RunTru Ameristar A4HP4017D Heat Pumps Installation Guide
- June 9, 2024
- RunTru Ameristar
Table of Contents
- Section 1. Safety
- Section 2. Unit Location Considerations
- Section 3. Unit Preparation
- Section 4. Setting the Unit
- Section 5. Refrigerant Line Considerations
- Section 6. Refrigerant Line Routing
- **
- Section 8. Refrigerant Line Leak Check
- Section 9. Evacuation
- Section 10. Service Valves
- Section 11. Electrical – Low Voltage
- Section 12. Electrical – High Voltage
- Section 13. Start Up
- Section 14. System Charge Adjustment (Systems can be rated with TXV, EEV
- Section 15. Checkout Procedures and Troubleshooting
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
RunTru Ameristar A4HP4017D Heat Pumps
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air- conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES.
IMPORTANT — This Document is customer property and is to remain with this unit. Please return to service information pack upon completion of work.
These instructions do not cover all variations in systems or provide for every
possible contingency to be met in connection with the installation. Should
further information be desired or should particular problems arise which are
not covered
sufficiently for the purchaser’s purposes, the matter should be referred to
your installing dealer or local distributor.
Note: The manufacturer recommends installing only approved matched indoor and outdoor systems. All of the manufacture’s split systems are AHRI rated with Piston/TXV/EEV indoor systems. Some of the benefits of installing approved matched indoor and outdoor split systems are maximum efficiency, optimum performance and the best overall system reliability
Section 1. Safety
WARNING
This information is intended for use by individuals possessing adequate backgrounds of electrical and mechanical experience. Any attempt to repair a central air conditioning product may result in personal injury and/or property damage. The manufacture or seller cannot be responsible for the interpretation of this information, nor can it assume any liability in connection with its use.
WARNING
These units use R-410A refrigerant which operates at 50 to 70% higher pressures than R-22. Use only R-410A approved service equipment. Refrigerant cylinders are painted a “Rose” color to indicate the type of refrigerant and may contain a “dip” tube to allow for charging of liquid refrigerant into the system. All R-410A systems use a POE oil that readily absorbs moisture from the atmosphere. To limit this “hygroscopic” action, the system should remain sealed whenever possible. If a system has been open to the atmosphere for more than 4 hours, the compressor oil must be replaced. Never break a vacuum with air and always change the driers when opening the system for component replacement. For specific handling concerns with R-410A and POE oil reference Retrofit Bulletins SS-APG006-EN and APP-APG011-EN or APP-APG012-EN.
WARNING
UNIT CONTAINS R-410A REFRIGERANT! R-410A operating pressures exceed the limit
of R-22. Proper service equipment is required. Failure to use proper service
tools may result in equipment damage or personal injury.
SERVICE
USE ONLY R-410A REFRIGERANT AND APPROVED POE COMPRESSOR OIL.
WARNING
Extreme caution should be exercised when opening the Liquid Line Service Valve. Turn counterclockwise until the valve stem just touches the rolled edge. No torque is required. Failure to follow this warning will result in abrupt release of system charge and may result in personal injury and /or property damage.
WARNING
LIVE ELECTRICAL COMPONENTS!
During installation, testing, servicing, and troubleshooting of this product,
it may be necessary to work with live electrical components. Failure to follow
all electrical safety precautions when exposed to live electrical components
could result in death or serious injury.
CAUTION
f using existing refrigerant lines make certain that all joints are brazed, not soldered.
CAUTION
Scroll compressor dome temperatures may be hot. Do not touch the top of compressor; it may cause minor to severe burning.
WARNING
WARNING!
