TOSHIBA MCY-MHP0806HS8-E MiNi SMMSe VRF Air Conditioning Heat Pump System Installation Guide
- June 12, 2024
- Toshiba
Table of Contents
MCY-MHP0806HS8-E MiNi SMMSe VRF Air Conditioning Heat Pump System
Product Information
The product is an Air Conditioner (Multi Type) with the model
name MCY-MHP0806HS8-E and MCY-MHP1006HS8-E. It is a heat pump model
designed for commercial use. The air conditioner uses R410A, an
environmentally friendly refrigerant.
Product Usage Instructions
Definition of Qualified Installer or Qualified Service
Person
The air conditioner must be installed, maintained, repaired, and
removed by a qualified installer or qualified service person. A
qualified installer or qualified service person is an agent who has
the qualifications and knowledge required for these tasks. When any
of these jobs need to be done, it is recommended to ask a qualified
installer or qualified service person to perform them.
Definition of Protective Gear
When transporting, installing, maintaining, repairing, or
removing the air conditioner, it is important to wear protective
gloves and safety work clothing. In addition to normal protective
gear, specific protective gear should be worn for
electrical-related work, work done at heights (50 cm or more),
transportation of heavy objects, and repair of the outdoor unit.
Failure to wear proper protective gear can lead to injuries such as
burns, electric shocks, and other injuries.
Warning Indications on the Air Conditioner Unit
-
WARNING ELECTRICAL SHOCK HAZARD: Disconnect
all remote electric power supplies before servicing. -
WARNING Moving parts: Do not operate the unit
with the grille removed. Stop the unit before servicing. -
CAUTION High temperature parts: Be cautious of
high temperature parts when removing panels to avoid burns. -
CAUTION Do not touch the aluminum fins:
Touching the aluminum fins may result in injury. -
CAUTION BURST HAZARD: Open the service valves
before operation to prevent burst. Never recover the refrigerant
into the outdoor unit. -
CAUTION Do not climb onto the top side:
Climbing onto the top side may result in injury. -
CAUTION Do not climb onto the fan guard:
Climbing onto the fan guard may result in injury.
Precautions for Safety
Before using the air conditioner, please follow these safety
precautions:
-
Read and understand all instructions provided in the
installation manual. -
Ensure that the air conditioner is installed, maintained,
repaired, and removed by a qualified installer or qualified service
person. -
Wear proper protective gear when handling the air
conditioner. -
Disconnect all remote electric power supplies before
servicing. -
Stop the unit before servicing and do not operate it with the
grille removed. -
Be cautious of high temperature parts and avoid touching the
aluminum fins. -
Open the service valves before operation to prevent burst and
never recover refrigerant into the outdoor unit. -
Avoid climbing onto the top side or fan guard of the air
conditioner.
AIR CONDITIONER (MULTI TYPE)
Installation Manual
Outdoor Unit
Model name:
Heat Pump Model
MCY-MHP0806HS8-E MCY-MHP1006HS8-E
For commercial use
DHV2 3 0 7 2 0 1 – 0 3
English Español Français Italiano Deutsch Português Polski Cesky Hrvatski
Magyar Türkçe Nederlands Svenska Suomi Norsk Dansk Românã Eesti Latviski
Slovenèina Slovensèina
Original instruction ADOPTION OF NEW REFRIGERANT
This Air Conditioner uses R410A an environmentally friendly refrigerant.
1
Installation Manual
Contents
1 Precautions for Safety . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . 4 2 Accessory Parts . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . 8 3 Installation of New
Refrigerant Air Conditioner . . . . . . . . . . . . . . . . . 8 4 Installation
Conditions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . 9 5 Refrigerant Piping . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . 13 6 Electric Wiring . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 7 Address
Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . 28 8 Test Run . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . 36 9 Troubleshooting . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
EN-1
EN-2
EN
Thank you for purchasing this Toshiba air conditioner. This Installation
Manual describes the installation method of the outdoor unit. For installation
of indoor units, follow the Installation Manual supplied with the indoor unit.
Moreover, as this installation manual includes the important articles
concerning the “Machinery” Directive (Directive 2006/42/EC), please read
through the manual and make sure you understand it. After installation, give
this Installation Manual, the Owner’s Manual and the Installation Manual
supplied with the indoor unit to the customer and tell the customer to keep
them safe. Prepare an exclusive power source for indoor units, independent to
that for outdoor units. Y-shaped branching joints or a branching header
(separately purchased) are required for connecting pipes between indoor and
outdoor units. Choose either of them considering the system capacity
concerning piping. For installing branching pipes, refer to the installation
manual of the Y-shaped branching unit or branching header (separately
purchased).
Generic Denomination: Air Conditioner
Definition of Qualified Installer or Qualified Service Person
The air conditioner must be installed, maintained, repaired and removed by a
qualified installer or qualified service person. When any of these jobs is to
be done, ask a qualified installer or qualified service person to do them for
you. A qualified installer or qualified service person is an agent who has the
qualifications and knowledge described in the table below.
Agent
Qualified installer
Qualifications and knowledge which the agent must have
· The qualified installer is a person who installs, maintains, relocates and
removes the air conditioners made by Toshiba Carrier Corporation. He or she
has been trained to install, maintain, relocate and remove the air
conditioners made by Toshiba Carrier Corporation or, alternatively, he or she
has been instructed in such operations by an individual or individuals who
have been trained and is thus thoroughly acquainted with the knowledge related
to these operations.
· The qualified installer who is allowed to do the electrical work involved in
installation, relocation and removal has the qualifications pertaining to this
electrical work as stipulated by the local laws and regulations, and he or she
is a person who has been trained in matters relating to electrical work on the
air conditioners made by Toshiba Carrier Corporation or, alternatively, he or
she has been instructed in such matters by an individual or individuals who
have been trained and is thus thoroughly acquainted with the knowledge related
to this work.
· The qualified installer who is allowed to do the refrigerant handling and
piping work involved in installation, relocation and removal has the
qualifications pertaining to this refrigerant handling and piping work as
stipulated by the local laws and regulations, and he or she is a person who
has been trained in matters relating to refrigerant handling and piping work
on the air conditioners made by Toshiba Carrier Corporation or, alternatively,
he or she has been instructed in such matters by an individual or individuals
who have been trained and is thus thoroughly acquainted with the knowledge
related to this work.
· The qualified installer who is allowed to work at heights has been trained
in matters relating to working at heights with the air conditioners made by
Toshiba Carrier Corporation or, alternatively, he or she has been instructed
in such matters by an individual or individuals who have been trained and is
thus thoroughly acquainted with the knowledge related to this work.
Installation Manual
Qualified service person
· The qualified service person is a person who installs, repairs, maintains,
relocates and removes the air conditioners made by Toshiba Carrier
Corporation. He or she has been trained to install, repair, maintain, relocate
and remove the air conditioners made by Toshiba Carrier Corporation or,
alternatively, he or she has been instructed in such operations by an
individual or individuals who have been trained and is thus thoroughly
acquainted with the knowledge related to these operations.
· The qualified service person who is allowed to do the electrical work
involved in installation, repair, relocation and removal has the
qualifications pertaining to this electrical work as stipulated by the local
laws and regulations, and he or she is a person who has been trained in
matters relating to electrical work on the air conditioners made by Toshiba
Carrier Corporation or, alternatively, he or she has been instructed in such
matters by an individual or individuals who have been trained and is thus
thoroughly acquainted with the knowledge related to this work.
· The qualified service person who is allowed to do the refrigerant handling
and piping work involved in installation, repair, relocation and removal has
the qualifications pertaining to this refrigerant handling and piping work as
stipulated by the local laws and regulations, and he or she is a person who
has been trained in matters relating to refrigerant handling and piping work
on the air conditioners made by Toshiba Carrier Corporation or, alternatively,
he or she has been instructed in such matters by an individual or individuals
who have been trained and is thus thoroughly acquainted with the knowledge
related to this work.
· The qualified service person who is allowed to work at heights has been
trained in matters relating to working at heights with the air conditioners
made by Toshiba Carrier Corporation or, alternatively, he or she has been
instructed in such matters by an individual or individuals who have been
trained and is thus thoroughly acquainted with the knowledge related to this
work.
Definition of Protective Gear
When the air conditioner is to be transported, installed, maintained, repaired
or removed, wear protective gloves and `safety’ work clothing. In addition to
such normal protective gear, wear the protective gear described below when
undertaking the special work detailed in the table below. Failure to wear the
proper protective gear is dangerous because you will be more susceptible to
injury, burns, electric shocks and other injuries.
Work undertaken All types of work
Electrical-related work
Work done at heights (50 cm or more) Transportation of heavy objects Repair of
outdoor unit
Protective gear worn Protective gloves `Safety’ working clothing Gloves to
provide protection for electricians Insulating shoes Clothing to provide
protection from electric shock Helmets for use in industry
Shoes with additional protective toe cap
Gloves to provide protection for electricians
EN-3
2
EN-4
3
Warning Indications on the Air Conditioner Unit
Warning indication
WARNING ELECTRICAL SHOCK HAZARD
Disconnect all remote electric power supplies before servicing.
WARNING
Moving parts. Do not operate unit with grille removed. Stop the unit before
the servicing.
CAUTION
High temperature parts. You might get burned when removing this panel.
CAUTION
Do not touch the aluminum fins of the unit. Doing so may result in injury.
Description
WARNING ELECTRICAL SHOCK HAZARD Disconnect all remote electric power supplies
before servicing.
WARNING Moving parts. Do not operate unit with grille removed. Stop the unit
before the servicing.
CAUTION High temperature parts. You might get burned when removing this panel.
CAUTION Do not touch the aluminum fins of the unit. Doing so may result in
injury.
CAUTION BURST HAZARD
Open the service valves before the operation, otherwise there might be the
burst. Never recover the refrigerant into the outdoor unit.
CAUTION Do not climb onto the top side.
Doing so may result in injury.
Installation Manual
CAUTION BURST HAZARD Open the service valves before the operation, otherwise
there might be the burst. Never recover the refrigerant into the outdoor unit.
CAUTION Do not climb onto the fan guard. Doing so may result in injury.
EN-5
EN-6
EN
1 Precautions for Safety
The manufacturer shall not assume any liability for the damage caused by not
observing the description of this manual.
WARNING
General · Before starting to install the air conditioner, read through the
Installation Manual carefully, and follow its instructions to install the air
conditioner. Otherwise, falling down of the unit may occur, or the unit may
cause noise, vibration or water leakage. · Only a qualified installer or
qualified service person is allowed to do installation work. If installation
is carried out by an unqualified individual, a fire, electric shocks, injury,
water leakage, noise or vibration may result. · Do not use any refrigerant
different from the one specified for complement or replacement. Otherwise,
abnormally high pressure may be generated in the refrigeration cycle, which
may result in a failure or explosion of the product or an injury to your body.
· If using separately sold products, make sure to use Toshiba specified
products only. Using unspecified products may cause fire, electric shock,
water leak or other failure. · Before opening the service panel of the outdoor
unit, set the circuit breaker to the OFF position. Failure to set the circuit
breaker to the OFF position may result in electric shocks through contact with
the interior parts. Only a qualified installer or qualified service person is
allowed to remove the service panel of the outdoor unit and do the work
required. · Before carrying out the installation, maintenance, repair or
removal work, be sure to set the circuit breakers for both the indoor and
outdoor units to the OFF position. Otherwise, electric shock may result. ·
Place a “Work in progress” sign near the circuit breaker while the
installation, maintenance, repair or removal work is being carried out. There
is a danger of electric shocks if the circuit breaker is set to ON by mistake.
Installation Manual
· Only a qualified installer or qualified service person is allowed to
undertake work at heights using a stand of 50 cm or more.
· When working at heights, use a ladder which complies with the ISO 14122
standard, and follow the procedure in the ladders instructions. Also wear a
helmet for use in industry as protective gear to undertake the work.
· Wear protective gloves and safety work clothing during installation,
servicing and removal.
· Do not touch the aluminium fin of the outdoor unit. You may injure yourself
if you do so. If the fin must be touched for some reason, first put on
protective gloves and safety work clothing, and then proceed.
· Do not climb onto or place objects on top of the outdoor unit. You may fall
or the objects may fall off of the outdoor unit and result in injury.
· When working at height, put a sign in place so that no-one will approach the
work location before proceeding with the work. Parts or other objects may fall
from above, possibly injuring a person below. Also, be sure that workers put
on helmets.
· When cleaning the filter or other parts of the outdoor unit, set the circuit
breaker to OFF without fail, and place a “Work in progress” sign near the
circuit breaker before proceeding with the work.
