RA14 Series
Efficiencies up to 14 SEER/11.5 EER Nominal Sizes 11/2 to 5 Ton [5.28 to 17.6
kW] Cooling Capacities 17.3 to 60.5 kBTU [5.7 to 17.7 kW]
“Proper sizing and installation of equipment is critical to achieve optimal performance. Split system air conditioners and heat pumps must be matched with appropriate coil components to meet Energy Star. Ask your Contractor for details or visit www.energystar.gov.”
- Composite base pan – dampens sound, captures louver panels, eliminates corrosion and reduces number of fasteners needed
- Powder coat paint system – for a long lasting professional finish
- Scroll compressor – uses 70% fewer moving parts for higher efficiency and increased reliability
- Modern cabinet aesthetics – increased curb appeal with visu-ally appealing design
- Curved louver panels – provide ultimate coil protection, enhance cabinet strength, and increased cabinet rigidity
- Optimized fan orifice – optimizes airflow and reduces unit sound
- Rust resistant screws – confirmed through 1500-hour salt spray testing
- PlusOne™ Expanded Valve Space – 3″-4″-5″ service valve space – provides a minimum working area of 27-square inches for easier access
- PlusOne™ Triple Service Access – 15″ wide, industry lead-ing corner service access – makes repairs easier and faster. The two fastener removable corner allows optimal access to internal unit components. Individual louver panels come out once fastener is removed, for faster coil cleaning and easier cabinet reassembly
- Diagnostic service window with two-fastener opening – provides access to the high and low pressure.
- External gauge port access – allows easy connection of “low-loss” gauge ports
- Single-row condenser coil – makes unit lighter and allows thorough coil cleaning to maintain “out of the box” performance
- 35% fewer cabinet fasteners and fastener-free base – allow for faster access to internal components and hassle-free panel removal
- Service trays – hold fasteners or caps during service calls
- QR code – provides technical information on demand for faster service calls
- Fan motor harness with extra long wires allows unit top to be removed without disconnecting fan wire.
Standard Feature Table
Available SKUs
Available Models | Description |
---|---|
RA1418AJ1NA | Classic ® Series 1 1/2 ton 14 SEER Single-Stage Air |
Conditioner-208/230/1/60
RA1418AJ1NB| Classic ® Series 1 1/2 ton 14 SEER Single-Stage Air
Conditioner w/ High/Low Pressure-208/230/1/60
RA1424BJ1NA| Classic ® Series 2 ton 14 SEER Single-Stage Air
Conditioner-208/230/1/60
RA1424BJ1NB| Classic ® Series 2 ton 14 SEER Single-Stage Air Conditioner w/
High/Low Pressure-208/230/1/60
RA1430AJ1NA| Classic ® Series 2 1/2 ton 14 SEER Single-Stage Air
Conditioner-208/230/1/60
RA1430AJ1NB| Classic ® Series 2 1/2 ton 14 SEER Single-Stage Air
Conditioner w/ High/Low Pressure-208/230/1/60
RA1436AC1NB| Classic ® Series 3 ton 14 SEER Single-Stage Air Conditioner w/
High/Low Pressure-208/230/3/60
RA1436AD1NB| Classic ® Series 3 ton 14 SEER Single-Stage Air Conditioner w/
High/Low Pressure-460/3/60
RA1436AJ1NA| Classic ® Series 3 ton 14 SEER Single-Stage Air
Conditioner-208/230/1/60
RA1436AJ1NB| Classic ® Series 3 ton 14 SEER Single-Stage Air Conditioner w/
High/Low Pressure-208/230/1/60
RA1442AD1NB| Classic ® Series 3 1/2 ton 14 SEER Single-Stage Air
Conditioner w/ High/Low Pressure-460/3/60
RA1442CC1NB| Classic ® Series 3 1/2 ton 14 SEER Single-Stage Air
Conditioner w/ High/Low Pressure-208/230/3/60
RA1442CJ1NA| Classic ® Series 3 1/2 ton 14 SEER Single-Stage Air
Conditioner-208/230/1/60
RA1442CJ1NB| Classic ® Series 3 1/2 ton 14 SEER Single-Stage Air
Conditioner w/ High/Low Pressure-208/230/1/60
RA1448AC1NB| Classic ® Series 4 ton 14 SEER Single-Stage Air Conditioner w/
High/Low Pressure-208/230/3/60
RA1448AD1NB| Classic ® Series 4 ton 14 SEER Single-Stage Air Conditioner w/
High/Low Pressure-460/3/60
RA1448AJ1NA| Classic ® Series 4 ton 14 SEER Single-Stage Air
Conditioner-208/230/1/60
RA1448AJ1NB| Classic ® Series 4 ton 14 SEER Single-Stage Air Conditioner w/
High/Low Pressure-208/230/1/60
RA1460CC1NB| Classic ® Series 5 ton 14 SEER Single-Stage Air Conditioner w/
High/Low Pressure-208/230/3/60
RA1460CD1NB| Classic ® Series 5 ton 14 SEER Single-Stage Air Conditioner w/
High/Low Pressure-460/3/60
RA1460CJ1NA| Classic ® Series 5 ton 14 SEER Single-Stage Air
Conditioner-208/230/1/60
RA1460CJ1NB| Classic ® Series 5 ton 14 SEER Single-Stage Air Conditioner w/
High/Low Pressure-208/230/1/60
Introduction to RA14 Air Conditioner
The RA14 is our 14 SEER air conditioner and is part of the Rheem air conditioner product line that extends from 13 to 20 SEER. This highly featured and reliable air conditioner is designed for years of reliable, efficient operation when matched with Rheem indoor aluminum evaporator coils and furnaces or air handler units with aluminum evaporators.
