Megger DCM330 Clampmeter User Guide
- June 3, 2024
- Megger
Table of Contents
DCM330
Clampmeter User Guide
Safety Information
To ensure safe operation and service of the Meter, follow these instructions.
Failure to observe warnings can result in severe injury or death.
- Avoid working alone so assistance can be rendered.
- To enhance safety, test leads should be disconnected from instrument when not in use.
- Do not use test leads or the Clamp Meter if they look damaged.
- Do not use the Meter if the Clamp Meter is not operating properly or if it is wet.
- Use the Clamp Meter only as specified in the Instruction card or the protection provided by the Clamp Meter might be impaired.
- Special precautions are necessary when operating in situations where exposed live parts at dangerous voltages may be encountered. Personal protective equipment (not supplied with this instrument) should be used.
- To avoid false readings that could lead to electric shock and injury, replace the battery as soon as the low battery indicator ( ) appears.
1.1 Maintenance
Do not attempt to repair this Clamp Meter.
It contains no user-serviceable parts. Repair or serving should only be
performed by qualified personal.
1.2 Cleaning
Periodically wipe the case with a dry cloth and detergent do not use abrasives
or solvents.
1.3 Safety, Hazard and Warning symbols on the instrument
This paragraph details the various safety and hazard icons on the instrument’s
outer case.
Icon | Description |
---|---|
Warning: High Voltage, risk of electric shock | |
Caution: Refer to user guide. | |
UK conformity. This equipment complies with current UK legislation | |
EU conformity. Equipment complies with current EU directives. | |
Equipment complies with current ‘C tick’ requirements. | |
**** | Do not dispose of in the normal waste stream. |
**** | Equipment protected throughout by double insulation. |
Reference earth connection. Not a protective earth terminal | |
Battery | |
Application around and removal from hazardous live conductors is permitted |
CAT IV – Measurement category IV: Equipment connected between the origin of
the lowvoltage mains supply and distribution panel.
CAT III -Measurement category III: Equipment connected between the
distribution panel and electrical outlets.
CAT II – Measurement category II: Equipment connected between the electrical
outlets and user’s equipment.
CAT I – Measurement category I: The circuits are not connected to mains.
Measurement equipment may be safely connected to circuits at the marked rating
or lower.
The connection rating is that of the lowest rated component in the measurement
circuit.
Operation
2.1 Power On / Off
2.2 Auto Power Off
The meter will automatically shut itself off after approximately 10 minutes
after power on.
2.3 AC V / DC V
2.4 Data Hold
2.5 Volt Finder
-
Volt Finder can be activated on any range including OFF.
-
Test leads are not used for the Volt Finder function.
-
Press and hold the Volt Finder button. The display will go black, a tone sounds and the red LED near the fork jaw will illuminate briefly to verify that the
instrument is operational. Continue to hold the Volt Finder button. -
If a voltage of 50 V to 1000 V (50 to 500 Hz) is detected near the jaw ,a continuous tone sounds and the red LED near the jaw illuminates.
2.6 Diode / Continuity
2.7 Resistance
2.8 ACA
CAT.IV.600 V with respect to earth for the jaw. Tactile Barrier for hand
guard.
Do not hold the meter in front of the Tactile Barrier.
2.9 Battery Replacement
To avoid false readings that could lead to electric shock and injury, replace the battery as soon as the low battery indicator ( ) appears.
Specifications
Specification | Detail |
---|
1-1 General Specifications
LCD display digits :| 3 1/2 digit large scale LCD readout.
Display count :| 2000 counts.
Measuring rate :| 1.5 times / sec.
Overrange display :| “OL” is displayed for “Ω” functions, shows the real value
for “A” and “V” function.
Automatic power off time :| Approximately 10 minutes after power on.
Low battery indicator :| ** is displayed. Replace battery immediately
Power requirement :| R03 UM4 AAA 1.5 V x 2 batteries
Battery life :| ALKALINE 250 hours. Not suitable for use with rechargeable
cells.
1-2 Environmental Conditions**
Indoor Use.|
Calibration :| One year calibration cycle.
Operating temperature :| 0 °C ~ 30 °C (±80% RH) 30 °C ~ 40 °C (±75% RH) 40 °C
~ 50 °C (±45% RH)
Storage temperature :| -20 to +60 °C, 0 to 80% RH (batteries not fitted).
Dimensions (W x H x D) :| 54 mm x 193 mm x 31 mm
Weight :| 280 g including battery.
Accessories :| Battery (installed), Carrying case and User manual.
Overvoltage category :| IEC 61010-1 1000 V CAT.III. 600 V CAT.IV.
Operating altitude :| 2000 m (6562 ft)
Conductor Size :| 16 mm diameter.
Pollution degree :| 2
EMC :| EN 61326-1
Shock vibration :| Sinusoidal vibration per MIL-T- 28800E
(5 ~ 55 Hz, 3 g maximum).
Drop Protection :| 1.2 m drop to hardwood on concrete floor.
