SANTA-FE DEHUMIDIFIER ULTRA120V Ultra Series Vertical Whole House Dehumidifier Instruction Manual
- June 4, 2024
- SANTA-FE DEHUMIDIFIER
Table of Contents
- SANTA-FE DEHUMIDIFIER ULTRA120V Ultra Series Vertical Whole House
- SAFETY INSTRUCTIONS
- DEHUMIDIFIER SET UP
- ATTACHING DUCT COLLARS
- ELECTRICAL REQUIREMENTS
- DRAIN INSTALLATION
- DUCTING TO HVAC SYSTEMS
- FRESH AIR VENTILATION
- CONTROLS
- AIR FILTRATION
- SERVICE
- WARRANTY
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
SANTA-FE DEHUMIDIFIER ULTRA120V Ultra Series Vertical Whole House
Dehumidifier
SAFETY INSTRUCTIONS
READ THE INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS CAREFULLY BEFORE
INSTALLING AND OPERATING THIS DEVICE. PROPER ADHERENCE TO THESE INSTRUCTIONS
IS ESSENTIAL TO OBTAIN MAXIMUM BENEFIT FROM YOUR SANTA FE WHOLE HOUSE
VENTILATING DEHUMIDIFIER.
WARNING THIS SYMBOL MEANS IMPORTANT INSTRUCTIONS. FAILURE TO HEED THEM
CAN RE-SULT IN SERIOUS INJURY OR DEATH.
CAUTION! THIS SYMBOL MEANS IMPORTANT INSTRUCTIONS. FAILURE TO HEED THEM
CAN RE-SULT IN INJURY OR MATERIAL PROPERTY DAMAGE.
Registrations The Santa Fe Ultra120V conforms to unified standard UL
60335-2-40 and CSA standard C22.2.60335-2-40.
WARNING 120 VOLTS MAY CAUSE SERIOUS INJURY FROM ELECTRIC SHOCK.
DISCONNECT ELECTRICAL POWER BEFORE STARTING INSTALLATION OR SERVICING, AND
LEAVE POWER DISCONNECTED UNTIL INSTALLATION OR SERVICE IS COMPLETED.
CAUTION! READ ALL INSTRUCTIONS BEFORE BEGINNING INSTALLATION.
ALWAYS USE CAUTION AND WEAR CUT RESISTANT GLOVES WHEN HANDLING SHEET METAL.
IMPROPER INSTALLATION MAY CAUSE PROPERTY DAMAGE OR INJURY.
INSTALLATION, SERVICE, AND MAINTENANCE MUST BE PERFORMED BY A QUALIFIED
SERVICE TECHNICIAN.
DEHUMIDIFIER IS HEAVY. HANDLE WITH CARE AND FOLLOW INSTALLATION INSTRUCTIONS.
NEVER OPERATE A UNIT WITH A DAMAGED POWER CORD. IF THE POWER CORD IS
DAMAGED, IT MUST BE REPLACED BY THE MANUFACTURER, ITS SERVICE AGENT, OR A
SIMILARLY QUALIFIED PERSON IN ORDER TO AVOID A HAZARD.
THIS APPLIANCE IS NOT INTENDED FOR USE BY PERSONS (INCLUDING CHILDREN) WITH
REDUCED PHYSICAL, SENSORY OR MENTAL CAPABILITIES, OR LACK OF EXPERIENCE
OR KNOWLEDGE, UNLESS THEY HAVE BEEN GIVEN SUPERVISION OR INSTRUCTION
CONCERNING THE USE OF THE APPLIANCE BY A PERSON RESPONSIBLE FOR THEIR
SAFETY. CHILDREN SHOULD BE SUPERVISED TO ENSURE THAT THEY DO NOT PLAY WITH THE
APPLIANCE.
DEHUMIDIFIER SET UP
Important Precautions
- The device is designed to be installed indoors in a space that is protected from rain and flooding.
- Install the unit with enough space to access the front panel for maintenance and service.
- Avoid directing the discharge air at people. The dehumidifier should be used in the upright position.
- If used near a water source, be certain there is no chance the unit could fall into the water or get splashed and that it is plugged into a dedicated circuit and Ground Fault Circuit Interrupter (GFCI) protected outlet.
