank is installed as part of a solar water heater to an in-
series storage water heater, then these AS 3498 and Clause G12 requirements
can be satisfied provided the storage water heater is energised and the
thermostat setting is 60°C or higher.
If this storage tank is installed as part of a solar water heater to an in-
series continuous flow gas booster, then these AS 3498 and Clause G12
requirements can be satisfied provided the booster is energised, its preset
outlet temperature setting is 70°C or higher and a remote temperature
controller is not used.
HOTTER WATER INCREASES THE RISK OF SCALD INJURY.
This storage tank can deliver hot water at a temperature up to 75°C if its
primary source of water heating is a Rheem heavy duty or commercial water
heating system. This temperature is sufficiently hot to cause severe scalding.
Water at this temperature may have been plumbed to fixtures where water hotter
than 50°C is allowed, such as a kitchen, laundry and other areas requiring
sanitising temperatures.
Check the water temperature before use, such as when entering a shower or
filling a bath or basin, to ensure it is suitable for the application and will
not cause scald injury.
We recommend and it may also be required by regulations that an approved
temperature limiting device be fitted into the hot water pipe work to
bathrooms, ensuites, public amenities or other ablution areas when this
storage tank is installed. This will keep the water temperature below the
maximum permitted by the Plumbing Code of Australia and New Zealand Building
Code Clause G12 to these areas. The risk of scald injury will be reduced and
still allow hotter water to the kitchen, laundry and other areas requiring
sanitising temperatures.
TEMPERATURE ADJUSTMENT
We advise the thermostats of the primary heating plant are adjusted to the
lowest temperature setting that meets your needs, especially if there are
young children or elderly people in the premises, but they should not be set
to less than 60°C. Refer to “Hotter Water Increases the Risk of Scald Injury”
on page 10.
PRECAUTIONS
Under certain installation conditions where damage to property can occur in
the event of the water heater leaking AS/NZS 3500.4 requires the water heater
be installed in a safe tray. Construction, installation and draining of a safe
tray must comply with AS/NZS 3500.4 and all local codes and regulatory
authority requirements. In New Zealand the safe tray must also meet the
requirements of Clause G12 of the New Zealand Building Code. AS/NZS 3500.4 and
the NZBC also have particular requirements when a safe tray must be installed.
Alternatively, where additional leak protection is required for installations
not defined by AS/NZS 3500.4, a suitable bund may be constructed to surround
the water heater in lieu of using a safe tray.
The storage tank must be maintained in accordance with the Owner’s Guide and
Installation Instructions. Refer to “Maintenance Requirements” on page 12.
If this storage tank is to be used where an uninterrupted hot water supply is
necessary for your application or business you should ensure that you have
back-up redundancy within the hot water system design. This should ensure the
continuity of hot water supply in the event that this storage tank were to
become inoperable for any reason. We recommend you seek advice from a plumber
or specifier about your needs and building back-up redundancy into your hot
water supply system.
TO TURN OFF THE STORAGE TANK
If it is necessary to turn off the storage tank:
- Turn off the primary water heating plant and switch off the electrical supply at the isolating switch to the circulating pump(s).
- Close the cold water isolation valve on the cold water line to the storage tank(s) to shut down the entire system, or;
- Close the isolation valves on the cold, flow / return and hot water branches to shut down an individual storage tank in a bank.
TO TURN ON THE STORAGE TANK
-
Open the isolation valves fully on the cold, flow / return and hot water branches to the storage tank(s) installed in a bank.
-
Open the cold water isolation valve on the cold water line to the storage tank(s). Air will be forced out of the taps.
-
Switch on the electrical supply at the isolating switch to the circulating pump(s) and turn on the primary water heating plant.
VICTORIAN CUSTOMERS
Notice to Victorian Customers from the Victorian Building Authority. This
storage tank must be installed by a licensed person as required by the
Victorian Building Act 1993.
Only a licensed person will give you a Compliance Certificate, showing that
the work complies with all the relevant Standards. Only a licensed person will
have insurance protecting their workmanship for 6 years. Make sure you use a
licensed person to install this storage tank and ask for your Compliance
Certificate.
DOES THE WATER CHEMISTRY AFFECT THE STORAGE TANK?
The storage tank is suitable for most public water supplies, however some
water chemistries may have detrimental effects on the storage tank, its
components and fittings. Refer to “Water Supplies” on page 13.
If you are in a known harsh water area or you are not sure of your water
chemistry, have your water checked against the conditions described on pages
13 to 16.
HOW LONG WILL THE STORAGE TANK LAST?
The storage tank is supported by a manufacturer’s warranty (refer to page 4).
