NordCap SDH 40 L Ice Cube Maker Instruction Manual
- June 4, 2024
- NordCap
Table of Contents
SDH 40 L Ice Cube Maker
Instruction Manual
GENERAL INFORMATION AND INSTALLATION
A. INTRODUCTION
This manual provides the specifications and the step-by-step procedures for
the installation, startup, operation, maintenance, and cleaning of the SIMAG
SDH Series Icemakers. The SIMAG SDH cubers are quality designed, engineered,
and manufactured.
Their ice-making systems are thoroughly tested providing the utmost
flexibility to fit the needs of a particular user.
NOTE. To retain the safety and performance built into this icemaker, it
is important that installation and maintenance be conducted in the manner
outlined in this manual.
B. UNPACKING AND INSPECTION
-
Call your authorized SIMAG Distributor or Dealer for proper installation.
-
Visually inspect the exterior of the packing and skid. Any severe damage noted should be reported to the delivering carrier and a concealed damage claim form filled in subjet to an inspection of the contents with the carrier’s representative present.
-
a) Cut and remove the plastic strip securing the carton box to the skid.
b) Remove the packing nails securing the carton box to the skid.
c) Cut open the top of the carton and remove the polystyrene protection sheet.
d) Pull out the polystyrene posts from the corners and then remove the carton. -
Remove the front and rear panels of the unit and inspect for any concealed damage.
Notify the carrier of your claim for the concealed damage as stated in step 2 above. -
Remove all internal support packing and masking tape.
-
Check that refrigerant lines do not rub against or touch other lines or surfaces, and that the fan blades move freely.
-
Check that the compressor fits snugly onto all its mounting pads.
-
See the data plate on the rear side of the unit and check that the local main voltage corresponds with the voltage specified on it.
CAUTION. The incorrect voltage supplied to the icemaker will void your parts replacement program. -
Remove the manufacturer’s registration card from the inside of the User Manual and filling all parts including the Model and Serial Number is taken from the data plate.
Forward the completed self-addressed registration card to the SIMAG factory.
C. LOCATION AND LEVELLING
WARNING. This Ice Maker is designed for indoor installation only. Extended
periods of operation at temperatures exceeding the following limitations will
constitute misuse under the terms of the SIMAG Manufacturer’s Limited Warranty
resulting in a LOSS of warranty coverage.
-
Position the machine bin in the selected permanent location and tighten the four legs.
Criteria for selection of location include:
a) Minimum room temperature 10 °C (50°F)
and maximum room temperature is 40°C (100°F).
b) Water inlet temperatures: minimum 5°C (40°F) and maximum 40°C (100°F).
c) Well-ventilated location for air-cooled models (clean the air-cooled condenser at frequent intervals).
d) Service access: adequate space must be left for all service connections through the rear of the ice maker. A minimum clearance of 15 cm
(6″) must be left at the sides of the unit for routing cooling air drawn into and exhausted out of the compartment to maintain the proper condensing operation of air-cooled models.
NOTE. With the unit in “built-in” conditions, the ice production is gradually reduced with respect to the levels shown in the graph, up to a maximum of 10% at room temperatures higher than 32°C.
The daily ice-making capacity is directly related to the condenser air inlet temperature, water temperature, and age of the machine.
To keep your SIMAG CUBER at peak performance levels, periodic maintenance checks must be carried out as indicated in this manual. -
Level the Icemaker in both the left-to-right and front-to-rear directions by means of the adjustable legs.
D. ELECTRICAL CONNECTIONS
See the data plate for current requirements to determine the wire size to be
used for electrical connections. All SIMAG icemakers require a solid earth
wire.
All SIMAG ice machines are supplied from the factory completely pre-wired and
require only electrical power connections to the wire cord provided at the
rear of the unit.
Make sure that the ice machine is connected to its own circuit and
individually fused (see data plate for fuse size).
The maximum allowable voltage variation should not exceed -10% and +10% of the
data plate rating. Low voltage can cause faulty functioning and may be
responsible for serious damage to the overload switch and motor windings.
NOTE. All external wiring should conform to national, state, and local
standards and regulations.