· The refrigerant used by this air conditioner is the R410A. · You shall
ensure that the air conditioner is transported in stable
condition. If you find any part of the product broken, contact your dealer. ·
Do not modify the products. Do not also disassemble or modify the
parts. It may cause a fire, electric shock or injury. · Before starting to
repair the air conditioner, read carefully through
the Service Manual, and repair the air conditioner by following its
instructions. · Only qualified service person is allowed to repair the air
conditioner. Repair of the air conditioner by unqualified person may give rise
to a fire, electric shocks, injury, water leaks and/or other problem. · Once
the repair work has been completed, check for refrigerant leaks, and check the
insulation resistance and water drainage. Then
EN-7
4
EN-8
5
Installation Manual
perform a trial run to check that the air conditioner is running properly. ·
This appliance is intended to be used by expert or trained users in
shops, in light industry, or for commercial use by lay persons. · This
appliance is not intended for use by persons (including children)
with reduced physical, sensory or mental capabilities, or lack of experience
and knowledge, unless they have been given supervision or instruction
concerning use of the appliance by a person responsible for their safety. ·
Children should be supervised to ensure that they do not play with the
appliance.
Selection of installation location · If you install the unit in a small room,
take appropriate measures to
prevent the refrigerant from exceeding the limit concentration even if it
leaks. Consult the dealer from whom you purchased the air conditioner when you
implement the measures. Accumulation of highly concentrated refrigerant may
cause an oxygen deficiency accident. · Do not install the air conditioner in a
location that may be subject to a risk of exposure to a combustible gas. If a
combustible gas leaks and becomes concentrated around the unit, a fire may
occur. · When transporting the air conditioner, wear shoes with additional
protective toe caps. · When transporting the air conditioner, do not take hold
of the bands around the packing carton. You may injure yourself if the bands
should break. · Do not place any combustion appliance in a place where it is
directly exposed to the wind of air conditioner, otherwise it may cause
imperfect combustion. · Places where the operation sound of the outdoor unit
may cause a disturbance. (Especially at the boundary line with a neighbour,
install the air conditioner while considering the noise.) · When transporting
the air conditioner, use a forklift and when moving the air conditioner by
hand, move the unit with 6 people.
Installation
EN-9
· Follow the instructions in the installation manual to install the air
conditioner. Failure to follow these instructions may cause the product to
fall down or topple over or give rise to noise, vibration, water leakage, etc.
· The designated bolts (M12) and nuts (M12) for securing the outdoor unit must
be used when installing the unit.
· Install the outdoor unit property in a location that is durable enough to
support the weight of the outdoor unit. Insufficient durability may cause the
outdoor unit to fall, which may result in injury.
· Install the unit in the prescribed manner for protection against strong wind
and earthquake. Incorrect installation may result in the unit falling down, or
other accidents.
· Be sure to fix the screws back which have been removed for installation or
other purposes.
Refrigerant piping · Install the refrigerant pipe securely during the
installation work
before operating the air conditioner. If the compressor is operated with the
valve open and without refrigerant pipe, the compressor sucks air and the
refrigeration cycles is over pressurized, which may cause a injury. · Tighten
the flare nut with a torque wrench in the specified manner. Excessive tighten
of the flare nut may cause a crack in the flare nut after a long period, which
may result in refrigerant leakage. · Ventilate the air if the refrigerant gas
leaks during installation. If the leaked refrigerant gas comes into contact
with fire, toxic gas may be produced. · After installation work, check the
refrigerant gas does not leak. If the refrigerant gas leaks in the room,
poisonous gas generates when gas touches to fire such as fan heater, stove or
cocking stove though the refrigerant gas itself is innocuous. · When the air
conditioner has been installed or relocated, follow the instructions in the
Installation Manual and purge the air completely so that no gases other than
the refrigerant gas will be mixed in the
EN-10
Installation Manual
EN
refrigerating cycle. Failure to purge the air completely may cause the air
conditioner to malfunction. · Nitrogen gas must be used for the airtight test.
· The charge hose must be connected in such a way that it is not slack. · If
refrigerant gas has leaked during the installation work, ventilate the room
immediately. If the leaked refrigerant gas comes in contact with fire, noxious
gas may be generated.
Electrical wiring · Only a qualified installer or qualified service person is
allowed to
carry out the electrical work of the air conditioner. Under no circumstances
must this work be done by an unqualified individual since failure to carry out
the work properly may result in electric shocks or electrical leaks. · When
connecting the electrical wires, repairing the electrical parts or undertaking
other electrical jobs, wear gloves to provide protection for electricians,
insulating shoes and clothing to provide protection from electric shocks.
Failure to wear this protective gear may result in electric shocks. · When
executing address setting, test run, or troubleshooting through the checking
window on the electric parts box, put on insulated gloves to provide
protection from electric shock. Otherwise you may receive an electric shock. ·
Use wiring that meets the specifications in the Installation Manual and the
stipulations in the local regulations and laws. Use of wiring which does not
meet the specifications may give rise to electric shocks, electrical leakage,
smoking or a fire. · Check that the product is properly earthed. (grounding
work) Incomplete earthing may cause electric shock. · Do not connect the earth
line to a gas pipe, water pipe, lightning conductor, or a telephone earth
line. · After completing the repair or relocation work, check that the ground
wires are connected properly. · Install a circuit breaker that meets the
specifications in the installation
EN-11
6
manual and the stipulations in the local regulations and laws. · Install the
circuit breaker where it can be easily accessed by the
qualified service person. · When installing the circuit breaker outdoors,
install one which is
designed to be used outdoors. · Under no circumstances must the power cable be
extended.
Connection trouble in the places where the cable is extended may give rise to
smoking or a fire. · Electrical wiring work shall be conducted according to
law and regulation in the community and installation manual. Failure to do so
may result in electrocution or short circuit. · Do not supply power from the
power terminal block equipped on the outdoor unit to another outdoor unit.
Capacity overflow may occur on the terminal block and may result in fire. ·
When carrying out electric connection, use the wire specified in the
Installation Manual and connect and fix the wires securely to prevent them
applying external force to the terminals. Improper connection or fixing may
result in fire. · If the supply cord is damaged, it must be replaced by the
manufacturer, its service agent or similarly qualified persons in order to
avoid a hazard.
Installation of earth leakage circuit breaker · Install the earth leakage
circuit breaker that meets the stipulations
in the local regulations and laws. · The earth leakage circuit breaker needs
to have over-current
protection and leakage prevention function that can be manually reset.
Test run · Before operating the air conditioner after having completed the
work, check that the electrical parts box cover of the indoor unit and service
panel of the outdoor unit are closed, and set the circuit breaker to the ON
position. You may receive an electric shock if the power is turned on without
first conducting these checks. · When you have noticed that some kind of
trouble (such as when an
EN-12
7
Installation Manual
error display has appeared, there is a smell of burning, abnormal sounds are
heard, the air conditioner fails to cool or heat or water is leaking) has
occurred in the air conditioner, do not touch the air conditioner yourself but
set the circuit breaker to the OFF position, and contact a qualified service
person. Take steps to ensure that the power will not be turned on (by marking
“out of service” near the circuit breaker, for instance) until qualified
service person arrives. Continuing to use the air conditioner in the trouble
status may cause mechanical problems to escalate or result in electric shocks
or other failure. · After the work has finished, be sure to use an insulation
tester set (500 V Megger) to check the resistance is 1 MÙ or more between the
charge section and the non-charge metal section (Earth section). If the
resistance value is low, a disaster such as a leak or electric shock is caused
at user’s side. · Upon completion of the installation work, check for
refrigerant leaks and check the insulation resistance and water drainage. Then
conduct a test run to check that the air conditioner is operating properly.
Explanations given to user · Upon completion of the installation work, tell
the user where the
circuit breaker is located. If the user does not know where the circuit
breaker is, he or she will not be able to turn it off in the event that
trouble has occurred in the air conditioner. · If you have discovered that the
fangard is damaged, do not approach the outdoor unit but set the circuit
breaker to the OFF position, and contact a qualified service person to have
the repairs done. Do not set the circuit breaker to the ON position until the
repairs are completed. · After the installation work, follow the Owner’s
Manual to explain to the customer how to use and maintain the unit.
Relocation · Only a qualified installer or qualified service person is allowed
to
relocate the air conditioner. It is dangerous for the air conditioner to
EN-13
be relocated by an unqualified individual since a fire, electric shocks,
injury, water leakage, noise or vibration may result. · When carrying out the
pump-down work shut down the compressor before disconnecting the refrigerant
pipe. Disconnecting the refrigerant pipe with the service valve left open and
the compressor still operating will cause air or other gas to be sucked in,
raising the pressure inside the refrigeration cycle to an abnormally high
level, and possibly resulting in rupture, injury or other trouble. · Never
recover the refrigerant into the outdoor unit. Be sure to use a refrigerant
recovery machine to recover the refrigerant when moving or repairing. It is
impossible to recover the refrigerant into the outdoor unit. Refrigerant
recovery into the outdoor unit may result in serious accidents such as
explosion of the unit, injury or other accidents.
CAUTION
New Refrigerant Air Conditioner Installation · This air conditioner adopts the
new HFC refrigerant (R410A)
which does not destroy ozone layer. · The characteristics of R410A refrigerant
are; easy to absorb water,
oxidizing membrane or oil, and its pressure is approx. 1.6 times higher than
that of refrigerant R22. Accompanied with the new refrigerant, refrigerating
oil has also been changed. Therefore, during installation work, be sure that
water, dust, former refrigerant, or refrigerating oil does not enter the
refrigerating cycle. · To prevent charging an incorrect refrigerant and
refrigerating oil, the sizes of connecting sections of charging port of the
main unit and installation tools are changed from those for the conventional
refrigerant. · Accordingly the exclusive tools are required for the new
refrigerant (R410A). · For connecting pipes, use new and clean piping designed
for R410A, and please care so that water or dust does not enter.
EN-14
EN
2 Accessory Parts
Part name Owner’s Manual
Q’ty
Shape
Usage
1
Hand this directly to the customer.
Installation Manual
CD-ROM (Owner’s manual, Installation manual)
F-GAS label
Attached pipe
1
Hand this directly to the customer.
1
–
For other languages that do not appear in this Installation Manual, Please refer to the enclosed CD-ROM.
1
Fill the items on the label after adding refrigerant.
1
Gas pipe connection pipe Ø19.05 to Ø22.22 (MCY-MHP1006HS8* only)
NOTE
· Before installing the unit, check that the unit has the correct model name
to prevent the wrong unit from being installed in the wrong place.
· Before proceeding to braze the refrigerant pipe, be sure to pass nitrogen
through the pipe. · Before installing the indoor units, read the instructions
in the installation manual provided with the indoor units. · Before installing
a branch pipe, read the instructions in the installation manual provided with
the branch pipe kit.
Installation Manual
3 Installation of New Refrigerant Air
Conditioner
This air conditioner adopts the new HFC refrigerant (R410A) which does not
deplete the ozone layer. · R410A refrigerant is vulnerable to impurities such
as water, oxidizing membranes, or oils because the pressure of
R410A refrigerant is higher than that of the former refrigerant by
approximately 1.6 times. As well as the adoption of the new refrigerant, the
refrigerating oil has been also changed. Therefore, pay attention so that
water, dust, former refrigerant, or refrigerating oil does not enter the
refrigerating cycle of the new refrigerant air conditioner during
installation. · To prevent mixing of refrigerant or refrigerating oil, the
size of the charge port of the main unit or connecting section of the
installation tool differs to that of an air conditioner for the former
refrigerant. Accordingly, exclusive tools are required for the new refrigerant
(R410A) as shown below. · For connecting pipes, use new and clean piping
materials so that water or dust does not enter.
Required tools and cautions on handling
It is necessary to prepare the tools and parts for installation as described
below. The tools and parts which will be newly prepared in the following items
should be restricted to exclusive use.
Explanation of symbols : Newly prepared (It is necessary to use it exclusively
with R410A, separately from those for R22 or R407C.) : Former tool is
available.
Used tools
Usage
Proper use of tools / parts
Gauge manifold Charging hose
Vacuuming, charging refrigerant and operation check
Exclusive to R410A Exclusive to R410A
Charging cylinder
Charging refrigerant
Unusable (Use the Refrigerant charging balance.)
Gas leak detector
Checking gas leak
Exclusive to R410A
Vacuum pump
Vacuum drying
Usable if a counter-flow preventive adapter is attached
Vacuum pump with counterflow Vacuum drying
R22 (Existing article)
Flare tool
Flare processing of pipes
Usable by adjusting size
Bender
Bending processing of pipes
R22 (Existing article)
Refrigerant recovery device
Recovering refrigerant
Exclusive to R410A
Torque wrench
Tightening flare nut
Choose a torque wrench fit with nut specification
Pipe cutter
Cutting pipes
R22 (Existing article)
Refrigerant canister
Charging refrigerant
Exclusive to R410A Enter the refrigerate name for identification
Welding machine / Nitrogen gas cylinder
Welding of pipes
R22 (Existing article)
Refrigerant charging balance Charging refrigerant
R22 (Existing article)
EN-15
8
EN-16
9
4 Installation Conditions
Before installation
Be sure to prepare to the following items before installation.