There are a number of factors that will affect the length of service the
storage tank will provide. These include but are not limited to the water
chemistry, the water pressure, the water temperature (inlet and outlet) and
the water usage pattern. Refer to “Precautions” on page 11.
MAINTENANCE REQUIREMENTS
MINOR MAINTENANCE EVERY SIX MONTHS
It is recommended minor maintenance be performed every six (6) months. Minor
maintenance can be performed by a responsible officer.
The minor maintenance includes:
-
Operate the easing lever on the temperature pressure relief valve. It is very important the lever is raised and lowered gently. Refer to “Relief Valves” on page 8.
Warning: Water discharged from the temperature pressure relief valve drain line will be hot. Exercise care to avoid any splashing of water by standing clear of the drain line’s point of discharge when operating the valve’s easing lever. -
Operate the easing lever on the expansion control valve (if fitted). It is very important the lever is raised and lowered gently. Refer to “Relief Valves” on page 8.
-
Check the drain line from the safe tray (if one is installed) is not blocked.
MAJOR SERVICE EVERY FIVE YEARS
It is recommended a major service be conducted on the water heater every five
(5) years.
Warning: Servicing of the storage tank must only be carried out by qualified personnel. Phone Rheem Service or their nearest Accredited Service Agent / Centre.
Note: The major service and routine replacement of any components, such as the relief valve(s), are not included in the Rheem warranty. A charge will be made for this work. Only genuine replacement parts should be used on this water heater.
The major service includes the following actions:
-
Replace the temperature pressure relief valve.
-
Inspect and flush the expansion control valve (if fitted). If required, replace the valve.
-
Drain and flush the storage tank if required.
In commercial applications where large volumes of hot water are used, sediment may build up on the bottom of the cylinder. In extreme cases, particularly in areas of high water sediment, draining and flushing out may be necessary. -
Visually check the unit for any potential problems.
-
Inspect all connections.
-
Check the drain line from the safe tray (if one is installed) is not blocked.
Note: The storage tank may need to be drained during this service. After the completion of the service, the water heater will take some time to reheat the water. Depending upon the heating source, hot water may not be available for a while.
WATER SUPPLIES
This storage tank must be installed in accordance with this advice to be
covered by the Rheem warranty.
This storage tank is manufactured to suit the water conditions of most public
reticulated water supplies. However, there are some known water chemistries
which can have detrimental effects on the water heater and its operation and /
or life expectancy. A list of postcodes is available on the Rheem website
(www.rheem.com.au) indicating known areas where the
stainless steel cylinder is not covered by the Rheem warranty due to the water
chemistry of the area. The list is not necessarily exhaustive and there may be
areas outside of these postcodes where the stainless steel cylinder is not
covered by the Rheem warranty due to the water chemistry of the area. If you
are unsure of your water chemistry, you may be able to obtain information from
your local water supply authority. This water heater should only be connected
to a water supply which complies with these guidelines, which takes precedence
over the list of postcodes, for the Rheem warranty to apply. It is recommended
to install a suitable filter on the cold water supply line to the water heater
if the water supply contains or has a future risk of containing suspended
solids. The Rheem warranty will not cover resultant faults on components
including the stainless steel cylinder due to the effects of sludge and/or
sediment settling in the water heater.
CHANGE OF WATER SUPPLY
The changing or alternating from one water supply to another can have a
detrimental effect on the operation and/or life expectation of a water heater
cylinder, a temperature pressure relief valve and a heating unit.
Where there is a changeover from one water supply to another, e.g. a rainwater
tank supply, bore water supply, desalinated water supply, public reticulated
water supply or water brought in from another supply, then water chemistry
information should be sought from the supplier or it should be tested to
ensure the water supply meets the requirements given in these guidelines for
the Rheem warranty to apply.
Note: Some water analysis reports may state the conductivity of the water
rather than the level of total dissolved solids. Conductivity, measured in
microsiemens per centimetre (µS / cm), is directly proportional to the TDS
content of the water. TDS, in mg / L, is approximately 70% of the conductivity
in µS / cm.
CHLORIDE AND PH
In a high chloride water supply, the water can corrode stainless steel parts
and cause them to fail.
Where the chloride level exceeds 250 mg / L the Rheem warranty does not apply
to a stainless steel cylinder.
pH is a measure of whether the water is alkaline or acid. In an acidic or very
alkaline water supply, the water can attack stainless steel parts and cause
them to fail.
Where the pH is less than 6.0 or greater than 9.5, the Rheem warranty does not
apply to a stainless steel cylinder. Water with a pH less than 6.0 may be
treated to raise the pH.
The water supply from a rainwater tank in a metropolitan area is likely to be corrosive due to the dissolution of atmospheric contaminants. This may result in pH of less than 6.0. It is recommended an analysis on the water from a rainwater tank be conducted prior to connecting this type of water supply to a water heater with a stainless steel cylinder.
Refer to the pH and Chloride chart below.
SATURATION INDEX
The saturation index is used as a measure of the water’s corrosive or scaling
properties. The saturation index figures stated are calculated using a water
temperature of 80°C.
In a corrosive water supply, the water can attack copper parts and cause them
to fail. Where the saturation index is less than –1.0, the water is very
corrosive and the Rheem warranty does not apply to a copper sheathed heating
unit.
A corrosion-resistant heating unit must be used for the Rheem warranty to
apply to the heating unit. This water heater is supplied fitted with a
corrosion-resistant heating unit. In a scaling water supply calcium carbonate
is deposited out of the water onto any hot metallic surface. Where the
saturation index exceeds +0.40, the water is very scaling. An expansion
control valve must be fitted on the cold water line after the non-return valve
to protect and for the Rheem warranty to apply to the temperature pressure
relief valve and water heater cylinder.
Where the saturation index exceeds +0.80, the Rheem warranty does not apply to
a stainless steel cylinder or a standard watts-density heating unit. A low-
watt-density heating unit must be used for the Rheem warranty to apply to the
heating unit.
Water which is scaling may be treated with a water-softening device to reduce the saturation index of the water. Contact Rheem Service or their nearest Accredited Service Agent if a replacement heating unit is required.
Refer to the Saturation Index chart on page 16. Refer to the cold water connection detail on page 35 for the position of the expansion control valve.
TOTAL DISSOLVED SOLIDS
The stainless steel cylinder of the storage tank is only covered by the Rheem
warranty when the total dissolved solids (TDS) content in the water is less
than 600 mg / L.
Note: Some water analysis reports may state the conductivity of the water
rather than the level of total dissolved solids. Conductivity, measured in
microsiemens per centimetre (μS / cm), is directly proportional to the TDS
content of the water. TDS, in mg / L, is approximately 70% of the conductivity
in μS / cm.
SUMMARY OF WATER CHEMISTRY ADVICE AFFECTING WARRANTY
The water heater and its components are not suitable for certain water
chemistries. Those chemistries are listed below. If the water heater is
connected at any time to a water supply with the following water chemistry,
the Rheem warranty will not cover any resultant faults on the components
listed below:
Water Chemistry
-
Chloride > 250 mg/L
-
Total Dissolved Solids (TDS) > 600 mg/L
-
pH < 6.0 or > 9.5
-
Saturation Index (SI) < -1.0
-
Saturation Index (SI) > +0.4
(if expansion control valve is not fitted) -
Saturation Index (SI) > +0.8
Component
- Storage tank cylinder
- storage tank cylinder
- Storage tank cylinder
- copper sheathed heating unit
- Storage tank cylinder temperature pressure relief valve
- standard watts density heating unit
SAVE A SERVICE CALL
Check the items below before making a service call. You will be charged for attending to any condition or fault that is not related to manufacture or failure of a part.
NOT ENOUGH HOT WATER (OR NO HOT WATER)
-
Are you using more hot water than you think?
Are outlets (especially the showers) using more hot water than you think? Very often it is not realised the amount of hot water used, particularly when showering. Carefully review the hot water usage. Have a plumber fit a flow control valve to each shower outlet to reduce water usage. -
Relief valve running
Is the relief valve discharging too much water? Refer to “Temperature Pressure Relief Valve or Expansion Control Valve Running” on page 17. -
Thermostat setting
Ensure the thermostat setting of the primary heating source is appropriate. You may choose to have your electrician adjust the thermostats upwards to gain additional hot water capacity.
Warning: Hotter water increases the risk of scald injury. -
Water heater size
Do you have the correct size water heater or sufficient storage for your requirements? The sizing guide in the Rheem sales literature and on the Rheem website (www.rheem.com.au) suggests average sizes that may be needed.
TEMPERATURE PRESSURE RELIEF VALVE OR EXPANSION CONTROL VALVE RUNNING
-
Normal Operation
It is normal and desirable the temperature pressure relief valve or expansion control valve (if fitted) allows a quantity of water to escape during the heating cycle. This quantity should be equal to approximately 1/50 of the hot water used, as water expands by this volume when heated. However, if it discharges more than a bucket full of water in 24 hours, there may be another problem.