Our unique composite base (1) reduces sound emission, eliminates rattles, significantly reduces fasteners, eliminates corrosion and has integrated brass compressor attachment inserts (2). Furthermore it has incorporated into the design, water management features, means for hand placement (3) for unit maneuvering, screw trays (4) and inserts for lifting off unit pad. (5)
Service Valves (6) are rigidly mounted in the composite base with 3″ between suction and discharge valves, 4″ clearance below service valves and a minimum of 5″ above the service valves, creating industry leading installation ease. The minimum 27 square-inches around the service valves allows ample room to remove service valve schrader prior to brazing, plenty of clearance for easy brazing of the suction and discharge lines to service valve outlets, easy access and hookup of low loss refrigerant gauges (7), and access to the service valve caps for opening. For applications with long-line lengths up to 250 feet total equivalent length, up to 200 feet condenser above evaporator, or up to 80 feet evaporator above condenser, the long-line instructions in the installation manual should be followed.
Controls are accessed from the corner of the unit by removing only two fasteners from the control access cover, revealing the industry’s largest 15″ wide and 14″ tall control area (8). With all this room in the control area the high voltage electrical whip (9) can easily be inserted through the right size opening in the bottom of the control area. Routing it leads directly to contractor lugs for connection. The low voltage control wires (10) are easily connected to units low voltage wiring. If contactor or capacitor (11) needs to be replaced there is more than adequate space to make the repair. Furthermore, if high pressure and low pressure model was not purchased but is desired to be installed in the field, the service window (12) can be removed by removing two screws, to access the high and low side schrader fittings for easy field installation. The entire corner can be removed providing ultimate access to install the high and low pressure switch. (13)
If in the rare event, greater access is needed to internal components, such as the compressor, the entire corner of the unit can be removed along with the top cover assembly to have unprecedented access to interior of the unit (14). Extra wire length is incorporated into each outdoor fan and compressor so top cover and control panel can be positioned next to the unit. With minimal effort the plug can be removed from the compressor and the outdoor fan wires can be removed from the capacitor to allow even more uncluttered access to the interior of the unit (15). Outdoor coil heights range from as short as 22″ to 32″, aiding access to the compressor. Disassembly to this degree and complete reassembly only takes a first time service technician less than 10 minutes. (15)
All units utilize strong formed louver panels which provide industry leading coil protection. Louver removal for coil cleaning is accomplished by removing one screw and lifting the panel out of the composite base pan. (17) All RA14 units utilize single row coils (16) making cleaning easy and complete, restoring the performance of the air conditioner back to out of the box performance levels year after year.
The outdoor fan motor has sleeve bearings and is inherently protected. The motor is totally enclosed for maximum protection from weather, dust and corrosion. Access to the outdoor fan is made by removing four fasteners from the fan grille. The outdoor fan can be removed from the fan grille by removing 4 fasteners in the rare case outdoor fan motor fails. Each cabinet has optimized composite (19) fan orifice assuring efficient and quiet airflow .
The entire cabinet has powder post paint (20) achieving 1000 hour salt spray rating, allowing the cabinet to retain its aesthetics throughout its life.
Scroll compressors with standard internal pressure relief and internal thermal
overload are used on all capacities assuring longevity of high efficient and
quiet operation for the life of the product.
Each unit is shipped with filter drier for field installation and will trap
any moisture or dirt that could contaminate the refrigerant system.
All cabinets have industry leading structural strength due to the composite base pan (21), interlocking corner post (22), formed curved louver panels (23) and drawn top cover (24) making it the most durable cabinet on the market today. Each RA14 capacity has undergone rigorous psychometric testing to assure performance ratings of capacity, SEER and EER per AHRI Standard 210/240 rating conditions. Also each unit bears the UL mark and each unit is certified to UL 1995 safety standards. Each unit has undergone specific strain and modal testing to assure tubing (25) is outside the units natural frequency and that the suction and discharge lines connected to the compressor withstand any starting, steady state operation or shut down forces imposed by the compressor. All units have been sound tested in sound chamber to AHRI 270 rating conditions, and A-weighted Sound Power Level tables produced, assuring units have acceptable noise qualities (see page 9). Each unit has been ran in cooling operation at 95°F and 82°F and sound ratings for the RA14 range from as low as 74 dBA to 77 dBA. All units have been ship tested to assure units meet stringent “over the road” shipping conditions. As manufactured all units in the RA14 family have cooling capability to 55 °F. Addition of low ambient control will allow the unit to operate down to 0°F. Factory testing is performed on each unit. All component parts meet well defined specification and continually go through receiving inspections. Each component installed on a unit is scanned, assuring correct component utilization for a given unit capacity and voltage. All condenser coils are leak tested with pressurization test to 550#’s and once installed and assembled, each units’ complete refrigerant system is helium leak tested. All units are fully charged from the factory for up to 15 feet of piping. All units are factory run tested. The RA14 has a 10-year conditional compressor and parts warranty (registration required).
