ENGLANDER BLUE RIDGE 500-I Wood Insert Stove Owner’s Manual

June 12, 2024
ENGLANDER

ENGLANDER BLUE RIDGE 500-I Wood Insert Stove

ENGLANDER BLUE RIDGE 500-I Wood Insert Stove 

SAFETY INSTRUCTIONS

Safety tested according to ULC S628, UL 1482 and UL 737 by an accredited laboratory.

US Environmental Protection Agency phase II certified wood insert compliant with 2020 cord wood standard.

CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS AND INSTALLATION INSPECTION REQUIREMENTS IN THE AREA.

READ THIS ENTIRE MANUAL BEFORE INSTALLATION AND USE OF THIS WOOD INSERT. FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN PROPERTY DAMAGE, BODILY INJURY OR EVEN DEATH.

READ AND KEEP THIS MANUAL FOR REFERENCE

ONLINE WARRANTY REGISTRATION

If the unit requires repairs during the warranty period, proof of purchase must be provided. The purchase invoice must be kept. The date indicated on it establishes the warranty period. If it can not be provided, the warranty period will be determined by the date of manufacture of the product. It is also highly recommended to register the warranty online at

https://www.englander-stoves.com/ca/en/warranty-registration/

Registering the warranty will help to quickly find the information needed on the unit.

CERTIFICATION PLATE

Certification Plate

General Information

Performances

Values are as measured per test method, except for the recommended heating area, firebox volume, maximum burn time and maximum heat output.

Models Blue Ridge 500-I (ESW0014)
Type of combustion Dry Cordwood
Fuel Type Non-catalytic
Recommended heating area (sq. ft..)1 1,000 to 2,700 ft2 (93 to 251 m2)
Overall Firebox Volume2 3.5 ft3 (0.099 m3)
EPA Loading volume 2.88 ft3 (0.082 m3)
Maximum burn time1 10 hours
Maximum heat output (dry cordwood)2 110,000 BTU/h (32.2 kW)
__ Overall heat output rate (min. to max.)3 4 17,200 BTU/h to 57,800 BTU/h

(5.0 kW to 16.9 kW)
Average overall efficiency3 – Dry cordwood| 71 % (HHV)5| 76 % (LHV)6
Optimum overall efficiency7| 77 %
Optimum heat transfert efficiency8| 75 %
Average particulate emissions rate9| 1.6 g/h (EPA / CSA B415.1)10
Average CO11| 73 g/h

  1. Recommended heating area and maximum burn time may vary subject to location in home, chimney draft,heat loss factors, climate, fuel type and other variables. The recommended heated area for a given appliance is defined by the manufacturer as its capacity to maintain a minimum acceptable temperature in the designated area in case of a power failure.
  2. The overall firebox calculation is an approximation and is not intended to be used for loading. This volume includes a buffer zone to allow an easier fuel insertion, prevent ash spillage and allow the air wash to work properly.
  3. The maximum heat output (dry cordwood) is based on a loading density varying between 15 lb/ft3 and 20 lb/ft3. Other performances are based on a fuel load prescribed by the standard. The specified loading density varies between 7 lb/ft³ and 12 lb/ft3. The moisture content is between 19% and 25%.
  4. As measured per CSA B415.1 stack loss method.
  5. Higher Heating Value of the fuel.
  6. Lower Heating Value of the fuel.
  7. Optimum overall efficiency at a specific burn rate (LHV).
  8. The optimum heat transfer efficiency is for the low burn rate and represents the appliance’s ability to convert the energy contained in the wood logs into energy transferred to the room in the form of heat and does not take into account the chemical losses during combustion.
  9. This appliance is officially tested and certified by an independent agency.
  10. Tested and certified in compliance with CFR 40 part 60, subpart AAA, section 60.534(a)(1(ii) and ASTM E3053 based on the ATM send by EPA on October 12th, 2017.
  11. Carbon monoxide.
Specifications
Recommended log length 16 in (406 mm) east-west
Maximum log length1 22 in (560 mm) east-west
Flue outlet diameter 6 in (150 mm)
Recommended connector pipe diameter 6 in (150 mm)
Type of chimney ULC S635, CAN/ULC-S640, UL 1777
Minimum liner height 12 feet
Baffle material Vermiculite
Approved for alcove installation Not applicable
Approved for mobile home installation2 No
Type of door Simple, glass with cast iron frame
Type of glass Ceramic glass
Blower Included (Up to 144 CFM)
Particulate emission standard3 EPA / CSA B415.1
USA Standard (Safety) UL 1482, UL 737
Canada Standard (Safety) ULC-S628
  1. North-south: ends of the logs visible, East-west: sides of the logs visible.
  2. Mobile homes (Canada) or manufactured homes (USA): The US Department of Housing and Urban Development describes “manufactured homes” better known as “mobile homes” as follows; buildings built on fixed wheels and those transported on temporary wheels/axles and set on a permanent foundation. In Canada, a mobile home is a dwelling for which the manufacture and assembly of each component is completed or substantially completed prior to being moved to a site for installation on a foundation and connection to service facilities and which conforms to the CAN/CSAZ240 MH standard.
  3. Tested and certified in compliance with CFR 40 part 60, subpart AAA, section 60.534(a)(1(ii) and ASTM E3053 based on the ATM send by EPA on October 12th, 2017.
Dimensions