The expansion control valve (if fitted) will discharge water instead of the temperature pressure relief valve as it has a lower pressure rating. A benefit is that energy is conserved as the discharged water is cooler. This valve is installed in the cold water line to the storage tank (refer to the cold water connection diagram on page 25). -
Continuous dribble
Try gently raising the easing lever on the relief valve for a few seconds (refer to “Relief Valves” on page 8). This may dislodge a small particle of foreign matter and clear the fault. Release the lever gently. -
Steady flows for long period (often at night)
This may indicate the mains water pressure sometimes rises above the designed pressure of the storage tank. Ask a plumber to fit a pressure limiting valve.
Warning: Never replace the relief valve with one of a higher pressure rating. -
Heavy flows of hot water from the temperature pressure relief valve until storage tank is cold -then stops until water reheats
The primary heating source must be shut down and the energy source isolated. Phone Rheem Service or their nearest Accredited Service Agent / Centre to arrange for inspection.
IF YOU HAVE CHECKED ALL THE FOREGOING AND STILL BELIEVE YOU NEED ASSISTANCE, PHONE RHEEM SERVICE OR THEIR NEAREST ACCREDITED SERVICE AGENT / CENTRE
INSTALLATION
THIS STORAGE TANK IS NOT SUITABLE FOR POOL HEATING
INSTALLATION STANDARDS
The storage tank must be installed:
- by a qualified person, and
- in accordance with the installation instructions, and
- in compliance with the Plumbing Code of Australia (PCA), Standard AS/NZS 3500.4 and all local codes and regulatory authority requirements.
- in New Zealand also conforming to Clauses G12 and H1 of the New Zealand Building Code.
Warning: This water heater may deliver water at high temperature. Refer
to the Plumbing Code of Australia, local requirements and these installation
instructions to determine if additional delivery temperature control is
required. Refer to “Hot Water Delivery” on page 20.
All packaging materials must be removed from the storage tank prior to its
installation. This includes the removal of the cardboard base of the carton
from the underside of the storage tank.
STORAGE TANK APPLICATION
This storage tank is designed for the purpose of storing heated potable water.
Its use in an application other than this may shorten its life.
If this storage tank is to be used where an uninterrupted hot water supply is
necessary for the application or business, then there should be back-up
redundancy within the hot water system design. This should ensure the
continuity of hot water supply in the event that this storage tank was to
become inoperable for any reason. We recommend you provide advice to the
system owner about their needs and building back-up redundancy into the hot
water supply system.
Note: Australian Standard AS 3498 and New Zealand Building Code Clause
G12 requires that a water heater provides the means to inhibit the growth of
Legionella bacteria in potable water.
If this storage tank is installed as part of a solar water heater to an in-
series storage water heater, then these AS 3498 and Clause G12 requirements
can be satisfied provided the storage water heater is energised and the
thermostat setting is 60°C or higher.
If this storage tank is installed as part of a solar water heater to an in-
series continuous flow gas booster, then these AS 3498 and Clause G12
requirements can be satisfied provided the booster is energised, its preset
outlet temperature setting is 70°C or higher and a remote temperature
controller is not used.
STORAGE TANK LOCATION
This storage tank is suitable for either outdoor or indoor installation.
Whether located outdoor or indoor, the storage tank should be installed either
close to the most frequently used outlets or with a circulated flow and return
system, and its position chosen with safety and service in mind.
Clearance must be allowed for servicing of the storage tank. The storage tank
must be accessible without the use of a ladder or scaffold. Make sure the
temperature pressure relief valve lever is accessible and the thermostat
(Tankstat) if fitted can be removed for service.
You must be able to read the information on the rating plate. Remember you may
have to take the entire storage tank out later for servicing.
The storage tank is to be installed at ground or floor level and must stand vertically upright on a stable base as acceptable to local authorities. The base of the storage tank is made of corrosion resistant material, and it may be placed directly in contact with the supporting surface. It is not necessary to allow for free air circulation under the base of the storage tank.
Note: The storage tank should not be placed in direct contact with a
concrete surface that is less than two months old and not fully cured as this
may attack the metal coating of the storage tank base. A moisture barrier
should be used between the two surfaces in this instance. The barrier should
extend at least 100 mm from the water heater and may be trimmed after two
months.
Remember all local authorities have regulations about putting storage tanks
into roof spaces.
For a single storage tank installation, follow the diagram on page 24. For
multiple storage tank installations follow the instructions on pages 29 to 32.
SAFE TRAY
Under certain installation conditions where damage to property can occur in
the event of the water heater leaking AS/NZS 3500.4 requires the water heater
be installed in a safe tray. Construction, installation and draining of a safe
tray must comply with AS/NZS 3500.4 and all local codes and regulatory
authority requirements. In New Zealand the safe tray must also meet the
requirements of Clause G12 of the New Zealand Building Code. AS/NZS 3500.4 and
the NZBC also have particular requirements when a safe tray must be installed.