Airtight test
1 Before starting an airtight test, further tighten the spindle valves on the
gas and liquid sides. 2 Pressurize the pipe with nitrogen gas charged from the
service port to the design pressure to conduct an
airtight test.
3 After the airtight test is completed, evacuate the nitrogen gas.
Air purge
· To purge air, use a vacuum pump. · Do not use refrigerant charged in the
outdoor unit to purge air. (The air purge refrigerant is not contained in the
outdoor unit.)
Electrical wiring
Be sure to fix the power wires, indoor / outdoor connecting wires and remote
controller wires with clamps so that they do not come into contact with the
cabinet, etc.
Earthing
WARNING
Make sure that proper earthing is provided. Improper earthing may cause an
electric shock. For details on how to check earthing, contact the dealer who
installed the air conditioner or a professional installation company.
· Proper earthing can prevent charging of electricity on the outdoor unit
surface due to the presence of a high frequency in the frequency converter
(inverter) of the outdoor unit, as well as prevent electric shock. If the
outdoor unit is not properly earthed, you may be exposed to an electric shock.
· Be sure to connect the earth wire (grounding work). Incomplete earthing can
cause an electric shock. Do not connect earth wires to gas pipes, water pipes,
lightning rods or earth wires for telephone wires.
Test run
Turn on the leakage breaker at least 12 hours before starting a test run to
protect the compressor.
CAUTION
Incorrect installation work may result in a malfunction or complaints from
customers.
Installation Manual
Installation location
WARNING
Install the outdoor unit properly in a location that is durable enough to
support the weight of the outdoor unit. Insufficient durability may cause the
outdoor unit to fall, which may result in injury. This outdoor unit has a
weight of about 147 kg. Pay special attention when installing the unit onto a
wall surface.
CAUTION
Do not install the outdoor unit in a location that is subject to combustible
gas leaks. Accumulation of combustible gas around the outdoor unit may cause a
fire.
Install the outdoor unit in a location that meets the following conditions
after the customer’s consent is obtained. · A well-ventilated location free
from obstacles near the air intake and air discharge · A location that is not
exposed to rain or direct sunlight · A location that does not increase the
operating noise or vibration of the outdoor unit · A location that does not
produce any drainage problems from discharged water
Do not install the outdoor unit in the following locations. · A location with
a saline atmosphere (coastal area) or one that is full of sulfide gas (hot-
spring area) (Special
maintenance is required.) · A location subject to oil, vapor, oily smoke, or
corrosive gases · A location in which organic solvent is used · Places where
iron or other metal dust is present. If iron or other metal dust adheres to or
collects on the interior of
the air conditioner, it may spontaneously combust and start a fire. · A
location where high-frequency equipment (including inverter equipment, private
power generator, medical
equipment, and communication equipment) is used (Installation in such a
location may cause malfunction of the air conditioner, abnormal control or
problems due to noise from such equipment.) · A location in which the
discharged air of the outdoor unit blows against the window of a neighboring
house · A location where the operating noise of the outdoor unit is
transmitted · When the outdoor unit is installed in an elevated position, be
sure to secure its fixing leg. · A location in which drain water poses any
problems.
When collectively draining discharged water completely, use a drain pan.
EN-17
EN-18
EN
CAUTION
1. Install the outdoor unit in a location where the discharge air is not
blocked.
2. When an outdoor unit is installed in a location that is always exposed to
strong winds like a coast or on the high stories of a building, secure normal
fan operation by using a duct or wind shield.
3. When installing the outdoor unit in a location that is constantly exposed
to strong winds such as on the upper stairs or rooftop of a building, apply
the wind-proofing measures referred to in the following examples.
- Install the unit so that its discharge port faces the wall of the building. Keep a distance 800 mm or more between the unit and wall surface. 800 mm
Installation Manual
4. When installing the unit in an area where snowfalls may be heavy, take
steps to prevent the unit from being adversely affected by the fallen or
accumulated snow.
· Either make the foundation higher or install a stand (which is high enough
to ensure that the unit will be above the fallen or accumulated snow) and
place the unit on it.
· Attach a snow shield (locally procured).
Snow shield
Snow shield
- Consider the wind direction during the operational season of the air conditioner, and install the unit so that the discharge port is set at a right angle relative to the wind direction.
Strong wind
Strong wind
EN-19
10
EN-20
11
Installation Manual
Necessary space for installation (Unit: mm)
Be sure to observe the necessary space for instllation. Install the outdoor unit in a well-ventilated location. Failure to do so may cause short circuit (intake of discharge air) or performance deterioration due to locations around the outdoor unit.
Obstacle at rear side
Obstacle in front
Upper side is free 1. Single unit installation
Above unit is free 1. Single unit installation
Obstacles in both front and rear of unit
Open above and to the right and left of the unit. The height of an obstacle in
both the front and rear of the unit, should be lower than the height of the
outdoor unit.
Serial installation in front and rear
Open above and to the right and left of the unit. The height of an obstacle in
both the front and rear of the unit should be lower than the height of the
outdoor unit.
Standard installation 1. Single unit installation
Standard installation
150 or more
1,000 or 300 or 1,500 or
more
more more
2,000 or more
200 or more
1,000 or more
800 or more
200 or more 150 or more
2. Obstacles on both right and left sides
The height of the obstacle should be lower than the height of the outdoor
unit.
2. Serial installation of two or more units
300 or more
300 or more
150 or more
300 or more
3. Serial installation of two or more units The height of the obstacle should be lower than the height of the outdoor unit.
Obstacle also above unit 1,000 or more
800 or more
150 or more
300 or more
300 or more
Obstacle also above unit
150 or more
300 or more
Obstacles in front and both right and left side
150 or more
300 or more
1,000 or more
2. Serial installation of two or more units
200 or more
1,000 or more
250 or more
250 or more
Installation of outdoor unit
· Before installation, check the strength and horizontalness of the base so
that abnormal sounds do not emanate. · According to the following base
diagram, fix the base firmly with the anchor bolts.
(Anchor bolt, nut: M12 x 4 pairs)
Back side
164
660
164
Drain hole
500 or more 200 or more
800 or more
490 445
EN-21
Front side (Air discharge side)
Knockout hole
EN-22
EN
· As shown in the figure below, install vibration-proof rubber pads to directly support the bottom surface of the fixing leg. * When installing the foundation for an outdoor unit with downward piping, consider the piping work.
Correct
Correct
Fixing leg
Absorb vibration with vibration-proof rubber pads
Bottom plate of outdoor unit
Foundation
If only the end of the fixing leg is supported,
it may deform.
Incorrect
Foundation
Support the bottom surface of the fixing leg that is in contact with and underneath the bottom plate of the outdoor unit.
Do not support the outdoor unit only with the fixing leg.
Foundation Set the out margin of the anchor bolt to 20 mm or less.
20 or less
· When the unit is to be installed in a location where it is likely to be
exposed to strong winds or where the foundation is unstable, additional
measures must be taken to prevent tip-over as shown in the figure below.
Tip-over prevention part
Tip-over prevention part
Installation Manual
For reference
If a heating operation is to be continuously performed for a long time under
the condition that the outdoor temperature is 0 °C or lower, draining
defrosted water may be difficult due to the bottom plate freezing, resulting
in trouble with the cabinet or fan. It is recommended to procure an anti-
freeze heater locally in order to safely install the air conditioner. For
details, contact the dealer.
CAUTION
· Carry out the installation work by following the prescribed procedure to
make provision against the shaking of the unit caused by strong winds,
earthquakes, etc.
· Failure to carry out the installation work as prescribed may lead to the
unit tipping over, in turn causing an accident.
EN-23
12
EN-24
13
Installation Manual
5 Refrigerant Piping
Leading out the pipes
Front
Side
Bottom
· The indoor/outdoor unit connecting pipes can be connected in any of 4
directions. Use a screwdriver to punch out the knockout part of the front
panel or base. Wear heavy work gloves to protect yourself from injury while
doing this work. After punching out the knockout hole in a manner which
ensures that the pipes and wires will not be damaged in any way, remove the
burrs from around the hole.
REQUIREMENT
Follow the instructions in the installation manual provided with the branch
pipe kit and the instructions in the installation manual of the indoor unit to
connect the refrigerant pipe between the branch pipe and indoor unit.
Refrigerant piping connection
CAUTION
TAKE NOTE OF THESE 4 IMPORTANT POINTS BELOW FOR PIPING WORK 1. Keep dust and
moisture away from inside the connecting pipes. 2. Tightly connect the
connection between pipes and the unit. 3. Evacuate the air in the connecting
pipes using a VACUUM PUMP. 4. Check for gas leaks at connection points.
Pipe connection method
Flaring
1. Cut the pipe with a pipe cutter.
Correct 90°
Incorrect
Incorrect
Incorrect
Obliquity
Roughness
Warp
2. Remove the burr inside of the pipe. When removing the burr, be careful so that chips do not fall into the pipe. 3. Remove the flare nuts attached to the outdoor / indoor unit, then insert them into each of the pipes. 4. Flare the pipes. See the following table for the projection margin (A) and flaring size (B).
A
B
EN-25
Pipe
Outside diameter
Thickness
mm
mm
6.35
0.8
9.52
0.8
12.70
0.8
15.88
1.0
19.05
1.2
A
Rigid (clutch type) R410A tool
Imperial (wing nut type)
R410A tool
mm
mm
0 to 0.5
1.0 to 1.5
0 to 0.5
1.0 to 1.5
0 to 0.5
1.0 to 1.5
0 to 0.5
1.0 to 1.5
0 to 0.5
1.0 to 1.5
B
Flare Nut
Width across flat
Tighten torque
mm
mm
N·m
kgf·m
9.9
17
14 to 18
1.4 to 1.8
13.2
22
33 to 42
3.3 to 4.2
16.6
26
50 to 62
5.0 to 6.2
19.7
29
68 to 82
6.8 to 8.2
24.0
36
100 to 120 10.0 to 12.0
- In case of flaring for R410A with the conventional flare tool, pull the tool out approx. 0.5 mm more than that for R22 to adjust it to the specified flare size. The copper pipe gauge is useful for adjusting the projection margin size.
EN-26
ØC ØF
EN
REQUIREMENT
· For a brazing work of the refrigerant pipes, be sure to use nitrogen gas in
order to prevent oxidation of the inside of the pipes; otherwise clogging of
the refrigerating cycle due to oxidized scale may occur.
· Use clean and new pipes for the refrigerant pipes and perform piping work so
that water or dust does not contaminate the refrigerant.
- Remove all flux after brazing. · Be sure to use a double spanner to loosen or tighten the flare nut. If a single spanner is used, the required level of
tightening cannot be obtained. Tighten the flare nut with the specified torque. · Do not apply refrigerant oil to the surface of the flare.
Coupling size of brazed pipe
Connected section
External size
Internal size
K
G
Standard outer dia. of connected copper pipe
6.35 9.52 12.70 15.88 19.05 22.22
Connected section
External size
Internal size
Standard outer dia. (Allowable difference)
Min. depth of insertion
C
F
K
G
6.35 (±0.03) 9.52 (±0.03) 12.70 (±0.03) 15.88 (±0.03) 19.05 (±0.03) 22.22 (±0.03)
6.45
(
+0.04 -0.02
)
9.62
(
+0.04 -0.02
)
12.81
( ) +0.04 -0.02
16.00
( ) +0.04 -0.02
19.19
( ) +0.04 -0.02
22.36
( ) +0.03 -0.03
7
6
8
7
9
8
9
8
11
10
11
10
Oval value
0.06 or less 0.08 or less 0.10 or less 0.13 or less 0.15 or less 0.16 or less
(Unit: mm)
Min. thickness of coupling
0.50 0.60 0.70 0.80 0.80 0.90
Installation Manual
Selection of pipe materials and size
Selection of pipe material
Material: Phosphorus deoxidation seam-less pipe
Capacity code of indoor and outdoor units
· For the indoor unit, the capacity code is decided at each capacity rank. ·
The capacity codes of the outdoor units are decided at each capacity rank.
The maximum No. of connectable indoor unit and the total value of capacity
codes of the indoor units are also decided.
Minimum pipe thickness for R410A application
Soft
Half Hard or Hard
OD (Inch)
Correct
Correct
1/4″
Correct
Correct
3/8″
Correct
Correct
1/2″
Correct
Correct
5/8″
Incorrect *1
Correct
3/4″
Incorrect *1
Correct
7/8″
*1 If the pipe size is Ø19.05, use a suitable material.