Dimensions
Dimensions

EPA Loading

The loading methods shown below are those that were used during emissions certification.

Air control

The air control is located underneath the ash shelf. To open the air control, pull the air control handle completely (High). This will increase the burn rate. To close the air control, push the air control handle completely toward the insert (Low). This will decrease the burn rate.
Air control

High burn rate

Open the air control completely. Place height small pieces (2 1/2″ x 2 1/2″ approximately) of wood in two layers in the firebox crossing them at the greatest possible angle. Criss cross 15 to 20 kindling wood pieces (1″x1″ approximately) on the small pieces of wood in three or four layers at the greatest possible angle. Tie knot with five sheets of paper and place them on top of the kindling wood. Light up the paper and let the door ajar at 90° until all the kindling wood is on fire. Close the door. When there is no more fire in the front of the firebox and there are only faint flames on the wood in the back of the firebox, break ashes, level the coal bed and put six logs in the firebox. Put 3 pieces centered on the coal bed, without air space between them. Leave one inch of air space between the rear firebrick and the first piece. The three other pieces should be added on top of the first 3, still in an East-West configuration. Let the door ajar at 90° for 1 minute and then close the door

Medium and low burn rate

On a two inches thick coal bed that is still red, place three logs centered on the coal bed in an East-West orientation. There should be air space between each log and between the logs and the bricks. The three other pieces should be added on top of the first three, in an East-West orientation but slightly angled of 10° still with air space between each log and the bricks. Let the door ajar at 90° for approximately 5 min. Then, close the door with the primary air control open. Leave to burn with the primary air control open for approximately 10 more minutes and then close the primary air control completely for the low burn rate and halfway for the medium burn rate. For better results, close the air control gradually from the closing of the door to the complete closing of the air control.

Logs placement

The images below show how to place the logs in the combustion chamber as described previously.
Logs placement

Clearances to Combustible Material

When the insert is installed so that its surfaces are at or beyond the minimum clearances specified, combustible surfaces will not overheat under normal and even abnormal operating conditions.

NO PART OF THE INSERT MAY BE LOCATED CLOSER TO THE COMBUSTIBLE THAN THE MINIMUM CLEARANCE FIGURES GIVEN.

Minimum Masonry Opening and Clearances to Combustibles

Minimum Masonry Opening and Clearances to Combustibles

| MINIMUM CLEARANCES
---|---
F| 19″ (483 mm)
G| 9″ (229 mm)
H| 27″ (686 mm)
I| 27″ (686 mm)
Q| 84″ (213 cm)
| MAXIMUM THICKNESS
---|---
O| 5″ (127 mm)
P| 12″ (305 mm)
| MINIMUM MASONRY OPENING
---|---
J| 26 ¼” (660 mm)
K 1| 31″ (787 mm)
L| 18 3/8″ (457 mm)

Floor Protection

It is necessary to have a floor protection made of non-combustible materials that meets the measurements specified in the “Table 1 : Floor Protection” below.