Check the voltage on the line and the ice maker’s data plate before connecting
the unit.
E. WATER SUPPLY AND DRAIN CONNECTIONS
GENERAL
When choosing the water supply for the cuber consideration should be given to:
a) Length of run
b) Water clarity and purity
c) Adequate water supply pressure
Since water is the most important single ingredient in producing ice you
cannot emphasize too much the three items listed above.
Low water pressure, below 1 bar may cause malfunction of the ice maker unit.
Water containing excessive minerals will tend to produce cloudy-colored ice
cubes, plus scale build-up on the interior parts of the water system.
WATER SUPPLY
Connect the 3/4″ GAS male of the water inlet fitting, using the food-grade
flexible tubing supplied with the machine, to the cold water supply line with
regular plumbing fitting and a shut-off valve installed in an accessible
position between the water supply line and the unit.
If the water contains a high level of impurities, it is advisable to consider
the installation of an appropriate water filter or conditioner.
WATER DRAIN
Connect the drain fitting with a plastic tube to an open trapped and vented
drain. When the drain is a long run, allow 3 cm pitch per meter (1/4″ pitch
per foot).
On water-cooled versions, the water drain line from the condenser is
internally connected to the drain fitting of the unit.
It is strongly recommended therefore to install a vertical open vent on the
unit drain line high point to ensure good draining and to direct the drain
line to a trapped and vented floor drain receptacle.
NOTE. The water supply and the water drain must be installed to conform
with the local code. In some cases, a licensed plumber and/or a plumbing
permit is required.
F. FINAL CHECKLIST
- Is the unit in a room where ambient temperatures are within a minimum of 10 °C (50°F) even in winter months?
- Is there at least a 15 cm (6″) clearance around the unit for proper air circulation?
- Is the unit level? (IMPORTANT)
- Have all the electrical and plumbing connections been made, and is the water supply shut-off valve open?
- Has the voltage been tested and checked against the data plate rating?
- Has the water supply pressure been checked to ensure a water pressure of at least 1 bar (14 psi)? Open the shut-off valve and verify the absence of water losses from the connections.
- Have the bolts held the compressor down been checked to ensure that the compressor is snugly fitted onto the mounting pads?
- Check all refrigerant lines and conduit lines to guard against vibrations and possible failure.
- Have the bin liner and cabinet been wiped clean?
- Has the owner/user been given the User Manual and been instructed on the importance of periodic maintenance checks?
- Has the Manufacturer’s registration card been filled in properly? Check for the correct model and serial number against the serial plate and mail the registration card to the factory.
- Has the owner been given the name and phone number of the authorized SIMAG Service Agency serving him?
G. INSTALLATION PRACTICE
1. Hand shut-off valve | 6. Open trapped vented drain |
---|---|
2. Water filter | 7. Drain fitting |
3. Water supply line (flexible hose) | 8. Main switch |
4. 3/4″ GAS male fitting | 9. Power line |
5. Vented drain |
WARNING. This icemaker is not designed for outdoor installation and will
not function in ambient temperatures below 10°C (50°F) or above 40°C (100°F).
This icemaker will malfunction with water temperatures below 5 °C (40°F) or
above 40 °C (100°F).
OPERATING INSTRUCTIONS
STARTUP
After having correctly installed the ice maker and completed the plumbing and
electrical connections, perform the following “Start-up” procedure.
A. Put the icemaker in operation by moving the unit master switch ON position.
NOTE. The ice maker control is factory set with the timer in
defrost/harvest cycle.
The unit starts operating in the “defrost cycle” with the following components
being activated:
THE WATER INLET SOLENOID VALVE
THE HOT GAS SOLENOID VALVE
THE FAN MOTOR
THE COMPRESSOR
THE TIMER
B. During the water filling operation, check to see that the incoming
water dribblers, through the evaporator platen dribbler holes, down into the
sump reservoir to fill it up and also that the incoming surplus of water flows
out through the overflow pipe into the drain line.
NOTE. If, in the defrost cycle length, the machine sump reservoir does
not get filled with water up to the rim of the overflow pipe, remove the front
panel and rotate the shaft of the timer so to cause the dropping of the two
microswitches actuators into the beginning of the cam slot and check for:
- The water pressure of the water supply line, it must be at least 1 bar (14 psig) Minimum (Max 5 bar-70 psig).