Alternatively, where additional leak protection is required for installations
not defined by AS/NZS 3500.4, a suitable bund may be constructed to surround
the water heater in lieu of using a safe tray.
MAINS WATER SUPPLY
Where the mains water supply pressure exceeds that shown in the table below,
an approved pressure limiting valve is required and should be fitted as shown
in the cold water connection diagram on page 25
Model | 340, 430 |
---|---|
Temperature pressure relief valve setting | 1000kPa |
Expansion control valve setting* | 850kPa |
Maximum mains supply pressure | |
With expansion control valve | 680kPa |
Without expansion control valve | 800kPa |
Expansion control valve not supplied with storage tank
TANK WATER SUPPLY
If the storage tank is supplied with water from a tank supply and a pressure
pump system is not installed, then the bottom of the supply tank must be at
least 1 m above the highest point of the hot water plumbing system, including
the storage tank. Care must be taken to avoid air locks. The cold water line
to the storage tank should be adequately sized and fitted with a full flow
gate valve or ball valve. Consideration must be given to any minimum water
supply pressure requirements of water heater(s) which are part of the hot
water plumbing system.
REDUCING HEAT LOSSES
The cold water line to, primary flow and return lines and the hot water line
from the storage tank must be insulated in accordance with the requirements of
AS/NZS 3500.4. The insulation must be weatherproof and UV resistant if
exposed.
Keep temperature settings down. Lower temperatures reduce heat losses and
prolong cylinder life. Do not set the controlling thermostats on the primary
heating plant above 70°C unless it is necessary.
HOT WATER DELIVERY
This storage tank can deliver hot water at a temperature up to 75°C if its
primary source of water heating is a Rheem heavy duty or commercial water
heating system. This temperature is sufficiently hot to cause severe scalding.
Water at this temperature may have been plumbed to fixtures where water hotter
than 50°C is allowed, such as a kitchen, laundry and other areas requiring
sanitising temperatures.
The installing plumber may have a legal obligation to ensure the installation
of this storage tank as part of a water heater system meets the water
temperature delivery requirements of the Plumbing Code of Australia and New
Zealand Building Code Clause G12 so that heated water delivered to fixtures
and appliances used primarily for personal hygiene is at a temperature which
is unlikely to scald.
It is necessary and we recommend that a temperature-limiting device be fitted
between the storage tank and the fixtures and appliances used primarily for
personal hygiene such as in a bathroom, ensuite, public amenities or other
ablution areas, to reduce the risk of scalding.
Where a temperature limiting device is installed adjacent to the storage tank,
the cold water line to the temperature limiting device can be branched off the
cold water line either before or after the isolation valve and pressure
limiting valve to the solar storage tank, but it MUST BE before the non-return
valve. If an expansion control valve is required, it must always be installed
after the non-return valve and be the last valve prior to the solar storage
tank.
Warning: A non-return valve MUST BE installed on the cold water line to
the solar storage tank AFTER the cold water branch to a temperature limiting
device.
If a combination isolation valve and non-return valve (duo or trio valve) is
installed on the cold water line to the storage tank and the cold water line
to the temperature limiting device branches off after this valve, then a
second non-return valve must be installed between the cold water branch and
the solar storage tank.
If a pressure limiting valve is installed on the cold water line to the storage tank and the cold water line to a temperature limiting device branches off before this valve or from another cold water line in the premises, then a pressure limiting valve of an equal pressure setting may be required prior to the temperature limiting device.
CIRCULATED HOT WATER FLOW AND RETURN SYSTEM
If a storage tank is used with a primary water heating source and is to be
installed as part of a circulated hot water flow and return system, the
primary heating source must be able to provide a hot water outlet temperature
of at least 60°C.
If a storage tank is used as part of a solar water heater, it should not be
installed as part of a circulated hot water flow and return system in a
building, unless the system and control system is specifically designed for
this. Otherwise, the benefits of solar gain will be significantly reduced and
energy gained from the sun lost through the pipe work.
If a circulated flow and return system is required, it is necessary to connect
the flow and return lines to the in-series booster water heater, not the solar
storage tank. The in-series booster water heater makes up for the pipe heat
loss in the flow and return system and must be able to provide a hot water
outlet temperature of at least 60°C.
Note: The thermostat or preset outlet temperature of the primary heating
source or in-series booster water heater must always be set to at least 60°C.
Refer to the diagram Circulated Hot Water Flow and Return System Storage Tank
with Primary Water Heater on page 21.
Temperature Limiting Device
A temperature limiting device cannot be installed in circulated hot water flow
and return pipe work unless it is specifically designed to do so, such as the
Rheem Guardian warm water system.
The tempered water from a temperature limiting device cannot be circulated.
Where a circulated hot water flow and return system is required in a building,
a temperature limiting device can only be installed on a dead leg, branching
off the circulated hot water flow and return pipe.
If circulated tempered water were to be returned back to the water heater or storage tank, depending on the location of the return line connection on the water supply line to the water heater or storage tank, then either:
- water will be supplied to the cold water inlet of the temperature limiting device at a temperature exceeding the maximum recommended water supply temperature, or
- when the hot taps are closed no water will be supplied to the cold water inlet of the temperature limiting device whilst hot water will continue to be supplied to the hot water inlet of the temperature limiting device.
These conditions may result in either water at a temperature exceeding the requirements of AS/NZS 3500.4 being delivered to the hot water outlets in the ablution areas, or the device closing completely and not delivering water at all, or the device failing. Under either condition, the operation and performance of the device cannot be guaranteed.
SADDLING PIPE WORK
To prevent damage to the cylinder when attaching pipe clips or saddles to the
storage tank jacket, we recommend the use of self-drilling screws with a
maximum length of 13 mm. Should pre drilling be required, extreme caution must
be observed when penetrating the jacket of the storage tank.
Note: If the cylinder is damaged as a result of attaching pipe clips or saddles to the jacket, any resultant faults will not be covered by the Rheem warranty.
DIMENSIONS AND TECHNICAL DATA
DIMENSIONS AND TECHNICAL DATA TABLE
Model| 6N0325M0
Description| Storage Tank
Storage Capacity| Litres| 325
Delivery Rating| Litres| 315
Weight – Empty| kg| 55
Inlet/Outlet Connections (BSPF)| | Rp1-1/4
T&PR Valve Connection (BSPF)| | Rp3/4
T&PR Valve Setting| kPa| 1000
Expansion Control Valve (ECV)1 Setting| kPa| 850
Max. Water Supply Pressure without ECV1 fitted
with ECV1 fitted
| ****
kPa kPa
| ****
800
680
TYPICAL INSTALLATION – OUTDOOR LOCATION
TYPICAL INSTALLATION – INDOOR LOCATION
CONNECTIONS – PLUMBING
All plumbing work must be carried out by a qualified person and in accordance with the Standard AS/NZS 3500.4 and all local codes and regulatory authority requirements. In New Zealand the installation must also conform to Clauses G12 and H1 of the New Zealand Building Code.
CONNECTION SIZES
- Hot water connection: Rp 1 1/4
- Cold water connection: Rp 1 1/4
- Relief valve connection: Rp 3/4
WATER INLET AND OUTLET
All pipe work must be cleared of foreign matter before connection and purged
before attempting to operate the storage tank. All olive compression fittings
must use brass or copper olives. Use an approved thread sealant such as Teflon
tape on all threaded joints.
An isolation valve and non-return valve must be installed on the cold water
line to the storage tank. An acceptable arrangement is shown in the diagram
and on pages 31 or 32 for multiple installations. Refer also to “Hot Water
Delivery” on page 20 and to “Mains Water Supply” on page 19.
A disconnection union must always be provided at the cold water inlet, primary
flow / return connection and hot water outlet on the storage tank to allow for
disconnection of the storage tank.
This storage tank has a dip tube in the inlet fittings and the outlet
fittings. This must be in place for the water heater to function properly. Do
not remove or damage them by using heat nearby. It will be pushed into the
correct position as the fitting is screwed in.
This storage tank is intended to be permanently connected to the water mains and not connected by a hose-set. A braided flexible hose or semi-flexible connector may be used for connection to the water heater, where permitted by AS/NZS 3500.4.
PIPE SIZES
The pipe sizing of hot water supply systems for commercial installations
should be carried out by persons competent to do so, choosing the most
suitable pipe size for each individual application. Reference to the technical
specifications of the primary heating source, storage tank and local
regulatory authority requirements must be made.
TEMPERATURE PRESSURE RELIEF VALVE
The temperature pressure relief valve is shipped in a plastic bag attached to
the storage tank. The temperature pressure relief valve must be fitted before
the storage tank is operated. Before fitting the relief valve, make sure the
probe has not been bent.
To fit the relief valve:
-
Seal the thread with an approved thread sealant such as Teflon tape – never hemp. Make sure tape does not hang over the end of the thread.
-
Hand tighten the valve into the opening marked “Relief Valve” (refer to the installation diagram on page 24).