Table 1 : Floor Protection

| FLOOR PROTECTION
---|---
Canada| USA
B 1| 18″ (457 mm)| 16″ (406 mm)
M| 8″ (203 mm)| N/A
N| N/A| 8″ (203 mm)

Floor Protection

To determine the need to add floor protection (D) beyond the hearth extension (A), the following calculation must be done using the data in “Table 2 : Data for Floor Protection Calculation” of this section: D = B – G, where G = A-C.
Floor Protection

Table 2 : Data for Floor Protection Calculation

| A| B| C| D| E| Air Jacket
---|---|---|---|---|---|---
Maximum Extended| Dimension of the hearth extension| See section 9.2.1 and 9.2.2| 3 ⅝” (93 mm)| G = (A-C) D=B- G| 7 ⅛” (181 mm)| Back from fireplace facing 1 ⅜”
Minimum Extended| Dimension of the hearth extension| See section 9.2.1 and 9.2.2| 2 ¼” (57 mm)| G = (A-C) D=B- G| 8 ½” (216 mm)| Back from fireplace facing 2 ¾”

If the value (D) is negative or zero, additional floor protection in front of the unit is not needed because the masonry fireplace hearth extension is long enough. If the value (D) is positive, an additional floor protection in front of the hearth extension at least equivalent to the result (D) must be added.

Installation Raised of 6″ (152 mm) and Less

If non-combustible material floor protection needs to be added in front of and level with the hearth extension of the masonry fireplace (F = 6″ [152 mm) or less), an R-value equal to or greater than 2.00 is required and should extend at least 27″ (686 mm) in front of the unit (B). Refer to “Additional Floor Protection – Not Raised Installation”

Installation Raised of More Than 6″ (152 mm)

If the extension of the masonry hearth is raised at least 6″ (152 mm) from the floor protection, a noncombustible material, without an R-value, must extend at least 16″ (406 mm in USA) or 18″ (457 mm in Canada) in front of the unit (B). Refer to “Additional Floor Protection – Raised Installation”.

R Value

There are two ways to calculate the R-value of the floor protection. First, by adding the R-values of materials used, or by the conversion if the K factor and thickness of the floor protection are given. To calculate the total R value from R values of the materials used, simply add the R-values of materials. If the result is equal to or greater than the R-value requirements, the combination is acceptable. R-values of some selected materials are shown below.

Table 3 : Thermal Characteristics of Common Floor Protection Materials1

MATERIAL| CONDUCTIVITY (K) PER INCH| RESISTANCE (R) PER INCH THICKNESS
---|---|---
Micore® 160| 0.39| 2.54
Micore® 300| 0.49| 2.06
Durock®| 1.92| 0.52
Hardibacker®| 1.95| 0.51
Hardibacker® 500| 2.3| 0.44
Wonderboard®| 3.23| 0.31
Cement mortar| 5.00| 0.2
Common brick| 5.00| 0.2
Face brick| 9.00| 0.11
Marble| 14.3 – 20.00| 0.07 – 0.05
Ceramic tile| 12.5| 0.008
Concrete| 1.050| 0.950
Mineral wool insulation| 0.320| 3.120
Limestone| 6.5| 0.153
Ceramic board (Fibremax)| 0.450| 2.2
Horizontal still air (1/8″ thick)1| 0.135| 0,920**

Exemple:

Required floor protection R of 1.00. Proposed materials: four inches of brick and one inch of Durock® board: Four inches of brick (R = 4 x 0,2 = 0,8) plus 1 inch of Durock® (R = 1 x 0.52 = 0.52). 0.8 + 0.52 = 1.32.

This R value is larger than the required 1.00 and is therefore acceptable.

In the case of a known K and thickness of alternative materials to be used in combination, convert all K values to R by dividing the thickness of each material by its K value. Add R values of the proposed materials as shown in the previous example.

Exemple:

K value = 0.75
Thickness = 1
R value = Thickness/K = 1/0.75 = 1.33

Installing Options on Your Product and Replacing Parts

Replacement and Adjustment

Door

Note : The images shown are for guidance only and may be different from your product, but the assembly remains the same.

In order for the insert to burn at its best efficiency, the door must provide a perfect seal with the firebox. Therefore, the gasket should be inspected periodically to check for a good seal. The tightness of the door seal can be verified by closing and latching the door on a strip of paper. The test must be performed all around the door. If the paper slips out easily anywhere, either adjust the door or replace the gasket.

