Megger MET1000 All in One True RMS Electrical Tester
This document is copyright of:
Megger Limited, Archcliffe Road, Dover, Kent CT17 9EN. ENGLAND T +44 (0)1304
502101 F +44 (0)1304 207342 www.megger.com Megger
Ltd reserves the right to alter the specification of its products from time to
time without notice. Although every effort is made to ensure the accuracy of
the information contained within this document it is not warranted or
represented by Megger Ltd. to be a complete and up – to – date description.
For Patent information about this instrument refer to the following web site:
megger.com/patents This manual supersedes all
previous issues of this manual. Please ensure that you are using the most
recent issue of this document. Destroy any copies that are of an older issue.
Declaration of Conformity
Hereby, Megger Instruments Limited declares that radio equipment manufactured by Megger Instruments Limited described in this user guide is in compliance with Directive 2014/53/EU. Other equipment manufactured by Megger Instruments Limited described in this user guide is in compliance with Directives 2014/30/EU and 2014/35/EU where they apply. The full text of Megger Instruments EU declarations of conformity are available at the following internet address megger.com/company/about-us/eu- dofc
Safety Information
To ensure safe operation and service of the meter, follow these instructions. Failure to observe warnings can result in severe injury or death.
- If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
- Always use the proper terminals, switch position, and range for measurements.
- Ensure hands are kept behind the barrier / hand guard when making measurements
- To reduce the risk of fire or electric shock, do not use this product around explosive gas or in damp locations.
- Verify the Meter operation by measuring a known voltage. If in doubt, have the meter calibrated.
- Do not apply more than the rated voltage, as marked on meter, between terminals or between any terminal and earth.
- Avoid working alone.
- Do not use the tester if the tester is not operating properly or if it is wet.
- Personal protective equipment must be used if hazardous live parts in the installation where the measurement is to be carried out could be accessible.
- Use caution with voltages above 30 VAC rms, 42 VAC peak, or 60 VDC. These voltages pose a shock hazard.
- DO NOT USE the test leads if the internal white insulation layer becomes exposed.
- DO NOT USE the test leads for voltage or current measurement in any environment above the safety CAT rating printed on the probe or probe tip guard cap
- DO NOT USE the test leads without the probe tip guard cap in CAT III or CAT IV environments.
- Probe assemblies to be used for mains measurements shall be rated as appropriate for measurement Category III or IV according to IEC 61010-031 and shall have a voltage rating of at least the voltage of the circuit to be measured.
- Disconnect circuit power and discharge all high-voltage capacitors before testing resistance, continuity.
Symbols as marked on the Meter and Instruction manual
- CATIV: Measurement category IV: Equipment connected between the origin of the low-voltage mains supply outside the building and the consumer unit.
- CATIII: Measurement category III: Equipment connected between the consumer unit and the electrical outlets.
- CATII: Measurement category II: Equipment connected between the electrical outlets and the user’s equipment.
Making Basic Measurements
Observe all Warnings and Cautions before measurements.
CAUTION
- When connecting the test leads to the device under test connect the common test leads before connecting the live test lead. When removing the test leads, remove the live test lead before removing the common test lead.
- Make sure that the buzzer sound is perceptible before using it under high background noise environment.
Voltage/Continuity/Single Pole Mode
Voltage Measurement
LED G indicates measured voltage is high than ELV limit (50 VAC and/or 120 VDC).
Warning
- When batteries are not fitted or are exhausted, the tester is capable of measuring > 45 VAC and/or >35 VDC.
- Timing Rating (tr): 30 seconds, Recovery Time (rt): 240 seconds, when measuring > 300 V, recovery time is necessary.
- L/R LED may light up when measuring AC voltage.
- Due to the high internal resistance, capacitive and inductive voltage (ghost voltage) may be indicated.
Continuity Check
Single Pole Phase Check
Warning
- The MET1000 Single Pole Check feature consists of using only one test lead connected to the MET1000, remove second test lead if fitted.
- To carry out Single Pole Check test, while firmly holding the MET1000 connect the test lead into a live circuit, this will cause the MET1000 to repeatedly beep and the hazard symbol to illuminate without any voltage being displayed on the screen.
- If a voltage appears on the screen then use 2 Pole method to prove the circuit live.
Phase Rotation Test
Clockwise Phase Sequence L1-L2-L3 (Right)
Counter-clockwise Phase Sequence L1-L3-L2 (Left)
Warning
Phase Rotation Test works only on 3 phase 4 wire systems. The result is unreliable on any other systems.
Note
It maybe necessary to check the result by testing in reverse sequence.
Resistor Mode
Current Mode
Warning
- The barrier guard on the meter provides maximum protection when holding the unit in normal use.
- Remove the test leads from the back of the meter when measuring current.
Using the Functions
HOLD
Enable/Disable ELV Warning Voice
Press Ω/A button and “HOLD” button at the same time.
Using the Functions
Torch
Self-diagnostic test
Warning
- Do not use the tester if a fault is indicated during self-diagnostic test.
