Megger DCM1500 AC DC Clamp Meter User Guide
- June 4, 2024
- Megger
Table of Contents
DCM1500 clamp meter
1500 A TRMS CLAMP METER
User Guide
DCM1500_UG_en-fr-es-de-nl_V04 08 2021
Safety Information
To ensure safe operation and service of the meter, follow these instructions. Failure to observe warnings can result in severe injury or death.
- Avoid working alone so assistance can be rendered.
- To enhance safety, test leads should be disconnected from the instrument when not in use
- Do not use test leads or the clamp meter if they look damaged
- Do not use the clamp meter if the tester is not operating properly or if it is wet.
- Use the clamp meter only as specified in the instruction card or the protection provided by the clamp meter may be impaired.
- Special precautions are necessary when operating in situations where exposed live parts at dangerous voltages may be encountered. Personal protective equipment (not supplied with the instrument) should be used.
- The test leads should be disconnected from the instrument when making a current measurement.
- Use caution with voltages above 30 V AC RMS, or 60 V DC. These voltages pose a shock hazard.
- To avoid false readings that could lead to electric shock and injury, replace the battery as soon as the low battery indicator ( ) appears.
Symbols as marked on the meter and instruction card
| Risk of
electric shock
See instruction card
DC measurement
Equipment protected by double or reinforced insulation
Battery
Earth
AC measurement
Conforms to EU directives
---|---
Caution: If the meter is used in the vicinity of equipment that generates electromagnetic interference, the display may become unstable or the measurements may be subject to large errors.
Auto Power Off disables: Press buttons (except the Hold button) then switch the rotary knob to power on the meter.
AC A / DC A
CAT IV 600 V – With respect to earth for the jaw
Do not hold the meter in front of the tactile barrier.
Zero
Using the Relative mode (REL), a stable value can be stored, the instrument zeroed at that point, and then any variation from that value is displayed as a direct measurement relative to the stable value.
- Make measurements and then press the ZERO button. REL: Meter stores the measured value after pressing the ZERO buttons.
- REL (flashing): The meter saves the offset value. The present value is displayed.
- Normal: Press and hold ZERO for > 2 seconds to return to normal operation and cancel the offset value.
Data Hold
Min / Max Hold
2. MAX: Meter is saving the maximum and minimum values. The maximum value is
displayed.
3. MIN: Meter is saving the maximum and minimum values. The minimum value is
displayed.
4. MAX MIN (flashing): Meter is saving the maximum and minimum values. The
present value is displayed.
1. Normal: Press and hold MIN MAX to return to normal operation.
Battery Replacement
Replace battery: is displayed.
To avoid false readings that could lead to electric shock and injury, replace
the battery as soon as the low battery indicator ( ) appears.
Peak Hold
2. PMax: Meter is saving the peak maximum and minimum values. Peak maximum
value id displayed.
3. PMin: Meter is saving the peak maximum and minimum values. The Peak
minimum value is displayed.
4. CAL: Press and hold the PEAK button for> 3 seconds to calibrate the
instrument for accurate measurement.
1. Normal: Press and hold the PEAK button to return to normal operation.
Back Light
Backlight Automatic off after 60 seconds.
Specifications
General Specifications
LCD display digits: | 3 ¾ digit large scale LCD readout. |
---|---|
Display count: | 4000 counts. |
Measuring rate: | 1.5 times / sec. |
Overrange display: | “OL” is displayed for “Ω” functions, shows the real value |
for “A” and “V” functions.
Automatic power off time:| Approximately 30 minutes after power on.
Low battery indicator:| is displayed. Replace the battery when the indicator
appears in the display.
Power requirement:| 9 V PP3 / 6LR61 battery. Rechargeable batteries are not
recommended for use with this instrument.
Battery life:| 100 hours.
Environmental Conditions
Indoor Use.|
---|---
Calibration:|
Operating temperature :| 0°C ~ 30°C (≤ 80 % RH)
30°C ~ 40°C (≤ 75 % RH)
40°C ~ 50°C (≤45 % RH)
Storage temperature:| -20 to +60°C, 0 to 80% RH (batteries not fitted).
Measurement Category:| (acc. to CAT IV 600 V)
Application around and removal from UNINSULATED HAZARDOUS LIVE conductors permitted. Personal protection must always be observed.