- The filtering device installed in the water line may reduce the water pressure below the Minimum value of 1 bar (14 psig).
- Any clogging situation in the water circuit like the inlet water strainer and/or the flow control.
OPERATIONAL CHECKS
C. At the completion of the water filling phase the unit initiate
automatically the first freezing cycle with the start up of (Fig.1):
COMPRESSOR
WATER PUMP
FAN MOTOR
D. Check to see through the ice discharge opening that the spray system is
correctly seated and that the water jets uniformely reach the interior of the
inverted mold cups or the exterior of the evaporator tips; also make sure that
the plastic curtain is hanging freely and there is not excessive water
spilling through it.
E. The ice-making process takes place thereby, with the water sprayed into the
molds or onto the tips that gets gradually refrigerated by the heat exchange
with the refrigerant flowing into the evaporator serpentine.
During the first portion of the freezing cycle, the timer assy is standing.
F. Then, as the cube size control cut-in point is reached by the evaporator
temperature the control of the cycle is passed to the timer.
The components in operation during this 2nd phase of the cycle are:
COMPRESSOR
CONTACTOR COIL (SDN85-145-215)
WATER PUMP
FAN MOTOR
TIMER
G. After about 18 ÷20 minutes from the beginning of the freezing cycle, in an
hypothetic ambient temperature of 21°C, the defrost cycle takes place with the
hot gas and the water inlet valves being simultaneously activated.
The electrical components in operation are:
COMPRESSOR
CONTACTOR COIL (SDN85-145-215)
WATER INLET SOLENOID VALVE
HOT GAS VALVE
TIMER
FAN MOTOR
H. Check, during the defrost cycle, that the incoming water flows correctly
into the sump reservoir in order to refill it and that the surplus overflows
through the overflow drain tube.
I. Check the texture of ice cubes just released.
They have to be of the right size with a thickness of about 7÷8 mm.
If the ice cubes do have not the correct size, wait for a second harvest
before attempting any adjustment by setting the cube size control.
By rotating the control setting screw clockwise the ice cube thickness can be
increased; on the contrary, the thickness can be reduced by turning the
setting screw counterclockwise.
If the ice cubes are shallow and cloudy, it is possible that the ice maker
runs short of water during the freezing cycle second phase or, the quality of
the supplied water requires the use of an appropriate water filter or
conditioner.
J. With the ice maker in the harvest cycle, hold ice against the bin
thermostat control bulb to test its shut-off. This should cause the ice maker
to shut OFF after 30 seconds, 1 minute at the most, namely when the control
bulb temperature drops to reach +1°C.
By rotating the control setting screw clockwise the ice cube thickness can be
increased; on the contrary, the thickness can be reduced by turning the
setting screw counterclockwise.
If the ice cubes are shallow and cloudy, it is possible that the ice maker
runs short of water during the freezing cycle second phase or, the quality of
the supplied water requires the use of an appropriate water filter or
conditioner.
J. With the ice maker in the harvest cycle, hold ice against the bin
thermostat control bulb to test its shut-off. This should cause the ice maker
to shut OFF after 30 seconds, 1 minute at the most, namely when the control
bulb temperature drops to reach +1°C.
NOTE. In case this test is performed during the freezing cycle, the unit
will shut OFF only at the end of the freezing cycle.
Within minutes after the ice is removed from the sensing bulb, the bulb will
warm up to reach + 4°C and consequently will cause the icemaker to restart
from the harvest (defrost) cycle.
K. Instruct the owner/user on the general operation of the ice machine and
about the cleaning and care it requires.
PRINCIPLE OF OPERATION
In the SIMAG cube ice makers the water used to make the ice is kept constantly
in circulation by an electric water pump which primes it to the spray system
nozzles from where it is diverted into the molds of the evaporator.
A small quantity of the sprayed water freezes into ice; the rest of it
cascades by gravity into the sump assembly below for recirculation.