- DO NOT use the dehumidifier as a bench or table.
- DO NOT place the dehumidifier directly on structural building members without vibration absorbers or unwanted noise may result. Place the Santa Fe Ultra120V on supports to raise the base of the unit.
- A drain pan with a float switch MUST be placed under the dehumidifier if installed above a living area or above an area where water leakage could cause damage.
Location Considerations
-
Allow sufficient clearance to handle the unit’s overall dimensions as well as the necessary return and supply ductwork to the unit.
-
Allow sufficient clearance for filter removal and to prevent airflow obstruction.
-
Electrical service access will require the removal of the front panel. Allow sufficient clearance on this side of the unit.
-
Locate the dehumidifier in an area where the cord’s length (9′) easily reaches a 115 VAC electrical outlet with a minimum of a 15 Amp circuit capacity.
-
Locate the dehumidifier in an area where field wiring the control (low voltage) to the unit will be possible.
-
It is recommended that a backdraft damper be used in the discharge duct of the Santa Fe Ultra120V, especially when connecting to the supply ducting system. The backdraft damper prevents supply air from counter
flowing through the Santa Fe Ultra120V when it is not operating. The dehumidifier’s location should be chosen to allow installation of this accessory if necessary. -
DO NOT hang the Santa Fe Ultra120V from its cabinet.
-
Allow for proper routing and drainage of needed drain pipes.
ATTACHING DUCT COLLARS
Before installing the damper and duct collars listed below, apply the corresponding foam tape included for each.
-
Fresh Air Ventilation Duct
Fresh air ventilation is optional. A 6″ diameter damper is included with the unit and can be attached to the top using the corresponding foam tape provided. The 6″ damper should be closed if fresh air is not desired. If setting up the unit to provide fresh air ventilation, see page 9. -
Return Air Inlet
An 8″ diameter duct collar is included with the unit and can be attached to the top with the corresponding
foam tape provided. -
Supply Air Outlet #1
An 8″ diameter duct collar is included with the unit and can be attached to the side using the corresponding foam tape provided. -
Supply Air Outlet #2
An optional 8″ diameter duct collar is included with the unit and can be attached to the other side with the corresponding foam tape provided. -
Supply Air Duct Cover
An optional 8” diameter duct cover (attached) can be used to block one of the supply air outlets if not being used.
ELECTRICAL REQUIREMENTS
The Santa Fe Ultra120V plugs into a common grounded 115 VAC outlet. The device
draws 5.8 Amps at 80°F and 60% RH. Locate the dehumidifier in an area where
the cord’s length (9′) easily reaches a 115 VAC electrical outlet with a
minimum of 15 Amp circuit capacity. If used in an area that may become wet, a
GFCI protected circuit is recommended. Consult local electrical codes for
further information.
Santa Fe offers a variety of control devices for use with the Santa Fe
Ultra120V. The control is to be located remotely from the dehumidifier and
placed in the space to be conditioned. A low voltage (24 Volt) control MUST be
used with the Santa Fe Ultra120V and MUST be connected with low voltage (18-22
gauge) thermostat wire.
THE REMOTE CONTROLS OF THE SANTA FE ULTRA120V ARE POWERED BY A LOW VOLTAGE
CIR-CUIT (24 VAC) AND MUST NEVER CONTACT OR BE CONNECTED TO A HIGH VOLTAGE
CIRCUIT.
DO NOT ALLOW THE 24V TERMINAL TO CONTACT THE COM TERMINAL ON THE SANTA FE
ULTRA120V OR DAMAGE TO THE TRANSFORMER WILL RESULT.
SOME OF THE TERMINALS ON THE SANTA FE ULTRA120V MAY NOT BE USED WITH CERTAIN
CONTROLS AND SHOULD BE LEFT UNCONNECTED.
Electrical Precautions
- Do not install the control where it may not accurately sense the relative humidity such as near HVAC supply registers, near exterior doors, on an outside wall, near a window, or near a water source.
- The terminals on the Santa Fe Ultra120V and the control are labeled to prevent confusion.
- Be sure to consult the electrical schematic in the CONTROLS Section (Page 11) of this manual or inside the access panel of the Santa Fe Ultra120V before making control connections.
DRAIN INSTALLATION
The Santa Fe Ultra120V generates condensate.
Place a secondary drain pan with a float switch under the dehumidifier if it
is suspended above a finished area or above an area where water leakage could
cause damage.
The Santa Fe Ultra120V contains an internal drain trap for proper dehumidifier
operation. Install a 3/4” threaded male NPT adapter to the external condensate
fitting. Install a drain pipe assembly utilizing 3/4” PVC pipe to transport
the condensate to a drain. Pitch of drain should be 1″ per 10′.
An optional condensate pump kit is available for use with the Santa Fe
Ultra120V and may be installed if lift is
required to dispose of condensate. Condensate is automatically pumped to a
remote location when the water level in the pump’s reservoir rises to close
the float switch. The pump also contains a safety float switch. If the pump
fails, this switch opens the common control circuit and stops water production
before the reservoir overflows.
Note: An optional condensate pump kit can be purchased through your
dealer or online. Refer to the kit literature for installation instructions.
DUCTING TO HVAC SYSTEMS
The recommended installation creates a separate return for the Santa Fe
Ultra120V in a central area of the structure. Duct the supply of the unit to
the air supply of the existing HVAC system. Connect an insulated duct from
outside to the 6″ damper of the Santa Fe Ultra120V to provide fresh make-up
air.
DO NOT CONNECT WITH A STATIC PRESSURE GREATER THAN OR EQUAL TO +0.8 WG.
CONTACT TECHNICAL SUPPORT AT
800-533-7533 FOR ADDITIONAL DETAILS.
Ducting Considerations:
-
All flexible ducting connected to the Santa Fe Ultra120V should be UL listed.
-
A short piece of flexible ducting on all Santa Fe Ultra120V duct connections is recommended to reduce noise and vibration transmitted to rigid ductwork in the structure.
-
Use a minimum 8″ diameter round or equivalent rectangular duct for total duct lengths of up to 25′.
Use a minimum 10″ diameter round or equivalent rectangular duct for longer lengths. -
Grills or diffusers on the duct ends must not excessively restrict airflow.
-
Effective dehumidification may require that ducting be branched to isolated, stagnant air flow areas. When ducting to two or three areas, use 8″ or larger diameter branch ducting. When ducting to four or more areas, use 6″ or larger diameter branch ducting. Provisions must be made to provide airflow from supply locations to the central return location. Proper air distribution is important to ensure even humidity control and heat distribution throughout the structure.
-
DO NOT locate the return in a bathroom or a kitchen.
Please visit our website at www.Santa-Fe-Products.com/install- options/ for more installation options.
Recommended HVAC System Installation
Dedicated Santa Fe Return to HVAC Supply
- Install a dedicated return for the Santa Fe Ultra120V from a central area of the structure.
- Install an insulated duct from outside to the 6″ damper of the Santa Fe Ultra120V to provide fresh air ventilation (optional).
- The optional second supply of the Santa Fe Ultra120V may be ducted to another location. This can provide a second source of airflow to the basement or supply of the existing HVAC system with a backdraft damper.
- When using only one of the two supplies on the Santa Fe Ultra120V, the unused supply must be blocked using the duct cover plate included.
- DO NOT locate return in a bathroom or kitchen.
- Control should be located remotely from the dehumidifier and placed in a central location.
FRESH AIR VENTILATION
Fresh air ventilation is optional.
Fresh air may be brought into the structure by connecting an insulated duct
from outside the structure to the 6″ inlet of the Santa Fe Ultra120V. A
ventilation control is needed to program the time and frequency that the unit
introduces outside air. The time and frequency of ventilation should be based
on the size and occupancy of the residence.
- The fresh air ventilation duct should be connected to the 6″ damper on the top of the Santa Fe Ultra120V.
- An insulated 6″ diameter duct can provide up to 100 CFM of outside air.
- If the fresh air ventilation duct is to be used, the return of the Santa Fe Ultra120V must be ducted or an inline fan may be required on the fresh air ventilation line to bring in outside air.
- If a motorized damper is not being used, fresh air is controlled by the manual damper in the 6” collar of the Santa Fe Ultra120V.
- Performance of the Santa Fe Ultra120V can be impacted by inside and outside air conditions.
- When a 6″ motorized damper is used, a digital control is required.
- It may be necessary to use 8″ duct work if additional fresh air is required.
