FISHER PAYKEL RS6121SRHK1 61cm Integrated Column Refrigerator Water User Guide

June 4, 2024
Huawei

HUAWEI UPS5000-H-800 100 kVA Power Modules, Three-Phase Three-Wire User

Guide

01 Installing Cabinets

  1. Before installation, read the user manual carefully to get familiar with product information and safety precautions.
  2. Use insulated tools when installing the equipment.
  3. Only engineers certified by Huawei or its agent are allowed to install, commission, and maintain the UPS. Otherwise, personal injury or equipment damage may occur, and the resulting UPS faults are beyond the warranty scope of Huawei.
  4. This document describes the installation procedure for a single UPS. For details about how to install a parallel system, contact Huawei technical support.
Model Weight Dimensions (H x W x D)
UPS5000-H-800K-NTN < 1300 kg 2000 mm x 1600 mm x 1000 mm
Inductor cabinet < 550 kg 2000 mm x 400 mm x 1000 mm

02 Installing Rectifiers and Cables

04 Power-On Commissioning

.

NOTES

  1. Before powering on the UPS5000, ensure that the check items in the UPS5000 Startup Service Report and the post-installation check items are verified.
  2. Measure the voltage and frequency of the UPS upstream input switch. The line voltage range is 138–485 V AC, and the frequency range is 40–70 Hz.

4.2 Initial Startup

NOTES
  • If the UPS is powered on for the first time, you need to obtain the startup password from the
  • Service Expert app. Skip this step if the UPS is not powered on for the first time.
  • The Service Expert app can be downloaded from Google Play Store and can run on Android.
  1. . Obtain the startup password

  2. Set the language, time, date, network parameters, and system parameters on the Settings Wizard screen.

Notes

Set all battery parameters according to the actual situation: Assume that the battery specifications are 150 Ah/12 V, 40 batteries are connected in series, and two battery strings are connected to the UPS in parallel. Set Single battery voltage(V) to 12, Single battery capacity(Ah) to 150, Battery in a battery string to 40, and Number of battery strings to 2.

  1. After you perform the settings, the Bypass mode and No battery alarms are reported by the MDU and do not need to be cleared. If there is any other alarm, you need to rectify the fault.
  2. If the system has connected to the remote EPO switch, you need to choose Monitoring > UPS System > Running Parameter > System Settings on the WebUI and set EPO detection to Enable.
  3. View the system running status diagram on the MDU to check that the UPS is working in bypass mode.

4.3 Starting the Inverter

  1. On the main menu, choose Common Functions and tap Inv. ON.
  2.  In the displayed login window, enter the user name and password, and tap .
  3. In the displayed dialog box, tap Yes to start the inverter.
System User LCD Preset Password WebUI Preset Password
admin (system administrator) 000001 Changeme
operator (common user) 000001 Changeme

4.4 Powering On Loads

  1. After the inverter starts, the UPS works in normal mode. The Bypass mode alarm disappears from the MDU.
  2. After confirming that the battery strings are properly connected, switch on the battery string input circuit breaker. If there are multiple battery strings, switch on the circuit breaker for each battery string and then switch on the general circuit breaker between battery strings and the UPS. The No battery alarm disappears from the MDU.
  3. Turn on the UPS downstream output switch to supply power to the loads.

05 Shutting Down the UPS

5.1 Shutting Down the Inverter to Transfer the UPS to Bypass Mode

Nots

After you shut down the inverter, the UPS transfers to bypass mode if the bypass is normal;
the UPS supplies no power if the bypass is abnormal. Before shutting down the UPS, ensure that all loads have been shut down.

  1. On the main menu of the LCD, choose Common Functions and tap Inv. OFF.
  2. In the displayed login window, enter the user name and password, and tap .
  3. In the displayed dialog box, tap Yes to shut down the inverter.\\

5.2 Powering Off a Single UPS

Scan here for more documents:

You can also log in to Huawei technical support website: https://support.huawei.com/enterprise
https://support.huawei.com

Read More About This Manual & Download PDF:

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals