apollo SA4700-102APO Intelligent Input-Output Module Installation Guide

June 12, 2024
APOLLO

**Intelligent Input/Output Unit
Installation Guide

**

Part No Product Name
SA4700-102APO Intelligent Input/Output Unit

Technical Information

All data is supplied subject to change without notice. Specications are typical at 24V, 25°C and 50% RH unless otherwise stated.

Supply Voltage 17-35V dc
Quiescent Current 500µA
Power-up Surge Current 900µA
Relay Output Contact Rating 1A at 30V dc or ac
LED Current 1.6mA per LED
Maximum Loop Current (Imax; L1 in/out) 1A
Operating Temperature 0°C to 70°C
Humidity 0% to 95% RH (no condensation or icing)
Approvals EN 54-17 & EN 54-18

For additional technical information please refer to the following documents which are available on request.
PP2553 – Intelligent Input/Output Unit

Drill holes where required.apollo SA4700-102APO Intelligent Input-Output
Module - Drill holes Do not over tighten screwsapollo SA4700-102APO Intelligent Input-Output Module - tighten
screws Remove knockouts and tglands where required.![apollo SA4700-102APO Intelligent Input-Output Module

  • nockouts](https://manuals.plus/wp-content/uploads/2023/08/apollo-SA4700 -102APO-Intelligent-Input-Output-Module-nockouts.png)apollo SA4700-102APO
Intelligent Input-Output Module - glands Do not over tighten screwsapollo SA4700-102APO Intelligent
Input-Output Module - over The 8th segment must be in set to ‘0’ for Discovery / XP95 operationapollo
SA4700-102APO Intelligent Input-Output Module - ee Table
1 All CI tests must be carried before connecting the interface. For connectivity instruction see Figs 1, 2 & 3apollo SA4700-102APO Intelligent Input-Output Module -
carried Note the alignment marksapollo
SA4700-102APO Intelligent Input-Output Module -
alignmentapollo SA4700-102APO
Intelligent Input-Output Module - tated

Addressing

| XP9S / Discovery Systems| CoreProtocol Systems
---|---|---
Segment I| 1| Sets the address| Sets the address
2
3
4
5
6
7
8| Set to ‘0’ (Fault value is returned if set to ‘1’)
FS| Enables failsafe mode (compliant with 13S7273-4 for door holders)| Enables failsafe mode (compliant with B57273-4 for door holders)
| LED| Enables/Disables LED (except Isolator LED)| Enables/Disables LED (except Isolator LED)

Note : On mixed systems addresses 127 and 128 are reserved. Refer to system’s panel manufacturer for further information.

Address Setting Examples

|
---|---

Connectivity Examples

apollo SA4700-102APO Intelligent Input-Output Module - Fig.
1apollo SA4700-102APO Intelligent
Input-Output Module - Fig. 1apollo
SA4700-102APO Intelligent Input-Output Module - Fig. 3 When operated under XP95 or Discovery Protocols, EN54-13 type 2 devices can be connected. In case EN54-13 type 1 devices need to be connected they must be installed directly next to this module, with no transmission path according to EN 54-13.

LED Status Indicator

RLY Continuous Red Relay Active
Continuous Yellow Fault

POLL/
ISO| Flashing Green| Device Polled
Continuous Yellow| Isolator Active
IP| Continuous Red| Input Active
Continuous Yellow| Input Fault

Note : Not all LEDs can be on simultaneously.

Commissioning

The installation must conform to BS5839–1 (or applicable local codes).
Maintainence
Removal of the external cover must be carried out using a at screwdriver or similar tool.
Caution
Unit damage. No electrical supply greater than 50V ac rms or 75V dc should be connected to any terminal of this Input/Output Unit.
Note : For compliance with Electrical Safety Standards the sources switched by the output relays must be limited to a 71V transient over-voltage condition.
Contact Apollo for more information.

Troubleshooting

Before investigating individual units for faults, it is important to check that the system wiring is fault free. Earth faults on data loops or interface zone wiring may cause communication errors. Many fault conditions are the result of simple wiring errors. Check all connections to the unit.

Problem Possible Cause
No response or missing Incorrect address setting Incorrect loop wiring

Incorrect address setting
Incorrect loop wiring| Incorrect input wiring
Incorrect wiring
Control panel has incorrect cause
and effect programming
Relay energised continuously| Incorrect loop wiring
Incorrect address setting
Analogue value unstable| Dual address
Loop data fault, data corruption
Constant Alarm| Incorrect wiring
Incorrect end-of-line resistor  tted
Incompatible control panel software
Isolator LED on| Short-circuit on loop wiring
Wiring reverse polarity
Too many devices between isolators

**Mode Table***

Mode Description
1 DIL Switch XP Mode
2 Alarm Delays
3 Output and N/O input (can be equivalent for Output only)
4 Output and N/C input
5 Output with Feedback (N/C)
6 Failsafe Output with Feedback (N/C)
7 Failsafe Output without Feedback
8 Momentary Input Activation Sets Output Relay
9 Input Activation Sets Output

*CoreProtocol enabled systems only

© Apollo Fire Detectors Limited 20Apollo Fire
Detectors Limited, 36 Brookside Road, HPO9 1JR, UK

Tel: +44 (0) 23 9249 2412
Fax: +44 (0) 23 9

Email:techsalesemails@apollo-re.com
Website:

Documents / Resources

| apollo SA4700-102APO Intelligent Input-Output Module [pdf] Installation Guide
SA4700-102APO Intelligent Input-Output Module, SA4700-102APO, Intelligent Input-Output Module, Input-Output Module, Module
---|---

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals