SANTA FE Impact155 Horizontal Dehumidifier Instruction Manual
- June 12, 2024
- SANTA-FE
Table of Contents
INDOOR AIR QUALITY SOLUTIONS
SANTA FE | IMPACT155
Installation & Operation Instructions
The Santa Fe Impact155 dehumidifier features dual exhaust outlets for air
distribution to multiple locations. The Impact155 is engineered for extremely
quiet operation and optimized for low heat load. This dehumidifier has a
horizontal configuration, making it optimal for basements or crawl space
applications.
Not for Sale in California
Serial Number………………………….
Install Date…………………….
Sold By…………………..
Patent: thermastor.com/patents
Safety Instructions
READ THE INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS CAREFULLY BEFORE
INSTALLING AND OPERATING THIS DEVICE. PROPER ADHERENCE TO THESE INSTRUCTIONS
IS ESSENTIAL TO OBTAIN MAXIMUM BENEFIT FROM YOUR SANTA FE DEHUMIDIFIER.
WARNING!
THIS SYMBOL MEANS IMPORTANT INSTRUCTIONS. FAILURE TO HEED THEM CAN RESULT IN
SERIOUS INJURY OR DEATH.
CAUTION!
THIS SYMBOL MEANS IMPORTANT INSTRUCTIONS. FAILURE TO HEED THEM CAN RESULT IN
INJURY OR MATERIAL PROPERTY DAMAGE.
- Never operate a unit with a damaged power cord. If the power cord is damaged, it must be replaced by the manufacturer, its service agent, or a similarly qualified person in order to avoid a hazard.
- Do not unplug the unit by pulling on the cord. Grasp the plug firmly and pull it out of the wall socket or power receptacle.
- When plugging in the unit, use a Ground Fault Interrupter outlet.
- This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience or knowledge, unless they have been given supervision or instruction concerning the use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
- Never operate electrical equipment near or in standing water.
- Do not stick your fingers or other objects through the safety grill.
- The unit must be used in the upright position.
- When changing filters, do not stick fingers or other objects in the unit and make sure the dehumidifier is off.
- Do not restrict airflow in to or out of the unit. This may cause the unit to overheat.
- The unit should never be serviced or cleaned while it is plugged in.
- Do not sit or stand on the unit, or use as a shelf or table.
- Before leaving the unit unattended, ensure children do not have access to the equipment. Do not allow children to play with or near the unit or in its air flow.
- The unit is designed to be installed indoors only.
- Contact installer or call 1-800-533-7533 for all repair or warranty needs.
Intended Application(s)
The Santa Fe Impact155 dehumidifier is designed to operate in temperatures
between 56° and 95°F.
The Santa Fe Impact155 is registered with the DOE as a portable dehumidifier
with a capacity greater than 50 pints per day. It is a stand-alone
dehumidifier intended to operate within the dehumidified space, such as
basements: however, the unit can be placed in almost any residential setting
where dehumidification is desired.
The Santa Fe Impact155 is not for sale in California.
Registrations and Certifications
The Santa Fe Impact155 dehumidifier conforms to unified standard UL 60335-2-40
and CSA standard C22.2.60335-2-40.
The Santa Fe Impact155 is certified as a “Portable Dehumidifier” per 10CFR430
– Energy Conservation Program for Consumer Products
Brand Name| Individual
Model Number| Basic Model
Number| Rating
Conditions| Integrated Energy
Factor (L/kWh)| Capacity
(Pint/Day)
---|---|---|---|---|---
Santa Fe| Impact155| 155-P| 65F/60%| 2.089| 104.33
Dehumidifier Set Up
** CAUTION! REMOVE COMPRESSOR SHIPPING TIE FROM THE UNIT. FAILURE TO
REMOVE SHIPPING TIE WILL CAUSE EXCESS VIBRATION TO BE TRANSMITTED TO THE
FRAME.
The Santa Fe Impact155 dehumidifier uses a compressor to power the
refrigeration system. To protect the compressor and refrigeration system
during shipping a plastic tie wrap secures it to the units frame. Remove the
tie wrap by cutting the tie wrap and pulling from the unit as shown. After
removing tie wrap, insert plastic plugs provided into the holes.