1-3 Electrical Specifications
Accuracy is ±(% reading + number of digits) at 23 °C ±5 °C < 80%RH.
1-3 Electrical Specifications
Accuracy is ±(% reading + number of digits) at 23 °C ±5 °C < 80%RH.
Temperature coefficient :| Add 0.2 x (Specified accuracy) / °C, < 18 °C, > 28
°C .
DC / AC Volts|
| Range DC| Accuracy| AC Accuracy
200.0 V| ±(1.0% + 2dgt)| ±(1.5% + 5dgt)
50 Hz ~ 500 Hz
1000 V
Over voltage protection :| DC / AC1000 V
Input Impedance :| 2 MΩ // less than 100 pF.
CMRR / NMRR :| (Common Mode Rejection Ratio) (Normal Mode Rejection Ratio)
VAC :| CMRR > 60 dB at DC, 50 Hz / 60 Hz
VDC :| CMRR > 100 dB at DC, 50 Hz / 60 Hz NMRR > 50 dB
at DC, 50 Hz / 60 Hz
AC Conversion Type : Average sensing rms indication.
AC Current| | Function| Range| Accuracy
---|---|---
A~
(50~60 Hz)| 0.0 ~ 200.0 A| ±(3.0% + 3 dgt)
Overload protection :| 400 Arms
AC Conversion Type :| Average sensing rms indication.
-
Adjacent conductor influence :| <0.08 A/A
Resistance| | Range| Accuracy
---|---
200.0 Ω| ±(1.0% + 5 dgt) 2
2.000 KΩ| ±(1.0% + 2 dgt)
20.00 KΩ
200.0 KΩ
2.000 MΩ
20.00 MΩ| ±(1.9% + 5 dgt) 1
Overload protection :| 600 Vrms
Open circuit Voltage :| -1.3 V approx. -
1 < 100 dgt rolling.
-
2 < 10 dgt rolling.
Specifications
Diode Check and Continuity| | Resolution| Accuracy
---|---
1 mV| ±(1.5%+0.05 V)*
- For 0.4 V ~ 0.8 V
Max.Test Current :| 1.5 mA
Max. Open Circuit Voltage :| 3 V
Overload Protection :| 600 Vrms
Continuity :| Internal beeper activates if the resistance of the circuit under test is less than
50 Ω. It will then turn off if the resistance is increased beyond 250 Ω. Response time is approximately 0.25~1 sec.
Limited Warranty
This Meter is warranted to the original purchaser against defects in material
and workmanship for 1 year from the date of purchase. During this warranty
period, anufacturer will, at its option, replace or repair the defective
unit, subject to verification of the defect or malfunction. This warranty does
not cover , disposable batteries, or damage from abuse, neglect, accident,
unauthorized repair, alteration, contamination, or abnormal conditions of
operation or handling.
Any implied warranties arising out of the sale of this product, including but
not limited to implied warranties of merchantability and fitness for a
particular purpose, are limited to the above. The manufacturer shall not be
liable for loss of use of the instrument or other incidentalor consequential
damages, expenses, or economic loss, or for any claim or claims for such
damage, expense or economic loss. Some states or countries laws vary, so the
above limitations or exclusions may not apply to you.
Decommissioning
5.1 WEEE Directive
The crossed out wheeled bin symbol placed on Megger products is a reminder not
to dispose of the product at the end of its life with general waste.
Megger is registered in the UK as a Producer of Electrical and Electronic
Equipment. The Registration No is WEE/ HE0146QT.
For further information about disposal of the product consult your local
Megger company or distributor or visit your local Megger website.
5.2 Battery disposal
The crossed out wheeled bin symbol placed on a battery is a reminder not to
dispose of batteries with general waste when they reach the end of their
usable life.
For disposal of batteries in other parts of the EU contact your local Megger
branch or distributor. Megger is registered in the UK as a producer of
batteries (registration No.: BPRN00142). For further information see
www.megger.com
DCM330
www.megger.com
Manufacturing sites
Megger Limited
Archcliffe Road
Dover
Kent
CT17 9EN
ENGLAND
T. +44 (0)1 304 502101
F. +44 (0)1 304 207342
Megger USA – Dallas
4545 West Davis Street
Dallas TX 75237
USA
T. 800 723 2861 (USA only)
T. +1 214 333 3201
F. +1 214 331 7399
E. USsales@megger.com| Megger GmbH
Weststraße 59
52074 Aachen
T. +49 (0) 241 91380 500
E. info@megger.de
Megger AB
Rinkebyvägen 19, Box 724,
SE-182 17
DANDERYD
T. +46 08 510 195 00
E. seinfo@megger.com
| Megger USA – Valley Forge
Valley Forge Corporate Center
2621 Van Buren Avenue
Norristown
Pennsylvania, 19403
USA
T. +1 610 676 8500
F. +1 610 676 8610
Megger USA – Fort Collins
4812 McMurry Avenue
Suite 100
Fort Collins CO 80525
USA
T. +1 970 282 1200
---|---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>