Door Alignment

To align, open the door and loosen the pressures screws located on the lower and upper hinges of the door using a 3/32” Allen key to free the adjustable hinge rods.
Door Alignment

Using a flat screwdriver, turn the adjustable hinge rods in the direction shown to adjust the doors. Tighten all door hinge pressure screws when they are at the desired positions. Configurations 1-2-3-4-5-6, show in which direction these act on the adjustment of the door.
Door Alignment

Gasket

It is important to replace the gasket with another having the same diameter and density to maintain a good seal.

  1. Remove the door and place it face-down on something soft like a cushion of rags or a piece of carpet.
  2. Remove the old gasket from the door. Use a screwdriver to scrape the old gasket adhesive from the door gasket groove.
  3. Apply a bead of approximately 3/16″ (5 mm) of high temperature silicone in the door gasket groove. Starting from the middle, hinges side, press the gasket into the groove. The gasket must not be stretched during installation.
  4. Leave about ½″ (10 mm) long of the gasket when cutting and press the end into the groove. Tuck any loose fibers under the gasket and into the silicone.
  5. Close the door. Do not use the insert for 24 hours.
Mandatory Installation
  • Empty the combustion chamber and install the air control handle (A) with the set screw (B) as shown below:
    Mandatory Installation

  • ENGLISH • Install the combustion chamber side bricks as shown below.
    Mandatory Installation

  • Once the insert is properly positioned in the fireplace opening, secure the pipe with the pipe connectors (B) and screws (C) provided. Then tighten the floor fixing bolts located on each side of the unit (D).
    Mandatory Installation

Blower and Ash Lip Installation

Note : The images shown are for guidance only and may be different from your product, but the assembly remains the same.

  1. Install the ash lip on the insert with four screws.
    Blower and Ash Lip Installation

  2. Center the blower on the ash lip and push it against the firebox. Then push it until it clips.
    Blower and Ash Lip Installation

Faceplate and Trims Installation

Note : The images shown are for guidance only and may be different from your product, but the assembly remains the same.

  1. Lay the panels on a flat and non abrasive surface. Align the top panel holes (A) with the left and right panels (B). Secure together using the bolts (D) and nuts (C) provided.
    Faceplate and Trims Installation

  2. Center the insert into the fireplace opening. Adjust its height using the leveling bolts on each side of the convection air jacket box until the faceplate is properly seated on the floor of the hearth extension.
    Then install one faceplate retainer spring on each side of the faceplate and attach the other end of the spring to the brackets on the left and right sides of the insert. Push the faceplate against the fireplace’s front.
    Faceplate and Trims Installation

Optional Fresh Air Intake Kit Installation

Note: The images shown are for guidance only and may be different from your product, but the assembly remains the same.

The fresh air intake kit may be installed on the right or left end side of the unit. The unused side must be covered by the plate provided in the user manual kit.

  1. Install the fresh air intake adapter (E) with four screws (F) then secure the flexible pipe1 (H) (not included) to the adapter using one of the pipe clamps (G). Secure the other end of the pipe to the outside wall termination (J) using the other pipe clamp. The outside wall termination must be installed outside of the home.
    Optional Fresh Air Intake Kit Installation

  2. Install the plate (K) with four screws (L) on the unused side of the insert.
    Optional Fresh Air Intake Kit Installation

Optional Fire Screen Installation

Note: The images shown are for guidance only and may be different from your product, but the assembly remains the same.

In the United States or in provinces with a particulate emissions limit (e.g.: US EPA), the use of open-door wood stoves with a rigid fire screen is prohibited.

  1. Open the door.
    Optional Fire Screen Installation

  2. Hold the fire screen by the two handles and bring it close to the door opening.
    Optional Fire Screen Installation

  3. Lean the upper part of the fire screen against the top door opening making sure to insert the top fire screen brackets behind the primary air deflector.

