Submittal
Split System Heat Pump
E4HL5042A1000A
E4HL5042A-SUB-1A-EN
NOTE: “Graphics in this document are for representation only. Actual model may differ in appearance.”
Outline Drawing
Model | A | B | C | D | E | F | G | H |
---|---|---|---|---|---|---|---|---|
E4HL5042A1000A | 52.40 | 37.40 | 13.39 | 14.76 | 16.10 | 4.00 | 6.37 | 3.75 |
All dimensions are in inches
NOTE: ALL DIMENSIONS ARE REFERENCE DIMENSIONS
SOUND POWER LEVEL
Model| A-Weighted Sound Power Level [dB(A)]| Full Octave Sound Power [dB]
63Hz| 125Hz| 250Hz| 500Hz| 1000Hz| 2000Hz| 4000Hz| 8000Hz
E4HL5042A1000A| 68| 66| 62| 60| 63| 67| 57| 48| 38
Note: Rated in accordance with AHRI Standard 270–2015 For reference only.
Product Specifications
OUTDOOR UNIT (a) | E4HL5042A1000A |
---|---|
POWER CONNS. — V/PH/HZ (b) | 208/230/1/60 |
MIN. CIR. AMPACITY | 31 |
MAX. OVERCURRENT PROTECTION | 50 |
COMPRESSOR | Rotary |
NO. USED — NO. STAGES | 1-VARIBLE |
VOLTS/PH/HZ | 208/230/1/60 |
R.L. AMPS (c) | 21.6 |
FACTORY INSTALLED | |
START COMPONENTS (d) | NO |
INSULATION/SOUND BLANKET | YES |
COMPRESSOR HEAT | NO |
OUTDOOR FAN | PROPELLER |
DIA. (IN.) — NO. USED | 20-7/8″-2 |
TYPE DRIVE — NO. SPEEDS | DIRECT — VARIBLE |
NO. MOTORS — HP | 2-1/10 |
CFM @ 0.0 IN. W.G. (e) | 4200 |
MOTOR SPEED R.P.M. | 850 |
VOLTS/PH/HZ | 208/230/1/60 |
F.L. AMPS | 1.45 |
OUTDOOR COIL — TYPE | PLATE FIN |
ROWS — F.P.I. | 2-17 |
FACE AREA (SQ. FT.) | 14.34 |
TUBE SIZE (IN.) | 3/8″ |
REFRIGERANT CONTROL | ELEC. EXPANSION VALVE |
REFRIGERANT
LBS. – R-410A (O.D. UNIT) (f)| 9 LBS, 14 OZ
FACTORY SUPPLIED| YES
LINE SIZE — IN. O.D. GAS| 7/8″
LINE SIZE — IN. O.D. LIQ.| 3/8″
CHARGING SPECIFICATIONS
SUBCOOLING| 5°F
DIMENSIONS| H x W x D
CRATED (IN.)| 41-3/8″×54″×19-1/8″
UNCRATED (IN.)| 37-3/8″×52-3/8″×14- 3/8″
WEIGHT
Shipping| 238
Net (Lbs.)| 231
(a) Certified in accordance with the Air-Source Unitary Air-conditioner
Equipment certification program, which is based on AHRI standard 210/240.
(b) Calculated in accordance with Natl. Elec.
Codes. Use only HACR circuit breakers or fuses.
(c) This value shown for compressor RLA on the unit nameplate and on this
specification sheet is used to compute minimum branch circuit ampacity and
max. fuse size. The value shown is the branch circuit selection current.
(d) No means no start components.
(e) Standard Air — Dry Coil — Outdoor
(f) This value is approximate. For more precise value see unit nameplate.
Mechanical Specification Options
General
The outdoor condensing units are factory charged with the system charge
required for the outdoor condensing unit, ten (10) feet of tested connecting
line, and the smallest rated indoor evaporative coil match. This unit is
designed to operate at outdoor ambient temperatures as high as 115°F. Cooling
capacities are matched with a wide selection of air handlers and furnace coils
that are AHRI certified. The unit is certified to UL 60335-2-40. Exterior is
designed for outdoor application.
Casing
Unit is painted with a glossy corrosion resistant finish on all panels. Unit
casing is constructed of heavy gauge, galvanized steel and painted with a
weather-resistant powder paint finish. All panels are subjected to our 500
hour salt spray test.
Refrigerant Controls
Refrigeration system controls include condenser fan, compressor drive and low
pressure switches.
Compressor
The compressor features external over temperature and pressure protection.
Other features include: Centrifugal oil pump and low vibration and noise.
Condenser Coil
The outdoor coil provides low airflow resistance and efficient heat transfer.
The coil is protected on all four sides by grilles and panels.
Low Ambient Cooling
As manufactured, this system has a cooling capacity to 5°F.
About Trane and American Standard Heating and Air Conditioning
Trane and American Standard create comfortable, energy efficient indoor
environments for residential applications. For more information, please visit
www.trane.com or
www.americanstandardair.com
The AHRI Certified mark indicates company participation in the AHRI
Certification program. For verification of individual certified products, go
to ahridirectory.org.
The manufacturer has a policy of continuous data improvement and it reserves
the right to change design and specifications without notice. We are committed
to using environmentally conscious print practices.
E4HL5042A-SUB-1A-EN 24 Apr 2023
Supersedes (New)
©2023
Documents / Resources
|
RUNTRU E4HL5042A1000A Split System Heat
Pump
[pdf] Owner's Manual
E4HL5042A1000A, E4HL5042A1000A Split System Heat Pump, E4HL5042A1000A Heat
Pump, Split System Heat Pump, Split System, Heat Pump, Pump
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>