Items Included in Box:**
- Santa Fe Impact155 Dehumidifier
- Santa Fe Impact155 Dehumidifier Installation & Operation Instructions
- Santa Fe Impact155 Dehumidifier Leveling Feet
- 8′ Drain Hose
- MERV-13 Filter (Dimensions: 16” x 20” x 2”)
Important Precautions
- Do not install the Santa Fe Impact155 dehumidifier with the intake or exhaust of the unit within 1′ of a wall or other obstruction. Avoid directing the discharge air at people. The dehumidifier should be used in the upright position.
- Do not place the unit where curtains or debris can be drawn into the intake and restrict airflow.
- The device is designed to be installed indoors in a space that is protected from rain and flooding.
- Do not operate in standing water or place the unit near open water. If used near a water source; be certain there is no chance the unit could fall into the water or get splashed and that it is plugged into a dedicated circuit and Ground Fault Circuit Interrupter (GFCI) protected outlet.
- Install the unit with enough space to access all sides for maintenance and service. The rear panel where the power cord is located needs to be removed in order to do repairs.
- DO NOT use the dehumidifier as a bench or table.
- DO NOT place the dehumidifier directly on structural building members without vibration absorbers or unwanted noise may result. Place the Santa Fe Impact155 dehumidifier on supports to raise the base of the unit.
Location Considerations
- Locate the dehumidifier near a suitable drain (8′ drain hose included). Allow for proper drainage and routing of needed drain pipes.
- Locate the dehumidifier in an area where the cord’s length (9′) easily reaches a 115 VAC electrical outlet with a minimum of a 15 Amp circuit capacity.
- The unit is designed to operate while level. If the unit is placed on an unlevel surface, refer to section below (Installing Leveling Feet). Failure to level the unit may result in leakage or improper drainage.
- The unit should be suspended with a hang kit from the floor joists if there is any possibility of flooding. A flooded unit is not covered by warranty. Feet will be installed as a securing measure after the hang kit is put on the dehumidifier. DO NOT hang the Santa Fe Impact155 dehumidifier from its’ cabinet.
- Allow sufficient clearance to handle the unit’s overall dimensions as well as any optional return and supply ductwork to the unit.
- Allow sufficient clearance for filter removal and to prevent airflow obstruction.
- Electrical service access will require the removal of the rear panel where the power cord is located. Allow sufficient clearance around the unit.
Installing Leveling Feet
- Lay down a protective pad (pillow, blanket, etc.).
- Carefully turn unit onto side.
- Install leveling feet and adjust to the desired position to ensure unit is level for proper drainage.
- Carefully bring unit to upright position.
- Wait a minimum of 10 minutes before operating.
Drain Installation
The Santa Fe Impact155 dehumidifier generates condensate.
Place a secondary drain pan under the dehumidifier if it is suspended above a
finished area or above an area where water leakage could cause damage.
A drain trap is required for the dehumidifier to run properly. Install a 3/4″
threaded male NPT adapter to the drain port or drain pan if one is being used.
Install a drain pipe assembly utilizing 3/4″ PVC pipe to transport the
condensate to a drain. The pitch/slope of the drain pipe should be no less
than 1 inch per 10 feet of drain pipe.
An optional condensate pump kit is available for use with the Santa Fe
Impact155 dehumidifier and may be installed if lift is required to dispose of
condensate. Condensate is automatically pumped to a remote location when the
water level in the pump’s reservoir rises to close the float switch.
CAUTION!
The Santa Fe Impact155 dehumidifier requires a drain trap.
Creating a drain trap allows a small amount of water to build up inthe trap
area of the clear hose. This prevents air from back flowingthrough the hose
and into the dehumidifier; essentially causing theunit to backflow water out
of the corners of the machine. Position the trap in the hose approximately
8″-10” from the dehumidifier and make sure the highest point of the trap is
still at least 2” belowthe black drain port adapter on the dehumidifier. If
the highest point of the trap is above the drain port, water will back flow
into the dehumidifier. Check the hose regularly to ensure water is draining
properly.
CAUTION!
CHECK DRAIN LINE WHEN CHANGING FILTER TO ENSURE THERE IS NO BUILD UP OF ALGAE
OR SLUDGE.
Use care to keep the hose as flat to the floor as possible after your trap is
in place. Be sure the hose is not kinked or otherwise restricted so water can
pass through the hose freely. Improper installation of the drain hose may
result in water leakage.
If the Santa Fe Impact155 dehumidifier is located too far from the floor drain
and the provided hose does not reach, you may use a 1/2” PVC rigid pipe to
extend the drain.
Rigid PVC tubing is readily available from your local hardware store. Be sure
the extension is at a downward slope to the drain.