OD (mm) 6.35 9.52 12.70 15.88 19.05 22.22
Minimum pipe thickness (mm) 0.80 0.80 0.80 1.00 1.00 1.00
Table 1
Indoor unit capacity type
005 type 007 type 009 type 012 type 015 type 018 type 024 type
Capacity code
Equivalent to HP
Equivalent to capacity
0.6
1.7
0.8
2.2
1.0
2.8
1.25
3.6
1.7
4.5
2.0
5.6
2.5
7.1
Indoor unit capacity type
027 type 030 type 036 type 048 type 056 type 072 type 096 type
Capacity code
Equivalent to HP
Equivalent to capacity
3.0
8.0
3.2
9.0
4.0
11.2
5.0
14.0
6.0
16.0
8.0
22.4
10.0
28.0
Table 2
Outdoor unit capacity type
0806 type
Capacity code Equivalent to HP
8
No. of connetable indoor units
2 to 12
1006 type
10
2 to 16
Total capacity code of connectable indoor units
Min. (HP)
Max. (HP)
6.4
10.4
13.0 (When the number of indoor units is 2 to 12) 8.0
11.0 (When the number of indoor units is 13 to 16)
EN-27
14
EN-28
Pipe connection method of valve at the gas side (Example)
15
Installation Manual
CAUTION
· The brazed part of the pipe connection should be sufficiently away from the
ball valve. · When carrying out brazing nearthe ball valve, wrap the ball
valve in a wet cloth to keep it cool and prevent the heat
from the torch from damaging it, and, prepare a shield plate on-site to
prevent the soundproofing cloth or other part from catching fire.
Diameter of pipe
Front and right leading out
Attach the Ø19.05 pipe to the ball valve by flare conection.
Ball valve
Downward direction leading out
Attach the Ø19.05 pipe to the ball valve by flare conection.
Ball valve
O.D. 19.05 mm
Ø19.05 Main pipe (Locally procured)
Ø19.05 Main pipe (Locally procured)
Wet cloth Brazing
Attach Ø19.05-Ø22.22 socket to the ball valve by
flare conection and braze the locally procured
Ø22.22 main pipe.
Ball valve
O.D. 22.22 mm
Ø19.05-Ø22.22 socket (Attached)
Ø22.22 Main pipe (Locally procured)
Attach Ø19.05 pipe to the ball valve by flare conection and braze the locally
procured Ø19.05Ø22.22 socket and Ø22.22 main pipe.
Ball valve
Ø19.05 pipe (Locally procured)
Ø19.05-Ø22.22 socket (Locally procured)
Ø22.22 Main pipe (Locally procured)
EN-29
EN-30
EN
Selection of refrigerant piping
Outdoor unit
Gas pipe
Main pipe L1 (1)
Liquid pipe
1st branching Branching
section
pipe
(4)
(2)
Branching header
(5)
Height difference between indoor and outdoor units H1
(3)
(3)
Branching pipe
(2)
(3)
(3)
Y-shaped branching joint
(4)
(3) (3)
Indoor unit
Indoor unit
No. Piping parts – Outdoor unit
Name
Size of valve
Connection Valve
Gas side 19.05
Selection of pipe size
Liquid side 9.52
Remarks –
Installation Manual
Size of main pipe 0806 type
Outdoor unit
(1)
1st branching
section
Main pipe
Conditions for size of main pipe selection*
Height between
Equivalent
indoor and outdoor length of main
units H1(m)
pipe L1(m)
50 H > 40
No condition
40 H > 30
30 > L1 L1 30
30 H > 20
40 > L1 L1 40
20 H > 10
60 > L1 L1 60
10 H > 0
No condition
Size of main pipe
Gas Liquid pipe pipe
19.05
12.70 9.52 12.70 9.52 12.70 9.52 12.70 9.52
1006 type
Conditions for size of main pipe selection*
Height between
Equivalent
indoor and outdoor length of main
units H1(m)
pipe L1(m)
50 H > 30
No condition
30 H > 20
30 > L1 L1 30
20 H > 10
40 > L1 L1 40
10 H > 0
50 > L1 L1 50
Size of main pipe
Gas Liquid pipe pipe
22.22
12.70 9.52 12.70 9.52 12.70 9.52 12.70
*The main liquid pipe size differs based on outdoor unit capacity type, equivalent length of main pipe, and hight difference between outdoor and indoor units.
Pipe size between branching sections
(2)
Branching section Branching section
Branching pipe
Total capacity codes of indoor units at down stream
side
Equivalent to Equivalent to
HP
capacity
Below 2.4
Below 6.6
2.4 to below 6.6 to below
6.4
18.0
6.4 or more 18.0 or more
Gas pipe
12.70 15.88 22.22
Liquid pipe
9.52 9.52 12.70
Pipe size differs based on the total capacity code value of indoor units at the downstream side. If the total value exceeds the capacity code of the outdoor unit, apply the capacity code of the outdoor unit. (See Table 1 and 2.)
- When exceed the main pipe size, use the same size as the main pipe.
EN-31
16
EN-32
Connecting pipe size of indoor unit
Branching section Indoor unit
(3)
connecting
Indoor unit
pipe
Capacity rank 005 to 012 type 015 to 018 type 024 to 056 type 072 to 096 type
Gas pipe 9.52 12.70 15.88 22.22
Liquid pipe 6.35 6.35 9.52 12.70
Selection of branching section (Y-shaped branching joint)
Y-shaped
(4) Branching section branching joint
Y-sharp branch joint
Total capacity codes of indoor units at down stream side
Equivalent to Equivalent to
HP
capacity
Below 6.4
Below 18.0
6.4 or more 18.0 or more
Model name
RBM-BY55E RBM-BY105E
Selection of branching section (Branching header)
(5)
Branching section
Branching header
Branching header
For 4 branches For 8 branches
Model name RBM-HY1043E RBM-HY1083E
17
Installation Manual
Selection of refrigerant piping for quiet place (with PMV Kit)
Outdoor unit
Gas pipe Main pipe L1
(1)
Height difference between indoor and outdoor units H1
Liquid pipe
1st branching section
(4)
Branching pipe
(2)
Branching header
(5)
(6)
(6)
(3) (3)
(6)
(3)
(3)
Branching pipe (2)
Y-shaped branching joint
(4)
PMV Kit
(6) Indoor unit
(6)
(6)
(3)
(3)
Indoor unit
No. Piping parts – Outdoor unit
Name
Size of valve
Connection Valve
Gas side 19.05
Selection of pipe size
Liquid side 9.52
Remarks –
EN-33
EN-34
EN
Size of main pipe 0806 type
Outdoor unit
(1)
1st branching
section
Main pipe
Conditions for size of main pipe selection*
Height between
Equivalent
indoor and outdoor length of main
units H1(m)
pipe L1(m)
50 H > 40
No condition
40 H > 30
30 > L1 L1 30
30 H > 20
40 > L1 L1 40
20 H > 10
60 > L1 L1 60
10 H > 0
No condition
Size of main pipe
Gas Liquid pipe pipe
19.05
12.70 9.52 12.70 9.52 12.70 9.52 12.70 9.52
1006 type
Conditions for size of main pipe selection*
Height between
Equivalent
indoor and outdoor length of main
units H1(m)
pipe L1(m)
50 H > 30
No condition
30 H > 20
30 > L1 L1 30
20 H > 10
40 > L1 L1 40
10 H > 0
50 > L1 L1 50
Size of main pipe
Gas Liquid pipe pipe
22.22
12.70 9.52 12.70 9.52 12.70 9.52 12.70
*The main liquid pipe size differs based on outdoor unit capacity type, equivalent length of main pipe, and hight difference between outdoor and indoor units.
Pipe size between branching sections
Total capacity codes of indoor units at down stream
side
Gas pipe
Pipe size differs based
Liquid pipe
on the total capacity code value of indoor
(2)
Branching section Branching section
Branching pipe
Equivalent to Equivalent to
HP
capacity
Below 2.4
Below 6.6
2.4 to below 6.6 to below
6.4
18.0
12.70 15.88
units at the downstream
side. If the total value
9.52
exceeds the capacity
code of the outdoor unit,
9.52
apply the capacity code
of the outdoor unit. (See
6.4 or more 18.0 or more 22.22
12.70 Table 1 and 2.)
- When exceed the main pipe size, use the same size as the main pipe.
Installation Manual
Connecting pipe size of indoor unit
Branching section Indoor unit
(3)
connecting
Indoor unit
pipe
Capacity rank 005 to 012 type 015 to 018 type 024 to 056 type 072 to 096 type
Gas pipe 9.52 12.70 15.88 22.22
Liquid pipe 6.35 6.35 9.52 12.70
Selection of branching section (Y-shaped branching joint)
Y-shaped
(4) Branching section branching joint
Y-sharp branch joint
Total capacity codes of indoor units at down stream side
Equivalent to Equivalent to
HP
capacity
Below 6.4
Below 18.0
6.4 or more 18.0 or more
Model name
RBM-BY55E RBM-BY105E
Selection of branching section (Branching header)
(5)
Branching section
Branching header
Branching header
For 4 branches For 8 branches
Model name RBM-HY1043E RBM-HY1083E
(6) PMV Kit
PMV Kit
Selection of PMV Kit
Capacity rank
Model name
005 to 012 type
RBM-PMV0363E, RBM-PMV0361U-E
015 to 027 type
RBM-PMV0903E, RBM-PMV0901U-E
- PMV kit can be connected less than 027 type FCU.
EN-35
18
EN-36
Allowable length / height difference of refrigerant piping
Outdoor unit
19
Installation Manual
Allowable length / height difference of refrigerant piping for quiet places (with PMV Kit)
Outdoor unit
Main pipe L1
Branching pipe L2
Branching header
Height difference between indoor and outdoor units H1
1st branching section
Branching pipe
L3
abcd
Indoor unit Equivalent length corresponded to farthest piping L Equivalent length corresponded to farthest piping after 1st branching Li
e
f
Y-shaped
branching joint
A *1
Height difference between indoor units H2
Piping Length
Height Difference
Total extension of pipe (liquid pipe, real length)
Furthest piping length L Real length
(*1)
Equivalent length
Max. equivalent length of main pipe
Max. real length of furthest piping from 1st branching Li (*1)
Max. real length of indoor unit connecting pipe
Height between indoor Upper outdoor unit and outdoor units H1 Lower outdoor unit
Height between indoor units H2
Allowable value 300 m 150 m 180 m
80 m(2)
70 m
15 m 50 m(2) 30 m(*2)
15 m
Pipes L1 + L2 + L3 + a + b + c + d + e + f
L1 + L3 + f L1
L3 + f a, b, c, d, e, f
1 Furthest indoor unit from 1st branch to be named “A”. 2 The main liquid pipe size varies depending on L1 and H1. See the page of “Selection of refrigerant piping” for
details.
Main pipe
L1
Branching pipe L2
Branching header
1st branching section
abcd
Height difference between indoor and outdoor units H1
Branching pipe L3
g
h
i
j
Indoor unit
Equivalent length corresponded to farthest piping L Equivalent length corresponded to farthest piping after 1st branching Li
PMV Kit
Height difference between indoor unit and PMV Kit H2 Between highest
unit and lower units.
Example)
H2
e
f
Y-shaped
H2
branching joint
k
l
A *1
H2
Piping Length
Height Difference
Total extension of pipe (Liquid pipe, real length)
Furthest piping length L Real length
(*1)
Equivalent length
Max. equivalent length of main pipe
Max. real length of furthest piping from 1st branching Li (*1)
Max. real length of indoor unit connecting pipe
Real length between PMV Kit and indoor unit
Height between indoor Upper outdoor unit and outdoor units H1 Lower outdoor
unit
Height between indoor units (PMV Kit) H2
Allowable value
250 m
130 m 160 m 70 m(*2)
Pipes L1 + L2 + L3 + a + b + c + d + e + f + g + h
+ i + j + k + l
L1 + L3 + f + l
L1
60 m
L3 + f + l
15 m 2 m or more Below 10 m
50 m(2) 30 m(2)
15 m
a + g, b + h, c + i, d + j, e + k, f + l g, h, i, j, k, l
1 Furthest indoor unit from 1st branch to be named “A”. 2 The main liquid pipe size varies depending on L1 and H1. See the page of “Selection of refrigerant piping” for
details.
EN-37
EN-38
EN
NOTE
Do not connect two or more indoor units to one PMV Kit. Arrange one indoor unit and one PMV Kit set to 1 by 1.
Incorrect
Correct
PMV Kit
PMV Kit
Indoor unit
Indoor unit
Installation Manual
Airtight test
Before starting an airtight test, further tighten the spindle valves on the
gas side and liquid side. Pressurize the pipe with nitrogen gas charged from
the service port to the design pressure to conduct the airtight test. After
the airtight test is completed, evacuate the nitrogen gas. · Apply pressure
from the service ports of the packed valves (or ball valves) at liquid side
and gas side. · An air tight test can be only performed to the service ports
at liquid side and gas side of the outdoor unit. · Close fully valves at
liquid side and gas side. As there is possibility that nitrogen gas enters in
the refrigerant cycle,
re-tighten the valve rods before applying pressure. (Re-tightening of the
valve rods are unnecessary for valves at gas side because they are ball
valves.) · For each refrigerant line, apply pressure gradually with steps at
liquid side and gas side. Apply pressure to gas side and liquid side.
REQUIREMENT
Do not use “Oxygen”, “Flammable gas” and “Noxious gas” in an airtight test.