This product can expose you to chemicals including lead, which are known to
the State of California to cause cancer and birth defects or other
reproductive harm. For more information go to
www.P65Warnings.ca.gov
Section 2. Unit Location Considerations
Unit Dimensions and Weight
Table 2.1
Unit Dimensions and Weight
Models| H x D x W (in)| Weight* (lb)
A4HP4017D| 28.6 X 25.6 X 25.6| 143
A4HP4018D| 32.6 X 29.8 X 29.8| 162
A4HP4024D| 32.6 X 29.8 X 29.8| 162
A4HP4030D| 28.6 X 29.8 X 29.8| 159
A4HP4036D| 36.6 X 34.3 X 34.3| 199
A4HP4042D| 44.6 X 34.3 X 34.3| 227
A4HP4048D| 44.6 X 34.3 X 34.3| 250
A4HP4060D| 44.6 X 34.3 X 34.3| 250
- Weight values are estimated uncrated.
When mounting the outdoor unit on a roof, be sure the roof will support the unit’s weight.
Properly selected isolation is recommended to alleviate sound or vibration
transmission to the building structure.
Service Valves Locations
- The locations of the below listed valves in the unit are shown in the figure.
a) Liquid line connection
b) Access valve for compressor suction pressure measurement
c) Suction line connection
Refrigerant Piping Limits
- The maximum TOTAL length of refrigerant lines from outdoor to indoor unit should NOT exceed 150 feet (including lift).
- The maximum vertical change should not exceed 50 feet.
- Service valve connection diameters are shown in Table 5.1.
Note: For other line lengths, Refer to Refrigerant Piping Application
Guide, SS-APG006-EN or Refrigerant Piping Software Program, 32- 3312-03 (or
latest revision).
Suggested Locations for Best Reliability
Ensure the top discharge area is unrestricted for at least five (5) feet above the unit.
Three (3) feet clearance must be provided in front of the control box (access panels) and any other side requiring service.
It is not recommended to install in a location where noise may distract the
building occupants. Some examples of these types of locations are sleeping
quarters and by windows of a living area. Please discuss location with the
building owner prior to installation.
Avoid locations such as near windows where condensation and freezing defrost vapor can annoy a customer.
Position the outdoor unit a minimum of 12” from any wall or surrounding shrubbery to ensure adequate airflow.
Outdoor unit location must be far enough away from any structure to prevent
excess roof runoff water or icicles from falling directly on the unit.
Cold Climate Considerations
NOTE: It is recommended that these precautions be taken for units being installed in areas where snow accumulation and prolonged below freezing temperatures occur.
- Units should be elevated 3-12 inches above the pad or roof top, depending on local weather. This additional height will allow drainage of snow and ice melted during defrost cycle prior to its refreezing. Ensure that drain holes in unit base pan are not obstructed preventing draining of defrost water.
- If possible, avoid locations that are likely to accumulate snow drifts. If not possible, a snow drift barrier should be installed around the unit to prevent a build-up of snow on the sides of the unit.
Section 3. Unit Preparation
Prepare The Unit For Installation
STEP 1 – Check for damage and report promptly to the carrier any
damage found to the unit.
Section 4. Setting the Unit
Pad Installation
When installing the unit on a support pad, such as a concrete slab, consider the following:
- The pad should be at least 1” larger than the unit on all sides.
- The pad must be separate from any structure.
- The pad must be level.
- The pad should be high enough above grade to allow for drainage.
- The pad location must comply with National, State, and Local codes.
Section 5. Refrigerant Line Considerations
Refrigerant Line and Service Valve Connection Sizes
Table 5.1
| Line Sizes| Service Valve Connection Sizes
---|---|---
Model| Vapor Line| Liquid Line| Vapor Line Connection| Liquid Line Connection
A4HP4017D| 3/4| 3/8| 3/4| 3/8
A4HP4018D| 3/4| 3/8| 3/4| 3/8
A4HP4024D| 3/4| 3/8| 3/4| 3/8
A4HP4030D| 3/4| 3/8| 3/4| 3/8
A4HP4036D| 7/8| 3/8| 7/8| 3/8
A4HP4042D| 7/8| 3/8| 7/8| 3/8
A4HP4048D| 7/8| 3/8| 7/8| 3/8
A4HP4060D| 7/8| 3/8| 7/8| 3/8
Factory Charge
The outdoor condensing units are factory charged with the system charge required for the outdoor condensing unit, ten (10) feet of tested connecting line, and the smallest rated indoor evaporative coil match. Always verify proper system charge via subcooling (TXV/EEV) or superheat (fixed orifice) per the unit nameplate.
