BANNER Engineering R95C-8UI-KQ 8-Port Analog In to IO Link Hub User Guide
R95C 8-Port Analog In to IO-Link Hub Quick Start Guide
Features
This guide is designed to help you set up and install the R95C 8-Port Analog In to IO-Link Hub. For complete information on programming, performance, troubleshooting, dimensions, and accessories, please refer to the Instruction Manual at www.bannerengineering.com. Search for part number 232750 to view the Instruction Manual. Use of this document assumes familiarity with pertinent industry standards and prac tices.
Overview
When an analog input value is received by the R95C-8UI-KQ hub, the numerical representational value is sent to an IO-Link Master via Process Data In (PDI).
PDI Analog Ranges
Voltage = 0 mV to 10,000 mV
Current = 4,000 µA to 20,000 µA
PFM Out
Enables a PFM representation of an analog input as an output
Mechanical Installation
Install the R95C to allow access for functional checks, maintenance, and
service or replacement. Do not install the R95C in such a way to al low for
intentional defeat.
Fasteners must be of sufficient strength to guard against breakage. The use of
permanent fasteners or locking hardware is recommended to
prevent the loosening or displacement of the device. The mounting hole (4.5
mm) in the R95C accepts M4 (#8) hardware
CAUTION: Do not overtighten the R95C’s mounting screw during installation. Overtightening can affect the perfor mance of the R95C.
Status Indicators
The R95C 8-Port Analog In to IO-Link Hub has matching amber LED indicators on both sides for each analog in port to allow for installation needs and still provide adequate indication visibility. There is also an additional amber LED indicator on both sides of the converter, which is specific to the IOLink communication.
Power Indicator Green LED
Indication| Status
Off| Power off
Solid Green| Power on
IOLink Amber LED
Indication| Status
Off| IOLink communications are not present
Flashing Amber (900 ms On, 100 ms Off)| IOLink communications are active
Analog In Amber LED
Indication| Status
Off| Analog current value is less than setpoint SP1 OR analog value is greater
than setpoint SP2
Solid Amber| Analog current value is between setpoint SP1 AND setpoint SP2
Default Current Values:
• SP1 = 0.004 A
• SP2 = 0.02 A
| Default Voltage Values:
• SP1 = 0 V
• SP2 = 10 V
Specifications
Supply Voltage 18 V DC to 30 V DC at 400 mA maximum
Power Pass-Through Current 500 mA per port maximum
Analog Input Impedance
Current version: Approximately 450 ohms Voltage version: Approximately 14.3K
ohms
Original Instructions July 25, 2023
© Banner Engineering Corp.
Supply Protection Circuitry
Protected against reverse polarity and transient voltages
Leakage Current Immunity 400 µA
Indicators
Green: Power
Amber: IO-Link communications Amber: Analog In status
Connections
8) Integral 4-pin M12 female quick-disconnect connector
(1) Integral 4-pin M12 male quick-disconnect connector
Construction
Coupling Material: Nickel-plated brass Connector Body: PVC translucent black
Vibration and Mechanical Shock
Meets IEC 60068-2-6 requirements (Vibration: 10 Hz to 55 Hz, 0.5 mm amplitude,
5 minutes sweep, 30 minutes dwell)
Meets IEC 60068-2-27 requirements (Shock: 15G 11 ms dura- tion, half sine
wave) Certifications
Environmental Rating IP65, IP67, IP68
NEMA/UL Type 1
Operating Conditions
Temperature: –40 °C to +70 °C (–40 °F to +158 °F)90% at +70 °C maximum
relative humidity (non-condensing) Storage Temperature: –40 °C to +80 °C (–40
°F to +176 °F)
Required Overcurrent Protection
WARNING: Electrical connections must be made by qualified personnel in ac- cordance with local and national electri- cal codes and regulations.
Overcurrent protection is required to be provided by end prod- uct application
per the supplied table.
Overcurrent protection may be provided with external fusing or via Current
Limiting, Class 2 Power Supply.
Supply wiring leads < 24 AWG shall not be spliced.
For additional product support, go
to www.bannerengineering.com.
Supply Wiring (AWG)|
Required Overcurrent Protection (A)
| Supply Wiring (AWG)|
Required Overcurrent Protection (A)
---|---|---|---
20| 5.0| 26| 1.0
22| 3.0| 28| 0.8
24| 1.0| 30| 0.5
Banner Engineering Corp Limited Warranty
Banner Engineering Corp. warrants its products to be free from defects in material and workmanship for one year following the date of ship- ment. Banner Engineering Corp. will repair or replace, free of charge, any product of its manufacture which, at the time it is returned to the factory, is found to have been defective during the warranty period. This warranty does not cover damage or liability for misuse, abuse, or the improper application or installation of the Banner product.
THIS LIMITED WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER EXPRESS OR IMPLIED (INCLUD- ING, WITHOUT LIMITATION, ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE), AND WHETHER ARISING UNDER COURSE OF PERFORMANCE, COURSE OF DEALING OR TRADE USAGE.
This Warranty is exclusive and limited to repair or, at the discretion of Banner Engineering Corp., replacement. IN NO EVENT SHALL BAN- NER ENGINEERING CORP. BE LIABLE TO BUYER OR ANY OTHER PERSON OR ENTITY FOR ANY EXTRA COSTS, EXPENSES, LOSSES, LOSS OF PROFITS, OR ANY INCIDENTAL, CONSEQUENTIAL OR SPECIAL DAMAGES RESULTING FROM ANY PRODUCT DEFECT OR FROM THE USE OR INABILITY TO USE THE PRODUCT, WHETHER ARISING IN CONTRACT OR WARRANTY, STATUTE, TORT, STRICT LIABILITY, NEGLIGENCE, OR OTHERWISE.
Banner Engineering Corp. reserves the right to change, modify or improve the
design of the product without assuming any obligations or lia- bilities
relating to any product previously manufactured by Banner Engineering Corp.
Any misuse, abuse, or improper application or installa- tion of this product
or use of the product for personal protection applications when the product is
identified as not intended for such purposes will void the product warranty.
Any modifications to this product without prior express approval by Banner
Engineering Corp will void the prod- uct warranties. All specifications
published in this document are subject to change; Banner reserves the right to
modify product specifications or update documentation at any time.
Specifications and product information in English supersede that which is
provided in any other lan- guage. For the most recent version of any
documentation, refer to:
www.bannerengineering.com.
For patent information, see
www.bannerengineering.com/patents.