FREEZING CYCLE
The hot gas refrigerant discharged out from the compressor reaches the
condenser where, being cooled down, condenses into liquid. Flowing into the
liquid line it passes through the drier filter, then it goes all the way
through the capillary tube where, due to the heat exchanging action, it looses
some of its heat content so that its pressure and temperature are lowered as
well.
Next, the refrigerant enters into the evaporator serpentine (which has a
larger I.D. then the capillary) and starts to boil off; this reaction is
emphasized by the heat transferred by the sprayed water.
The refrigerant then increases in volume and changes entirely into vapor.
The vapor refrigerant then passes through the suction accumulator (used to
prevent that any small amount of liquid refrigerant may reach the compressor)
and through the suction line. In both the accumulator and the suction line it
exchanges heat with the refrigerant flowing into the capillary tube (warmer),
before to be sucked in the compressor and to be recirculated as hot compressed
refrigerant gas.
The freezing cycle is controlled by the evaporator thermostat (which has its
bulb in contact with the evaporator serpentine) which determines the length of
its first portion of the cycle.
When the temperature of the evaporator thermostat bulb drops to a pre-set
value, the evaporator thermostat changes its contacts (from 3-4 to 3-2)
supplying power to the finishing timer that takes the control of the second
timed portion of the freezing cycle up to its completion.
The length of this second timed portion of the freezing cycle is pre-fixed and
related to the setting of the upper part of the timer cam.
The electrical components in operation during the freezing cycle are:
COMPRESSOR
FAN MOTOR
WATER PUMP
and during the second phase of the freezing cycle (Time mode) they are joined
by the
TIMER
On the SDH 64 the refrigerant head pressure, in the course of the freezing
cycle, ranges between 11 ÷14,5 bars being controlled by the hi-pressure
control controlled by the hi-pressure control.
NOTE. In case of shortage/insufficient cooling water or air condenser
dirty, the operation of the safety device by hand reset will stop the machine
as soon as the temperature reaches 70/75 °C (160/170 °F) or the corresponding
pressure. After eliminating the cause of the stop put the machine in operation
by pushing the reset button of the safety thermostat or pressure switch across
the holes in the down/right side of the front panel or removing it.
SDE220 with the cubes fully formed in the cup molds.
The total length of the freezing cycle ranges from 18 to 20 minutes.
DEFROST OR HARVEST CYCLE
As the electric timer has carried the system throughout the second phase of
the freezing cycle, the defrost cycle starts.
NOTE. The length of the defrost cycle is predetermined by the setting of
the timer.
In case it is possible to modify the defrost cycle length through its set
screw.
ATTENTION. The defrost period is the most critical for the icemaker’s
main components expecially the compressor.
To avoid to abuse of them it is strongly recommended to limit the harvest
cycle extension to 3 minutes at the most.
The electrical components in operation during this phase are: COMPRESSOR
FAN MOTOR
WATER INLET SOLENOID VALVE
HOT GAS SOLENOID VALVE
TIMER
The incoming water, passing through the water inlet valve and in its
incorporated flow control (outlet), runs over the evaporator platen and then
flows by gravity through the dribbler holes down into the sump/reservoir.
The water filling the sump/reservoir forces part of the left-over water from
the previous batch to run out to the waste through the overflow pipe. This
overflow limits the level of the sump water which will be used to produce the
next batch of ice cubes.
Meanwhile, the refrigerant as hot gas, discharged from the compressor, flows
through the hot gas valve directly into the evaporator serpentine bypassing
the condenser.
The hot gas circulating into the serpentine of the evaporator warms up the
copper molds or the tips causing the defrost of the ice cubes. The ice cubes,
released from the molds, drop by gravity onto a slanted grid chute, then
through a curtained opening, they fall into the storage bin.
At the end of the defrost cycle, both the hot gas and the water inlet valves
close and the machine starts again a new freezing cycle.
OPERATION – CONTROL SEQUENCE At the start of the freezing cycle, the
evaporator the thermostat controls the length of the first part of the
freezing cycle. As its bulb senses a predetermined temperature, it closes its
contacts to supply power to the timer motor which, in turn, takes over the
control of the freezing cycle. This second part of the cycle has a pre-fixed
time duration of 12 minutes.