Connected to indoor unit Main pipe
Ball valve fully closed (Gas side)
Outdoor unit
Low pressure High pressure
guage
guage
Gauge manifold
Flare connection
Flare connection
Ø6.4 Copper pipe Service port
Reducing valve
Service port
Packed valve fully closed (Liquid side)
Ø6.4 Copper pipe Nitrogen gas
To detect a gross leakage 1. Apply pressure 0.3 MPa (3.0 kg / cm2G) for 3
minutes or more. 2. Apply pressure 1.5 MPa (15 kg / cm2G) for 3 minutes or
more.
To detect a slow leakage 3. Apply pressure 4.15 MPa (42.3 kg / cm2G) for
approx. 24 hours.
· Check pressure down. No pressure down: Accepted Pressure down: Check the
leaked position.
EN-39
20
EN-40
21
Installation Manual
NOTE
However, if the environmental temperature changes from the moment of applying
pressure to 24 hours after that, the pressure will change by about 0.01 MPa
(0.1 kg / cm2G) per 1 °C. Consider the pressure change when checking the test
result.
REQUIREMENT
When pressure decrease is detected in steps 1-3, check the leakage at the
connecting points. Check the leakage using a foaming agent or other measures
and seal the leak with re-brazing, flare retightening or other methods. After
sealing, execute an airtight test again.
Air purge
NOTE
For the air purge at installation time (Discharge of air in connecting pipes),
use “Vacuum pump method” from viewpoint of the protection of the earths
environment. · For protection of the earths environment, do not discharge the
refrigerant gas in the air. · Eliminate the remaining air (nitrogen gas, etc.)
in the unit by using a vacuum pump. If gas remains, performance and
reliability of the unit may be reduced.
After the airtight test, discharge nitrogen gas. Then connect the gauge
manifold to the service ports at gas side and liquid side, and connect the
vacuum pump as shown in the following figure. Perform vacuuming for gas side
and liquid side. · Perform vacuuming from both liquid and gas sides. · Use a
vacuum pump with counter-flow preventive function so that oil in the pump does
not back up in the pipe of the
air conditioner when the pump has been stopped. (If oil in the vacuum pump
enters in to the air conditioner with R410A refrigerant, an error may occur in
the refrigeration cycle.)
Connected to indoor unit
Low pressure High pressure
guage
guage
Main pipe
Ball valve fully closed (Gas side)
Outdoor unit
Gauge manifold
Flare connection
Flare connection
Service port
Service port
Packed valve fully closed (Liquid side)
Vacuum pump
· Use a vacuum pump that has a high vacuum (below -755 mmHg) and a large
exhaust gas amount (over 40 L / minute).
· Perform vacuuming for 2 or 3 hours though time differs due to pipe length.
In this time, check all valves at liquid and gas sides are fully closed.
· If vacuuming valve amount is not decreased to below -755 mmHg even after
vacuuming for 2 hours or more, continue vacuuming for 1 hour or more. If -755
mmHg or less cannot be obtained by 3 hours or more vacuuming, detect and
repair the leak.
· When the vacuuming valve has reached -755 mmHg or less after vacuuming for 2
hours or more, close valves VL and VH on the gauge manifold fully. Stop the
vacuum pump, leave it as it is for 1 hour and then check the vacuum does not
change. If it does change then there may be a leak within the system.
· After the above procedure for vacuuming has finished, exchange the vacuum
pump with a refrigerant cylinder and advance to the additional charging of
refrigerant.
EN-41
EN-42
EN
Adding refrigerant
After finishing vacuuming, exchange the vacuum pump with a refrigerant
canister and start additional charging of refrigerant.
Calculation of additional refrigerant charge amount Default refrigerant amount
does not include the refrigerant for pipes at the local site. For refrigerant
to be charged in pipes at the local site, calculate the amount and charge it
additionally.
NOTE
Do not degas the refrigerant from the air conditioner when the result of
additional refrigerant charge amount calculation is negative value.
Outdoor unit type Charging amount (kg)
0806HS8 4.4
1006HS8 4.4
Additional refrigerant charge amount at local site
=
Real length of liquid pipe
×
Additional refrigerant charge amount per
1 m liquid pipe (Table 1)
Corrective amount of refrigerant depending
on the indoor units (Table 2)
Compensation by outdoor HP (Table 3)
Table 1
Liquid pipe dia. (mm)
Additional refrigerant amount / 1 m liquid pipe (kg / m)
6.35 0.025
9.52 0.055
12.70 0.105
Table 2
Capacity rank
005 007 009 012 015 018 024 027 030 036 048 056 072 096
Capacity code (Equivalent to HP)
0.6 0.8 1.0 1.25 1.7 2.0 2.5 3.0 3.2 4.0 5.0 6.0 8.0 10.0
4-way cassette
MMU-*P***HP
– – 0.4 0.4 0.8 0.8 0.8 0.8 0.8 1.2 1.2 1.2 – –
Compact 4-way cassette
2-way cassette
MMU-*PMH MMU-PWH*
0.3 0.4 0.4 0.4 0.6 0.6 – – – – – – – – 0.4 0.4 0.4 0.5 0.7 0.7 0.7 0.7 1.1 1.1 1.1 – –
1-way cassette
MMU-*P***YH / SH – 0.4 0.4 0.4 0.5 0.5 0.6 – – – – – – –
MMU-*P***YHP
0.3 0.3 0.3 0.3 0.4 0.4 0.5 0.5 – – – – – –
Indoor unit model name
Concealed duct Slim duct Compact slim duct Concealed duct High static pressure Ceiling
MMD-*P*BHP MMD-AP**SPH MMD-PSPHY
MMD-PHP
MMC-P***HP
– 0.3 0.3 0.3 0.5 0.5 0.8 0.8 0.8 1.1 1.1 1.1 – 0.3 0.3 0.3 0.3 0.5 0.5 0.8
0.8 – – – – – 0.3 0.4 0.4 0.4 0.5 0.5 0.7 0.7 – – – – – –
– – – – – 0.7 0.7 0.7 – 1.1 1.1 1.1 2.1 2.1
– – – – 0.6 0.6 0.8 0.8 – 1.2 1.2 1.2 – –
High wall
MMK-APH MMK-PHP*
– 0.5 0.5 0.5 0.7 0.7 0.7 – – – – – – 0.3 0.3 0.3 0.3 0.7 0.7 0.7 0.9 0.9 0.9 – – – –
Floor standing
MMF-*P***H
Floor standing cabinet MML-*P***H
– – – – 0.7 0.7 1.0 1.0 – 1.3 1.3 1.3 – – 0.5 0.5 0.5 0.5 0.8 0.8 – – – – – – –
Console
MML-*P***NH(P)
– 0.5 0.5 0.5 0.5 0.5 – – – – – – – (Unit: kg)
Installation Manual
Mid temperature Hot water module
Capacity rank
027
056
Capacity code
Equivalent to Capcity
7.1
14.0
Equivalent to HP
2.5
5.0
MMW-*P***LQ
0.2
0.4
Table 3 Outdoor unit type Compensation by outdoor HP (kg)
0806HS8 1.0
1006HS8 1.0
Example: (1006 type)
L1
L2
L3
L4
L5
L6
L7
A
B
C
D
L1
Ø9.52: 10 m
L2
Ø9.52: 10 m
L3
Ø9.52: 5 m
L5
Ø6.35: 3 m
L6
Ø6.35: 4 m
L7
Ø6.35: 5 m
A
MMU-UP0561HP*
B
MMU-UP0181HP*
C
MMU-UP0071MH*
Additional charge amount R (kg) = ( Lx × 0.025 kg/m) + ( Ly × 0.055 kg/m) + ( a + b + c + d ) + ( 1.0 kg ) = ( 12 × 0.025 kg) + ( 28 × 0.055 kg) + ( 2.7 kg ) + ( 1.0 kg ) = 3.54 kg
L4
Ø9.52: 3 m
D MMD-UP0051SPHY*
Lx: Real total length of liquid pipe diameter 6.35 mm (m) Ly: Real total length of liquid pipe diameter 9.52 mm (m) a: Corrective amount of refrigerant depending on the unit A [kg] b: Corrective amount of refrigerant depending on the unit B [kg] c: Corrective amount of refrigerant depending on the unit C [kg] d: Corrective amount of refrigerant depending on the unit D [kg]
Charging of refrigerant · Keeping the valve of the outdoor unit closed, be
sure to charge the liquid refrigerant into the service port at the
liquid side. · If the specified amount of refrigerant cannot be charged, fully
open the valves of the outdoor unit at liquid and gas
sides, operate the air conditioner in COOL mode, and then charge refrigerant
into service port at the gas side. In this time, choke the refrigerant
slightly by operating the valve of the canister to charge liquid refrigerant.
· The liquid refrigerant may be charged suddenly, therefore be sure to charge
refrigerant gradually.
EN-43
22
EN-44
23
Installation Manual
Full opening of the valve
Open the valves of the outdoor unit fully.
Liquid side Packed valve Using a 4 mm-hexagonal wrench, fully open the valve
rods.
Charge port
Gas side
Ball valve Using a minus screwdriver, turn it counterclockwise by 90° until it
hits the stopper. (Full open).
Body cap
Body cap
Charge port
Using a minus screwdriver, turn it counterclockwise by 90° until it hits the
stopper. (Full open)
Flare nut
Grooves
Closed
for
Opened fully
completely driver
Refer to the table below when you tight the valve cap
Valve
Liquid side Gas side
Tightening force[N·m]
Body cap
Charge port
14 ~ 18
14 ~ 18
20 ~ 25
14 ~ 18
F-GAS label
Contains fluorinated greenhouse gases · Chemical Name of Gas · Global Warming Potential (GWP) of Gas
R410A 2088 (ex.R410A ref.AR4)
CAUTION
(1) Stick the enclosed refrigerant label adjacent to the service ports for
charging or recovering location and where possible adjacent to existing
nameplates or product information label.
(2) Clearly write the charged refrigerant quantity on the refrigerant label
using indelible ink. Then, place the included transparent protective sheet
over the label to prevent the writing from rubbing off.
(3) Prevent emission of the contained fluorinated greenhouse gas. Ensure that
the fluorinated greenhouse gas is never vented to the atmosphere during
installation, service or disposal. When any leakage of the contained
fluorinated greenhouse gas is
EN-45
detected, the leak shall be stopped and repaired as soon as possible. (4) Only qualified service personnel are allowed to access and service this product. (5) Any handling of the fluorinated greenhouse gas in this product, such as when moving the product or recharging the gas, shall comply under (EU) Regulation No.517/2014 on certain fluorinated greenhouse gases and any relevant local legislation. (6) Periodical inspections for refrigerant leaks may be required depending on European or local legislation. (7) Contact dealers, installers, etc., for any questions.
Heat insulation for pipe
· Apply heat insulation of pipe separately at the liquid, gas, and balance sides. · Be sure to use thermal insulator resistant up to 120 °C or higher for pipes at the gas side.
Finishing after connecting pipes
· After piping connection work has been finished, cover the opening of the
piping / wiring panel with the piping cover, or fill silicon or putty into the
space between the pipes.
· In case of drawing-out the pipes downward or sideward, also close the
openings of the base plate and the side plate. · Under the opened condition, a
problem may be caused due to the entering of water or dust.
When using the piping cover
When not using the piping cover
Drawing-out sideward
Drawing-out frontward
Drawing-out downward
Close the opening with the pipe cover.
Pipe holding bracket
Attach pipe holding brackets following the table below.
Diameter of pipe (mm) Ø19.05 or less Ø22.22 or more
Interval 2 m 3 m
Drawing-out frontward
Drawing-out sideward
Drawing-out downward
Fill silicon or putty into the periphery of the pipes.
EN-46
EN
6 Electric Wiring
WARNING
The appliance shall be installed in accordance with national wiring
regulations. Capacity shortages of the power circuit or an incomplete
installation may cause an electric shock or fire.
CAUTION
· Perform wiring of power supply complying with the rules and regulations of
the local electric company.
· Do not connect 380-415 V power to the terminal blocks for control cables
(U1, U2, U3, U4); otherwise, the unit may break down.
· Be sure that electric wiring does not come into contact with hightemperature
parts of piping; otherwise, the coating of cables may melt and cause an
accident.
· After connecting wires to the terminal block, take off the traps and fix the
wires with cord clamps.
· Do not conduct power to indoor units until vacuuming of the refrigerant
pipes has finished.
· For the wiring of power to indoor units and that between indoor and outdoor
units, follow the instructions in the installation manual of each indoor unit.