Optional Accessories
(Refer to accessory chart for model #)
Compressor Crankcase Heater
Protects against refrigerant migration that can occur during low ambient
operation
Compressor Sound Cover
- Reinforced vinyl compressor cover containing a 1½ inch thick batt of fiberglass insulation
- Open edges are sealed with a one-inch wide hook and loop fastening tape
Compressor Hard Start Kit
- Single-phase units are equipped with a PSC compressor motor, this type of motor normally does not need a potential relay and start capacitor
- Kit may be required to increase the compressor starting torque, in conditions such as low voltage
Low Ambient Kit
- Air conditioners operate satisfactorily in the cooling mode down to 55°F outdoor air temperature without any additional controls
- This Kit can be added in the field enabling unit to operate properly down to 0° in the cooling mode
- Crankcase heater and freezestat should be installed on compressors equipped with a low ambient kit 3″/6″/12″
- Gray high density polyethylene feet are available to raise unit off of mounting surface away from moisture
Low Pressure
- Can be added in field enabling the unit to shut off compressor on loss of charge
NOTE: Unit can be purchased with high and low pressure installed at factory. (Refer to SKU list)
High Pressure
- Can be added in field enabling unit to shut off the compressor if unit loses outdoor fan operation.
NOTE: Unit can be purchased with high and low pressure installed at factory. (Refer to SKU list)
Decorative Top
- Can be installed on fan grille
Air Conditioners
Physical Data
PHYSICAL DATA
Model No.| RA1418| RA1424| RA1430| RA1436|
RA1442| RA1448| RA1460
Nominal Tonnage| 1.5| 2.0| 2.5| 3.0| 3.5| 4.0| 5.0
Valve Connections|
Liquid Line O.D. – in.| 3/8| 3/8| 3/8| 3/8| 3/8| 3/8| 3/8
Suction Line O.D. – in.| 3/4| 3/4| 3/4| 3/4| 7/8| 7/8| 7/8
Refrigerant (R410A) furnished oz.¹| 68| 80| 87| 106| 134|
129| 199
Compressor Type| Scroll
Outdoor Coil|
Net face area – Outer Coil| 9.1| 11.1| 12.1| 14.8| 17.3| 18.9| 28.27
Net face area – Inner Coil| —| —| —| —| —| —| —
Tube diameter – in.| 3/8| 3/8| 3/8| 3/8| 3/8| 3/8| 3/8
Number of rows| 1| 1| 1| 1| 1| 1| 1
Fins per inch| 22| 22| 22| 22| 22| 22| 22
Outdoor Fan|
Diameter – in.| 20| 20| 20| 24| 24| 26| 26
Number of blades| 2| 2| 2| 3| 3| 2| 3
Motor hp| 1/10| 1/8| 1/8| 1/6| 1/5| 1/5| 1/3
CFM| 2225| 2295| 2605| 3105| 4105| 4264| 5000
RPM| 1075| 1121| 1075| 850| 833| 820| 795
watts| 130| 138| 142| 173| 236| 236| 239
Shipping weight – lbs.| 143| 148| 158| 178| 207| 232| 268
Operating weight – lbs.| 122| 141| 151| 171| 200| 221| 261
Electrical Data
Line Voltage Data (Volts-Phase-Hz)| 208/230-1- 60|
208/230-1- 60| 208/230-1- 60| 208/230-1- 60|
208/230-1- 60| 208/230-1- 60| 208/230-1- 60
Maximum overcurrent protection (amps)²| 20| 25| 25| 30| 35|
45| 50
Minimum circuit ampacity³| 13| 15| 17| 19| 23| 27| 32
Compressor
Rated load amps| 9.7| 10.9| 12.8| 14.1| 16.7| 19.9| 24.4
Locked rotor amps| 48| 62.9| 64| 77| 109| 109| 110
Condenser Fan Motor
Full load amps| 0.6| 0.8| 0.8| 0.8| 1.2| 1.2| 1
Locked rotor amps| 1.1| 1.5| 1.4| 1.5| 2.0| 2.3| 2.6
Line Voltage Data (Volts-Phase-Hz)| —| —| —| 208/230-3-
60| 208/230-3- 60| 208/230-3- 60| 208/230-3- 60
Maximum overcurrent protection (amps)²| —| —| —| 20| 25| 30| 35
Minimum circuit ampacity³| —| —| —| 13| 16| 18| 21
Compressor
Rated load amps| —| —| —| 9| 11.2| 13.1| 16
Locked rotor amps| —| —| —| 71| 84| 83.1| 110
Condenser Fan Motor
Full load amps| —| —| —| 0.8| 1.2| 1.2| 1
Locked rotor amps| —| —| —| 1.5| 3.0| 2.3| 2.6
Line Voltage Data (Volts-Phase-Hz)| —| —| —| 480-3-
60| 480-3- 60
RA1442AD
| 480-3- 60| 480-3- 60
RA1460CD
Maximum overcurrent protection (amps)²| —| —| —| 15| —| 15| 15
³Minimum circuit ampacity| —| —| —| 8| —| 9| 11
Compressor|
Rated load amps| —| —| —| 5.6| —| 6.1| 7.8
Locked rotor amps| —| —| —| 38| —| 41| 60
Condenser Fan Motor|
Full load amps| —| —| —| 0.5| —| 0.6| 0.5
Locked rotor amps| —| —| —| 1.1| —| 1.6| 1.4
- Refrigerant charge sufficient for 15 ft. length of refrigerant lines. For longer line set requirements see the installation instructions for information about set length and additional refrigerant charge required.