An optional condensate pump kit may be installed if lift is required to remove
condensate. To order, contact your local dealer or visit our website at www
.santa-fe-products.com. You may also reach
us by phone at 800-533-7533 and we can
direct you to a dealer.
Operation
Humidity Control Adjustment
The humidity control is an adjustable switch that turns the dehumidifier on
and off. It turns on when the relative humidity (RH) rises to the dial set
point. It turns off when the RH is within ±5% of the set point.
Approximate Humidity Levels Per Setting
“Drier” 35% to 45% Relative Humidity
“Normal” 45% to 55% Relative Humidity
(Recommended for most applications)
“Humid” 55% to 65% Relative Humidity
**CAUTION!
The dehumidifier will run continuously until the RH is reduced to the humidity
control dial setting. It is not recommended to set the humidity control to
“dry” in rooms under 65°; doing so will result in long periods of ineffective
dehumidifier run time.
To turn unit on, turn the humidity dial clockwise to the recommended “NORMAL”
position and set fan control to “FAN AUTO.” To turn the unit off, turn the
humidity dial counter clockwise to the “OFF” position and set fan control to
“FAN AUTO.”
Defrost Cycle
This product includes a defrost thermostat. This feature prevents internal
damage caused by excessive frost forming within the unit. When the unit is
experiencing excessive frost the system will stop dehumidfying and the fan
will run until normal operating conditions are present.
Fan Operation**
Turning the fan switch “FAN ON” will cause the unit’s internal blower to run
continuously, whether the unit is dehumidifying or not. This function is
desirable if the unit is used for air circulation or filtration. Turning the
fan switch to “FAN AUTO” (recommended) will cause the unit’s internal blower
to run only while the unit is dehumidifying.
Air Filtration
The Santa Fe Impact155 dehumidifier is equipped with a MERV-13 filter (89-90%
ASHRAE dust spot). An optional MERV11 filter is available at
www.ThermastorFilters.com. The filter
should be checked and replaced every three to six months.
Operating the unit with a dirty filter will reduce dehumidifier capacity and
efficiency.
DO NOT operate the unit without the standard MERV-13 filter or optional
MERV-11 filter. Filter non-compliance voids the product warranty.
CAUTION!
MAKE SURE UNIT IS OFF BEFORE CHANGING THE FILTER. FAILURE TO FOLLOW FILTER
HANDLING INSTRUCTIONS MAY RESULT IN IMPROPER FUNCTION OF THE DEHUMIDIFIER AND
CAUSE PREMATURE FILTER WEAR OR UNIT DAMAGE.
Changing the Filter
For greatest filtration and efficiency of the Santa Fe Impact155 dehumidifier,
it is recommended the air filter be replaced every three to six months with a
MERV-13 filter.
Step 1: Release the latch from the cabinet by pulling it down and out.
Remove the filter door by pulling it out of the bottom tab. Step 2: Remove the
filter by gently pulling it straight out of the unit. Insert new filter by
gently pushing it straight into the unit. Make sure the AIR FLOW arrow on the
filter is pointing into the unit.![SANTA FE Impact155 Horizontal Dehumidifier
- straight](https://manuals.plus/wp-content/uploads/2023/08/SANTA-FE-Impact155 -Horizontal-Dehumidifier-straight.jpg)Step 3: Close the filter door by swinging it shut and reattaching the latch.
Ducting To Finished Areas (Optional)
Attaching Duct Collars
Return Air Inlet
An 12” diameter duct collar and a front panel are attached to the unit.
Supply Air Outlet
Two 10” diameter duct collars attach to the outlets on each side of the unit.
CAUTION! BOTH EXHAUST OUTLETS MUST BE LEFT OPEN OR DUCTED USING THE TWO
10” DUCT COLLARS.
DO NOT BLOCK OFF ONE SIDE. FAILURE TO DO SO WILL RESULT IN DAMAGE OF THE
UNIT. Ducting To Finished Areas (Optional)
Recommended Installations
- Place the Santa Fe Impact155 dehumidifier in the unfinished area of the basement, near a drain access (condensate will drain via gravity or with an optional pump kit).
- Using the supply duct collar, supply the dry air from the dehumidifier into a large, open area in the finished and unfinished sections of the basement.
- Place a return grill / passive vent on the other side of the wall that separates the finished and unfinished areas. This will allow for a circular air flow throughout the basement.
