SIEMENS RDG200KN Room Thermostats Instruction Manual

June 9, 2024
SIEMENS

RDG200KN Room Thermostats
Instruction ManualSIEMENS RDG200KN Room Thermostats - Featured
Image RDG200KN, RDG204KN
RDG260KN, RDG264KN

https://www.siemens.com/btproduct?S55770-T409

RDG200KN Room Thermostats

Operating Instructions
RDG2..KN – Room thermostat with KNX communications allowing users to set ideal temperature, relative humidity and CO2 level (RDG204KN&RDG264KN). The thermostat offers the operating modes Comfort, Economy and Protection.
In addition, it can operate in Auto mode as per a schedule via KNX bus or local.
The fan operates either in Auto mode or at the selected speed in Manual mode.
Users can either use the factory settings or adjust settings as desired.

Main display

SIEMENS RDG200KN Room Thermostats - overview

| Operating mode selection *
---|---
| Scheduler
| Fan speed selection
| Escape
| Delete schedule
| Confirm parameters
| Number of schedules or slave alarms
| Outside temperature
| Parameter
| Digits for setpoint display
| Time bar for schedule
| Additional user information, such as outside temperature, time of day from KNX bus, relative humidity, or indoor air quality
AMPM| Morning: 12-hour format; Afternoon: 12-hour format
| Relative humidity
| Degrees Celsius or Fahrenheit
| Indoor air quality
PPM| CO2 values
| Value with thermometer: Digits for room temperature display

A Operating mode button *
B Fan mode button
C Rotary knob
D Green leaf
E Protection hospitality mode or scheduler button

Operating mode

| Holiday mode
---|---
| Protection mode
| Economy mode
| Comfort mode
| Cooling mode
| Electric heater active
| Heating mode
| Scheduler mode
| Manual changeover
| Auto mode
| Temporary timer
| Fault
| Fresh air indication
| Condensation in room (dewpoint sensor active) or humidity control active
| Button lock
| Automatic fan
| Fan speed I
| Fan Speed II
| Fan Speed III

  • When P002 = 3, the icon is displayed as and the button can be used to switch unit between °C and °F. (scan the above QR code for the latest version info).
    Changing the room temperature
    Turn the rotary knob clockwise to i ncrease, or counterclockwise to decrease the current room temperature setpoint.

Note: The setting range is 5…40 °C; it can be limited by parameters P013 and P016. (for parameter settings, see Control parameters on page 2).

Adjusting the fan speed

  • Press the right button repeatedly until the desired fan mode is reached.
  • In Auto mode , the fan speed is automatically selected by the thermostat depending on setpoint and current room temperature.
  • In Manual mode, the fan operates independently and runs at the speed set by the user: speed I / speed II / speed III.

Changing the operating mode

SIEMENS RDG200KN Room Thermostats - temperature 3

  1. Comfort mode
    • In Comfort mode, the thermostat maintains the room temperature at the setpoint which can be adjusted with the rotary knob.

  2. Economy mode
    •  In Economy mode, the thermostat maintains the room temperature at a lower or higher setpoint, thus saving energy and money.
    •  The thermostat can be set to Economy mode either by pressing the operating mode button if enabled (P002 = 2), or via an external signal (switch or KNX bus command) such as keycard or presence detector.
    •  The Economy setpoints are factory-set to 15 °C for heating and 30 °C for cooling. They can be adjusted via parameters P019 and P020 (for parameter settings, see Control parameters on page 2).

  3. Protection mode
    • In Protection mode, the thermostat stops operating. However, if the room temperature drops below 8 °C, heating is switched on to protect the room against frost.
    •  The thermostat switches to Protection mode when the window contact (local or on KNX) is activated.
    The setpoints for Protection mode can be changed by your HVAC installer if desired:
    Changes made by installer: Frost protection: _____ ˚C Heating protection: __˚C

  4. Auto mode
    •  In Auto mode, the thermostat automatically switches over between Comfort and Economy mode as per the KNX bus or local schedule (enabled via P005).
    If no schedule is available, Comfort replaces Auto.

