Mounting instructions
GDx13x Gamma 13
The Assembly (DBO) designated markings must be completed as specified in IEC/EN 61439 – 3 clause 6.1.
Reference| Admissible thermal dissipation loss for wall mounted distribution
boards at temperarture rise ∆T*
---|---
10K W| 15K W| 20K W| 25K W| 30K W
GD113x| 4,9| 8,2| 11,7| 15,4| 19,3
GD213x| 6,4| 10,5| 15,1| 19,9| 24,9
GD313x| 7,8| 13,0| 18,5| 24,5| 30,7
GD413x| 9,3| 15,4| 22,0| 29,1| 36,5
*) ∆T is the temperature difference between the upper limiting temperature of the installed equipment and the ambient air temperature of the distribution board.
T +49 6842 945 0 F +49 6842 945 4625
info@hager.com hager.com –
01.2022
Ech. 15%