- The passive grill will prevent the unfinished room from being placed under a negative pressure and also allow the dehumidifier to focus on keeping the unfinished area dry as well.
- The onboard dehumidistat control can be used on the unit for this application or a 120 volt dehumidistat can be placed in the finished basement as well (we recommend using an electrician to run the wiring).
- Be sure to keep all doors open to any other rooms in the basement to help with proper air circulation (bedrooms, bathrooms, etc.)
Service – Troubleshooting
CAUTION!
TROUBLESHOOTING SHOULD BE PERFORMED BY A QUALIFIED HVAC TECHNICIAN.
Symptom | Possible Reason | Troubleshooting Procedure |
---|
Fan is not running. Dehumidification or fan is being
called for.| 1.Loose connection in fan circuit.
2.Obstruction prevents fan impeller rotation.
3.Defective fan.
4.Defective fan relay.| WARNING!
ELECTRICAL SHOCK HAZARD:
ELECTRICAL POWER MUST BE PRESENT TO PER-FORM SOME TESTS. THESE TESTS SHOULD BE
PERFORMED BY A QUALIFIED SERVICE PERSON.
Troubleshooting Procedure for Performance Related Issues
This method of diagnosis is used to function check i the internal components
in the dehumidifi-
er. This is to be used when a performance issue is
suspected.
1.Set the humidity controller all the way to the most humid setting or off
position — Did the unit shut off?
2.If yes, turn the fan setting to the ON position — does the fan start?
3.If fan starts, leave in the fan ON position and set the humidity all the way
to driest setting. May have to wait 5 minutes for the compressor to start.
4.Listen for a distinct buzzing/humming sound of a compressor starting up — do
you hear this noise?
5.If compressor is running and continues to run, after about 15 minutes you
should feel a slight increase in air temperature being discharged out of the
discharge air side of the unit.
6.If so, depending on your environmental conditions (temp/Rh%), you should see
some water production out of the hose within 30 minutes or so. (Note: If the
room
temperature is 55 degrees or below and/or in area of low relative humidity,
the
dehumidifier will produce little to no water.)
Collecting the water removed in a 24 hour period will give a measurement of
performance.
Low dehumidification capacity (evaporator is frosted
continuously). Dehumidification is being called for.| 1.Defrost thermostat
loose or defective.
2.Low refrigerant charge.
3.Dirty air filter(s) or air flow restricted.
4.Excessively restrictive ducting connected to unit.
Dehumidifier removes some water, but not as much as expected.| 1.Air
temperature and/or humidity have dropped.
2.Humidity meter and or thermometer used are out of calibration.
3.Unit has entered defrost cycle.
4.Dirty air filter(s) or air flow is restriced.
5.Defective defrost thermostat.
6.Low refrigerant charge.
7.Air leak such as loose cover or ducting leaks.
8.Defective compressor.
9.Restrictive ducting.
CAUTION!
TROUBLESHOOTING SHOULD BE PERFORMED BY A QUALIFIED HVAC TECHNICIAN.
Symptom | Possible Reason |
---|
Neither fan nor compressor running.
Dehumidification is being called for.| 1. Dehumidifier unplugged or no power
to outlet.
2. Humidity control set too high.
3. Loose connection in internal or control wiring.
4. Defective compressor relay.
Compressor is not running.
Dehumidification is being called for.
Fan is running.| 1. Defective compressor run capacitor.
2. Loose connection in compressor circuit.
3. Defective compressor overload.
4. Defective compressor.
5. Defrost thermostat open.
Compressor cycles on and off.
Dehumidification is being called for.| 1. Low ambient temperature and/or
humidity causing unit to cycle through defrost mode.
2. Defective compressor overload.
3. Defective compressor.
4. Defrost thermostat defective.
5. Dirty air filter(s) or air flow restricted.
6. Defective fan or relay.
WARNING!
SERVICING THE SANTA FE IMPACT155 DEHUMIDIFIER, WITH ITS HIGH PRESSURE
REFRIGERANT SYSTEM AND HIGH VOLTAGE CIRCUITRY PRESENTS A HEALTH HAZARD WHICH
COULD RESULT IN DEATH, SERIOUS BODILY INJURY, AND/OR PROPERTY DAMAGE. ONLY
QUALIFIED SERVICE PEOPLE SHOULD SERVICE THIS UNIT.