  4. Lift the fire screen upwards and push the bottom part towards the insert then let the fire screen rest on the bottom of the door opening.
    Warning: Never leave the insert unattended while in use with the fire screen.
    Optional Fire Screen Installation

Air Tubes and Baffle Installation
  1. Starting with the rear tube, lean and insert the right end of the secondary air tube into the rear right channel hole. Then lift and insert the left end of the tube into the rear left channel.
    Air Tubes and Baffle Installation

  2. Align the notch in the left end of the tube with the key of the left air channel hole. Using a « Wise grip » hold the tube and lock it in place by turning the tube as shown. Make sure the notch reaches the end of the key way.

  3. Install the baffle.

  4. Repeat steps 1 and 2 for the three other tubes.

  5. To remove the tubes use the above steps in reverse order.
    Air Tubes and Baffle Installation
    Note that secondary air tubes (A) can be replaced without removing the baffle board (B) and that all tubes are identical.
    Air Tubes and Baffle Installation

Log retainers installation

Log retainers installation

Removal Instructions

For inspecting purposes, the insert may need to be removed. To remove the insert, follow these instructions:

  • Remove the faceplate (D) by pulling it and releasing the springs holding it in place.
  • Remove the blower assembly (E).
  • Remove the three screws securing the pipe connector (B).
  • Unscrew the bolts securing the insert to the floor on each side of the unit (C).
    Removal Instructions
Exploded Diagram and Parts List

Exploded Diagram and Parts List

IMPORTANT: THIS IS DATED INFORMATION. When requesting service or replacement parts for this unit, please provide the model number and the serial number. We reserve the right to change parts due to technology upgrades or availability. Contact an authorized dealer to obtain any of these parts. Never use substitute materials. Use of non-approved parts can result in poor performance and safety hazards.

# Item Description Qty
1 21565 C-CAST 3.5 SERIE BAFFLE 22″ X 14″ X 1 1/4″ 1
2 PL70864 SECONDARY AIR TUBE 4
3 29010 4 1/2″ X 9″ X 1 1/4″ REFRACTORY BRICK 17
4 29015 4” X 9” X 1 1/4” REFRACTORY BRICK 4
5 PL74051 4 1/2” X 7 1/2” X 1 1/4” REFRACTORY BRICK 1
6 PL36759 2” X 9” X 1 1/4” REFRACTORY BRICK 8
7 30131 BLACK METAL SCREW #10 X 1/2″ TYPE “A” PAN QUADREX 3
8 PL34052 LINER FIXATION BRACKET 3
9 SE74208 REGULAR FACEPLATE 32” X 50” 1
10 PL74208 TOP FACEPLATE 1
11 PL74207 FACEPLATE SIDE 2
12 AC05959 METALLIC BLACK STOVE PAINT – 342 g (12oz) AEROSOL 1
13 SE46325 BLUE RIDGE 500I MANUAL KIT 1
14 PL74203 DECORATIVE SIDE 2
15 30337 SQUARE HEAD SET SCREW 1/2-13 X 1-1/2″ 2
16 PL74033 ASH TRAY 1
17 30507 BLACK TORX SCREW WITH FLAT HEAD TYPE F 1/4-20 X 3/4″ 4
18 PL74013 GLASS MOULDING 2
19 SE70920 AIR CONTROL ROD ASSEMBLY 1
20 AC07866 1/4″ BLACK COIL HANDLE 1
21 30124 SCREW #8 – 32 X 5/16” TRUSS QUADREX ZINC 10
22 SE74865 GLASS AND MOULDING KIT 1
23 AC06400 3/4″ X 6′ FLAT BLACK SELF-ADHESIVE GLASS GASKET (AC-GGK) 1
24 SE74199 GLASS WITH GASKET 17-5/8” X 12-3/4” 1
25 SE24347-2 CAST IRON DOOR 1
26 44080 RHEOSTAT WITHOUT NUT (MODEL KBMS-13BV) 1
27 AC07869 3/8″ BLACK COIL HANDLE 1
28 AC06500 SILICONE AND 5/8″ X 8′ BLACK DOOR GASKET KIT (AC-DGKNC) 1
29 30025 1/4-20 X 1/2″ PAN-HEAD QUADREX BLACK SCREW 2
30 30187 STAINLESS WASHER ID 17/64″ X OD 1/2″ 2
31 SE31318 DOOR HINGE REPLACEMENT KIT 1
32 AC01281 RIGID FIRESCREEN 1
33 30898 ROUND WOODEN BLACK HANDLE 2
34 60013 POWER CORD 96″ X 18-3 type SJT (50 pcs per carton) 1
35 44085 RHEOSTAT KNOB 1
36 SE74193 INSERT BLOWER 1
37 44028 CERAMIC THERMODISC F110-20F 1
38 44089 DOUBLE CAGE BLOWER 144 CFM 115V – 60Hz – 1.1A 1
39 AC01298 5″Ø FRESH AIR INTAKE KIT 1
40 49028 5″ WHITE AIR INTAKE TERMINATION 1