NOTE. The wiring diagram shows the unit as it is in the Evaporator Thermostat mode of the Freezing Cycle.
BEGINNING FREEZE
Electrical components (Loads) ……. | ON | OFF |
---|---|---|
Compressor…………………………………. | • | |
Fan motor ……………………………………. | • | |
Hot gas valve ………………………………. | • | |
Water inlet valve…………………………… | • | |
Water pump…………………………………. | • | |
Contactor coil ………………………………. | ||
Timer motor ……………………….. | • | |
Electric Controls ………………………… | ON | OFF |
--- | --- | --- |
Contacts 3-4 evaporator thermostats.. | • | |
Contacts 3-2 evaporator thermostats.. | • | |
Bin thermostat ……………………………… | • |
TIMED FREEZE
Electrical components (Loads) ……. | ON | OFF |
---|---|---|
Compressor…………………………………. | • | |
Fan motor ……………………………………. | • | |
Hot gas valve ………………………………. | • | |
Water inlet valve…………………………… | • | |
Water pump…………………………………. | • | |
Contactor coil ………………………………. | ||
Timer ……………………….. | • | |
Electric Controls ………………………… | ON | OFF |
--- | --- | --- |
Contacts 3-4 evaporator thermostats.. | • | |
Contacts 3-2 evaporator thermostats.. | • | |
Bin thermostat ……………………………… | • |
I° PORTION HARVEST CYCLE
Electrical components (Loads) ……. | ON | OFF |
---|---|---|
Compressor…………………………………. | • | |
Fan motor ……………………………………. | • | |
Hot gas valve ………………………………. | • | |
Water inlet valve…………………………… | • | |
Water pump…………………………………. | • | |
Contactor coil ………………………………. | ||
Timer ……………………….. | • | |
Electric Controls ………………………… | ON | OFF |
--- | --- | --- |
Contacts 3-4 evaporator thermostats.. | • | |
Contacts 3-2 evaporator thermostats.. | • | |
Bin thermostat ……………………………… | • |
II° PORTION HARVEST CYCLE
Electrical components (Loads) ……. | ON | OFF |
---|---|---|
Compressor…………………………………. | • | |
Fan motor ……………………………………. | • | |
Hot gas valve ………………………………. | • | |
Water inlet valve…………………………… | • | |
Water pump…………………………………. | • | |
Contactor coil ………………………………. | ||
Timer ……………………….. | • | |
Electric Controls ………………………… | ON | OFF |
--- | --- | --- |
Contacts 3-4 evaporator thermostats.. | • | |
Contacts 3-2 evaporator thermostats.. | • | |
Bin thermostat ……………………………… | • |
OPERATING CHARACTERISTICS
On air-cooled models during the freezing cycle the discharge pressure is kept
between 10,5/12,5 bars SH 18/24/30/40/50 and 11 ÷ 14,5 bars SDH 64.
At the same time, the suction pressure will gradually decline, reaching its
lowest point just before harvest. Compressor amps experience a similar drop.
A. EVAPORATOR THERMOSTAT
The evaporator thermostat with its sensing bulb intimately in contact with the
refrigerant outlet tube from the evaporator senses the evaporating refrigerant
temperature (which declines in the course of the freezing cycle) and when this
one reaches the pre-set value, it switches its contacts from 3-4 to 3-2 to
activate the finishing cycle (2nd phase) which has a pre-set determined by
the electronic timer.
B. BIN THERMOSTAT
The bin thermostat, which has its sensing bulb down into the storage bin,
shuts-OFF automatically the icemaker when the ice storage bin is filled and
ice contacts its bulb. Factory settings are 1°C (35°F) OUT and 4°C (39°F) IN.
After ice is removed from the bin and its bulb warm-up it allows the unit to
restart from the beginning of the harvest cycle which, in the circumstance, is
more likely a water-filling cycle.
C. TIMER
Equipped with two DIP switches and a Potentiometer. it is located inside the
control box.
The function of the timer begins when activated by the cube size control
(evap. thermostat). The large diameter lobe of its cam determines
A potentiometer was used to adjust the defrost time from 60″ min to 180″ max.