Refrigerant Charging
If the refrigerant charge is lost due to service or a leak, a new charge must
be accurately weighed in. If any of the old charge is left in the system, it
must be recovered before weighing in the new charge. Refer to the unit
nameplate for the correct charge weight and refrigerant type.
Compressor/Capacitor Replacement
This compressor is equipped with a two terminal external overload and a run
capacitor, but no start capacitor or relay.
Electrical Requirements
The Santa Fe Impact155 dehumidifier plugs into a common grounded 115VAC
outlet. The Impact155 draws 8.0 Amps at 80°F and 60% RH. Locate the
dehumidifier in an area where the cord’s length (9′) easily reaches a 115 VAC
electrical outlet with a minimum of 15 Amp circuit capacity. If used in an
area that may become wet, a GFCI protected circuit is recommended. The unit
should not be used in areas prone to flooding. Consult local electrical codes
for any further information.
An optional remote dehumidistat is available for use with the Santa Fe
Impact155 dehumidifier and is to be located remotely from the dehumidifier.
**CAUTION!**
ELECTRICAL SHOCK HAZARD: Electrical power must be present to perform some
tests. These tests should be performed by a qualified service person.
Warranty
Limited Warranty. Therma-Stor, LLC (“Therma-Stor”) warrants as follows: (i)
the Santa Fe Impact155 dehumidifier (“Product”) will be free of material
defects in workmanship or materials for a period of 2 years (“Two-Year
Warranty”) following the date of initial purchase of such Product by an
original customer purchasing from Therma-Stor or an authorized reseller
(“Customer”); and (ii) the Product’s components will be free of material
defects in workmanship or materials for a period of six (6) years following
the date of initial purchase of such Product by a Customer.
Limitation of Remedies. CUSTOMER’S SOLE AND EXCLUSIVE REMEDY UNDER THE ABOVE
LIMITED WARRANTY AND THERMA- STOR’S ENTIRE LIABILITY THEREUNDER, SHALL BE, AT
THE SOLE OPTION OF THERMA-STOR, REPLACEMENT OR REPAIR OF SUCH PRODUCT OR ITS
COMPONENTS (“COMPONENTS”) BY THERMA-STOR OR THERMA-STOR’S AGENTS ONLY.
REFRIGERANT, PIPING, SUPPLIES, TRANSPORTATION COSTS, LABOR COSTS INCURRED IN
REPAIR OR REPLACEMENT OF SUCH COMPONENTS ARE NOT INCLUDED. THIS DISCLAIMER AND
EXCLUSION SHALL APPLY EVEN IF THE EXPRESS WARRANTY AND LIMITED REMEDY SET
FORTH HEREIN FAILS OF ITS ESSENTIAL PURPOSE. CUSTOMER ACKNOWLEDGES THAT NO
REPRESENTATIVE OF THERMA-STOR OR OF ITS AFFILIATES OR RESELLERS IS AUTHORIZED
TO MAKE ANY REPRESENTATION OR WARRANTY ON BEHALF OF THERMA-STOR OR ANY OF ITS
AFFILIATES OR RESELLERS THAT IS NOT IN THIS AGREEMENT. Notwithstanding the
above, during the term of the TwoYear Warranty only, Therma-Stor will provide,
free of charge to Customer, all Components and labor (except costs related to
removal and installation of Product) required to fulfill its obligations under
such Two-Year Warranty.
Disclaimer of Warranties. EXCEPT FOR ABOVE LIMITED WARRANTY, WHICH IS THE SOLE
AND EXCLUSIVE WARRANTY PROVIDED WITH RESPECT TO THE PRODUCT AND ITS
COMPONENTS, THERMA-STOR HEREBY DISCLAIMS ALL EXPRESS AND IMPLIED WARRANTIES,
INCLUDING, WITHOUT LIMITATION, THE IMPLIED WARRANTIES OF MERCHANTABILITY AND
FITNESS FOR A PARTICULAR PURPOSE.
Warranty Limitations. The foregoing limited warranty extends only to a
Customer and shall be null and void upon attempted assignment or transfer. A
“defect” under the terms of the limited warranty shall not include problems
resulting from Customer’s or Customer’s employees’, agents’, invitees’ or a
third party’s misuse, improper installation, improper design of any system in
which the Product is included, abuse, lack of normal care, failure to follow
written instructions, tampering, improper repair, or freezing, corrosion, acts
of nature or other causes not arising out of defects in Therma-Stor’s
workmanship or material. If a Product or Component is replaced while under
warranty, the applicable limited warranty period shall not be extended beyond
the original warranty time period. The limited warranty does not cover any
costs related to changes to a Product or Component that may be required by any
codes, laws, or regulations that may become effective after initial purchase
of the Product by Customer.
