Literature Library R8GE-ULN Single Package Gas Heating Electric Cooling Instructions

June 12, 2024
Literature Library

**Literature Library R8GE-ULN Single Package Gas Heating Electric Cooling

**

RELAY REWORK INSTRUCTIONS

Single Package Gas Heating / Electric Cooling

  1. Turn off all power to the unit. Verify there is no voltage to the unit with a multimeter.

  2. Remove the #8 Brown wire from the existing relay and add the brown 4” extension wire.

  3. Remove the #12 Black wire from the existing relay and add the black 4” extension wire.
    Diagram of existing relay noting the wire numbers in steps #2 and #3.

  4. Remove the #13 and #14 wire from the existing relay and let them hang until step 11.

  5. Remove the existing relay.

  6. A new hole will have to be drilled 1.7” from the bottom hole to accommodate the new relay.

  7. Attach the new relay part number 622180 to the control panel.

  8. Attach the Brown wire with the brown extension wire to “NO” on the relay.

  9. Attach the Black wire with the black extension wire to the “COM” on the relay.

  10. Attach the Brown and white coil relay terminals. These have smaller 3/16” terminals and cannot be placed on any other connection points.
    Diagram of New relay and wiring

  11. Note: the “NC” on this relay is unused.

  12. Ensure the wiring is per the wiring diagram with this document.

  13. Apply power to the unit and verify the heating cycle.

WIRING DIAGRAM

Packaged Ultra Low NOx Single Stage Gas Heat/Electric Air Conditioner

NOTES:

  1. Disconnect all power before servicing.
  2. For supply connection use copper conductors only.
  3. Not suitable on systems that exceed 150V to ground.
  4. If any of the original wire as supplied with the furnace must be replaced, it must be replaced with wiring material having a temperature rating of at lest 105C.
  5. for supply wite ampacities and overcurrent protection, see unit rating plate.

230 Volt
Single Phase
60Hz

DIAGNOSTIC DESCRIPTION GREEN LED RED LED
Control Fault (No Power) Off Off
L1/Neutral Polarity Fault Flash Flash
1 Hour Lockout Alternating Flash
Normal Operation On On
Pressure Switch Closed Fault On Flash
Pressure Switch Open Fault Flash On
Open Limit Switch Fault Flash Off
DIAGNOSTIC DESCRIPTION YELLOW LED
Low Flame Sensor Signal Continuous Flash
Flame Present On

Specifications & illustrations subject to change without notice or incurring obligations (09/22). O’Fallon, MO, © Nortek Global HVAC LLC 2022. All Rights Reserved.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Literature Library User Manuals

Related Manuals