WARNING. Never set the defrost time for longer than 3 minutes as this
will jeopardize the compressor motor windings.
It goes without saying that an extension of the defrost period will directly
reduce the timed portion of the freezing cycle and vice-versa.
Consequently, any variation made at the timer requires a compensation
adjustment, very fine and very accurate, of the evaporator thermostat.
D. COMPRESSOR DIP SWITCH
The compressor DIP switch is located on the Timer of the control box and it
can be switched in two different positions which are:
Operation Supply power directly to the compressor motor.
Cleaning Shuts-off the compressor so that only the water pump and the water
inlet valve will remain in operation.
When positioned on “0 – of” the water pump primes the cleaning or the
bactericide solution all over the unit water system to generate a good
cleaning and sanitizing action of the ice maker.
NOTE. It is recommended to avoid rinsing, after the sanitation of the
unit water system, as any bactericide coating, which is beneficial to limit
the bacteria growth, left-over in the system may be removed.
E. HI PRESSURE CONTROL
Used o maintain the head pressure within the preset values of 10,5 ÷12,5 bars
SDH 18/24 SDH 30/40/50, and 11 ÷14,5 bars SDH 64, by intermittently activating
the fan
motor.
G. SAFETY THERMOSTAT/PRESSURE SWITCH (BY HAND RESET)
Fastened directly onto the refrigerant liquid line and electrically connected
upstream all other controls, this safety device shut-off the icemakers when
senses that the temperature at the liquid line has risen to the limit of 75 °C
(170°F) or corresponding pressure.
H. WATER SPRAY SYSTEM
It consists of one spray bar with several spray nozzles on its extension.
The water pumped is sprayed through its nozzles in each individual mold or
onto each evaporator tip to be frozen into ice.
I. WATER PUMP
The water pump operates continually throughout the freezing cycle.
The pump primes the water from the sump to the spray system and through the
spray nozzles sprays it to the copper molds or onto the evaporator tips to be
frozen into crystal clear ice cubes. It is recommended that the pump motor
bearings be checked at least every six months.
J. WATER INLET SOLENOID VALVE 3/4 MALE FITTING
The water inlet solenoid valve is activated by the timer microswitch only
during the defrost cycle. When energized it allows a metered amount of
incoming water to flow over the evaporator cavity to assist the hot gas in
defrosting the ice cubes. The water running over the evaporator cavity drops
by gravity, through the dribbler holes of the platen, into the sump reservoir
where it will be sucked by the water pump and primed to the spray system.
K. HOT GAS SOLENOID VALVE
The hot gas solenoid valve consists basically in two parts: the valve body and
the valve coil.
Located on the hot gas line, this valve is energized through the electronic
timer during the defrost cycle.
During the defrost cycle the hot gas valve coil is activated so to attract the
hot gas valve piston in order to give way to the hot gas discharged from the
compressor to flow directly into the evaporator serpentine to defrost the
formed ice cubes.
L. FAN MOTOR
The fan motor, in the SDH 64 model is electrically connected in series with
the pressure control and operates during the freezing cycle to draw cooling
air through the condenser fins so to keep the condensing pressure between the
two preset values 11÷14,5 bars.
In the other models, the fan motor works continuously in order to maintain the
condensing pressure between 10,5 ÷ 12,5 bars
O. COMPRESSOR
The hermetic compressor is the heart of the refrigerant system and it is used
to circulate and retrieve the refrigerant throughout the entire system. It
compresses the low-pressure refrigerant vapor causing its temperature to rise
and become high-pressure hot vapor which is then released through the
discharge valve.
SERVICE DIAGNOSIS
SYMPTOM | POSSIBLE CAUSE | SUGGESTED CORRECTION |
---|---|---|
Unit will not run | Main switch in OFF position |
Safety device intervention (thermostat – pressure switch)
Loose electrical connections Inoperative bin thermostat| Turn the switch to
the ON position
Eliminate the stop motivation and push the reset button or replace it.