- HACR type circuit breaker of fuse.
- Refer to National Electrical Code manual to determine wire, fuse and disconnect size requirements.
Accessories
Model No.| RA1418| RA1424| RA1430| RA1436|
RA1442| RA1448| RA1460
---|---|---|---|---|---|---|---
Compressor crankcase heater*| 44-17402-44| 44-17402-44| 44-17402-44|
44-17402-44| 44-17402-45| 44-17402-45| 44-17402-45
Low ambient control| RXAD-A08| RXAD-A08| RXAD-A08| RXAD-A08| RXAD-A08|
RXAD-A08| RXAD-A08
Compressor sound cover| 68-23427-26| 68-23427-26| 68-23427-26| 68-23427-26|
68-23427-25| 68-23427-25| 68-23427-25
Compressor hard start kit| SK-A1| SK-A1| SK-A1| SK-A1| SK-A1| SK-A1| SK-A1
Compressor time delay| RXMD-B01| RXMD-B01| RXMD-B01| RXMD-B01| RXMD-B01|
RXMD-B01| RXMD-B01
Low pressure control| RXAC-A07| RXAC-A07| RXAC-A07| RXAC-A07| RXAC-A07|
RXAC-A07| RXAC-A07
High pressure control| RXAB-A07| RXAB-A07| RXAB-A07| RXAB-A07| RXAB-A07|
RXAB-A07| RXAB-A07
Liquid Line Solenoid (24 VAC, 50/60 Hz)| Solenoid Valve| 200RD2T3TVLC|
200RD2T3TVLC| 200RD2T3TVLC| 200RD2T3TVLC| 200RD2T3TVLC| 200RD3T3TVLC|
200RD3T3TVLC
Solenoid Coil| 61-AMG24V| 61-AMG24V| 61-AMG24V| 61-AMG24V| 61-AMG24V|
61-AMG24V| 61-AMG24V
Liquid Line Solenoid (120/240 VAC, 50/60 Hz)| Solenoid Valve| 200RD2T3TVLC|
200RD2T3TVLC| 200RD2T3TVLC| 200RD2T3TVLC| 200RD2T3TVLC| 200RD3T3TVLC|
200RD3T3TVLC
Solenoid Coil| 61-AMG120/240V| 61-AMG120/240V| 61-AMG120/240V| 61-AMG120/240V|
61-AMG120/240V| 61-AMG120/240V| 61-AMG120/240V
Classic Top Cap w/Label| 91-101123-21| 91-101123-21| 91-101123-21|
91-101123-21| 91-101123-21| 91-101123-21| 91-101123-21
- Crankcase Heater recommended with Low Ambient Kit.
Weighted Sound Power Level (dBA)
A-WEIGHTED SOUND POWER LEVEL (dBA)
Unit Size – Voltage, Series| Standard Rating
(dBA)| TYPICAL OCTAVE BAND SPECTRUM (dBA without
tone adjustment)
125| 250| 500| 1000| 2000| 4000| 8000
RA1418| 76.0| 51.4| 59.6| 65.2| 65.9| 64.3| 58.5| 53.7
RA1424| 75.0| 50.0| 59.5| 63.2| 64.4| 61.4| 56.8| 52.6
RA1430| 74.0| 48.8| 57.5| 63.5| 64| 61.9| 56.1| 51
RA1436| 76.0| 52.2| 61.3| 65.4| 65.3| 62.4| 57.3| 53.1
RA1442| 73.0| 51.5| 54.7| 63.5| 63.3| 59.4| 54.9| 48.4
RA1448| 76.0| 52.3| 59.1| 66.7| 65.7| 62.4| 59.3| 55.9
RA1460| 74.8| 62.4| 58.7| 64.5| 64.9| 60.7| 55.3| 50.2
NOTE: Tested in accordance with AHRI Standard 270-08 (not listed in AHRI)
Unit Dimensions
MODEL NO.
| OPERATING| SHIPPING
---|---|---
H (Height)| L (Length)| W (Width)| H
(Height)| L (Length)| W (Width)
INCHES| mm| INCHES| mm| INCHES| mm| INCHES|
mm| INCHES| mm| INCHES| mm
RA1418| 25| 635| 29.75| 755| 29.75| 755| 26.75| 679| 32.38| 822| 32.38| 822
RA1424| 25| 635| 29.75| 755| 29.75| 755| 26.75| 679| 32.38| 822| 32.38| 822
RA1430| 27| 685| 29.75| 755| 29.75| 755| 28.75| 730| 32.38| 822| 32.38| 822
RA1436| 27| 685| 33.75| 857| 33.75| 857| 28.75| 730| 36.38| 924| 36.38| 924
RA1442| 35| 889| 33.75| 857| 33.75| 857| 36.75| 933| 36.38| 924| 36.38| 924
RA1448| 31| 787| 35.75| 908| 35.75| 908| 32.75| 832| 38.38| 975| 38.38| 975
RA1460| 45| 1143| 35.75| 908| 35.75| 908| 45.38| 1153| 38.25| 972| 38.25| 972
- Designates Metric Conversions
CLEARANCES
Control Wiring
Application Guidelines
- Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01 -in. wc.