Important: If setpoints are set to Off, there is no protective heating or cooling function. Risk of frost!
Green leaf indication
The green leaf indication is an energy-efficient setting and indicates the end user settings. Green leaf: Settings are within the preset energy-efficient range.
Red leaf: Settings exceed the preset energyefficient range.
End users can press the red leaf and return to the energy-efficient range.
Reminder to clean filter, display of external faults
This message reminds you to clean the filter on your HVAC equipment.
It appears after ___ “fan operating hours” and disappears when the thermostat is manually set to Protection. These fault messages tell you an external fault has occurred :
SIEMENS RDG200KN Room Thermostats - icon 34
Needs to be configured by HVAC installer
Scheduler
Set scheduleSIEMENS RDG200KN Room Thermostats - temperature
6

  • Press button once and then turn the rotary knob or press button continuously to select programming mode PROG.
  • Press button once to enter scheduler mode .
  • Turn the rotary knob to select the weekday to be set, then press button once.
  • Turn the rotary knob to view existing schedules, then press button once to select the schedule that need to be edited.
  • Comfort mode setting of selected schedule and icons and are displayed, then press button once. The start time for Comfort flashes and can be changed by turning the rotary knob.
  • Press button once to confirm the adjusted value and enter the Economy mode setting for the schedule. Icons and are displayed, then press button once. The start time for Economy flashes and can be changed by turning the rotary knob.
  • Press button once to confirm the adjusted value. Then users can view other schedules by turning the rotary knob and enter other schedule settings (same as edited schedule).

Note: User can press button to delete any schedule or (Esc) to cancel the change. The maximum number of set schedule is three per day.
Set TIMESIEMENS RDG200KN Room Thermostats - temperature
7

  • Press button once and then turn the rotary knob or press button continuously to select programming mode TIME.
  • Press button once and then turn the rotary knob to select time format (12H).
  • Press button once and then turn the rotary knob to select AM or PM.
  • Press button once and enter the hour setting.
  • The hour value flashes and can be changed by turning the rotary knob.
  • Press button once to confirm the adjusted value and enter the minutes setting.

Repeat the steps as for the hour.
Note: When time format is 24 h, AMPM is not displayed.
Set DATESIEMENS RDG200KN Room Thermostats - temperature
8

  • Press button once and then turn the rotary knob or press button continuously to select programming mode DATE.
  • Press button once to enter date setting.
  • Turn the rotary knob to select month / weekday / year, then press button once.
  • For example, enter the year setting. The Year value flashes and can be changed by turning the rotary knob.
  • Press button to confirm the adjusted value, or (Esc) to cancel the change.

Repeat steps for month and weekday settings.
Set AWAY (Holiday mode)SIEMENS RDG200KN Room Thermostats - temperature
9

  • Press button once and then turn the rotary knob or press button continuously to select programming mode AWAY. Holiday mode is displayed.
  • Press button once to enter scheduler mode .
  • Turn the rotary knob to adjust the holidays, then press button once.
  • Set the start time (AWAY): Set the month (MON) and then press button → Set the day (DAY)
  • Press button once to confirm the adjusted value; the idle page for Holiday mode is displayed once the start time reaches.

Button lock

  • If the button lock function is enabled (parameter P028 = 2), pressing the right button for 3 seconds locks or unlocks the buttons respectively. Locked buttons are indicated by the key symbol .
  • If “Auto lock” is configured (P028 = 1), the thermostat automatically locks the buttons 10 seconds after the last adjustment.

Commissioning (by qualified HVAC installer)
To adapt the thermostat to your system and optimize control performance, a number of control parameters can be adjusted. This can be done during operation, either via the buttons on the thermostat or via a commissioning tool.
Control parametersSIEMENS RDG200KN Room Thermostats - temperature
11 To change control parameters, proceed as follows:

  1. Press left and right buttons simultaneously for 3 seconds or until device beeps if buzzer function is enabled (P030).

  2. Service level: Release and within 0.5…4 seconds, press the right button again until “P001” is displayed.
    Expert level: Release and within 0.5…4 seconds, press the left button again until the temperature disappears.
    Turn the rotary knob counterclockwise minimum ½ rotation. P050 displays.

  3. Select the required parameter by turning the rotary knob.

  4. Press button (OK). The current value of the selected parameter flashes and can be changed by turning the rotary knob.

  5. Press button (OK) to confirm the adjusted value, or (Esc) to cancel the change.

To adjust additional parameters, repeat steps 3 through 5, or press (Esc) to quit parameter setting mode.
Note: If password protection (needs to be done by HVAC installer) is enabled, users must enter the password to open parameter setting mode. If the password is mistyped 5 times, the thermostat is locked and the password cannot be entered for 5 minutes.
Symbols and are displayed.

