RUNTRU A4AH4E24A1B60A Submittal 2.0 Ton Convertible Air Handler Instruction Manual
- June 12, 2024
- RunTru
Table of Contents
RUNTRU A4AH4E24A1B60A Submittal 2.0 Ton Convertible Air Handler
Outline Drawing
MINIMUM UNIT CLEARANCE TABLE
| SERVICE CLEARANCE (RECOMMENDED)
SIDES| 2 “
FRONT| 21 “
BACK| 0 “
INLET DUCT| 1 “
OUTLET DUCT| N/A
NOTE: THIS UNIT IS APPROVED FOR INSTALLATION CLEARANCES TO COMBUSTIBLE MATERIAL AS STATED ON THE UNIT RATING NAMEPLATE
NOTE: ALL DIMENSIONS ARE REFERENCE DIMENSIONS
PRODUCT DIMENSIONS
Air Handler Model| A| B| C| D| E| F| H| Flow Control| Gas Line Braze
A4AH4E24A1B60A| 45.02| 18.50| 16.50| 16.75| 4.68| 7.33| 18.34| TXV| 3/4
All dimensions are in inches
Product Specifications
MODEL | A4AH4E24A1B60A |
---|---|
RATED VOLTS/PH/HZ | 208-230/1/60 |
RATINGS (a) | See O.D. Specifications |
INDOOR COIL — Type | Plate Fin |
Rows — F.P.I. | 3 – 14 |
Face Area (sq. ft.) | 4.37 |
Tube Size (in.) | 3/8 |
Refrigerant Control | TXV |
Drain Conn. Size (in.)(b) | 3/4 NPT |
DUCT CONNECTIONS | See Outline Drawing |
INDOOR FAN — Type | Centrifugal |
Diameter-Width (In.) | 11 X 6 |
No. Used | 1 |
Drive – No. Speeds | Direct – 4 |
CFM vs. in. w.g. | See Fan Performance Table |
No. Motors — H.P. | 1 – 1/3 |
Motor Speed R.P.M. | 1050 |
Volts/Ph/Hz | 208-230/1/60 |
F.L. Amps | 2.8 |
FILTER | |
Filter Furnished? (c) | No |
REFRIGERANT | R-410A |
Ref. Line Connections | Brazed |
Coupling or Conn. Size — in. Gas | 3/4 |
Coupling or Conn. Size — in. Liq. | 3/8 |
DIMENSIONS | H x W x D |
Crated (In.) | 46 x 21 x 24 |
Uncrated | 45-1/8 x 18-1/2 x 21-1/8 |
WEIGHT | |
Shipping (Lbs.) / Net (Lbs.) | 116/110 |
(a) These Air Handlers are A.H.R.I certified with various Split System
Air Conditioners and Heat Pumps (AHRI STANDARD 210/240). Refer to the Split
System Outdoor Unit Product Data Guides for performance data.
(b) 3/4” Male Plastic Pipe (Ref: ASTM 1785–76)
(c) Remote filter required.
Minimum Airflow CFM
A4AH4E24A1B60A
Heater| Minimum Heat Speed Tap
| With Heat Pump| Without Heat Pump
BAYHTR1504BRK, BAYHTR1504LUG, BAYHTR1505BRK, BAYHTR1505LUG|
Low
|
Low
BAYHTR1508BRK, BAYHTR1508LUG, BAYHTR1510BRK, BAYHTR1510LUG, BAYHTR3510LUG|
High
|
Med
Heater Pressure Drop Table
Airflow CFM
| Number of Racks| | Heater Racks
---|---|---|---
1| 2| 3| 4| Heater Model| No. of Racks
Air Pressure Drop — Inches W.G.| BAYHTR1504| 1
1800| 0.02| 0.04| 0.06| 0.14| BAYHTR1505| 1
1700| 0.02| 0.04| 0.06| 0.14| BAYHTR1508| 2
1600| 0.02| 0.04| 0.06| 0.13| BAYHTR1510| 2
1500| 0.02| 0.04| 0.06| 0.12| BAYHTR1517| 3
1400| 0.02| 0.04| 0.06| 0.12| BAYHTR3510| 3
1300| 0.02| 0.04| 0.05| 0.11| BAYHTR3517| 3
1200| 0.01| 0.04| 0.05| 0.10| BAYHTR3515| 3
1100| 0.01| 0.03| 0.05| 0.09| BAYHTR1523| 4
1000| 0.01| 0.03| 0.04| 0.09| BAYHTR1525| 4
900| 0.01| 0.03| 0.04| 0.08| |
800| 0.01| 0.03| | | |
700| 0.01| 0.02| | | |
600| 0.01| 0.02| | | |
Performance and Electrical Data
- See Product Data or Air Handler nameplate for approved combinations of Air Handlers and Heaters.
- Heater model numbers may have additional suffix digits.
Table 1. Air Flow Performance
A4AH4E24A1B60A
EXTERNAL STATIC
(in w.g)
| AIRFLOW
Speed Taps: 208 – 230 VOLTS
| High| Med-High| Med †| Low
0.1| 1140| 1078| 930| 851
0.2| 1087| 1017| 870| 796
0.3| 1034| 955| 807| 733
0.4| 978| 894| 741| 663
0.5| 922| 834| 671| 584
0.6| 863| 774| 597| 497
0.7| 804| 715| 519| 403
- Values are with wet coil, no filter, and no heaters
- CFM Correction for dry coil = Add 3%
- † = Factory Setting
- Low = Taps 1–2, Med = Tap 3, Med-High= Tap 4, High = Tap 5
Table 2. Electrical Data
A4AH4E24A1B60A
Heater Model No.| No. of Circuits/ Phases| 240 Volt| 208 Volt
Capacity| Heater Amps per Circuit| Minimum Circuit Ampacity| Maximum Overload
Protection| Capacity| Heater Amps per Circuit| Minimum Circuit Ampacity|
Maximum Overload Protection
kW| BTUH| kW| BTUH
No Heater| | | | 2.8 | 4| 15| | | 2.8 | 4| 15
BAYHTR1504BRK BAYHTR1504LUG| 1/1| 3.8| 13100| 16.0| 24| 25| 2.9| 9800| 13.8|
21| 25
BAYHTR1505BRK BAYHTR1505LUG| 1/1| 4.8| 16400| 20.0| 29| 30| 3.6| 12300| 17.3|
25| 25
BAYHTR1508BRK BAYHTR1508LUG| 1/1| 7.7| 26200| 32.0| 44| 45| 5.8| 19700| 27.7|
38| 40
BAYHTR1510BRK BAYHTR1510LUG| 1/1| 9.6| 32800| 40.0| 54| 60| 7.2| 24600| 34.6|
47| 50
BAYHTR3510LUG| 1/3| 9.6| 32800| 23.1| 32| 35| 7.2| 24600| 20.0| 28| 30
- = Motor Amps
Features and Benefits
- Galvanized metal cabinet with captured foil face insulation
- 2% or less air leakage
- R-4.2 Insulating Value
- Multi-Position UP/Down Flow, Horizontal Left /Right
- ALL Aluminum Coil
- Electric Heaters with polarized plug connections (sold as accessory)
- R-410A Thermal Expansion Valve
- ECM Motor ( 3.0 – 5 Ton Models )
- Low Voltage Pigtail Connections
- Draw Through Design
- Horizontal Drain pan
- Single Color
- Fused 24V Power
- 5 year warranty
- Optional extended warranty available
Important: Condensate management kit is required for all 5 ton air handler models installed in downflow applications.
Customer Support
About Trane and American Standard Heating and Air Conditioning
Trane and American Standard create comfortable, energy efficient indoor environments for residential applications. For more information, please visit www.trane.com or www.americanstandardair.com.
The manufacturer has a policy of continuous data improvement and it reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.
A4AH4E24A1B-SUB-1A-EN 06 Sep 2022