- In cold climates or at times when the dew point is low, ventilation can be used to dehumidify the structure, making the Santa Fe Ultra120V capable of year-round drying.
Fresh Air Ventilation With Dehumidifier Off and Fan Only Operation
Outside air mixes with the dehumidifier’s return air before being supplied
to the home. Outside temperature, inside temperature and relative humidity
will impact the combined outlet air conditions.
Note: Temperature and relative humidity may vary depending on duct
distribution scheme.
Determine Ventilation Requirements
The MINIMUM ventilation requirement is calculated using ASHRAE 62.2-2016. Use
one or both of the options below to determine your ventilation requirement.
Follow all local and national building and safety codes.
Option 1: Calculating Airflow Requirement Using ASHRAE 62.2-2016 Airflow
Equation
ASHRAE Airflow in CFM = [House Area in Sq.Ft. x 0.03] + [(Number of Bedrooms
+1) x 7.5] NOTE: Use ‘Number of Bedrooms + 1’ or ‘Number of Occupants’,
whichever is larger.
-
Example 1: Number of Bedrooms + 1
1800 square foot house with 3 bedrooms, 4 occupants = [1800 X 0.03] + [(3+1) X 7.5] = 84 CFM -
Example 2: Number of Occupants
1800 square foot house with 3 bedrooms, 5 occupants = [1800 X 0.03] + [5 X 7.5] = 91.5 CFM
Record the required CFM ____
Option 2: Calculating Airflow Requirement Using Table 4.1 from ASHRAE
62.2-2016
Ventilation Air Requirements, CFM
Floor Area (ft2) | Number of Bedrooms |
---|---|
1 | 2 |
< 500 | 30 |
501 – 1000 | 45 |
1001 – 1500 | 60 |
1501 – 2000 | 75 |
2001 – 2500 | 90 |
2501 – 3000 | 105 |
3001 – 3500 | 120 |
CONTROLS
A control must be used with the Santa Fe Ultra120V. Santa Fe offers the DEH
3000 proprietary control. The DEH 3000 allows homeowners to monitor and
control relative humidity and proper ventilation levels in their home. This
control is also available with a remote sensing option.
Note: The DEH 3000 is sold separately and can be purchased online or through
your local dealer. Other thermostats are compatible with the Santa Fe
Ultra120V.
Wiring Controls
DO NOT ALLOW THE 24V TERMINAL FROM THE SANTA FE ULTRA120V TO CONTACT THE COM TERMI-NAL ON THE SANTA FE ULTRA120V OR DAMAGE TO THE TRANSFORMER WILL RESULT.
Circuit Breaker
To prevent damage to the 24 volt control transformer, the Santa Fe Ultra120V
comes with a resettable circuit breaker. Check wiring for any electrical short
and repair
before resetting breaker. Resetting the circuit breaker without correcting the
electrical short may result in transformer damage. Be sure to check the
electrical schematic in this manual or inside the access panel of the Santa Fe
Ultra120V be-fore making any control connections. The reset button for the
circuit breaker can be found on the side of the unit.
Control Connections
The control and the Santa Fe Ultra120V are labeled to prevent confusion.
Depending on the control, some of the screw terminals on the Santa Fe
Ultra120V may not be used. Be sure to consult the electrical schematic in this
manual or inside the access panel of the Santa Fe Ultra120V before making
control connections.
A low voltage control must be used with the Santa Fe Ultra120V.
Terminal Block Control Operation:
COM| 24VAC Power Transformer Neutral Side
FAN| Fan Control
24V| Transformer High Side
DEHU| Dehumidification (Fan and Compressor) Control
FLOAT| External low voltage float switch or water sensor (two
terminals). Use normally closed switch.
Between the COM lead and the 24V TERMINAL is a 40VA transformer. This low
voltage power source powers the relay coils which control the fan and
compressors. This 24VAC transformer can also be used to power HVAC accessories
external to the dehumidifier.
Compressor ON / Fan ON| Make contact between 24V and DEHU terminals
Compressor OFF / Fan ON| Make contact between 24V and FAN terminals
Power HVAC Accessory| Connect the accessory to the
COM and 24V terminals
AIR FILTRATION
The Santa Fe Ultra120V is equipped with a MERV-13 (Dimensions: 1.75” x 15.50”
x 19.50”) filter. An optional MERV-14 filter is available at
www.ThermastorFilters.com. The MERV-13 filter should be checked and replaced
every three to six months. If the MERV-14 filter is used, the MERV-13 should
act as a pre-filter and sit on top of the MERV-14 filter. Replacing the
MERV-13 filter every three to six months extends the life of the MERV-14
filter. The MERV-14 filter should be replaced every two to three years if a
MERV-13 is used as a pre-filter and replaced every three to six months.
Operating the unit with a dirty filter will reduce dehumidifier capacity and
efficiency.
DO NOT operate the unit without the recommended filter. Filter non-compliance
voids the product warranty.
MAKE SURE UNIT IS OFF BEFORE CHANGING THE FILTER.
Changing the Filter
For greatest filtration and efficiency of the Santa Fe Ultra120V, it is recom-
mended the air filter be replaced every three to six months with a MERV-13
filter.
- Step 1: The filter access door is located above the front panel of the dehumidifier. Pull straight up on the door latch to disengage from the front panel, then lift door to it’s vertical position.
- Step 2: Remove the used filter(s) from the housing. Insert the new filter by gently pushing it straight into the filter cavity. Make sure the air flow arrows on the filter are pointing down into the unit.
- Step 3: Close the filter access door by pushing up on the door latch, inserting the latch into the front panel, then releasing. Ensure that the latch is firmly engaged
with the front panel.
MERV Rating Chart
Standard 52.5 Minimum Efficiency Reporting Value| Dust Spot
Efficiency| Arrestance| Typical Controlled Contaminant| Typical
Applications and Limitations| Typical Air Filter/Cleaner Type|
---|---|---|---|---|---|---
20| n/a| n/a| < 0.30 pm Particle Size| Cleanrooms| > 99.999% eff. On
.10-.20 pm P articles|
19| n/a|
n/a| Virus (unattached)| Radioactive Materials| P articles|
18| n/a|
n/a| Carbon Dust| Pharmaceutical Man.| Particulates|
17| n/a|
n/a| All Combustion Smoke| Carcinogenetic Materials| >99.97% eff. On .30 pm
Particles|
16
15
| n/a
95%
| n/a n/a| .30-1.0 pm Particle Size All Bacteria| General Surgery Hospital
Inpatient Care| Bag Filter – Nonsupported microfine fiberglass or synthetic
media, 12-36 in. deep, 6-12 pockets. Box Filter – Rigid Style Cartridge
Filters 6 to 12″ deep may use lofted or paper media.|
14| 90-95%| >98%| Most Tobacco Smoke| Smoking Lounges|
13| ****
89-90%
| ****
98%
| ****
Proplet Nuceli (Sneeze)
| Superior Commercial Buildings|
12| 70-75%| >95%| 1.0-3.0 pm Particle Size Legionella| Superior Residential|
Bag Filter – Nonsupported microfine fiberglass or synthetic media, 12-36 in.
deep, 6- 12 pockets.
**** Box Filter – Rigid Style Cartridge Filters 6 to 12″ deep may use lofted or paper media.
|
11| 60-65%| >95%| Humidifier Dust Lead Dust| Better Commercial Buildings|
10
9
| ****
50-55%
40-45%
| ****
95%
90%
| Milled Flour Auto Emissions Welding Fumes| ****
Hospital Laboratories
|
8| 30-35%| >90%| 3.0-10.0 pm Particle Size| Commercial Buildings| Pleated
Filters – Disposable, extended surface area, thick with cotton-polyester blend
media, cardboard frame.
**** Cartridge Filters – Graded density viscous coated cube or pocket filters, synthetic media.
**** Throwaway – Disposable synthetic panel filter.
|
7
| ****
25-30%
| ****
90%
| Mold Spores Hair Spray| ****
Better Residential
|
6
| ****
<20%
| ****
85-90%
| Fabric Protector Dusting Aids| ****
Industrial Workplace
|
5
| ****
<20%
| ****
80-85%
| Cement Dust Pudding Mix| ****
Paint Booth Inlet
|
4
3
2
1
| <20%
<20%
<20%
<20%
| 75-80%
70-75%
65-70%
<65%
| >10.0 pm Particle Size Pollen
Dust Mites Sanding Dust Spray Paint Dust
Textile Fibers Carpet Fibers
| Minimal Filtration Residential
Window A/C Units
| Throwaway – Disposable fiberglass or synthetic panel filter.