Operating altitude: | 2000 m (6562 ft) |
---|---|
Conductor Size: | 5 1mm diameter. |
Pollution degree: | 2 |
EMC: | EN 61326-1 |
Shock vibration: | Sinusoidal vibration per MIL-T- 28800E (5 ~ 55 Hz, 3 g |
maximum).
1-3 Electrical Specifications
Accuracy is ±(% reading + a number of digits) at 23 °C ± 5 °C, less than 80% R.H.
Temperature coefficient: | 0.2 × (Specified accuracy) /°C, <18 °C, >28 °C |
---|---|
Operating temperature: | °C ~ 3 0°C (≤ 80% RH) |
3 0°C ~ 4 0°C (≤ 75% RH)
40 °C ~ 50 °C (≤ 45% RH)
AC Volts: Auto-ranging
Range | Resolution | Accuracy | Over-voltage protection |
---|---|---|---|
400.0 V | 100 mV | ±(1.0% reading + 5 digits) 5 0Hz ~ 50 0Hz * | 750 V RMS |
750 V | 1 V |
- add 2 digits to accuracy when reading less 15% of full scale.
Input Impedance: ≥ 1MΩ// less than 10 0pF.
AC Conversion Type:
AC Conversions are ac-coupled, true RMS responding, calibrated to the RMS value of a sine wave input. Accuracies are given for sine wave at full scale and non-sine wave below half scale. For non-sine wave add the following Crest Factor corrections:
For the Crest Factor of 1.4 to 2.0, add 1.0% to accuracy.
For the Crest Factor of 2.0 to 2.5, add 2.5% to accuracy.
For the Crest Factor of 2.5 to 3.0, add 4.0% to accuracy.
Max.CF 2 @ 600 V 1.5 @ 750 V
DC Volts: Auto-ranging
Range | Resolution | Accuracy | Over-voltage protection |
---|---|---|---|
400.0 V | 100 mV | ± (0.7% reading + 2 digits) | 1000 V rms |
1000 V | 1 V |
Input Impedance: ≥1MΩ
Resistance Auto-ranging
Range | Resolution | Accuracy | Over-voltage protection |
---|---|---|---|
400.0 Ω | 100 mΩ | ±(1.0% reading | |
+ 3 digits) | 600 V rms |
Continuity: Built-in buzzer sound when resistance is less than 30 Ω
approximately.
Frequency (for ACA)
Range | Resolution | Accuracy | Over-voltage protection |
---|---|---|---|
400 Hz | 1 Hz | ±(0.1% reading | |
+ 2 digits) | AC/DC 1000 A |
for 1 min.
Min. Input Frequency: 20Hz
Sensitivity: 3A RMS for < 400Hz
ACA
Range| Resolution| Accuracy| Frequency
Response
Overload| protection
---|---|---|---|---
400 A| 0.1A| ±(1.5% reading
+ 5 digits)| 50 Hz – 60 Hz| 1500 A rms
1000 A| 1 A| ±(1.9% reading
+7 digits)
1500 A| 1 A| ±(2.5% reading
+ 7 digits)
400 A| 0.1 A| ±(1.9% reading
+ 5 digits) *| 61 Hz – 400 Hz
1000 A| 1 A| ±(2.5% reading
+ 7 digits)| 61 Hz – 200 Hz
1500 A| 1 A| ±(3.0% reading
+ 7 digits)
AC Conversion Type: * add 2 digits to accuracy when reading less 15% of full
scale.
AC Conversions are ac-coupled, true RMS responding, calibrated to the RMS
value of a sine wave input. Accuracies are given for sine wave at full scale
and non-sine wave below half scale. For non-sine waves add the following Crest
Factor corrections:
For Crest Factor of 1.4 to 2.0, add 1.0% to accuracy.
For Crest Factor of 2.0 to 2.5, add 2.5% to accuracy.
For Crest Factor of 2.5 to 3.0, add 4.0% to accuracy.
Max.CF 2 @ 600 A
1.5 @ 1500 A
DCA
Range | Resolution | Accuracy | Over voltageprotection |
---|---|---|---|
1000 A | 0.1 A | ±(1.0% reading + 3 digits) | AC 1000 A for 1 min. |
400 A | 1:00 AM | ±(1.9% reading + 7 digits) | |
1500 A | 1:00 AM | ±(2.5% reading + 7 digits) |
Position Error: Add ±1% of LCD reading.