Function Button
Battery Replacement
Warning
- Replace the batteries as soon as the low battery indicator starts to flash to avoid false readings.
- Remove test leads from meter before opening the battery cover.
Probe Usage
Warning
- When using test leads or probes, keep your fingers behind the finger guards.
Warning
- For CAT III or CAT IV environments, use the test leads with the probe tip guard cap fixed firmly in place. Without the probe tip guard cap the test leads can ONLY be used in a CAT II environment.
- Make sure the test leads are firmly inserted in the instrument and other accessories are connected securely.
Test lead assembly
Warning
Do not attach test leads onto the back of the meter while measuring
current.
Press here
- For 19mm power socket
- For most applications except current measurement.
Specifications
Display count :| 10,000 counts.
Overrange display :| « OL » or « -OL »
Conversion rate :| 3 times per second
Dimensions (W x H x D) :| 57 x 220 x 35 mm
Weight :| 200 g
Power requirements :| AAA size battery x 2 (R03, LR03, 24D, 24A)
Battery life :| Approximately 1000 operations. (based on Alkaline
batteries, 30 sec. ON, 240 sec. OFF)
Maximum Conductor Size :| 16 mm diameter
Safety Standard Compliance :|
| IEC / EN 61010-1, IEC / EN 61010-2-032, IEC / EN 61010-2-033,
| IEC / EN 61010-031 for CAT IV 600V, CATIII 1000V
| IEC / EN 61326-1 IEC / EN 61243-3
Environmental Conditions
Indoor / Outdoor Use|
Pollution degree :| 2
Maximum Operating Altitude :| 2,000 m (6562 ft)
Operating Temperature & Relative Humidity :|
| -15 °C ~ 30 °C, ≤80 % RH. 30 °C ~ 40 °C, ≤75 % RH.
40 °C ~ 55 °C, ≤45 % RH.
Storage temperature :| -20 to +60 °C, 0 to 80 % RH. (no batteries)
Temperature coefficient :| 0,2 x (specified accuracy) / °C,
< 18 °C, > 28 °C
IP rating :| IP65
Vibration :| Random Vibration per MIL-PRF-28800F Class 2
Drop Protection :| 1.2 m drop to hardwood on concrete floor
Electrical Specifications
Accuracy is given as ± (% of reading + counts of least significant digit) at
23°C ± 5°C, with relative humidity less than 80% and is specified for 1 year
after calibration.
Condition of Auto Power On
With batteries fitted :`| ■ > 3.0 V or < -8.0 V between L2 and L1
■ Detect AC signal by Single Pole
■ Continuity
Without batteries :| > | ±35,0 V DC | or > 45.0 V AC
between L2 and L1
Auto Power Off
The meter automatically turns off if one of the following conditions are met
for approx 10 seconds:
■ The Auto Power On condition is not met.
■ Both buttons are not pressed.
The meter automatically turns off if one of the following conditions are met for approx 30 seconds:
■ The resistance is OL when the meter is in resistor mode.
■ The current is < 1.0 A when the meter is in current mode
For > 300 V, Time rating (tr): 30 seconds; Recovery time (rt): 240 seconds
AC Function :| ■ ACV and ACA specifications are AC coupled, true RMS.
■ For non-sinusoidal waveforms, Additional Accuracy by Crest Factor (C.F.):
Add 1.0% for C.F. 1.0 ~ 2.0
Add 2.5% for C.F. 2.0 ~ 2.5
Add 4.0% for C.F. 2.5 ~ 3.0
■ Max. Crest Factor of Input Signal:
3.0 @ 5000 counts
1.5 @ 10000 counts
Electrical Specification
DC Voltage
| | Range| Resolution| Accuracy
| With batteries| 7.0 V to 999.9 V| 0.1 V| ****
±(1.0 % + 2D)
| Without batteries(1)| 35 V to 999.9 V| 0.1 V
(1) Measurement without batteries is only available for < 35°C, > -15°C. The
meter will show “bAtt” and ELV LED when measurement is not available.
Max. Input Current :| < 3,5 mA @ 1,000 V
Overload Protection :| AC/DC 1,000 V
|
AC Voltage
| | Range| Resolution| Accuracy
| With batteries| 6.0 V(1) to 999.9 V| 0.1 V| ****
±(1.5 % + 5D)
| Without batteries(2)| 45 V to 999.9 V| 0.1 V
(1) For > 65 Hz, the minimum range is 8.0 V
(2) Measurement without batteries is only available for < 35°C, > -15°C. The
meter will show “bAtt” and ELV LED when measurement is not available
Frequency Response :| 45 Hz to 400 Hz
Max. Input Current :| < 3,5 mA @ 1 000 V
Overload Protection :| AC/DC 1,000 V
|
Resistor
| Range| Resolution| Accuracy
| 9999 Ω| 1 Ω| ±(1.5 % + 5D)
| 50.00 kΩ| 0.01 kΩ
Output Voltage :| About 0.5 V
Overload Protection :| AC/DC 1,000 V
Electrical Specification
Continuity :| The built-in buzzer sounds when measuring resistance less
than 1.8 kΩ and up to 2.7 kΩ. LED RX shows at the same time.