Required Refrigerant Line Length
Determine required line length and lift. You will need this later in STEP 2 of Section 14.
Total Line Length = __ Ft.
Total Vertical Change (lift) = __ Ft.
Refrigerant Line Insulation
Important: The Vapor Line must always be insulated. DO NOT allow the
Liquid Line and Vapor Line to come in direct (metal to metal)contact.
Reuse Existing Refrigerant Lines
CAUTION
If using existing refrigerant lines make certain that all joints are brazed, not soldered.
For retrofit applications, where the existing indoor evaporator coil and/or refrigerant lines will be used, the following precautions should be taken:
- Ensure that the indoor evaporator coil and refrigerant lines are the correct size.
- Ensure that the refrigerant lines are free of leaks, acid, and oil.
Section 6. Refrigerant Line Routing
Precautions
Important: Take precautions to prevent noise within the building structure due to vibration transmission from the refrigerant lines.
Comply with National, State, and Local Codes when isolating line sets from joists, rafters, walls, or other structural elements.
For Example:
- When the refrigerant lines have to be fastened to floor joists or other framing in a structure, use isolation type hangers.
- Isolation hangers should also be used when refrigerant lines are run in stud spaces or enclosed ceilings.
- Where the refrigerant lines run through a wall or sill, they should be insulated and isolated.
- Isolate the lines from all ductwork.
- Minimize the number of 90º turns.
Isolation From Joist/Rafter
Secure Vapor line from joists using isolators every 8 ft. Secure Liquid
Line directly to Vapor line using tape, wire, or other appropriate method
every 8 ft.
Isolation In Wall Spaces
Secure Vapor Line using isolators every 8 ft. Secure Liquid Line directly
to Vapor Line using tape, wire, or other appropriate method every 8 ft.
**
Section 7. Refrigerant Line Brazing**
Braze The Refrigerant Lines
STEP 1 – Remove caps or plugs. Use a deburing tool to debur the pipe ends. Clean both internal and external surfaces of the tubing using an emery cloth.
STEP 2 – Remove the pressure tap cap and valve cores from both service valves.
STEP 3 – Purge the refrigerant lines and indoor coil with dry nitrogen.
STEP 4 – Wrap a wet rag around the valve body to avoid heat damage and continue the dry nitrogen purge.
Braze the refrigerant lines to the service valves. Continue the dry nitrogen purge. Do not remove the wet rag until all brazing is completed.
Important: Remove the wet rag before stopping the dry nitrogen purge.
Note: Install drier in Liquid Line.
NOTE: Precautions should be taken Precautions should be taken to avoid
en to avoid heat damage to basepan during brazing. It is heat damage to
basepan during brazing. It is recommended to keep the flame directly off of
recommended to keep the flame directly off of the basepan.
STEP 5 – Replace the pressure tap valve cores after the service valves have cooled.
Section 8. Refrigerant Line Leak Check
Check For Leaks
STEP 1 – Pressurize the refrigerant lines and evaporator coil to 150 PSIG using dry nitrogen.
STEP 2 – Check for leaks by using a soapy solution or bubbles at each brazed location.
Remove nitrogren pressure and repair any leaks before continuing.
Section 9. Evacuation
Evacuate the Refrigerant Lines and Indoor Coil
Important: Do not open the service valves until the refrigerant lines and indoor coil leak check and evacuation are complete.
STEP 1 – Evacuate until the micron gauge reads no higher than 350 microns, then close off the valve to the vacuum pump.
STEP 2 – Observe the micron gauge. Evacuation is complete if the micron gauge does not rise above 500 microns in one (1) minute.
Once evacuation is complete blank off the vacuum pump and micron gauge, and close the valves on the manifold gauge set.
Section 10. Service Valves
Open the Gas Service Valve
Important: Leak check and evacuation must be completed before opening the service valves.