**** Washable – Aluminum Mesh.
**** Electrostatic – Self charging woven panel filter.
|
SERVICE
Troubleshooting
TROUBLESHOOTING SHOULD BE PERFORMED BY A QUALIFIED HVAC TECHNICIAN.
| |
---|---|---
Symptom| Possible Reason| Troubleshooting Procedure
Neither fan nor compressor running.
Dehumidification is being called for.
| 1. Dehumidifier unplugged or no power to outlet.
2. Humidity control set too high.
3. Loose connection in internal or control wiring.
| WARNING!
ELECTRICAL SHOCK HAZARD:
ELECTRICAL POWER MUST BE PRESENT TO PERFORM SOME TESTS. THESE TESTS SHOULD BE PERFORMED BY A QUALIFIED SERVICE PERSON.
Troubleshooting Procedure for Control Related Issues
This method of diagnosis will test the 3 main components of the control circuit individually to indicate any potential problems. This is to be used when the control will not activate the main unit.
1. Detach field control wiring connections from the terminals on the main unit.
2. Connect the 24V and FAN terminals together; only the fan should run. Disconnect the terminals.
3. Connect the 24V and DEHU terminals together; fan and compressor should run. Disconnect the terminals.
4. If this test works, the main unit is working correctly from a control standpoint.
5. Reconnect field control wiring to the terminals on the main unit.
6. Remove the control panel cover and detach the field wiring from the control connections.
7. Connect the 24V and FAN terminals together; only the fan should run. Disconnect the terminals.
8. Connect the 24V and DEHU terminals together; fan and compressor should run. Disconnect the terminals.
9. If this test works, then the field control wiring is ok.
10. If the problem persists, then the control is most likely faulty.
| 4. Defective compressor relay.
| 5. Defective control
transformer.
| 6. Missing jumper wire or open circuit between FLOAT terminals.
Compressor is not running.
Dehumidification is being called for. Fan is running.
| 1. Defective compressor run capacitor.
2. Loose connection in compressor circuit.
3. Defective compressor overload.
4. Defective compressor.
5. Defrost thermostat open.
Compressor cycles on and off. Dehumidification is being called for.| 1. Low
ambient temperature and/or humidity causing unit to cycle through defrost
mode.
| 2. Defective compressor overload.
| 3. Defective compressor.
| 4. Defrost thermostat defective.
| 5. Dirty air filter(s) or air flow restricted.
| 6. Defective fan or relay.
| |
---|---|---
Symptom| Possible Reason| Troubleshooting Procedure
Fan is not running. Dehumidification or fan is being called for.| 1. Loose
connection in fan circuit.
2. Obstruction prevents fan impeller rotation.
3. Defective fan.
4. Defective fan relay.
5. Open circuit between FLOAT terminals.
| WARNING!
ELECTRICAL SHOCK HAZARD:
ELECTRICAL POWER MUST BE PRESENT TO PERFORM SOME TESTS. THESE TESTS SHOULD BE PERFORMED BY A QUALIFIED SERVICE PERSON.
Troubleshooting Procedure for Performance Related Issues
This method of diagnosis is used to function check the internal components in the dehumidi- fier. This is to be used when a performance issue is suspected.
1. Set the humidity controller all the way to the most humid setting or off position – Did the unit shut off?
2. If yes, turn the fan setting to the ON position – does the fan start?
3. If fan starts, leave in the fan ON position and set the humidity all the way to driest setting. May have to wait 5 minutes for the compressor to start.
4. Listen for a distinct buzzing/humming sound of a compressor starting up – do you hear this noise?
5. If compressor is running and continues to run, after about 15 minutes you should feel a slight increase in air temperature being discharged out of the discharge air side of the unit.
6. If so, depending on your environmental conditions (temp/Rh%), you should see some water production out of the hose within
30 minutes or so. ( Note: If the room temperature is 55 degrees or below and/or in area of low relative humidity, the dehumidifier will produce little to no water. )
7. Collecting the water removed in a 24 hour period will give a measurement of performance.
Low dehumidification capacity (evaporator is frosted continuously).