- inimum outdoor operation air temperature for cooling mode without low-ambient operation accessory is 55°F (12.8°C).
- Maximum outdoor operating air temperature is 125°F (51.7°C).
- For reliable operation, unit should be level in all horizontal planes.
- Use only copper wire for electric connections at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided.
- Do not apply capillary tube indoor coils to these units.
- Factory – supplied filter drier must be installed.
Refrigerant Line Size Information
13 – 16 SEER Single-Stage Air-Conditioners
Unit Size
| ****
Allowable Liquid Line Size
| ****
Allowable Suction Line Size
| Apply Long Line Guidelines if Linear Line Length Exceeds Those Shown
Below (Feet)| Equivalent Length (Feet)
< **25| 26- 50| 51- 75| 76- 100| 101-
125| 126- 150| 151- 175| 176- 200| 201-
225| 226- 250
(- )A13| (- )A14**
A/B
| (-)A14 W| (- )A16| *Maximum Vertical Rise (Outdoor Unit Below Indoor Unit) / Capacity Multiplier**
1.5 Ton
**SEE NOTE 3
| 1/4″| 5/8″| N/R| N/R| N/R| N/R| 25 / 1.00| 50 / 0.99|
62 / 0.98| 43 / 0.98| 24 / 0.97| 5 / 0.97| N/R| N/R| N/R|
N/R
5/16″| 5/8″| N/R| 223| 198| 188| 25 / 1.00| 50 / 0.99| 75 / 0.98| 98 /
0.98| 93 / 0.97| 88 / 0.97| 83 / 0.96| 78 / 0.96| 73 / 0.95| 68 / 0.94
3/8″| 5/8″| 178| 148| 132| 125| 25 / 1.00| 50 / 0.99| 75 / 0.98| 100 / 0.98|
100 / 0.97| 100 / 0.97| 100 / 0.96| 100 / 0.96| 100 / 0.95| 100 / 0.94
1/4″| 3/4″| N/R| N/R| N/R| N/R| 25 / 1.00| 50 / 1.00|
62 / 0.99| 43 / 0.99| 24 / 0.99| 5 / 0.99| N/R| N/R| N/R|
N/R
5/16″| 3/4″| N/R| 223| 198| 188| 25 / 1.00| 50 / 1.00| 75 / 0.99| 98 /
0.99| 93 / 0.99| 88 / 0.99| 83 / 0.99| 78 / 0.98| 73 / 0.98| 68 / 0.98
3/8″| 3/4″**| 178| 148| 132| 125| 25 / 1.00| 50 / 1.00| 75 / 1.00| 100 / 0.99|
100 / 0.99| 100 / 0.99| 100 / 0.99| 100 / 0.98| 100 / 0.98| 100 / 0.98
2 Ton
| 1/4″| 5/8″| N/R| N/R| N/R| N/R| 25 / 0.99| 50 / 0.98|
21 / 0.97| N/R| N/R| N/R| N/R| N/R| N/R|
N/R
5/16″| 5/8″| 243| 193| 175| 175| 25 / 0.99| 50 / 0.98| 75 / 0.97| 87 / 0.96|
77 / 0.95| 69 / 0.94| 61 / 0.93| 53 / 0.92| 45 / 0.91| 37 / 0.90
3/8″| 5/8″| 162| 128| 117| 117| 25 / 0.99| 50 / 0.98| 75 / 0.97| 100 / 0.96|
100 / 0.95| 100 / 0.94| 98 / 0.93| 95 / 0.92| 92 / 0.91| 89 / 0.90
1/4″| 3/4″| N/R| N/R| N/R| N/R| 25 /1.00| 50 / 1.00| 21 /
0.99| N/R| N/R| N/R| N/R| N/R| N/R| N/R
5/16″| 3/4″| 243| 193| 175| 175| 25 /1.00| 50 / 1.00| 75 / 0.99| 87 / 0.99| 77
/ 0.98| 69 / 0.98| 61 / 0.98| 53 / 0.97| 45 / 0.97| 37 / 0.96
3/8″| 3/4″| 162| 128| 117| 117| 25 / 1.00| 50 / 1.00| 75 / 0.99| 100 / 0.99|
100 / 0.98| 100 / 0.98| 98 / 0.98| 95 / 0.97| 93 / 0.97| 90 / 0.96
2.5 Ton
| 5/16″| 5/8″| N/R| N/R| 110| 110| 25 / 0.99| 50 / 0.98| 75 / 0.96|
70 / 0.94| 59 / 0.93| 48 / 0.91| 36 / 0.90| N/R| N/R| N/R