Parameter list

No. Description Factory setting Setting range
P001 Control sequence 2-pipe: 1 = Cooling only
4-pipe: 4 = Heating and cooling 0 = Heating only

1 = Cooling only
2 = H/C changeover auto
3 = H/C changeover manual
4 = Heating and cooling
P002| Operation via room operating mode selector| 1| 1 = Auto – Protection / Auto – Comfort – Protection
(when there is local scheduler)
2 = Auto
– Comfort – Economy – Protection
3 = Auto * (Comfort) – Protection Hospitality
P003| Operation via fan operating selector| 0| 0 = Auto – Manual
1 = Manual
2 = Auto – Manual – Protection
3 = Auto – Protection
P004| Unit| 0| 0 = °C (parameter in °C)
1 = °F (parameter in °F)
P005| Scheduler| OFF| ON = Enabled; OFF = Disabled
P006| Measured value correction| 0 K| -5…5 K
P007| Humidity value correction| 0| -10…0…10 %
P008| Standard display| 0| 0 = Room temperature; 1 = Setpoint
P009| Additional display information| 0| 0 = — (No display)
1 = °C and °F
2 = Outside temperature
3 = Time of day (12 h)
4 = Time of day (24 h)
5 = Humidity
6 = Indoor air quality (numeric) ***

7 = Indoor air quality (text)
8 = Humidity and IAQ (numeric)

9 = Humidity and IAQ (text)
P010| Setpoint concept| 1| 1 = Comfort concept; 2 = Energy saving concept
P011| Comfort basic setpoint| 21 °C (70 °F)| 5…40 °C (41…104 °F)
P013| Comfort setpoint minimum| 5 °C (41 °F)| (P010 = 1): 5 °C (41 °F)…P016-1 K
(P010 = 2): 5 °C (41 °F)…P014-1 K
P014| Comfort setpoint maximum heating| 21 °C (70 °F)| P013+1 K…P015-1 K
P015| Comfort setpoint minimum cooling| 25 °C (77 °F)| P014+1 K…P016-1 K
P016| Comfort setpoint maximum| 35 °C (95 °F)| (P010 = 1): P013+1 K…40 °C (104 °F)
(P010 = 2): P015+1 K…40 °C (104 °F)
P017| Summer time| 1| OFF; 1 = Europe; 2 = Australia; 3 = New Zealand
P019| Economy heating setpoint| 15 °C (59 °F)| — (0), 5 °C…P020 (41 °F…P020)
P020 = 40 °C max. (P020 = 104 °F max.)
P020| Economy cooling setpoint| 30 °C (86 °F)| — (0), P019…40 °C (P019…104 °F)
P019 = 5 °C min. (P019 = 41 °F min.)
P023| Indoor air quality setpoint
| 1000 ppm| 10…2000 ppm
P024| Humidity setpoint high| 50| — (0), P026 or 20…90 %
P026| Humidity setpoint low| OFF| — (0), 20…90 % or P024
P027| Electric heater when cooling| ON| ON = Enabled; OFF = Disabled
P028| Keypad| 0| 0 = Unlocked
1 = Auto lock
✓ means function locked
2 = Manual lock
SIEMENS RDG200KN Room Thermostats - temperature 12
P029| Fan: Dead zone Comfort mode| 0| 0 = Fan disable
1 = Low speed (Heat and Cool)
2 = Low speed (Cooling only)
3 = Fan disable Auto & Manual
4 = Low speed Auto & Manual
5 = Low speed Auto & Manual Cooling
P030| Buzzer function| ON| ON = Enabled; OFF = Disabled
P031| Language| 1| 1 = English; 2 = Francais (French)
3 = Deutsch (German); 4 = Italiano (Italian)
5 = Espanol (Spanish); 6 = Nederlands (Dutch)
7 = Turkce (Turkish); 8 = Cesky (Czech)
9 = Suomi (Finnish); 10 = Polski (Polish)
11 = Magyar (Hungarian); 12 = Slovenski (Slovak)
13 = (Limba) Romana (Romanian); 14 = Dansk (Danish)
15 = Norsk (Norwegian)
P032| Room operating mode holidays| 0| 0 = Economy; 1 = Protection

* When no time schedule via KNX exists, Auto equals Comfort.
* Parameter P027 is displayed only for application 2-pipe with electric heater.
These parameter values are valid for RDG204KN and RDG264KN.
All temperature settings are in increments of 0.5 °C (except P006 of RDG204KN & RDG264KN is in 0.1 °C).

Remember to record all changes!

Issued by
Siemens Switzerland Ltd
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
Tel. +41 58 724 2424
www.siemens.com/buildingtechnologies
© Siemens Switzerland Ltd, 2020
Technical specifications and availability subject to change without notice.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

SIEMENS User Manuals

Related Manuals