Dehumidification is being called for.
| 1. Defrost thermostat loose or defective.
2. Low refrigerant charge.
3. Dirty air filter(s) or air flow restricted.
4. Excessively restrictive ducting connected to unit.
No ventilation. Ventilation is being called for.| 1. Loose connection in ventilation control circuit.
2. Loose connection in damper power circuit.
3. Defective fresh air damper.
Dehumidifier removes some water, but not as much as expected.| 1. Air temperature and/or humidity have dropped.
2. Humidity meter and/or thermometer used are out of calibration.
3. Unit has entered defrost cycle.
4. Dirty air filter(s) or air flow is restricted.
5. Defective defrost thermostat.
6. Low refrigerant charge.
7. Air leak such as loose cover or ducting leaks.
8. Defective compressor.
9. Restrictive ducting.
Refrigerant Charging
SERVICING THE SANTA FE ULTRA120V WITH ITS HIGH PRESSURE REFRIGERANT SYSTEM AND
HIGH VOLTAGE CIRCUITRY PRESENTS A HEALTH HAZARD WHICH COULD RESULT IN DEATH,
SERIOUS BODILY INJURY, AND/OR PROPERTY DAMAGE. SERVICE MUST BE PERFORMED BY A
QUALIFIED SERVICE TECHNICIAN.
If the refrigerant charge is lost due to service or a leak, the leak should be
repaired and a new charge must be accurately weighed in. If any of the old
charge is left in the system, it must be recovered before weighing in the new
charge. Refer to the unit nameplate for the correct charge weight and
refrigerant type.
WARRANTY
Limited Warranty. Therma-Stor, LLC (“Therma-Stor”) warrants as follows: (i)
the Santa Fe Ultra120V dehumidifier (“Product”) will be free of material
defects in workmanship or materials for a period of two (2) year (“Two-Year
Warranty”) following the date of initial purchase of such Product by an
original customer purchasing from ThermaStor or an authorized reseller
(“Customer”); and (ii) the Product’s components will be free of material
defects in workmanship or materials for a period of six (6) years following
the date of initial purchase of such Product by a Customer.
Limitation of Remedies. CUSTOMER’S SOLE AND EXCLUSIVE REMEDY UNDER THE ABOVE
LIMITED WARRANTY AND THERMA- STOR’S ENTIRE LIABILITY THEREUNDER, SHALL BE, AT
THE SOLE OPTION OF THERMA-STOR, REPLACEMENT OR REPAIR OF SUCH PRODUCT OR ITS
COMPONENTS (“COMPONENTS”) BY THERMA-STOR OR THERMA-STOR’S AGENTS ONLY.
REFRIGERANT, PIPING, SUPPLIES, TRANSPORTATION COSTS, LABOR COSTS INCURRED IN
REPAIR OR REPLACEMENT OF SUCH COMPONENTS ARE NOT INCLUDED. THIS DISCLAIMER AND
EXCLUSION SHALL APPLY EVEN IF THE EXPRESS WARRANTY AND LIMITED REMEDY SET
FORTH HEREIN FAILS OF ITS ESSENTIAL PURPOSE. CUSTOMER ACKNOWLEDGES THAT NO
REPRESENTATIVE OF THERMA-STOR OR OF ITS AFFILIATES OR RESELLERS IS AUTHORIZED
TO MAKE ANY REPRESENTATION OR WARRANTY ON BEHALF OF THERMA-STOR OR ANY OF ITS
AFFILIATES OR RESELLERS THAT IS NOT IN THIS AGREEMENT. Notwithstanding the
above, during the term of the Two-Year Warranty only, Therma-Stor will
provide, free of charge to Customer, all Components and labor (except costs
related to removal and installation of Product) required to fulfill its
obligations under such Two-Year Warranty.