NOTE: Do not vent refrigerant gases into the atmosphere.
STEP 1 – Remove valve stem cap.
STEP 2 – Using an adjustable wrench, turn valve stem 1/4 turn counterclockwise to the fully open position.
STEP 3 – Replace the valve stem cap to prevent leaks. Tighten finger tight plus an additional 1/6 turn.
Open the Liquid Service Valve
WARNING
Extreme caution should be exercised when opening the Liquid Line Service Valve. Turn counterclockwise until the valve stem just touches the rolled edge. No torque is required. Failure to follow this warning will result in abrupt release of system charge and may result in personal injury and /or property damage.
_ Important: Leak check and evacuation must be _completed before opening the service valves.
STEP 1 – Remove service valve cap.
STEP 2 – Fully insert 3/16” hex wrench into the stem and back out counterclockwise until valve stem just touches the rolled edge (approximately five (5) turns.)
STEP 3 – Replace the valve cap to prevent leaks. Tighten finger tight
plus an additional 1/6 turn.
Section 11. Electrical – Low Voltage
Low Voltage Maximum Wire Length
Table 11.1 defines the maximum total length of low voltage wiring from the outdoor unit, to the indoor unit, and to the thermostat.
Table 11.1
24 VOLTS
WIRE SIZE| MAX. WIRE LENGTH
18 AWG| 150 Ft.
16 AWG| 225 Ft.
14 AWG| 300 Ft.
Low Voltage Hook-up Diagrams
In AC systems for multiple stages of electric heat, jumper W1 and W2 together if comfort control has only one stage of heat.
-
Units with pigtails require wire nuts for connections. Cap all unused wires.
-
In AC systems for multiple stages of heat, jumper W1 and W2 together if comfort control has only one stage of heat.
-
If equipped with second stage heat
** When using a BK enabled comfort control, cut BK jumper and bypass Y and YLo at the furnace. Connect BK from comfort control to BK of the furnace
Defrost Control
Defrost controls have a selectable termination temperature. As shipped, defrost will terminate at 47°F. For a higher termination temperature, cut Jumper J2 to achieve 70°F. See Service Facts shipped in the outdoor unit for more information.
Pin Identification on J5 (See Illustration)
- TEST_COMMON (Shorting to FRC_DFT causes the control to initiate Forced Defrost. Leaving this pin open results in the normal mode of operation.)
- FRC_DFT = Forced Defrost (Short TEST_COMMON to this pin for two (2) seconds to initiate a forced defrost. Remove the short after defrost initiates.)
Defrost Control Checkout
Normal operation requires:
- Status LED on board flashing 1 time/second in standby or 2 times/second with a call for heating or cooling.
- 24V AC between R & B
- 24V AC between Y, Y0 & B with unit operating
- Defrost initiation when FRC_DFT pin is shorted to TEST_COMMON pin.
If a defrost control problem is suspected, refer to the service information in
control box.
Section 12. Electrical – High Voltage
High Voltage Power Supply
WARNING
LIVE ELECTRICAL COMPONENTS!
During installation, testing, servicing, and troubleshooting of this product,
it may be necessary to work with live electrical components. Failure to follow
all electrical safety precautions when exposed to live electrical components
could result in death or serious injury.
The high voltage power supply must agree with the equipment nameplate.
Power wiring must comply with national, state, and local codes.
Follow instructions on unit wiring diagram located on the inside of the
control box cover and in the Service Facts document included with the unit.
High Voltage Disconnect Switch
Install a separate disconnect switch at the outdoor unit.
For high voltage connections, flexible electrical conduit is recommended
whenever vibration transmission may create a noise problem within the
structure.
High Voltage Ground
Ground the outdoor unit per national, state, and local code requirements.
Section 13. Start Up
System Start Up
STEP 1 – Ensure Sections 7 through 12 have been completed.
STEP 2 – Set System Thermostat to OFF.
STEP 3 – Turn on disconnect(s) to apply power to the indoor and outdoor
units.
STEP 4 – Wait one (1) hour before starting the unit if compressor
crankcase heater accessory is used and the Outdoor Ambient is below 70ºF.