Installation Manual
Power wiring selection Standard model
Model MCY-MHP0806HS8-E MCY-MHP1006HS8-E
MCA: Maximum Circuit Amps MOCP: Maximum Overcurrent Protection (Amps)
Power Supply Nominal Voltage, Phase and frequency
MCA (A)
MOCP (A)
380-415V 3N~, 50Hz
17.0
20.0
20.0
25.0
Circuit breaker (Earth leakage breaker)
Main switch (Fuse)
EN-47
24
EN-48
25
Installation Manual
Specifications for communication wiring
Design of communication wiring Summary of communication wiring
Outdoor unit
Central controller U1 U2 U3 U4
Uv Uv (U1) (U2)
U1 U2 U3 U4
Communication wiring between indoor and outdoor units (Shield wire)
Communication wiring between indoor units (Shield wire)
A B Uv Uv
(U1) (U2)
Indoor unit
A B Uv Uv
(U1) (U2)
Indoor unit
A B Uv Uv
(U1) (U2)
Indoor unit
A B Uv Uv
(U1) (U2)
Indoor unit
AB Remote controller
AB Remote controller
AB
Remote controller (Group control)
Communication wiring and central control wiring use 2-core non-polarity wires. Use 2-core shield wires to prevent noise trouble. In this case, for the system grounding, close (connect) the end of shield wires, and isolate the end of terminal. Use 2-core non-polarity wire for remote controller. (A, B terminals) Use 2-core non-polarity wire for wiring of group control. (A, B terminals)
Keep the rule of below tables about size and length of communication wiring.
Central controller
U1 U2 U3 U4
Outdoor unit
U3 U4
U1 U2
Uv Uv (U1) (U2)
L1
This system L4
U3 U4 U1 U2
L2
Table-1
Other system
Header unit
U3 U4
Follower unit
U3 U4
U1 U2 U5 U6 U1 U2 U5 U6
Table-1
Table-2 L5
L3
Indoor unit
Uv Uv (U1) (U2)
AB
Uv Uv (U1) (U2)
AB
Table-3
Uv Uv (U1) (U2)
AB
Uv Uv (U1) (U2)
AB
L7
Remote controller
Remote controller
Uv Uv (U1) (U2)
AB
L6
Uv Uv (U1) (U2)
AB
Uv Uv (U1) (U2)
AB
Uv Uv (U1) (U2)
AB
L7 L6
Remote controller
Uv Uv (U1) (U2)
AB
Table-1
Control wiring between indoor and outdoor units (L1, L2, L3), Central control wiring (L4)
Wiring
2-core, non-polarity
Type Size / Length *1
Shield wire 1.25 mm2: Up to 1000 m 2.0 mm2: Up to 2000 m
*1 Total of control wiring length for all refrigerant circuits ( L1 + L2 + L3 + L4 )
Table-2
Control wiring between outdoor units (L5) (Other system)
Wiring
2-core, non-polarity
Type Size / Length
Shield wire
1.25 mm2 to 2.0 mm2 Up to 100 m (L5)
Table-3 Wiring Size
Length
Remote controller wiring (L6, L7)
2-core 0.5 mm2 to 2.0 mm2
· Up to 500 m (L6 + L7) · Up to 400 m with of wireless remote controller in
group control. · Up to 200 m total length of control wiring between indoor
units ( L6 )
EN-49
EN-50
EN
Group control through a remote controller
Group control of multiple indoor units (8 units) through a single remote controller
Indoor unit No.1
No.2
No.3
No.4
No.7 No.8
AB
AB
AB
AB
Remote controller
(A.B)
AB
AB
Connection of power wires and communication wires
Remove knockouts on the piping / wiring panel on the front of the unit or the
panel on the bottom to get the power and communication wires through the
holes. Use protective parts (such as jugged bushings) to prevent the power
wires and communication wires from directly touching the edge of the sheet
metal. The local installer must purchase the non-removable jugged bushings to
wrap around the hole, and use insulated bushings (locally purchased) to
protect the wires from directly touching the sheet metal.
Remove the front panel and then remove the cover of the electrical control box.
Installation Manual
Knockout for the communication wires and refrigerant piping
NOTE
Separate the power wire and communication wires.
Jugged bushings (locally purchased)
The cover of the electrical control box
Terminal block (Communication)
Earth screw (Communication)
Cord clamp (Communication) Terminal block (Power supply)
Earth screw (Power supply)
Cord clamp (Power supply)
Power supply wires
Communication wires
EN-51
26
EN-52
27
Installation Manual
Power supply wire connection
1. Insert the power supply wire through the cutout on the side of the
electrical control box and connect the power supply wire to the power supply
terminal block and the earth line to the earth screw. After that, fix the
power supply wire with the cord clamp.
2. Use round-type crimping terminals for power connection. Also, apply
insulating sleeves to the crimping parts. Use a driver of appropriate size to
fix the terminal screws.
L1 L2 L3 N
L1 L2 L3 N
60 mm or less Power supply wire
10 mm or more Earth line
Wire size 4.0 mm2 Design 60245 IEC66 Screw size and tightening torque
Power supply terminal Earth screw
Screw size
M6 M8
Tightening torque (N·m)
2.5 to 3.0
5.5 to 6.6
Communication wire connection
Connect the communication wires to the communication wire terminals from under
the electrical control box, and fix them with the communication cable clamps.
[U1, U2] and [U3, U4] not connected [U1, U2] and [U3, U4] connected
CN02
CN02
CN10
U1 U2 U3 U4
CN10
Communication terminal board
U1 U2 U3 U4
TO INDOOR TO CENTRAL
UNIT
CONTROLLER
U1 U2 U3 U4
Communication terminal board
U1 U2 U3 U4
TO INDOOR TO CENTRAL
UNIT
CONTROLLER
Screw size and tightening torque Communication wire terminal
U3, U4: Central control device U1, U2: Communication wiring between Indoor / Outdoor unit
Screw size M4
Tightening torque (N·m)
1.2 to 1.4
EN-53
EN-54
EN
Regulation of high frequency wave
This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal to Ssc (1) at the interface point between the user’s supply and the public system. It is the responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with a short-circuit power Ssc greater than or equal to Ssc (1).
Furthermore, when similar equipment or other equipment which may cause harmonic current emissions are to be connected to the same interface point with this equipment, to reduce the risk of possible problems which may be caused from addition of those harmonic current emissions, it is recommended to make sure that the short-circuit power Ssc at the interface point is greater than the sum of the minimum Ssc required by all the equipment which will be connected to the interface point.
Ssc (*1)
Model MCY-MHP0806HS8-E MCY-MHP1006HS8-E
Ssc (kVA) 1596
This unit complies with EN 61000-3-11. However, the impedance of the power
supply system to be connected to the unit at the incoming power point must be
less than the Zmax given below. In order to meet this condition, consult with
the supply authority as required.
Zmax = 0.39 (Ù)
In addition, it is recommended that voltage drops occurring during the unit’s
operation in the area at the power input shall be around 3.3% of the nominal
power-supply voltage or less.
Installation Manual
7 Address Setting
On this unit, it is required to set the addresses of the indoor units before
starting air conditioning. Set the addresses following the steps below.
CAUTION
· Be sure to complete the electric wiring before setting the addresses.
· If you turn on the outdoor unit before turning on the indoor units, the CODE
No. [E19] is indicated on the 7-segment display on the interface P.C. board of
the outdoor unit until the indoor units are turned on. This is not a
malfunction.
· It may take up to ten minutes (normally about five minutes) to address one
refrigerant line automatically.
· Settings on the outdoor unit are required for automatic addressing. (Address
setting is not started simply by turning on the power.)
· Running the unit is not required for address setting. · The addresses can be
set manually.
Automatic addressing: setting addresses using SW15 on the interface P.C. board
on the outdoor unit
Manual addressing: setting addresses on the wired remote controller.
- When setting an address manually, the wired remote controller must temporarily be paired with an indoor unit one-to-one. (when the system is organized for group operation and no Remote controller)
REQUIREMENT
High voltage parts exist in the electrical control box. If you set addresses on an outdoor unit, operate the unit through the cover of electrical control box, to avoid electric shock. Do not remove the cover of electrical control box.
EN-55
28
EN-56
29
Installation Manual
Automatic address setting
No central control (single refrigerant line): Central control of 2 or more
refrigerant lines:
go to Address setting procedure 1 go to Address setting procedure 2
(Example) Address setting procedure
When controlling a single refrigerant line centrally
To procedure 1
When controlling 2 or more refrigerant lines centrally
To procedure 2
System wiring diagram
Outdoor Central Outdoor Central
controller
controller
Indoor Indoor Indoor Indoor
Outdoor
Outdoor Central controller
Indoor Indoor Indoor Indoor
Remote Remote Remote controller controller controller
Remote Remote Remote controller controller controller
Address setting procedure 1
1 Turn on indoor units first, and then turn on outdoor units. 2 About one
minute after turning the power on, confirm that the 7-segment display on the
interface P.C.
board of the outdoor unit indicates U. 1. L08 (U. 1. flash) .
3 Press SW 15 to start the automatic address setting.
(It may take up to 10 minutes (normally about 5 minutes) to complete one
line’s setting.)
4 The 7-segment display indicates Auto 1 Auto 2 Auto 3 .
After the indication, U. 1. – – – (U. 1. flash) starts flashing on the
display. When the flashing stops and U. 1. – – – (U. 1. light) remains lit on
the display, the setting is complete.
Interface P.C. board on the outdoor unit
SW04 SW05 SW15
3
D600 D601 D602 D603 D604
2, 4
SW01 SW02 SW03
REQUIREMENT
· When 2 or more refrigerant lines are controlled as a group, be sure to turn
on all the indoor units in the group before setting addresses.
· If you set the unit addresses of each line separately, each line’s header
indoor unit is set separately. In that case, the CODE No. “L03” (Indoor header
unit overlap) is indicated as running starts. Change the group address to make
one unit the header unit using wired remote controller.
(Example)
Controlling 2 or more refrigerant lines as a group
Outdoor
Outdoor
System wiring diagram
Indoor Indoor Indoor Indoor
Remote controller
(Group control)
Address setting procedure 2
1 Set a system address for each system using SW 13 and 14 on the interface
P.C. board on the outdoor unit
of each system. (Factory default: Address 1)
NOTE
Be sure to set a unique address on each system. Do not use a same address as
another system (refrigerant line) or a custom side.
Interface P.C. board on the outdoor unit
SW06
SW07
SW09
SW10
1 2 34
SW11
1 2 34
SW12
1 2 34
SW13
1 2 34
SW14
1234 1234 1234 1234
EN-57
EN-58
EN
Switch settings for a line (system) address on the interface P.C. board on the outdoor unit ( : switch ON, : switch OFF)
SW13
SW14
Line (system) address
1
2
3
4
1
2
3
4
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
“”: not used for system address setting (Do not change their positions.)
Installation Manual
2 In all the outdoor units connected to the central control, please make sure
that the relay connector of the
interface P.C. board “CN10” has not been connected to the “CN02”.
NOTE
If you connect a relay connector “CN10” to “CN02”, the communication line [U1,
U2] will be connected to [U3, U4]. If [U1, U2] is connected to the [U3, U4],
refrigerant line address cannot be set correctly.
)
[U1, U2] and [U3, U4] not connected
CN02
U1 U2 U3 U4
CN10
Communication terminal board
U1 U2 U3 U4
TO INDOOR TO CENTRAL
UNIT
CONTROLLER
3 Turn on indoor units first, and then turn on outdoor units. 4 About 1 minute
after turning the power on, confirm that the 7-segment display on the
interface P.C. board
of the outdoor unit indicates U. 1. L08 (U. 1. flash) .
5 Press SW 15 to start the automatic address setting.
(It may take up to 10 minutes (normally about 5 minutes) to complete one
line’s setting.)
6 The 7-segment display indicates Auto 1 Auto 2 Auto 3 .
After the indication, U. 1. – – – (U. 1. flash) starts flashing on the
display. When the flashing stops and U. 1. – – – (U. 1. light) remains lit on
the display, the setting is complete.
7 Repeat steps 4 to 6 for other refrigerant lines. 8 After completing address
setting of all systems, turn off dip switch 2 of SW30 on the interface P.C.
boards of
all the outdoor units connected to the same central control, except the unit
that has the lowest address. (For unifying the termination of the wiring for
the central control of indoor and outdoor units)
EN-59
30
EN-60
31
Installation Manual
Header unit interface P.C. board
SW06 SW07 SW09 SW10 SW11 SW12 SW13 SW14 SW16 SW17
SW04 SW05 SW15 D600 D601 D602 D603 D604 SW01 SW02 SW03
SW30
SW30
9 Connect the relay connectors “CN10” to “CN02”, which are mounted on the
interface P.C. boards of all
the outdoor units connected to the central control.
NOTE
Please make sure that before you perform this task, address setting of the
refrigerant line all have been completed.
[U1, U2] and [U3, U4] connected
CN02
CN10
U1 U2 U3 U4
Communication terminal board
U1 U2 U3 U4
TO INDOOR TO CENTRAL
UNIT
CONTROLLER
10 Set the central control address.
(For the setting of the central control address, refer to the installation
manuals of the central control devices.)
EN-61
Switch setting (setting example when controlling 2 or more refrigerant lines centrally)
Outdoor units (setting manually)
*The items in bold font must be set manually.