Continuity Indicator :| 2.7 kHz Tone Buzzer and RX LED
Response Time of Buzzer :| < 100 ms
Output Voltage :| About 0.5 V
Overload Protection :| AC/DC 1,000 V
|
AC Currant :
| Range| Resolution| Accuracy
200.0 A| 0.1 A| ±(3.0 % + 5D)
Frequency Response :| 45 Hz to 65 Hz
Overload Protection :| AC/DC 200 A
|
Rotary Field Indication :| For 3 phase 4 wire system only
Sensitivity :| 90 V to 1000 V (Phase-to-ground)
Frequency Range :| 45 Hz to 65 Hz
“L” LED is on when the signal of L2 probe lead the signal of L1 probe; “R” LED
is on when the signal of L1 probe lead the signal L2 probe.
Single-Pole Phase Check
Sensitivity :| 90 V to 1000 V (Phase-to-Earth)
Frequency Range :| 45 Hz to 65 Hz
Indicator :| 3 kHz Tone Buzzer and ELV LED
Maintenance
Do not attempt to repair this detector. It contains no user-serviceable parts. Repair or servicing should only be performed by qualified personnel.
Cleaning
Periodically wipe the case with a dry cloth and detergent, do not use
abrasives or solvents.
WEEE Directive
The crossed out wheeled bin symbol on the instrument and on the batteries
is a reminder not to dispose of them with general waste at the end of their
life. Megger is registered in the UK as a Producer of Electrical and
Electronic equipment. The registration No is; WEE/DJ2235XR. Users of Megger
products in the UK may dispose of them at the end of their useful life by
contacting B2B Compliance at
www.b2bcompliance.org.uk or by telephone on
01691 676124. Users of Megger products in other regions should contact their
local Megger office or distributor.
Battery Disposal
The batteries in this product are classified as Portable Batteries under
the Batteries Directive. Please contact either Megger Ltd, your local Megger
office or distributor for instructions on the safe disposal of these
batteries. Megger is registered in the UK as a producer of batteries. The
registration number is BPRN01235. For further information see
www.megger.com
Warranty (3 years)
This meter is warranted to the original purchaser against defects in material and workmanship for 3 year from the date of purchase. During this warranty period, the manufacturer will, at its option, replace or repair the defective unit, subject to verification of the defect or malfunction. This warranty does not cover fuses, disposable batteries, or damage from abuse, neglect, accident, unauthorised repair, alteration, contamination, or abnormal conditions of operation or handling. Any implied warranties arising out of the sale of this product, including but not limited to implied warranties of merchantability and fitness for a particular purpose, are limited to the above. The manufacturer shall not be liable for loss of use of the instrument or other incidental or consequential damages, expenses, or economic loss, or for any claim or claims for such damage, expense or economic loss. Some states or countries laws vary, so the above limitations or exclusions may not apply to you.
- Megger Limited
- Archcliffe Road
- Dover
- Kent
- CT17 9EN
- Tel: +44 (0) 1304 502 101 Fax: +44 (0) 1304 207 342
- www.megger.com
Local Sales office
-
Megger Limited
-
Archcliffe Road
-
Dover
-
Kent
CT17 9EN -
ENGLAND
-
T. +44 (0)1 304 502101
-
F. +44 (0)1 304 207342
Manufacturing sites
- Megger Limited Archcliffe Road
- Dover
- Kent
- CT17 9EN
- ENGLAND
- Megger USA – Dallas 4271 Bronze Way
- Dallas TX 75237-1019 USA
- T 800 723 2861 (USA only) T. +1 214 333 3201
- F. +1 214 331 7399
- E. USsales@megger.com
Megger GmbH Weststraße 59
- 52074 Aachen,
- GERMANY
- T. +49 (0) 241 91380 500 E. info@megger.de
- Megger AB
- Rinkebyvägen 19, Box 724, SE-182 17
- Danderyd
- T. +46 08 510 195 00
- E. seinfo@megger.com
Megger USA – Valley Forge Valley Forge Corporate Center 2621 Van Buren Avenue Norristown Pennsylvania, 19403 USA T. +1-610 676 8500 F. +1-610-676-8610 Megger USA – Fort Collins 4812 McMurry Avenue Suite 100FortCollins CO 80525 USA T. +1 970 282 1200 This instrument is manufactured in the Taiwan. The company reserves the right to change the specification or design without prior notice. Megger is a registered trademark. The Bluetooth® word mark and logos are registered trademarks owned by Bluetooth SIG, Inc and is used under licence. Part No: MET1000_UG_EN_V01 © Megger Limited 2020 www.megger.com
References
- EU declarations of conformity PDF download | Megger
- B2B Compliance - The not-for-profit WEEE Compliance scheme
- Electrical test equipment | power station to plug | Megger