Auto Power Off (APO)
The meter will automatically shut itself off after approximately 30 minutes after power on.
Peak Hold:| ±(3% reading +10 digits)
-
750 V Unspecified.
-
800 A Unspecified.
---|---
Min/Max Hold:| Add ± 15 digits to accuracy for ACA and DCA.
Maintenance
Do not attempt to repair this meter. It contains no user-serviceable parts. Repair or servicing should only be performed by qualified personnel.
Cleaning
Periodically wipe the case with a dry cloth and detergent, do not use abrasives or solvents.
CATIV| Measurement category IV: Equipment connected between the origin of the
low-voltage mains supply outside the building and the consumer unit.
---|---
CATIII| Measurement category III: Equipment connected between the consumer
unit and the electrical outlets.
CATII| Measurement category II: Equipment connected between the electrical
outlets and the user’s equipment.
WEEE Directive
The crossed-out wheeled bin symbol on the instrument and on the batteries is a
reminder not to dispose of them with general waste at the end of their life.
Megger is registered in the UK as a Producer of Electrical and Electronic
equipment. The registration no is; WEE/DJ2235XR. Users of Megger products in
the UK may dispose of them at the end of their useful life by contacting B2B
Compliance at www.b2bcompliance.org.uk or
by telephone at 01691 676124. Users of Megger products in other parts of the
EU should contact their local Megger company or distributor.
Battery Disposal
Batteries in this product are classified as Portable Batteries under the Batteries Directive. Please contact Megger Ltd for instructions on the safe disposal of these batteries.
- For disposal of batteries in other parts of the EU contact your local distributor.
- Megger is registered in the UK as a producer of batteries.
- The registration number is BPRN01235.
- For Further information see www.megger.com
Limited Warranty
This meter is warranted to the original purchaser against defects in material
and workmanship for 1 year from the date of purchase. During this warranty
period, the manufacturer will, at its option, replace or repair the defective
unit, subject to verification of the defect or malfunction.
This warranty does not cover fuses, disposable batteries, or damage from
abuse, neglect, accident, unauthorized repair, alteration, contamination, or
abnormal conditions of operation or handling.
Any implied warranties arising out of the sale of this product, including but
not limited to implied warranties of merchantability and fitness for a
particular purpose, are limited to the above. The manufacturer shall not be
liable for loss of use of the instrument or other incidental or consequential
damages, expenses, or economic loss, or for any claim or claims for such
damage, expense or economic loss. Some states’ or countries’ laws vary, so the
above limitations or exclusions may not apply to you.
Deceleration of Conformity
Hereby, Megger Instruments Limited declares that radio equipment
manufactured by Megger Instruments Limited described in this user guide is in
compliance with Directive 2014/53/EU. Other equipment manufactured by Megger
Instruments Limited described in this user guide is in compliance with
Directives 2014/30/EU and 2014/35/EU where they apply. The full text of Megger
Instruments EU declarations of conformity are available at the following
internet address: megger.com/eu-dofc.
Megger Limited
Arncliffe Road, Dover
Kent CT17 9EN England
T +44 (0)1 304 502101
F +44 (0)1 304 207342
E uksales@megger.com| Megger
Valley Forge Corporate Centre
2621 Van Buren Avenue
Norristown, PA 19403, USA
Tel: +1 610-676-8500
Fax: +1 610-676-8610
---|---
Megger
Z.A. Du Buisson de la Couldre
23 rue Eugène Henaff
78190 TRAPPED France
T +33 (0)1 30.16.08.90
F +33 (0)1 34.61.23.77
E infos@megger.com| Megger GmgH
Obere Zeil 2
61440 Oberursel
Germany
T 06171-92987-0
F 06171-92987-19
This instrument is manufactured in Taiwan.
The company reserves the right to change the specification or design
without prior notice.
Megger is a registered trademark
DCM1500_UG_en-fr-es-de-nl_V02
www.megger.com
Documents / Resources
|
Megger DCM1500 AC DC Clamp
Meter
[pdf] User Guide
DCM1500, AC DC Clamp Meter, DCM1500 AC DC Clamp Meter, DC Clamp Meter, Clamp
Meter, Meter
---|---
References
- B2B Compliance - The not-for-profit WEEE Compliance scheme
- EU declarations of conformity PDF download | Megger
- B2B Compliance - The not-for-profit WEEE Compliance scheme
- Electrical test equipment | power station to plug | Megger
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>