STEP 5 – Set system thermostat to ON.
Section 14. System Charge Adjustment (Systems can be rated with TXV, EEV
or Piston)
NOTE : For systems using a indoor piston metering device, refer to the Superheat charging method and chart. For systems using a TXV or EEV indoor metering device, refer to Subcool charging method and charts.
Temperature Measurements
STEP 1 – Check the outdoor temperatures.
Subcooling (in cooling mode) is the only recommended method of charging above 55º F ambient outdoor temperature. See Section 14.2.
See Section 14.2 for Outdoor Temperatures Above 55º F
For outdoor temperatures below 55º F, see Section 14.3.
Note: It is important to return in the spring or summer to accurately charge the system in the cooling mode when outdoor ambient temperature is above 55º F.
See Section 14.3 for Outdoor Temperatures Below 55º F
For best results the indoor temperature should be kept between 70º F to 80º F.
Subcooling Charging in Cooling (Above 55º F Outdoor Temp.)
STEP 1 – Use the refrigerant line total length and lift measurements from Section 5.3.
Total Line Length = __ Ft.
Vertical Change (Lift) = __ Ft.
Note: Use this method when matched with a TXV or EEV indoor unit.
STEP 2 – Determine the final subcooling value using total Line Length and Lift measured in STEP 1 and the charts below.
1 1/2 Ton Heat Pump
2 Ton Heat Pump
2 1/2 Ton Heat Pump
3 Ton Heat Pump
3 1/2 Ton Heat Pump
4 Ton Heat Pump
5 Ton Heat Pump
Design Subcooling Value = __º F (from nameplate or Service Facts)
Subcooling Correction = __º F
Final Subcooling Value = __º F
STEP 3 – Stabilize the system by operating for a minimum of 20 minutes
At startup, or whenever charge is removed or added, the system must be
operated for a minimum of 20 minutes to stabilize before accurate measurements
can be made.
STEP 4 – Measure the liquid line temperature and pressure at the outdoor unit’s service valve.
Measured Liquid Line Temp = __ º F
Liquid Gage Pressure = __ PSIG
Final Subcooling Value = __ º F
STEP 5 – Use the final subcooling value, refrigerant temperature and pressure from STEP 4, to determine the proper liquid gage pressure using Table 14.2.
Example: Assume a 12º F Final Subcooling value and liquid temp of 90º F.
- Locate 12º F Final Subcooling in Table 14.2.
- Locate the Liquid Temperature (90º F) in the left column.
- The Liquid Gage Pressure should be approximately 327 PSIG. (This is the shown as the intersection of the Final Subcooling column and the Liquid Temperature row.
STEP 6 – Adjust refrigerant level to attain proper gage pressure.
Add refrigerant if the Liquid Gage Pressure is lower than the chart value.
- Connect gages to refrigerant bottle and unit as illustrated.
- Purge all hoses.
- Open bottle.
- Stop adding refrigerant when liquid line temperature and Liquid Gage Pressure matches the charging chart Final Subcooling value
Recover refrigerant if the Liquid Gage Pressure is higher than the chart value.
STEP 7 – Stabilize the system.
-
Wait 20 minutes for the system condition to stabilize between adjustments.
Note: When the Liquid Line Temperature and Gage Pressure approximately match the chart, the system is properly charged. -
Remove gages.
-
Replace service port caps to prevent leaks. Tighten finger tight plus an additional 1/6 turn.
STEP 8 – Verify typical performance
Refer to System Pressure Curves in the Service Facts to verify typical performance.
Fixed Orifice Superheat Charging Table
|
Indoor Wet Bulb Temp (F)
---|---
Outdoor Dry Bulb Temp. (F)| | 50| 51| 52| 53| 54| 55| 56| 57| 58| 59| 60| 61|
62| 63| 64| 65| 66| 67| 68| 69| 70| 71| 72| 73| 74| 75| 76| 77| 78
55| 7| 9| 10| 11| 12| 14| 15| 17| 18| 20| 21| 23| 24| 26| 27| 29| 30| | | | |
| | | | | | |
60| 5| 7| 8| 9| 10| 12| 13| 15| 16| 18| 19| 21| 22| 24| 25| 27| 28| 30| 31| |
| | | | | | | |
65| | | 4| 6| 8| 10| 11| 13| 14| 16| 17| 18| 19| 21| 22| 24| 25| 27| 28| 27|
31| | | | | | | |
70| | | | | 5| 7| 8| 10| 11| 13| 14| 16| 17| 18| 19| 21| 22| 24| 25| 27| 28|
30| 31| | | | | |
75| | | | | | | 5| 6| 7| 9| 10| 12| 14| 16| 18| 19| 21| 22| 24| 26| 28| 29|
31| 32| | | | |
80| | | | | | | | | 4| 6| 7| 9| 10| 11| 12| 14| 16| 18| 19| 21| 23| 25| 26|
28| 29| 31| 33| |
85| | | | | | | | | | | 4| 6| 7| 9| 10| 13| 14| 16| 18| 20| 21| 23| 24| 26|
28| 29| 30| 31| 32
90| | | | | | | | | | | | | 4| 6| 8| 10| 11| 13| 14| 16| 18| 20| 22| 24| 25|
27| 28| 30| 31
95| | | | | | | | | | | | | | | 4| 6| 8| 10| 13| 14| 16| 18| 20| 22| 23| 25|
26| 28| 29
100| | | | | | | | | | | | | | | | | 6| 8| 10| 12| 13| 16| 18| 20| 21| 23| 25|
27| 29
105| | | | | | | | | | | | | | | | | 4| 6| 7| 9| 11| 13| 15| 18| 20| 22| 24|
26| 28
110| | | | | | | | | | | | | | | | | | | 4| 7| 9| 11| 13| 16| 18| 21| 23| 26|
28
115| | | | | | | | | | | | | | | | | | | | | 6| 9| 12| 14| 16| 19| 21| 24| 26
Using a digital psychrometer, measure the return air wet-bulb temperature at
the unit just before the coil. Also measure the outdoor dry-bulb temperature.
Use these temperatures to locate the target superheat on the charging table.
Do not attempt to charge the system if these conditions fall outside of this
charging table.
ADD refrigerant to DECREASE total superheat. REMOVE refrigerant to INCREASE
total superheat. Always allow 10 to 15 minutes of operature after any
refrigerant or air flow change prior to determining the final superheat.
STEP 9 – Record System Information for reference.
Record system pressures and temperatures after charging is complete.
Outdoor model number = _____
Measured Outdoor Ambient = __ º F
Measured Indoor Ambient = __ º F
Measured Liquid Line Temp = __ º F
Measured Suction Line Temp = __ º F
Liquid Gage Pressure = __ PSIG
Suction Gage Pressure = __ PSIG
Subcooling Charging Below 55º F Outdoor Temp. (In Heating Only)
The Subcooling Charging method in cooling is not recommended below 55º F outdoor temperature.
The only recommended method of charging at outdoor temperatures below 55º F is weighing in the charge in heating mode.
STEP 1 – Determine additional charge.
Note: The nameplate charge value represents the amount of refrigerant shipped in the outdoor unit and is compatible with 10 feet of AHRI rated refrigerant lines and the smallest AHRI rated coil.
Using the method below, find the charge associated with the additional length of tubing above 10 ft. and record it below.
Calculating Charge Using the Weigh-In Method
STEP 1 – Measure in feet the distance between the outdoor unit and the indoor unit. (Include the entire length of the line from the service valve to the IDU.) Subtract 10 ft from this entire length and record on line 1.
STEP 2 – Enter the charge multiplier (0.6 oz/ft). Each linear foot of interconnecting tubing requires the addition of 0.6 oz of refrigerant.
STEP 3 – Multiply the total length of refrigerant tubing (Line 1) times the value on Step 2. Record the result on Line 3 of the Worksheet.