Customer Responsibilities. As a further condition to obtaining warranty
coverage hereunder, the Customer must send a valid warranty claim to
ThermaStor such that Therma-Stor receives such claim prior to
the end of the applicable warranty period.
Therma-Stor shall have no obligation hereunder with respect to any claim
received by Therma-Stor after the expiration of the applicable warranty
period. As a further condition to obtaining warranty coverage hereunder, the
Customer must present forms of invoices evidencing proof of purchase of a
Product. If such invoices do not clearly indicate the date of initial
purchase by a Customer, the applicable Product’s date of manufacture will be
used instead ofthe date of initial purchase for the purpose of calculating the
commencement of the applicable warranty period. Warranty service must be
performed by Therma-Stor or a servicer authorized by Therma-Stor. In order
toobtain warranty service, the
Customer should call Therma-Stor at
1-800-533-7533 and ask for the Therma-
Stor Products Service Department, which will then arrange for applicable
warranty service. Warranty service will beperformed during customary, daytime
working hours. If the Product must be shipped for service, Customer shall be
solely responsible for properly packaging the Product, for all freight
charges, and for all risk of loss associated with shipment.
Limitation of Liability. IN NO EVENT SHALL THERMA-STOR, IN CONNECTION WITH THE
DESIGN, SALE, INSTALLATION, USE, REPAIR, REPLACEMENT OR PERFORMANCE OF ANY
PRODUCT, COMPONENT, PART THEREOF OR WRITTEN MATERIAL PROVIDED THEREWITH, BE
LIABLE, TO THE EXTENT ALLOWED UNDER APPLICABLE LAW, UNDER ANY LEGAL THEORY FOR
ANY SPECIAL, DIRECT, INDIRECT, COLLATERAL OR CONSEQUENTIAL DAMAGES OF ANY
KIND. NOTWITHSTANDING THE ABOVE LIMITATIONS AND WARRANTIES, THE SOLE AND
EXCLUSIVE LIABILITY OF THERMA-STOR, REGARDLESS OF THE NATURE OR THEORY OF THE
CLAIM, SHALL UNDER NO CIRCUMSTANCES EXCEED THE PURCHASE PRICE OF THE PRODUCT,
COMPONENT OR PART UPON WHICH THE CLAIM IS PREMISED.
Applicable Law and Venue. ANY ARBITRATION, ENFORCEMENT OF AN ARBITRATION OR
LITIGATION RELATED TO THE PRODUCT WILL BE BROUGHT EXCLUSIVELY IN DANE COUNTY,
WISCONSIN, AND CUSTOMER CONSENTS TO THE JURISDICTION OF THE FEDERAL AND STATE
COURTS LOCATED THEREIN, SUBMITS TO THE JURISDICTION THEREOF AND WAIVES THE
RIGHT TO CHANGE VENUE. CUSTOMER FURTHER CONSENTS TO THE EXERCISE OF PERSONAL
JURISDICTION BY ANY SUCH COURT WITH RESPECT TO ANY SUCH PROCEEDING.
Miscellaneous. If any term or condition of this Limited Warranty is found by a
court of competent jurisdiction to be invalid, illegal or otherwise
unenforceable,
the same shall not affect the other terms or conditions hereof or thereof or
the whole of this Limited Warranty. Any delay or failure by Therma-Stor to
exercise any right or remedy will not constitute a waiver of Therma-Stor to
thereafter enforce such rights.
WARRANTY REGISTRATION CARD
IMPORTANT WARRANTY INFORMATION – DO NOT DISCARD
REGISTER YOUR PRODUCT.
WARRANTY
SERIAL
NUMBER
PART
NUMBER
www.thermastor.com/registration
Register your product using the serial number and part number above at
www.thermastor.com/registration
This is important
Warranty Information.
Please DO NOT DISCARD!
Santa-Fe-Products.com
1.800.533.7533
CPNTS-2035|VN129189|CSNXXXX
TS-2035 05/23 Rev A
Santa-Fe-Products.com | 800.533.7533
4201 Lien Rd. Madison, WI 53704
1-800-533-7533
www.Thermastor.com
www.Santa-Fe-Products.com
© 2016 Therma-Stor LLC