Outdoor unit’s interface P.C. board
SW13, 14 (Line (system) address)
Dip switch 2 of SW30 (Terminator of indoor / outdoor communication line and
central control line)
Relay connector
Outdoor unit 1
ON
Connect after setting addresses.
Outdoor unit 2
Set to OFF after setting addresses.
Connect after setting addresses.
Outdoor unit
3
Set to OFF after setting addresses.
Connect after setting addresses.
Factory default 1 ON
Open
Outdoor unit [U1, U2] and [U3, U4] connected
CN02
U1 U2
U3 U4
CN10
Uv Uv (U1) (U2)
Outdoor unit [U1, U2] and [U3, U4] connected
CN02
U1 U2
U3 U4
CN10
Outdoor unit [U1, U2] and [U3, U4] connected
CN02
U1 U2
U3 U4
CN10
Central controller
Uv Uv (U1) (U2)
AB
Uv Uv (U1) (U2)
AB
Uv Uv (U1) (U2)
AB
Uv Uv (U1) (U2)
AB
Uv Uv (U1) (U2)
AB
Remote controller
Remote controller
Individual
Indoor units (automatic setting)
Line (system) address Indoor unit address Group address
CAUTION
Remote controller
Group
1
1
2
1
2
1
0
0
1
Remote controller
2
3
2
1
2
0
Relay connector connection Never connect relay connectors between the [U1, U2] and [U3, U4] terminals before completing address setting of all the refrigerant lines. Otherwise, the addresses cannot be set correctly.
EN-62
EN
Manual address setting with the remote controller
Procedure when setting indoor units’ addresses first under the condition that
indoor wiring has been completed and outdoor wiring has not been started
(manual setting using the remote controller)
Wiring example of 2 refrigerant lines
Refrigerant line 1
Refrigerant line 2
Outdoor unit
Outdoor unit
Remote controller
Indoor unit 1 Indoor unit 2 Indoor unit 3
Indoor unit 1 Indoor unit 2
Line (system) address Indoor unit address
Group address
1
1
1 Header unit
1
1
2
3
2
2
Follower unit Follower unit
2
2
1
2
2
2
Follower unit Follower unit
In the example above, disconnect the remote controller connections between the indoor units and connect a wired remote controller to the target unit directly before address setting.
2, 5, 8 SET DATA 4, 7, 10 11
SET DATA SETTING
TEMP.
UNIT No. R.C. No.
CODE No.
ON / OFF
TIMER SET
FILTER RESET TEST
TIME SET CL
CODE No.
3, 6, 9
1
Pair the indoor unit to set and the remote controller one-to-one.
Turn on the power.
1 Push and hold the , , and
LCD starts flashing.
buttons at the same time for more than 4 seconds.
Installation Manual
<Line (system) address>
2 Push the TEMP.
/
buttons repeatedly to set the CODE No. to .
3 Push the TIME / buttons repeatedly to set a system address.
(Match the address with the address on the interface P.C. board of the outdoor unit in the same refrigerant line.)
4 Push the button.
(It is OK if the display turns on.)
5 Push the TEMP.
/
buttons repeatedly to set the CODE No. to .
6 Push the TIME / buttons repeatedly to set an indoor unit address.
7 Push the button.
(It is OK if the display turns on.)
/ buttons repeatedly to set the CODE No. to .
/ buttons repeatedly to set a group address. If the indoor unit is individual, set the
; header unit,
; follower unit,
.
Individual
: 0000
Header unit Follower unit
: 0001 : 0002
In case of group control
10 Push the button.
(It is OK if the display turns on.)
11 Push the button.
The address setting is complete.
(
flashes. You can control the unit after
has disappeared.)
NOTE
1. Do not use address numbers 29 or 30 when setting system addresses using
the remote controller. These 2 address numbers cannot be used on outdoor units
and the CODE No. [E04] (Indoor / outdoor communication error) will appear if
they are mistakenly used.
2. If you set addresses to indoor units in 2 or more refrigerate lines
manually using the remote controller and will control them centrally, set the
outdoor unit of each line as below. · Set a system address for the outdoor
unit of each line with SW13 and 14 of their interface P.C. boards. · Turn off
dip switch 2 of SW30 on the interface P.C. boards of all the outdoor units
connected to the same central control, except the unit that has the lowest
address. (For unifying the termination of the wiring for the central control
of indoor and outdoor units) · Connect the relay connectors (CN10) between the
[U1, U2] and [U3, U4] terminals on the interface P.C. board to CN02 in all the
outdoor units to which the central control is connected. · After finishing all
the settings above, set the address of the central control devices. (For the
setting of the central control address, refer to the installation manuals of
the central control devices.)
EN-63
32
EN-64
33
Installation Manual
Confirming the indoor unit addresses and the position of an indoor unit using
the remote controller
Confirming the numbers and positions of indoor units
To see the indoor unit address of an indoor unit which you know the position
of
When the unit is individual (the indoor unit is paired with a wired remote
controller one-to-one), or it is a group-controlled one.
UNIT No.
CODE No.
TEMP.
TIMER SET
FILTER RESET TEST
TIME SET CL
ON / OFF
1
Starts running
2
(Execute it while the units are running.)
1 Push the
button if the units stop.
2 Push the UNIT LOUVER button (left side of the button).
A unit numbers is indicated on the LCD (it will disappear after a few seconds). The indicated number shows
the system address and indoor unit address of the unit.
When 2 or more indoor units are connected to the remote controller (group- controlled units), a number of other connected units appears each time you push the UNIT LOUVER button (left side of the button).
To find an indoor unit’s position from its address
When checking unit numbers controlled as a group
3
Stop
1
SET DATA SETTING
TEMP.
UNIT No. R.C. No.
CODE No.
ON / OFF
TIMER SET
FILTER RESET TEST
TIME SET CL
2
EN-65
(Execute it while the units are stopped.) The indoor unit numbers in a group are indicated one after another. The fan and louvers of the indicated units are activated.
1 Push and hold the
and buttons at the same time for more than 4 seconds.
·
appears on UNIT No. on the LCD display.
· The fans and louvers of all the indoor units in the group are activated.
2 Push the UNIT LOUVER button (left side of the button). Each time you push the button, the indoor unit numbers
are indicated one after another.
· The first-indicated unit number is the address of the header unit.
· Only the fan and louvers of the indicated indoor unit are activated.
3 Push the button to finish the procedure.
All the indoor units in the group stop.
To check all the indoor unit addresses using an arbitrary wired remote controller. (When communication wirings of 2 or more refrigerant lines are interconnected for central control)
SET DATA SETTING
TEMP.
UNIT No. R.C. No.
CODE No.
ON / OFF
1
TIMER SET
FILTER RESET TEST
TIME SET CL
6
4
35
2
(Execute it while the units are stopped.) You can check indoor unit addresses and positions of the indoor units in a single refrigerant line. When an outdoor unit is selected, the indoor unit numbers of the refrigerant line of the selected unit are indicated one after another and the fan and louvers of the indicated indoor units are activated.
1 Push and hold the TIME and buttons at the same time for more than 4 seconds.
At first, the line 1 and CODE No. (Address Change) are indicated on the LCD
display. (Select an outdoor unit.)
2 Push the UNIT LOUVER (left side of the button) and SWING/FIX buttons
repeatedly to select a system address. 3 Push the button to confirm the system
address selection.
· The address of an indoor unit connected to the selected refrigerant line is
indicated on the LCD display and its fan and louvers are activated.
4 Push the UNIT LOUVER button (left side of the button). Each time you push
the button, the indoor unit numbers
of the selected refrigerant line are indicated one after another. · Only the
fan and louvers of the indicated indoor unit are activated.
EN-66
Installation Manual
EN
To select another system address
5 Push the button to return to step 2.
· After returning to step 2, select another system address and check the
indoor unit addresses of the line.
6 Push the button to finish the procedure.
Changing the indoor unit address using a remote controller
To change an indoor unit address using a wired remote controller.
The method to change the address of an individual indoor unit (the indoor unit
is paired with a wired remote controller one-to-one), or an indoor unit in a
group. (The method is available when the addresses have already been set
automatically.)
3 5 8
Finish
1
SET DATA SETTING
TEMP.
UNIT No. R.C. No.
CODE No.
ON / OFF
TIMER SET
FILTER RESET TEST
TIME SET CL
4
2, 6, 7
(Execute it while the units are stopped.)
1 Push and hold the , , and buttons at the same time for more than 4 seconds.
(If 2 or more indoor units are controlled in a group, the first indicated UNIT No. is that of the head unit.)
2 Push the UNIT LOUVER button (left side of the button) repeatedly to select an indoor unit number to change if 2
or more units are controlled in a group. (The fan and louvers of the selected indoor unit are activated.)
(The fan of the selected indoor unit is turned on.)
3 Push the TEMP.
/
buttons repeatedly to select for CODE No.
4 Push the TIME / buttons repeatedly to change the value indicated in the SET DATA section to that
you want.
5 Push the button.
6 Push the UNIT LOUVER button (left side of the button) repeatedly to select another indoor UNIT No. to change.
Repeat steps 4 to 6 to change the indoor unit addresses so as to make each of them unique.
7 Push the UNIT LOUVER button (left side of the button) to check the changed addresses.
8 If the addresses have been changed correctly, push the button to finish the procedure.
To change all the indoor unit addresses using an arbitrary wired remote
controller. (The method is available when the addresses have already been set
automatically.) (When communication wirings of 2 or more refrigerant lines are
interconnected for central control)
NOTE
You can change the addresses of indoor units in each refrigerant line using an
arbitrary wired remote controller.
- Enter the address check / change mode and change the addresses.
SET DATA SETTING
TEMP.
UNIT No. R.C. No.
CODE No.
ON / OFF
1
TIMER SET
FILTER RESET TEST
TIME SET CL
3
2
Cancels the line selection
If no number appears on UNIT No., no outdoor unit exists on the line. Push button and select another line following step 2.
(Execute it while the units are stopped.)
1 Push and hold the TIME and buttons at the same time for more than 4 seconds.
At first, the line 1 and CODE No. (Address Change) are indicated on the LCD
display.
2 Push UNIT LOUVER (left side of the button) and SWING/FIX buttons repeatedly
to select a system address. 3 Push the button.
· The address of one of the indoor units connected to the selected refrigerant
line is indicated on the LCD display and the fan and louvers of the unit are
activated. At first, the current indoor unit address is displayed in SET DATA.
(No system address is indicated.)
4 8
Finish
SET DATA SETTING
TEMP.
UNIT No. R.C. No.
CODE No.
ON / OFF
TIMER SET
FILTER RESET TEST
TIME SET CL
5, 7 Press to finish setting.
6
EN-67
34
EN-68
35
Installation Manual
4 Push the TIME / buttons repeatedly to change the value of the indoor unit
address in SET DATA.
Change the value in SET DATA to that of a new address.
5 Push the button to confirm the new address on SET DATA. 6 Push the UNIT
LOUVER button (left side of the button) repeatedly to select another address
to change.
Each time you push the button, the indoor unit numbers in a refrigerant line
are indicated one after another. Only the fan and louvers of the selected
indoor unit are activated. Repeat steps 4 to 6 to change the indoor unit
addresses so as to make each of them unique.
7 Push the button.
(All the segments on the LCD display light up.)
8 Push the button to finish the procedure.
Resetting the address (Resetting to the factory default (address undecided))
Method 1 Clearing each address separately using a wired remote controller. Set
the system address, indoor unit address and group address to “0099” using a
wired remote controller. (For the setting procedure, refer to the address
setting procedures using the wired remote controller on the previous pages.)
Method 2 Clearing all the indoor unit addresses on a refrigerate line at once
from the outdoor unit.
1 Turn off the refrigerant line to reset to the factory default and set the
outdoor unit of the line as below.
- Disconnect the relay connectors between the [U1, U2] and [U3, U4] terminals. (Leave them as they are if they have already been disconnected.)
- Turn on dip switch 2 of SW30 on the interface P.C. board of the outdoor unit if the switch is OFF. (Leave it as it is if it has already been set to ON.)
[U1, U2] and [U3, U4]
not connected
Outdoor unit
U3 U4
CN02
CN10
U1 U2
[U1, U2] and [U3, U4] connected
Outdoor unit
U3 U4
CN02
CN10
U1 U2
Central controller
U1 U2 U3 U4
[U1, U2] and [U3, U4] connected
Outdoor unit
U3 U4
CN02
CN10
U1 U2
Uv Uv (U1) (U2)
Uv Uv (U1) (U2)
AB
Uv Uv (U1) (U2)
AB
Uv Uv (U1) (U2)
AB
Uv Uv (U1) (U2)
AB
Uv Uv (U1) (U2)
AB
Remote controller
Remote controller
Remote controller
Indoor units to have their addresses initialized
Remote controller
2 Turn on the indoor and outdoor units of the refrigerant line for which you
want to initialize the addresses.