Disclaimer of Warranties. EXCEPT FOR ABOVE LIMITED WARRANTY, WHICH IS THE SOLE
AND EXCLUSIVE WARRANTY PROVIDED WITH RESPECT TO THE PRODUCT AND ITS
COMPONENTS, THERMA-STOR HEREBY DISCLAIMS
ALL EXPRESS AND IMPLIED WARRANTIES, INCLUDING, WITHOUT LIMITATION, THE IMPLIED
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
Warranty Limitations. The foregoing limited warranty extends only to a
Customer and shall be null and void upon attempted assignment or transfer. A
“defect” under the terms of the limited warranty shall not include problems
resulting from Customer’s or Customer’s employees’, agents’, invitees’ or a
third party’s misuse, improper installation, improper design of any system
in which the Product is included, abuse, lack of normal care, failure to
follow written instructions, tampering, improper repair, or freezing,
corrosion, acts of nature or other causes not arising out of defects in
Therma-Stor’s workmanship or material. If a Product or Component is replaced
while under warranty, the applicable limited warranty period shall not be
extended beyond the original warranty time period. The limited warranty does
not cover any costs related to changes to a Product or Component that may be
required by any codes, laws, or regulations that may become effective after
initial purchase of the Product by Customer.
Customer Responsibilities. As a further condition to obtaining warranty
coverage hereunder, the Customer must send a valid warranty claim to Therma-
Stor such that Therma-Stor receives such claim prior to the end of the
applicable warranty period. ThermaStor shall have no obligation hereunder with
respect to any claim received by Therma-Stor after the expiration of the
applicable warranty period. As a further condition to obtaining warranty
coverage hereunder, the Customer must present forms of invoices evidencing
proof of purchase of a Product. If such invoices do not clearly indicate the
date of initial purchase by
a Customer, the applicable Product’s date of manufacture will be used instead
of the date of initial purchase for the purpose of calculating the
commencement of the applicable warranty period. Warranty service must be
performed by ThermaStor or
a servicer authorized by ThermaStor. In order to obtain warranty service, the
Customer should call Therma-Stor at
1-800-533-7533 and ask for the Therma-
Stor Products Service Department, which will then arrange for applicable
warranty service. Warranty service will be performed during customary, daytime
working hours. If the Product must be shipped for service, Customer shall be
solely responsible for properly packaging the Product, for all freight
charges, and for all risk of loss associated with shipment.
Limitation of Liability. IN NO EVENT SHALL THERMA-STOR, IN CONNECTION WITH THE
DESIGN, SALE, INSTALLATION, USE, REPAIR, REPLACEMENT OR PERFORMANCE OF ANY
PRODUCT, COMPONENT, PART THEREOF OR WRITTEN MATERIAL PROVIDED THEREWITH, BE
LIABLE, TO THE EXTENT ALLOWED UNDER APPLICABLE LAW, UNDER ANY LEGAL THEORY FOR
ANY SPECIAL, DIRECT, INDIRECT, COLLATERAL OR CONSEQUENTIAL DAMAGES OF ANY
KIND. NOTWITHSTANDING THE ABOVE LIMITATIONS AND WARRANTIES, THE SOLE AND
EXCLUSIVE LIABILITY OF THERMA-STOR, REGARDLESS OF THE NATURE OR THEORY OF THE
CLAIM, SHALL UNDER NO CIRCUMSTANCES EXCEED THE PURCHASE PRICE OF THE PRODUCT,
COMPONENT OR PART UPON WHICH THE CLAIM IS PREMISED.
Applicable Law and Venue. ANY ARBITRATION, ENFORCEMENT OF AN ARBITRATION OR
LITIGATION RELATED TO THE PRODUCT WILL BE BROUGHT EXCLUSIVELY IN DANE COUNTY,
WISCONSIN, AND CUSTOMER CONSENTS TO THE JURISDICTION OF THE FEDERAL AND STATE
COURTS LOCATED THEREIN, SUBMITS TO THE JURISDICTION THEREOF AND WAIVES THE
RIGHT TO CHANGE VENUE. CUSTOMER FURTHER CONSENTS TO THE EXERCISE OF PERSONAL
JURISDICTION BY ANY SUCH COURT WITH RESPECT TO ANY SUCH PROCEEDING.
Miscellaneous. If any term or condition of this Limited Warranty is found by a
court of competent jurisdiction to be invalid, illegal or otherwise
unenforceable, the same shall not affect the other terms or conditions hereof
or thereof or the whole of this Limited Warranty. Any delay or failure by
Therma-Stor to exercise any right or remedy will not constitute a waiver of
Therma- Stor to thereafter enforce such rights.