STEP 4 – This is the amount of refrigerant to weigh in prior to opening the service valves.
- Total Line length (ft) – 10 ft __
- Charge multiplier x _0.6 oz ___
- Step 1 x Step 2 = _____
- Refrigerant (oz) = _____
STEP 2 – Stabilize the system by operating for a minimum of 20 minutes.
At startup, or whenever charge is removed or added, the system must be operated for a minimum of 20 minutes to stabilize before accurate measurements can be made.
STEP 3 – Check the liquid line temperature and liquid gage pressure to obtain a minimum of 10º subcooling in heating mode.
Measured Liquid Line Temp = __ º F
Liquid Gage Pressure = __ PSIG
STEP 4 – Add charge if a minimum of 10º subcooling is not obtained with the namplate charge plus additional charge previously added.
STEP 5 – Return to site for adjustment. Important: Return in the spring or summer to accurately charge the system in the cooling mode with outdoor ambient above 55º F.
Section 15. Checkout Procedures and Troubleshooting
Operational And Checkout Procedures
Final phases of this installation are the unit Operational and Checkout Procedures. To obtain proper performance, all units must be operated and charge adjustments made.
Important: Perform a final unit inspection to be sure that factory tubing has not shifted during shipment. Adjust tubing if necessary so tubes do not rub against each other when the unit runs. Also be sure that wiring connections are tight and properly secured.
CHECKOUT PROCEDURE
After installation has been completed, it is recommended that the entire system be checked against the following list:
-
Leak check refrigerant lines. …………………………………. [ ]
-
Properly insulate suction lines and fittings. ………………. [ ]
-
Properly secure and isolate all refrigerant lines. ……….. [ ]
-
Seal passages through masonry.
If mortar is used, prevent mortar from coming into direct contact with copper tubing. …………………….. [ ] -
Verify that all electrical connections are tight. …………… [ ]
-
Observe outdoor fan during on cycle for clearance and smooth operation. ………………………………………….. [ ]
-
Be sure that indoor coil drain line drains freely. Pour water into drain pan. ……………………………………………………… [ ]
-
Be sure that supply registers and return grilles are open and unobstructed. ………………………………………………… [ ]
-
Be sure that a return air filter is installed. ………………… [ ]
-
Be sure that the correct airflow setting is used. (Indoor blower motor) …………………………………………… [ ]
-
Operate complete system in each mode to ensure safe operation. ………………………………………….. [ ]
Troubleshooting
SYSTEM FAULTS| WHAT TO CHECK MODE| POWER SUPPLY| HIGH VOLTAGE WIRING|
COMPRESSOR
IOL| RUN CAPACITOR| START CAPACITOR| START RELAY| CONTACTOR CONTACTS| LOW
VOLTAGE WIRING| CONTROL TRANSFORMER| THERMOSTAT| CONTACTOR COIL| LOW VOLTAGE
FUSE| STUCK COMPRESSOR| INEFFICIENT
COMP.| REF. UNDERCHARGE| REF. OVERCHARGE| EXCESSIVE EVAP.
LOAD| NONCONDENSABLES| RES. O.D. AIRFLOW| O.D. AIR RECIRCULATION| TXV/EEV
STUCK OPEN| SUPERHEAT| RES. I.D. AIRFLOW| REF. CIR. RESTRICTIONS| SOV LEAKING|
SOV COIL DEFECTIVE| CHECK VALVE LEAKING| *
DEFROST RELAY DEF.| DEFROST CONTROL DEF.