-
Using a spanner engaged on the valve’s spanner flats and applying medium pressure to tighten, turn the relief valve an additional ½ to 1 ½ turns to secure and make the joint water tight, leaving the valve drain pointing downwards.
Warning: Do not use a pipe wrench or poor fitting tool on the valve body nor over tighten the valve, as this could damage the valve and prevent safe operation. -
Operate the easing lever on the valve to check the smooth operation of the valve plunger. It is very important the lever is raised and lowered gently. The lever should move smoothly and without undue force.
-
If the lever cannot be moved or is jerky in its movement, then the valve has been damaged and must be replaced.
-
A copper drain line must be fitted to the temperature pressure relief valve (refer to “Relief Valve Drain” on page 27).
-
The valve must be insulated with closed cell polymer insulation or similar (minimum thickness 9 mm) and the insulation installed so as not to impede the operation of the valve.
The insulation must be weatherproof and UV resistant if exposed.
EXPANSION CONTROL VALVE
Local regulations may make it mandatory to install an expansion control valve
(ECV) in the cold water line to the storage tank. In other areas, an ECV is
required if the saturation index is greater than +0.4 (refer to “Water
Supplies” on page 13).
The expansion control valve must always be installed after the non-return
valve and be the last valve installed prior to the storage tank (refer to
diagram on page 25). A copper drain line must be fitted to the expansion
control valve (refer to “Relief Valve Drain” on page 27).
The valve, if installed within 500 mm of the water heater, must be insulated with closed cell polymer insulation or similar (minimum thickness 9 mm) and the insulation installed so as not to impede the operation of the valve. The insulation must be weatherproof and UV resistant if exposed.
RELIEF VALVE DRAIN
DN20 copper drain lines must be fitted to the temperature pressure relief
valve and expansion control valve (if one is installed) to carry the discharge
clear of the storage tank. Connect the drain lines to the valves using
disconnection unions. The drain line from the valve to the point of discharge
should be as short as possible, have a continuous fall all the way from the
storage tank to the discharge outlet and have no tap, valves or other
restrictions in the pipe work. A drain line from a relief valve must comply
with the requirements of AS/NZS 3500.4.
A drain line must be no longer than 9 metres with no more than three bends
greater than 45° before discharging at an outlet or air break. The maximum
length of 9 metres for a drain line is reduced by 1 metre for each additional
bend required of greater than 45°, up to a maximum of three additional bends.
Where the distance to the point of final discharge exceeds this length, the
drain line can discharge into a tundish.
Subject to local regulatory authority approval, the drain lines from the
temperature pressure relief valve and expansion control valve from an
individual storage tank may be interconnected.
The outlet of a drain line must be in such a position that flow out of the
pipe can be easily seen, but arranged so discharge will not cause injury,
damage or nuisance. The termination point of a drain line must comply with the
requirements of AS/NZS 3500.4. Drain lines must not discharge into a safe
tray.
In locations where water pipes are prone to freezing, drain lines must be
insulated, must not exceed 300 mm in length and are to discharge into a
tundish through an air gap of between 75 mm and 150 mm.
If a drain line discharges into a tundish, the drain line from the tundish
must be not less than DN25. The drain line from a tundish must meet the same
requirements as for a drain line from a relief valve.
For multiple installations the drain lines from several storage tanks can
discharge into a common tundish (refer to “Multiple Installations” on pages 29
and 30).
Warning: As the function of the temperature pressure relief valve on this storage tank is to discharge high temperature water under certain conditions, it is strongly recommended the pipe work downstream of the relief valve be capable of carrying water exceeding 93°C. Failure to observe this precaution may result in damage to pipe work and property.
CONNECTIONS – ELECTRICAL
The power supply to the primary heating source and circulating pumps must not
be switched on until the storage tank is filled with water and a satisfactory
megger reading is obtained.
No electrical connections are required to be made on the storage tank, except
if a remote thermostat is fitted. All electrical work and permanent wiring
must be carried out by a qualified person and in accordance with the Wiring
Rules AS/NZS 3000 and all local codes and regulatory authority requirements.
REMOTE THERMOSTAT
It is possible to connect a remote thermostat (Tankstat), Rheem part number
56609162, to the storage tank. The thermostat well is located at the front of
the storage tank at the same height as the primary return connection.
MULTIPLE INSTALLATIONS
A multiple installation of Rheem storage tanks on a single manifold or multiple manifolds is possible, using the Rheem Equa-Flow® manifold system, where large volumes of hot water is required. The Equa-Flow principle will function with storage tanks in line, around a corner or in rows back to back (refer to the diagrams on page 30).
The cold water and hot water manifolds must be designed to balance the flow from each storage tank. To achieve this, there are basic installation requirements and principles which must be followed:
- The maximum number of storage tanks in a bank should be 8, however several banks of storage tanks can be installed.