3/8″| 5/8″| 142| 117| 73| 73| 25 / 0.99| 50 / 0.98| 75 / 0.96| 100 / 0.94| 98
/ 0.93| 94 / 0.91| 90 / 0.90| N/R| N/R| N/R
5/16″| 3/4″| 213| 175| 110| 110| 25 / 1.00| 50 / 0.99| 75 / 0.99| 70 / 0.98|
59 / 0.98| 48 / 0.97| 36 / 0.96| 25 / 0.96| 13 / 0.95| N/R
3/8″| 3/4″| 142| 117| 73| 73| 25 / 1.00| 50 / 0.99| 75 / 0.99| 100 / 0.98| 98
/ 0.98| 94 / 0.97| 90 / 0.96| 86 / 0.96| 82 / 0.95| 78 / 0.95
3 Ton
| 5/16″| 5/8″| N/R| N/R| N/R| N/R| 25 / 0.99| 50 / 0.97|
66 / 0.94| 49 / 0.92| 32 / 0.90| N/R| N/R| N/R| N/R|
N/R
3/8″| 5/8″| 108| 85| 90| 82| 25 / 0.99| 50 / 0.97| 75 / 0.94| 95 / 0.92| 89 /
0.90| N/R| N/R| N/R| N/R| N/R
5/16″| 3/4″| N/R| 128| 135| 123| 25 / 1.00| 50 / 0.99| 66 / 0.98| 49 /
0.98| 32 / 0.97| 15 / 0.96| N/R| N/R| N/R| N/R
3/8″| 3/4″| 108| 85| 90| 82| 25 / 1.00| 50 / 0.99| 75 / 0.98| 95 / 0.98| 89 /
0.97| 84 / 0.96| 78 / 0.95| 72 / 0.94| 67 / 0.93| 61 / 0.93
1/2″| 3/4″| 54| 43| 45| 41| 25 / 1.00| 50 / 0.99| 75 / 0.98| 100 / 0.98| 100 /
0.97| 100 / 0.96| 100 / 0.95| 100 / 0.94| 100 / 0.93| 100 / 0.93
5/16″| 7/8″| N/R| 128| 135| 123| 25 / 1.00| 50 / 1.00| 66 / 1.00| 49 /
0.99| 32 / 0.99| 15 / 0.99| N/R| N/R| N/R| N/R
3/8″| 7/8″| 108| 85| 90| 82| 25 / 1.00| 50 / 1.00| 75 / 1.00| 95 / 0.99| 89 /
0.99| 84 / 0.99| 78 / 0.98| 72 / 0.98| 67 / 0.98| 61 / 0.97
1/2″| 7/8″| 54| 43| 45| 41| 25 / 1.00| 50 / 1.00| 75 / 1.00| 100 / 0.99| 100 /
0.99| 100 / 0.99| 100 / 0.98| 100 / 0.98| 100 / 0.98| 100 / 0.97
3.5 Ton
| 3/8″| 3/4″| 150| 102| 75| 75| 25 / 0.99| 50 / 0.98| 75 / 0.97| 88 / 0.96| 80
/ 0.95| 72 / 0.94| 65 / 0.92| 57 / 0.91| 49 / 0.90| N/R
1/2″| 3/4″| 75| 51| 38| 38| 25 / 0.99| 50 / 0.98| 75 / 0.97| 100 / 0.96| 100 /
0.95| 100 / 0.94| 100 / 0.92| 100 / 0.91| 100 / 0.90| N/R
3/8″| 7/8″| 150| 102| 75| 75| 25 / 1.00| 50 / 1.00| 75 / 0.99| 88 / 0.99| 80 /
0.99| 72 / 0.98| 65 / 0.97| 57 / 0.97| 49 / 0.96| 42 / 0.96
1/2″| 7/8″| 75| 51| 38| 38| 25 / 1.00| 50 / 1.00| 75 / 0.99| 100 / 0.99| 100 /
0.99| 100 / 0.98| 100 / 0.97| 100 / 0.97| 100 / 0.96| 100 / 0.96
NOTES:
- Do not exceed 200 ft linear line length.
- Do not exceed 100 ft vertical separation if outdoor unit is above indoor unit.
- 3/4″ suction line should only be used for 1.5 ton systems if outdoor unit is below or at same level as indoor to assure proper oil return.
- Always use the smallest liquid line allowable to minimize refrigerant charge.
- Applications shaded in light gray indicate capacity multipliers between 0.90 and 0.96 which are not recommended, but are allowed.
- Applications shaded in dark gray are not recommended due to excessive liquid or suction pressure drop.
NOTE: Values based on 105°F liquid temperature and 45°F evaporator temperature in cooling mode depending on size
Refrigerant Line Size Information (con’t.)