ENGLANDER LIMITED LIFETIME WARRANTY

The warranty of the manufacturer extends only to the original retail purchaser and is not transferable. This warranty covers brand new products only, which have not been altered, modified nor repaired since shipment from factory. Please provide a proof of purchase (dated bill of sale), model name and serial number when making any warranty claim to your ENGLANDER dealer.

This warranty applies to normal residential use only. This warranty is void if the unit is used to burn material other than cordwood (for which the unit is not certified by EPA) and void if not operated according to the owner’s manual. Damages caused by misuse, abuse, improper installation, lack of maintenance, over firing, negligence or accident during transportation, power failures, downdrafts, venting problems or under-estimated heating area are not covered by this warranty. The recommended heated area for a given appliance is defined by the manufacturer as its capacity to maintain a minimum acceptable temperature in the designated area in case of a power failure.

This warranty does not cover any scratch, corrosion, distortion, or discoloration. Any defect or damage caused by the use of unauthorized or other than original parts void this warranty. An authorized qualified technician must perform the installation in accordance with the instructions supplied with this product and all local and national building codes. Any reclamation related to an improper installation is not covered by this warranty.

The manufacturer may require that defective products be returned or that digital pictures be provided to support the claim. Returned products are to be shipped prepaid to the manufacturer for investigation. Transportation fees to ship the product back to the purchaser will be paid by the manufacturer. All parts costs covered by this warranty are limited according to the table below.

The manufacturer, at its discretion, may decide to repair or replace any part or unit after inspection and investigation of the defect. The manufacturer may, at its discretion, fully discharge all obligations with respect to this warranty by refunding the wholesale price of any warranted but defective parts. The manufacturer shall, in no event, be responsible for any uncommon, indirect, consequential damages of any nature, which are in excess of the original purchase price of the product. A one-time replacement limit applies to all parts benefiting from lifetime coverage. This warranty applies to products purchased after June 20th, 2022.

DESCRIPTION **WARRANTY APPLICATION***

PARTS
Combustion chamber (welds only) & cast iron door frame.| 5 years
Surrounds, heat shield, ash drawer, steel legs, pedestal & convector air- mate.| 2 years
Removable stainless steel combustion chamber components, secondary air tubes
, deflectors & supports.|

2 years

Glass retainers, handle assembly & air control mechanism.| 2 years
Carbon steel combustion chamber components, vermiculite baffle & ceramic glass (thermal breakage only).|

1 year

Blower, heat sensors, switches, rheostat, wiring & other controls.| 1 year
Firebricks, paint & gaskets.| –
Any parts replaced under the warranty.| 90 days

*Subject to limitations above Picture required**

Shall your unit or a components be defective, contact immediately your ENGLANDER dealer. To accelerate processing of your warranty claim, make sure to have on hand the following information when calling:

  • Your name, address and telephone number
  • Bill of sale and dealer’s name
  • Installation configuration
  • Serial number and model name as indicated on the nameplate fixed to the back of your unit
  • Nature of the defect and any relevant information

Before shipping your unit or defective component to our plant, you must obtain an Authorization Number from your ENGLANDER dealer.
Any merchandise shipped to our plant without authorization will be refused automatically and returned to sender.

Customer Support

This document is available for free download on the manufacturer’s website. It is a copyrighted document. Resale is strictly prohibited. The manufacturer may update this document from time to time and cannot be responsible for problems, injuries, or damages arising out of the use of information contained in any document obtained from unauthorized sources.

Stove Builder International inc.

250, rue de Copenhague,

St-Augustin-de-Desmaures (Québec) Canada

G3A 2H3

1-877-356-6663

https://www.englander-stoves.com/

[email protected]

Logo

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

ENGLANDER User Manuals

Related Manuals