About one minute after turning on the power, confirm that the 7-segment
display on the outdoor unit indicates U. 1. – – – and operate the interface
P.C. board on the outdoor unit of the refrigerant line as follows.
SW01 SW02 SW03
SW04
Clearable addresses
Confirm that the 7-segment display indicates
2
1
2
A.d.buS and turn SW04 ON for more than
System / indoor unit / group address
five seconds.
Confirm that the 7-segment display indicates
2
2
2
A.d.nEt and turn SW04 ON for more than
five seconds.
Central control address
3 Confirm that the 7-segment display indicates A.d. c.L. and set SW01, SW02
and SW03 to 1, 1, 1
respectively.
4 After a time U.1.L08 appears on the 7-segment display if the address
clearing has been completed
successfully. If A.d. n.G. appears on the 7-segment display, the outdoor unit
may still be connected to another refrigerant line. Check again the connection
of the relay connectors (CN10) between the [U1, U2] and [U3, U4] terminals.
NOTE
Take care to carry out the procedure above correctly; otherwise, addresses in
other refrigerate lines may also be cleared.
5 Set the addresses again after finishing the clearance.
EN-69
EN-70
EN
8 Test Run
Settings for hot water modules
After automatic addressing is completed, if there is hot water module in the
system, 7-segment display will indicate / .
Please adjust the DIP switch as below, and slide SW09-bit4 to “ON” position.
SW06
SW07
SW09
SW10
1 2 34 SW11
1 2 34 SW12
1 2 34
1 2 34
1234 1234
Before test run
Confirm that the valve of the refrigerate pipe of the outdoor unit is OPEN. ·
Before turning on the power, confirm that the resistance between the terminal
block of power supply and the earth is
more than 1 MÙ using a 500 V megohmmeter. Do not run the unit if it is less
than 1 MÙ.
CAUTION
· Turn on the power and turn on the case heater of the compressor. To save the
compressor when it is activated, leave the power on for more than 12 hours.
Methods of test run
When executing a test run using a remote controller
Operate the system normally to check the running condition using the wired
remote controller. Follow the instructions in the supplied owner’s manual when
operating the unit. If you use a wireless remote controller for operations,
follow the instructions in the installation manual supplied with the indoor
unit. To execute a test run forcibly under the condition that the thermostat
automatically turns the unit off due to the indoor temperature, follow the
procedure below. The forcible test run will automatically stop after 60
minutes to prevent continuous forcible running and return to normal running.
CAUTION
Do not use forcible running except for a test run as it overloads the unit.
Installation Manual
TEMP.
TIMER SET
FILTER RESET TEST
TIME SET CL
ON / OFF
2, 4 3
1, 5
1 Push and hold the button for more than 4 seconds. TEST appears on the LCD
display and the unit
enters the test mode. (TEST is indicated on the LCD display during the test
run.)
TEST
2 Push the 3 Push the
button. button to switch the running mode to COOL or HEAT.
NOTE
· Do not run the unit in any mode other than COOL or HEAT. · You cannot change
the temperature setting during the test run. · Errors are detected as usual.
TEST
4 Push the
button to stop running after finishing the test run.
The indication on the LCD display returns to the status of procedure 1.
5 Push the button to exit the test mode.
EN-71
36
EN-72
37
Installation Manual
(TEST disappears on the LCD display and the status changes to normal stopped mode.)
When executing a test run using the interface P.C. board on the outdoor unit
You can execute a test run by operating switches on the interface P.C. board
of the outdoor unit. “Individual test run”, which tests each indoor unit
separately, and “collective test run”, which tests all the indoor units
connected, are available.
7-segment display
[A] [B] [U1] [ ]
2 Set the rotary switches on the interface P.C. board of the outdoor unit:
SW01 to [16], SW02 and SW03 to
the address of the indoor unit to be tested.
SW02 1 to 16 1 to 16 1 to 16 1 to 16
SW03 1 2 3 4
1 to 16 17 to 32 33 to 48 49 to 64
Indoor unit address Set number of SW02 Set number of SW02 + 16 Set number of SW02 + 32 Set number of SW02 + 48
7-segment display
[A] [ ] Address display of the corresponding
indoor unit [B] [ ]
3 Push and hold SW04 for more than 10 seconds.
7-segment display
[A] [ ] Address display of the corresponding
indoor unit [B] [ ] [FF] is displayed for 5
seconds.
NOTE
· The running mode follows the mode setting on the remote controller of the target indoor unit. · You cannot change the temperature setting during the test run. · Errors are detected as usual. · The unit does not perform test run for 3 minutes after turning the power on or stopping running.
Finishing operation
1 Set the rotary switches on the interface P.C. board of the outdoor unit
back: SW01 to [1], SW02 to [1] and
SW03 to [1].
7-segment display
[A] [B] [U1] [ ]
7-segment display
[A] [C ] [H ] [B] [ ] [ ]
2 Push and hold SW04 for more than 2 seconds.
7-segment display
[A] [C ] [H ] [B] [ -C ] [ -H ]
NOTE
EN-73
EN-74
· You cannot change the temperature setting during the test run. · Errors are detected as usual. · The unit does not perform test run for 3 minutes after turning the power on or stopping running.
Stop operation
1 Set the rotary switches on the interface P.C. board of the outdoor unit
back:
SW01 to [1], SW02 to [1] and SW03 to [1].
7-segment display
[A] [B] [U1] [ ]
Interface P.C. board
SW06 SW07 SW09 SW10 SW11 SW12 SW13 SW14 SW16 SW17
SW04 SW05 SW15 D600 D601 D602 D603 D604 SW01 SW02 SW03
SW30
Push switch
7-segment display [A]
SW04 SW05 SW15
D600 D601 D602 D603 D604
Push switch
7-segment display [B]
SW01 SW02 SW03 Rotary switches
EN-75
Installation Manual
9 Troubleshooting
In addition to the CODE No. on the remote controller of an indoor unit, you
can diagnose failure type of an outdoor unit by checking the 7-segment display
on the interface P.C. board. Use the function for various checks. Set every
dip switch to OFF after checking.
7-Segment display and check code
Rotary switch setting value
SW01 SW02 SW03
Indication
LED
D600 D601 D602 D603 D604
A
B
A
1
1
1
Outdoor unit check code
B
Outdoor unit number (U1)
Check code display*
- If a check code has an auxiliary code, the display indicates the check code for three seconds and the auxiliary code for one second alternately.
Check code (indicated on the 7-segment display on the outdoor unit) Indicated when SW01 = [1], SW02 = [1], and SW03 = [1].
Check code
Indication on 7-segment display on the outdoor unit
Auxiliary code
E06 Number of indoor units which received normally
E07
—
E08
—
E15
—
E16 00: Capacity over 01 or more: No. of connected units
E20
01: Other line outdoor connected 02: Other line indoor connected
E31 IPDU quantity information*1
F04
—
F06
—
F07
01: TL1 sensor 03: TL3 sensor
F08
—
F12
01: TS1 sensor 03, 04: TS3 sensor
F13
—
F15
—
F16
—
F23
—
F24
—
Check code name
Decrease of number of indoor units, or HWM unit only Indoor / Outdoor
communication circuit trouble Duplication of indoor addresses No indoor unit
during automatic addressing Number of connected capacity over / indoor units
Other line connected during automatic addressing
IPDU communication trouble TD sensor trouble TE sensor trouble
TL1 or TL3 sensor trouble
TO sensor trouble
TS1 or TS3 sensor trouble
TH sensor (Board installed) trouble Outdoor temp. sensor miswiring (TE, TL1)
Outdoor pressure sensor miswiring (Pd, Ps) Ps sensor trouble Pd sensor trouble
38
EN-76
EN
39
Installation Manual
Check code
Indication on 7-segment display on the outdoor unit
Auxiliary code
F31
—
H01
—
H02
—
H03
—
H05
—
H06
—
H07
—
H08 01
H16 01
L04
—
L06 Number of indoor units with priority
L08
—
L10
—
L23 02
L29 IPDU quantity information *1
L30 Detected indoor unit address
P03
—
P04
—
00
P05 E (: Fan motor number)
—
P07
—
P10 Detected indoor unit address
P13
—
P15 01: TS condition 02: TD condition
P19
—
P20
—
*0: Elemental device short
*1: Position detective circuit trouble
*2: Input current sensor trouble
P22
3: Fan motor lock trouble 4: Motor current trouble *5: Synchronize, step out trouble
*C: Sensor temperature trouble
*D: Sensor short, free trouble
(*: Fan motor number)
P26
—
P29
—
Check code name
Outdoor program trouble Compressor breakdown Compressor trouble (Lock) Current
detective circuit system trouble TD sensor miswiring Low-pressure protective
operation Oil level down detection TK sensor trouble for oil level Oil level
detector circuit trouble Outdoor system address duplicated Duplication of
indoor units with priority Indoor group / Address unset Outdoor capacity unset
SW setting trouble when connecting to HWM unit IPDU quantity error External
interlock of indoor unit Discharge temp TD trouble High-pressure switch
trouble Phase missing detection Fan motor Vdc trouble Compressor Vdc trouble
Heat sink overheat trouble Indoor overflow trouble Outdoor liquid back
detection trouble Gas leak detection 4-way valve operation trouble High-
pressure protective operation
Outdoor fan IPDU trouble
Compressor IPM short protection trouble Compressor position detective circuit
system trouble
*1 IPDU number information
01: Compressor 02: Fan 1 03: Compressor and Fan 1 04: Fan 2 05: Compressor and
Fan 2 06: Fan 1 and Fan 2 07: Compressor, Fan 1 and Fan 2 08: Fan 3 09:
Compressor and Fan 3 0A: Fan 1 and Fan 3 0B: Compressor, Fan 1 and Fan 3 0C:
Fan 2 and Fan 3 0D: Compressor, Fan 2 and Fan 3 0E: Fan 1, Fan 2 and Fan 3 0F:
Compressor, Fan 1, Fan 2 and Fan 3
EN-77
WARNINGS ON REFRIGERANT LEAKAGE
Check of Concentration Limit
The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its concentration will not exceed a set limit.
The refrigerant R410A which is used in the air conditioner is safe, without the toxicity or combustibility of ammonia,
and is not restricted by laws to be imposed which protect the ozone layer. However, since it contains more than air, it
poses the risk of suffocation if its concentration should rise excessively. Suffocation from leakage of R410A is almost
non-existent. With the recent increase in the number of high concentration buildings, however, the installation of multi
air conditioner systems is on the increase because of the need for effective use of floor space, individual control,
energy conservation by curtailing heat and carrying power etc.
Most importantly, the multi air conditioner system is able to replenish a large amount of refrigerant compared with
conventional individual air conditioners. If a single unit of the multi conditioner system is to be installed in a small
room, select a suitable model and installation procedure so that if the refrigerant accidentally leaks out, its
concentration does not reach the limit (and in the event of an emergency, measures can be made before injury can
occur).
In a room where the concentration may exceed the limit, create an opening with adjacent rooms, or install mechanical
ventilation combined with a gas leak detection device.
The concentration is as given below.
Total amount of refrigerant (kg) Min. volume of the indoor unit installed room (m3)
Concentration limit (kg/m3)
The concentration limit of R410A which is used in multi air conditioners is 0.3 kg/m3.
NOTE 1
If there are 2 or more refrigerating systems in a single refrigerating device,
the amounts of refrigerant should be as charged in each independent device.
e.g., charged amount (10 kg)
Outdoor unit e.g., charged amount (15 kg)
Indoor unit
Room A Room B Room C Room D Room E Room F
For the amount of charge in this example: The possible amount of leaked
refrigerant gas in rooms A, B and C is 10 kg. The possible amount of leaked
refrigerant gas in rooms D, E and F is 15 kg.
EN-78
Important
NOTE 2
The standards for minimum room volume are as follows. (1) No partition (shaded
portion)
(2) When there is an effective opening with the adjacent room for ventilation of leaking refrigerant gas (opening without a door, or an opening 0.15% or larger than the respective floor spaces at the top or bottom of the door).
Outdoor unit Refrigerant piping
Indoor unit
(3) If an indoor unit is installed in each partitioned room and the refrigerant piping is interconnected, the smallest room of course becomes the object. But when a mechanical ventilation is installed interlocked with a gas leakage detector in the smallest room where the density limit is exceeded, the volume of the next smallest room becomes the object.
Refrigerant piping
Outdoor unit
Indoor unit
Very small room
Small room
Medium room
Large room
Mechanical ventilation device – Gas leak detector
NOTE 3
The minimum indoor floor area compared with the amount of refrigerant is
roughly as follows: (When the ceiling is 2.7m high)
m2 40 35 30 25
Range below the density limit of 0.3 kg/m3 (countermeasures not needed)
20
Range above the density
15
limit of 0.3 kg/m3
10
(countermeasures needed)
5
0
10
20
30
Total amount of refrigerant
kg
EN-79
40
Min. indoor floor area
EN
Installation Manual
DHV2307201-03
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>