Check to wire Replace thermostat
Compressor cycles intermittently| Low voltage
Contactor with burnt contacts Non-condensable gas in system
Compressor starting device with loose wires
To high room temperature| Check the circuit for overloading Check voltage at
the supply to the building. If low, contact the power company
Clean or replace Purge the system
Check for loose wires in starting device
Move the unit in a more suitable place
Cubes too small| Freezing cycle too short
Capillary tube partially restricted
Moisture in the system Shortage of water
Shortage of refrigerant Inoperative evaporator thermostat| Review setting of
DIP SWITCH keys
Blow charge, add new gas & drier, after evacuating the system with a vacuum
pump Same as above
See remedies for the shortage of water Check for leaks & recharge Replace
thermostat
Cloudy cubes| Shortage of water
Dirty water supply
Accumulated impurities cleaner Water pump losing discs. pressure| See remedies
for the shortage of water Use a water softener or water filter
Use Cleaner Ice Machine Check bearings. Replace.
Shortage of water| Water spilling out through curtain Water solenoid valve not
opening Water leak in the sump area
Water flow control plugged| Check or replace curtain Replace valve
Locate and repair
Remove and clean
SYMPTOM| POSSIBLE CAUSE| SUGGESTED CORRECTION
---|---|---
Irregular cubes size & some cloudy| Some jets plugged Shortage of the water
Unit not level| Remove jet cover and clean See shortage of water
Level as required
Cubes too large| Freezing cycle too long Inoperative evaporator thermostat|
Adjust evap. thermostat Replace thermostat
Decreased ice capacity| Inefficient compressor
Leaky water valve
Non-condensable gas in system
Poor air circulation or excessive hot location
Overcharge of refrigerant
Capillary tube partially restricted
Hot gas solenoid valve leaking Undercharge of refrigerant Discharge head
pressure too high| Replace
Repair or replace
Purge the system
Relocate the unit or provide for more ventilation
Correct the charge. Purge off slowly
Blow charge, add new gas & drier, after evacuating system with vacuum pump
Replace valve
Charge to data plate indication See incorrect discharge pressure
Poor harvest| Restriction in the incoming water line
Water inlet valve not opening
Hot gas valve orifice restricted Discharge head pressure too low| Check water
valve strainer and flow control. If necessary enlarge the flow control orifice
Valve coil with open winding Replace valve
Replace hot gas valve assy
See incorrect discharge pressure
Incorrect discharge pressure| Inoperative fan pressure control Inoperative fan
motor
Water regulating valve misadjusted| Replace pressostat Replace
Adjust its setting stem
Excessive water in unit base| Water tubing leaking| Check. Tighten or replace
MAINTENANCE AND CLEANING INSTRUCTIONS
A. GENERAL
The periods and the procedures for maintenance and cleaning are given as
guides and are not to be construed as absolute or invariable.
Cleaning, especially, will vary depending upon local water and ambient
conditions and the ice volume produced; and, each icemaker must be maintained
individually, in accordance with its particular location requirements.
B. ICEMAKER
The following maintenance should be scheduled at least two times per year on
these icemakers, by using the SIMAG technical service.
-
Check and clean the water line strainer.
-
Check that the icemaker is leveled in side to side and in front to rear directions.
-
Clean the water system, evaporator, bin, and spray jets using a solution of Ice Machine Cleaner.
Refer to procedure C cleaning instructions and after cleaning will indicate the frequency and procedure to be followed in local areas.
NOTE. Cleaning requirements vary according to the local water conditions and individual user operation. Continuous checks of the clarity of ice cubes and visual inspection of the water spraying parts before and after cleaning will indicate the frequency and procedure to be followed in local areas. -
With the ice machine and fan motor OFF on air-cooled models, clean the condenser using a vacuum cleaner, whisk broom, or nonmetallic brush taking care to do not to damage both the condenser and ambient temperature sensors.
-
Check for water leaks and tighten drain line connections. Pour water down the bin drain line to be sure that the drain line is open and clear.
-
Check the size, condition, and texture of ice cubes. Perform adjustment of the evaporator thermostat or cube size control by turning its adjusting screw clockwise for a thicker ice cube and counterclockwise for a thinner one.
-
Check the bin thermostat to test shut-off.
Put a handful of ice cubes in contact with its bulb.