13 – 16 SEER Single-Stage Air-Conditioners
Unit Size
| ****
Allowable Liquid Line Size
| ****
Allowable Suction Line Size
| Apply Long Line Guidelines if Linear Line Length Exceeds Those Shown
Below (Feet)| Equivalent Length (Feet)
< **25| 26- 50| 51- 75| 76- 100| 101-
125| 126- 150| 151- 175| 176- 200| 201-
225| 226- 250
(- )A13| (- )A14**
A/B
| (-)A14 W| (- )A16| *Maximum Vertical Rise (Outdoor Unit Below Indoor Unit) / Capacity Multiplier**
4 Ton
| 3/8″| 3/4″| 148| 110| N/R| 35| 25 / 0.99| 50 / 0.98| 75 / 0.96| 77 /
0.95| 67 / 0.93| 57 / 0.92| 46 / 0.91| N/R| N/R| N/R
1/2″| 3/4″| 74| 55| N/R| 18| 25 / 0.99| 50 / 0.98| 75 / 0.96| 100 /
0.95| 100 / 0.93| 100 / 0.92| 100 / 0.91| N/R| N/R| N/R
3/8″| 7/8″| 148| 110| N/R| 35| 25 / 1.00| 50 / 0.99| 75 / 0.99| 77 /
0.98| 67 / 0.97| 57 / 0.97| 46 / 0.96| 36 / 0.96| 26 / 0.95| 15 / 0.95
1/2″| 7/8″| 74| 55| N/R| 18| 25 / 1.00| 50 / 0.99| 75 / 0.99| 100 /
0.98| 100 / 0.97| 100 / 0.97| 100 / 0.96| 100 / 0.96| 99 / 0.95| 97 / 0.95
5 Ton
| 3/8″| 3/4″| 78| 0| N/R| 0| 25 / 0.99| 50 / 0.97| 75 / 0.94| 61 / 0.92|
46 / 0.90| N/R| N/R| N/R| N/R| N/R
1/2″| 3/4″| 39| 0| N/R| 0| 25 / 0.99| 50 / 0.97| 75 / 0.94| 100 / 0.92|
100 / 0.90| N/R| N/R| N/R| N/R| N/R
3/8″| 7/8″| 78| 0| N/R| 0| 25 / 1.00| 50 / 0.99| 75 / 0.98| 61 / 0.97|
46 / 0.96| 32 / 0.95| 18 / 0.94| N/R| N/R| N/R
1/2″| 7/8″| 39| 0| N/R| 0| 25 / 1.00| 50 / 0.99| 75 / 0.98| 100 / 0.97|
100 /0.96| 100 / 0.95| 97 / 0.94| 95 / 0.94| 92 / 0.93| 89 / 0.92
3/8″| 1-1/8″| 78| 0| N/R| 0| 25 / 1.01| 50 / 1.01| 75 / 1.00| 61 / 1.00|
46 / 0.99| 32 / 0.99| 18 / 0.99| N/R| N/R| N/R
1/2″| 1-1/8″| 39| 0| N/R| 0| 25 / 1.01| 50 / 1.01| 75 / 1.00| 100 /1.00|
100 / 0.99| 100 / 0.99| 97 / 0.99| 95 / 0.99| 92 / 0.99| 89 / 0.98
NOTES:
- Do not exceed 61 meters linear line length.
- Do not exceed 30 meters vertical separation if outdoor unit is above indoor unit.
- 19.05 mm [3/4 in.] suction line should only be used for 1.5 ton systems if outdoor unit is below or at same level as indoor to assure proper oil return.
- lways use the smallest liquid line allowable to minimize refrigerant charge.
- pplications shaded in light gray indicate capacity multipliers between 0.90 and 0.96 which are not recommended, but are allowed.
- pplications shaded in dark gray are not recommended due to excessive liquid or suction pressure drop.
Designates Metric Conversions
Performance Data @ AHRI Standard Conditions – Cooling
Tested Combination
Outdoor Unit| Indoor Coil| Total Capacity BTU/H
[kW]| Net Sensible BTU/H [kW]| Net Latent BTU/H [kW]|
SEER| EER| Indoor CFM [L/s]
RA1418AJ1| RCF2417STA+RXMD-C04| 17800| [5.2]| 12100| [3.5]| 5700 [1.7]| 14.00|
11.50| 600 [283.2]
RA1424BJ1| RCF2417STA+RXMD-C04| 23200| [6.8]| 17500| [5.2]| 5700 [1.7]| 14.00|
11.50| 800 [376.0]
RA1430AJ1| RCF3617STA+RXMD-C04| 28800| [8.4]| 19500| [5.7]| 9300 [2.7]| 14.00|
11.50| 1000 [471.9]
RA1436AJ1| RCF3617STA+RXMD-C04| 34200 [10.0]| 23200| [6.8]| 11000 [3.2]|
14.00| 11.50| 1050 [495.5]
RA1436AC1| RCF3617STA+RXMD-C04| 34200 [10.0]| 23200| [6.8]| 11000 [3.2]|
14.00| 11.50| 1050 [495.5]
RA1436AD1| RCF3617STA+RXMD-C04| 34200 [10.0]| 23200| [6.8]| 11000 [3.2]|
14.00| 11.50| 1050 [495.5]
RA1442CJ1| RCF4821STA+RXMD-C04| 39500 [11.6]| 28900| [8.5]| 10600 [3.1]|
14.00| 11.50| 1350 [634.5]
RA1442CC1| RCF4821STA+RXMD-C04| 39500 [11.6]| 28900| [8.5]| 10600 [3.1]|
14.00| 11.50| 1350 [634.5]
RA1448AJ1| RCF4821STA+RXMD-C04| 46000 [13.5]| 31200| [9.1]| 14800 [4.3]|
14.00| 11.70| 1450 [684.3]
RA1448AC1| RCF4821STA+RXMD-C04| 46000 [13.5]| 31200| [9.1]| 14800 [4.3]|
14.00| 11.70| 1450 [684.3]
RA1448AD1| RCF4821STA+RXMD-C04| 46000 [13.5]| 31200| [9.1]| 14800 [4.3]|
14.00| 11.70| 1450 [684.3]
RA1460CJ1| RCF6024STA+RXMD-C04| 57000 [16.8]| 40200 [11.8]| 16800 [5.0]|
14.00| 11.50| 1550 [731.5]
RA1460CD1| RCF6024STA+RXMD-C04| 57000 [16.8]| 40200 [11.8]| 16800 [5.0]|
14.00| 11.50| 1550 [731.5]
RA1460CC1| RCF6024STA+RXMD-C04| 57000 [16.8]| 40200 [11.8]| 16800 [5.0]|
14.00| 11.50| 1550 [731.5]
Note: This data includes DTC (Designated Test Combination) ratings and is for reference purposes only. A full listing of official ratings and system match ups, along with downloadable certificates, can be accessed from the AHRI website: www.ahridirectory.org
Designates Metric Conversions
GUIDE SPECIFICATIONS
General
System Description
Outdoor-mounted, air-cooled, split-system air conditioner com-posite base pan unit suitable for ground or rooftop installation. Unit consists of a hermetic compressor, an air-cooled coil, pro-peller-type condenser fan, suction and legend line service valve, and a control box. Unit will discharge supply air upward as shown on contract drawings. Unit will be used in a refrigeration circuit to match up to a coil unit.