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
REFRIGERANT CIRCUIT
Head Pressure Too High| C| | | | | | | | | | | | | | | | P| P| S| P| S| | | |
S| | | | |
H| | | | | | | | | | | | | | | | P| P| S| | | | | P| S| | | | |
Head Pressure Too Low| C| | | | | | | | | | | | | | S| P| | | | | | S| S| | S|
S| S| P| |
H| | | | | | | | | | | | | | S| P| | | | | | S| S| | S| S| | P| |
Suction Pressure Too High| C| | | | | | | | | | | | | | S| | P| P| | | | | S|
| | P| | P| |
H| | | | | | | | | | | | | | S| | | | | | | | S| | | P| | | |
Suction Pressure Too Low| C| | | | | | | | | | | | | | | P| | | | | | | S| P|
S| | S| | |
H| | | | | | | | | | | | | | | P| | | | S| S| | S| | S| | | | |
Liquid Refrig. Floodback (TXV/EEV)| C| | | | | | | | | | | | | | | | | | | | |
P| | | | | | P| |
H| | | | | | | | | | | | | | | | | | | | | P| | | | | | P| |
Liquid Refrig. Floodback (Cap. Tube)| C| | | | | | | | | | | | | | | | P| | |
S| S| | S| P| | | | | |
H| | | | | | | | | | | | | | | | P| | | S| S| | S| | | | S| | |
I.D. Coil Frosting| C| | | | | | | | | | | | | | | P| | | | S| S| | | | | | |
| |
H| | | | | | | | | | | | | | | | | | | | | | | | | | | | |
Compressor Runs
Inadequate or No Cooling/Htg| C| | | | | | | | | | | | | | S| P| | S| S| | | |
S| P| S| S| S| S| |
H| | | | | | | | | | | | | | S| P| | | S| | | | S| P| S| S| | S| |
ELECTRICAL
Compressor & O.D. Fan Won’t Start| C| P| P| | | | | | S| P| S| P| P| | | | | |
| | | | | | | | | | |
H| P| P| | | | | | S| P| S| P| P| | | | | | | | | | | | | | | | |
Compressor Will Not Start But O.D. Fan Runs| C| | P| S| P| S| S| S| | | | | |
P| | | | | | | | | | | | | | | |
H| | P| S| P| S| S| S| | | | | | P| | | | | | | | | | | | | | | |
O.D. Fan Won’t Start| C| | P| | P| | | S| | | | | | | | | | | | | | | | | | |
| | |
H| | P| | P| | | S| | | | | | | | | | | | | | | | | | | | | |
Compressor Hums But Won’t Start| C| | | | P| S| S| S| | | | | | P| | | | | | |
| | | | | | | | |
H| | | | P| S| S| S| | | | | | P| | | | | | | | | | | | | | | |
Compressor Cycles on IOL| C| | P| S| P| S| S| S| | | | | | P| S| P| P| S| | S|
S| | S| | | S| | | |
H| | P| S| P| S| S| S| | | | | | P| S| P| P| S| | S| | | S| P| | S| | | |
I.D. Blower Won’t Start| C| P| P| | | | | | S| P| S| | S| | | | | | | | | | |
| | | | | |
H| P| P| | | | | | S| P| S| | S| | | | | | | | | | | | | | | | |
DEFROST
Unit Won’t Initiate Defrost| C| | | | | | | | | | | | | | | | | | | | | | | |
| | | | |
H| | | | | | | | | | | | | | | | | | | | | | | | | | P| | P| P
Defrost Terminates on Time| C| | | | | | | | | | | | | | | | | | | | | | | | |
| | | |
H| | | | | | | | | | | | | | | P| | | | | | | | | | | | | | P
Unit Icing Up| C| | | | | | | | | | | | | | | | | | | | | | | | | | | | |
H| | | | | | | | | | | | | | | P| | | | S| S| | | S| | | P| | | P
*C – Cooling H – Heating P – Primary Causes S – Secondary Causes – 3 Phase Only**
About Trane and American Standard Heating and Air Conditioning Trane and American Standard create comfortable, energy efficient indoor environments for residential applications. For more information, please visit www.trane.com or www.americanstandardair.com
The AHRI Certified mark indicates company participation in the AHRI Certification program. For verification of individual certified products, go to ahridirectory.org.
The manufacturer has a policy of continuous data improvement and it reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.
References
- DWG.no - DWG Cad Software | DWG View | DWG til PDF | Norsk nettside som går gjennom nyheter og muligheter innen 2D og 3D design
- P65Warnings.ca.gov
- Trane Heating & Air Conditioning
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>