This should cause the ice maker to shut off within 20÷30″, but only at the end of the freezing cycle!
NOTE. Perform the above check only at the beginning of the harvest cycle as during the freezing cycle the bin thermostat contacts are bypassed by the front microswitch of the timer.
When removing the ice cubes from its sensing bulb the unit will restart after a few seconds from the defrost cycle assuring the filling up of the water tank.
NOTE. It is possible to adjust the setting temperature of the bin thermostat by slightly turning its adjusting screw. -
Check for refrigerant leaks.
C. CLEAN – REPLACE OF AIR CONDENSER FILTER
-
Withdraw the air filter from the front through the opening of the front panel.
-
Blow pressurized air on the opposite direction of the condenser air flow so to remove the dust accumulated.
-
If pressurized air is not available, use tap water always in the counter flow air direction.
Once cleaned shake it so as to remove most of the accumulated water, then dry it using a hair dryer.
NOTE. In case the air filter strainer is damaged replace it with a new one. -
Install it again by pushing it through the front panel opening.
D. CLEANING INSTRUCTIONS OF WATER SYSTEM
-
Remove the front and the top panels to gain access either to the control box and to the evaporator.
-
Wait till the end of defrost cycle then, shut the unit OFF by means of its master switch.
-
Scoop out all the ice cubes stored into the bin in order to prevent them from being contaminated with the cleaning solution then flush out the water from the sump reservoir by removing the overflow stand-pipe.
-
Remove the plastic cup located on the bottom of sump/freezing chamber to drain out all water and scale deposits.
-
Prepare the cleaning solution by diluting in a plastic container two or three liters of warm water (45°÷50°C) with a 0,2 ÷0,3 liters of Ice Machine Cleaner PIN 00100901.
WARNING. The Ice Machine Cleaner contains Phosphoric and Hydroxyacetic acids. These compounds are corrosive and may cause burns if swallowed, DO
NOT induce vomiting. Give large amounts of water or milk. Call Physician immediately. In case of external contact flush with water. KEEP OUT OF THE
REACH OF CHILDREN -
Remove the evaporator cover then slowly pour onto the evaporator platen the cleaning solution. With the help of a brush dissolve the most resistant and remote scale deposits in the platen.
-
Set the compressor switch on “0 – OFF” position and give power to the unit by the master switch (Fig.6).
NOTE. With the system in CLEANING mode the water pump is the only component in operation to circulate the cleaning solution in the entire water system. -
Let the unit to remain in the CLEANING mode for about 20 minutes then switch OFF the machine.
-
Flush out the cleaning solution from the sump reservoir then pour into the evaporator cavity one or two liters of clean potable water with the antibacterial solution P/N 26400002 to rinse and sanitize the molds and the spray system.
If necessary remove the spary bar and nozzles to clean them separately then refit them. -
Set back the master switch to ON. The water pump is again in operation to circulate the water and the antibacterial solution in order to rinse the entire water system.
Switch OFF the unit after approx. 10 minutes and flush out the rinsing water from the sump reservoir.
11. To rotate the timer so that the microswitches reach the beginning of the defrost cycle (low part of the cam) give power to the unit by the master switch.
By doing so are energized the water pump and the water inlet valve. In this way the incoming water flows away to fill up the water tank. -
When the water tank is filled up (water flowing out from the drain) put the compressor switch on the I ON position to restart the machine in the automatic mode.
-
Re-fit the evaporator cover and the unit service panels.
-
At the completion of the freezing and harvest cycle make sure of the proper texture and clearness of the ice cubes and that, they do not have any acid taste.
ATTENTION. In case the ice cubes are cloudy, white and have an acid taste, melt them immediately by pouring on them some warm water.
This to prevent somebody from using them. -
Wipe clean and rinse the inner surfaces of the storage bin.
REMEMBER. To prevent the accumulation of undesirable bacteria it is necessary to sanitize the interior of the storage bin with an anti-algae disinfectant solution every week.
Finanzen/Service
28307 Bremen
Thalenhorststraße 15
Tel.+49 421 48557-0
Fax+49 421 488650
bremen@nordcap.de
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>