Quality Assurance
- Unit will be rated in accordance with the latest edition of AHRI Standard 210.
- Unit will be certified for capacity and efficiency, and listed in the latest AHRI directory.
- Unit construction will comply with latest edition of ANSI/ ASHRAE and with NEC.
- Unit will be constructed in accordance with UL standards and will carry the UL label of approval. Unit will have c-UL-us approval.
- Unit cabinet will be capable of withstanding ASTM B117 1000- hr salt spray test.
- Air-cooled condenser coils will be leak tested at 150 psig and pressure tested at 550 psig.
- Unit constructed in ISO9001 approved facility.
- Delivery, Storage, and Handling
- Unit will be shipped as single package only and is stored and handled per unit manufacturer’s recommendations. Warranty (for inclusion by specifying engineer) — U.S. and Canada only.
Products
Equipment
Factory-assembled, single-piece, air-cooled air conditioner unit. Contained
within the unit enclosure is all factory wiring, piping, controls, compressor,
refrigerant charge R-410A, and special fea-tures required prior to field
start-up.
Unit Cabinet
- Unit cabinet will be constructed of galvanized steel, bonder- ized, and coated with a powder coat paint.
- All units constructed with louver coil protection and corner post. Louver can be removed by removing one fastener per louver panel.
AIR-COOLED, SPLIT-SYSTEM AIR CONDITIONER RA14 1-1/2 TO 5 NOMINALTONS
Fans
- Condenser fan will be direct-drive propeller type, discharging air upward.
- Condenser fan motors will be totally enclosed, 1-phase type with class B insulation and permanently lubricated bearings. Shafts will be corrosion resistant.
- Fan blades will be statically and dynamically balanced.
- Condenser fan openings will be equipped with coated steel wire safety guards.
Compressor
- Compressor will be hermetically sealed.
- Compressor will be mounted on rubber vibration isolators.
Condenser Coil
- Condenser coil will be air cooled.
- Coil will be constructed of aluminum fins mechanically bonded to copper tubes.
Refrigeration Components
- Refrigeration circuit components will include liquid-line shutoff valve with sweat connections, vapor-line shutoff valve with sweat connections, system charge of R-410A refrigerant, and compressor oil.
- Unit will be equipped with filter drier for R-410A refrigerant for field installation.
Operating Characteristics
- The capacity of the unit will meet or exceed Btuh at a suction temperature of °F/°C. The power consumption at full load will not exceed _____ kW.
- Combination of the unit and the evaporator or fan coil unit will have a total net cooling capacity of Btuh or greater at conditions of CFM entering air temperature at the evaporator at
- °F/°C wet bulb and °F/°C dry bulb, and air entering the unit at °F/°C.
- The system will have a SEER of _____ Btuh/watt or greater at DOE conditions.
Electrical Requirements
- Nominal unit electrical characteristics will be, single phase, 60 hz. The unit will be capable of satisfactory operation within voltage limits of v to v.
- Nominal unit electrical characteristics will be, three-phase, 60 hz. The unit will be capable of satisfactory operation within voltage limits of v to v.
- Unit electrical power will be single point connection.
- Control circuit will be 24v.
Special Features
- Refer to section of this literature identifying accessories and descriptions for specific features and available enhancements.
GENERAL TERMS OF LIMITED WARRANTY
Rheem will furnish a replacement for any part of this product which fails in
normal use and service within the applicable period stated, in accordance with
the terms of the limited warranty.
For complete details of the Limited and Conditional Warranties, including
applicable terms and conditions, contact your local contractor or the
Manufacturer for a copy of the product warranty certificate.
Conditional Parts (Registration Required)………………………….Ten (10) Years
In keeping with its policy of continuous progress and product improvement, Rheem reserves the right to make changes without notice
- Rheem Heating, Cooling & Water Heating
- 5600 Old Greenwood Road
- Fort Smith, Arkansas 72908
- www.rheem.com