- The hot water line from the manifold must leave from the opposite end to which the cold water line enters the manifold.
- The storage tanks must be of the same model.
- The cold water line, cold and hot headers and hot water line must be sized to meet the requirements of both AS/NZS 3500.4 and the application.
- The primary flow and return lines must be sized to meet the requirements of AS/NZS 3500.4 and suit the primary heating source. Refer to the literature supplied with the primary heating source.
- A non-return valve, isolation valve and if required a pressure limiting valve and expansion control valve, must be installed on the cold water line to the system.
- A full flow gate valve or ball valve (not a stop tap, as used on a single storage tank installation) must be installed on the cold water branch, primary flow /return branch and hot water branch of each storage tank.
- Non-return valves or pressure limiting valves must not be installed on the branch lines to the storage tanks.
- All fittings, valves and branch lines must be matched sets all the way along the manifold.
- Sufficient space must be left to enable access, servicing or removal of any storage tank.
- The temperature pressure relief valve drain line from each storage tank can terminate at a common tundish (funnel) with a visible air break at each drain discharge point (refer to the diagram on page 30 and to “Relief Drain Line” on page 27).
Refer to the diagrams on pages 30 to 32 for installation.
INSTALLATION DIMENSIONS – RHEEM COMMERCIAL STORAGE TANKS
Notes | Installation Layout Minimum Dimensions |
---|
1. Minimum recommended space between wall and back of storage tank is 100 mm.
2. A minimum of 900 mm (E & F) should be left in front of the storage tank for access, servicing and storage tank removal.
| | Model| A| B| C| D| E | F
| 6N0325M0| 900| 625| 300| 100| 1680| 900
MANIFOLD ARRANGEMENT
COMMISSIONING
TO FILL AND TURN ON THE STORAGE TANK
The power supply to the primary heating source and circulating pumps must not
be switched on until the storage tank is filled with water and a satisfactory
megger reading is obtained.
-
Open all of the hot water tap(s) in the building (don’t forget the shower(s)) and supply cock(s) and valve(s) in the system.
-
Open the isolation valves fully on the cold, flow/return and hot water branches to the storage tank(s) installed in a bank.
-
Open the cold water isolation valve on the cold water line to the storage tank(s).
Air will be forced out of the taps. -
Close each tap as water flows freely from it.
-
Check the pipe work for leaks.
-
Inspect for leaks at the temperature pressure relief valve connection to the water heater.
If a leak is detected, close the cold water isolation valve fully and relieve pressure from the water heater by either operating the easing lever on the temperature pressure relief valve or opening a hot tap. Remove the valve and all of its thread sealant from the threads of the valve. Reapply new thread sealant and refit the valve. Refer to the procedure in “Temperature Pressure Relief Valve” on page 26. -
Operate the easing lever on the temperature pressure relief valve to check the smooth operation of the valve plunger and that water discharges freely from the drain line. It is very important the lever is raised and lowered gently. The lever should move smoothly and without undue force.
If the lever cannot be moved or is jerky in its movement, then the valve has been damaged and must be replaced. -
Switch on the electrical supply at the isolating switch to the circulating pump(s) and turn on the primary water heating plant.
-
When the system has reached its working temperature, check the pipe work again for leaks.
Explain to a responsible officer the functions and operation of the water heating system. Upon completion of the installation and commissioning of the water heating system, leave this guide with a responsible officer.
TO TURN OFF THE STORAGE TANK
If it is necessary to turn off the storage tank on completion of the
installation, such as on a building site or where the premises is vacant,
then:
- Shut down the primary water heating plant and switch off the electrical supply at the isolating switch to the circulating pump(s).
- Close the cold water isolation valve on the cold water line to the storage tank(s) to shut down the entire system, or;
- Close the isolation valves on the cold, flow / return and hot water branches to shut down an individual storage tank in a bank.
DRAINING THE STORAGE TANK
Warning: Exercise care, as water discharged from the storage tank may be of a very high temperature.
To drain the storage tank:
-
Turn off the storage tank (refer to “To Turn Off The Storage Tank” on page 33).
-
Close all hot water taps.
-
Operate the relief valve lever – do not let the lever snap back or you will damage the valve seat. It is very important the lever is raised and lowered gently.
Operating the lever will release the pressure in the storage tank. -
Undo the union at the cold water inlet to the storage tank and attach a hose to the storage tank side of the union.
Let the other end of the hose go to a drain. -
Open the relief valve by holding the lever in the raised position.
This will let air into the storage tank and allow the water to drain through the hose.