POLAR CK640 G Series Countertop Blast Chiller Instruction Manual
- June 13, 2024
- Polar
Table of Contents
Blast Chiller / Freezer
Instruction manual
Quick Start Guide
Blast chiller/freezer
Handleiding
Model CK640
CK640 G Series Countertop Blast Chiller
Quick Start Guide
Control panel
Timed positive blast chilling and storage cycle
To Set and Start Cycle:
- Make sure unit is in “standby” mode. The temperature of unit will flash in standby mode. If still in cycle mode, press the Start/Stop button for 2 seconds to clear.
- Once in “Standby” mode, press SET to select “PoS” and ensure the timer LED is flashing.
- Press FNC ****within 15 s to show the pre-set time.
- To adjust the time, press SET, then press FNC to reduce or to increase the value.
- Press SET or take no action for 15 s, to save the new parameter.
- Press to start the cycle. The cycle will take 2 minutes to start. The timer LED will start flashing once SET is pressed. The timer LED will then remain ON.
Please be aware, if previous cycle was a negative, a positive cycle will not
run until device is back up to temperature.
The settings are temporary. When a new cycle is activated (and after a power
failure), the device will restore the r3/r4, r5/r6, r7/r8 and r9/rA values.
Timed negative chilling and storage cycle
To Set and Start Cycle:
- Make sure unit is in “standby” mode. The temperature of unit will flash in standby mode. If still in cycle mode, press the Start/Stop button for 2 seconds to clear.
- Once in “Standby” mode, press SET to select “nEG” and ensure the timer LED is flashing.
- Press FNC within 15 s to show the pre-set time.
- To adjust the time, press SET, then press FNC to reduce or to increase the value.
- Press SET or take no action for 15 s, to save the new parameter.
- Press to start the cycle. The cycle will take 2 minutes to start. The timer LED will start flashing once SET is pressed. The timer LED will then remain ON.
Please be aware, The settings are temporary. When a new cycle is activated (and after a power failure), the device will restore the r3/r4, r5/r6, r7/r8 and r9/rA values.
Set-Temperature positive blast chilling and storage cycle To Set and Start
Cycle:
- Make sure unit is in “standby” mode. The temperature of unit will flash in standby mode. If still in cycle mode, press the Start/Stop button for 2 seconds to clear.
- Once in “Standby” mode, press SET to select “PoS” and ensure the temperature LED is flashing.
- Press FNC within 15 s to view the product temperature at the end of blast chilling.
- To adjust the temperature, press SET , then press FNC to reduce or to increase the value.
- Press SET or take no action for 15 s, to save the new parameter.
- Press to start the cycle. The cycle will take 2 minutes to start. The temperature LED will start flashing once SET is pressed. The temperature LED will then remain ON.
Please be aware, if previous cycle was a negative, a positive cycle will not
run until device is back up to temperature.
The settings are temporary. When a new cycle is activated (and after a power
failure), the device will restore the r3/r4, r5/r6, r7/r8 and r9/rA values.
Set-Temperature negative chilling and storage cycle To Set and Start Cycle:
- Make sure unit is in “standby” mode. The temperature of unit will flash in standby mode. If still in cycle mode, press the Start/Stop button for 2 seconds to clear.
- Once in “Standby” mode, press SET to select “nEG” and ensure the temperature LED is flashing.
- Press FNC within 15 s to view the product temperature at the end of blast chilling.
- To adjust the temperature, press SET , then press FNC to reduce or to increase the value.
- Press SET or take no action for 15 s, to save the new parameter.
- Press to start the cycle. The cycle will take 2 minutes to start. The temperature LED will start flashing once is pressed. The temperature LED will then remain ON.
Please be aware, The settings are temporary. When a new cycle is activated (and after a power failure), the device will restore the r3/r4, r5/r6, r7/r8 and r9/rA values.
Safety Instructions
-
Position on a flat, stable surface.
-
A service agent/qualified technician should carry out installation and any repairs if required. Do not remove any components or service panels on this product.
-
Consult Local and National Standards to comply with the following:
– Health and Safety at Work Legislation
– BS EN Codes of Practice
– Fire Precautions
– IEE Wiring Regulations
– Building Regulations -
DO NOT use jet/pressure washers to clean the appliance.
-
DO NOT use the appliance outside.
-
DO NOT use this appliance to store medical supplies.
-
DO NOT allow oil or fat to come into contact with the plastic components or door seal. Clean immediately if contact occurs.
-
Always carry, store and handle the appliance in a vertical position and move by holding the base of the appliance.
-
Always switch off and disconnect the power supply to the unit before cleaning.
-
Keep all packaging away from children. Dispose of the packaging in accordance with the regulations of local authorities.
-
If the power cord is damaged, it must be replaced by a POLAR agent or a recommended qualified technician in order to avoid a hazard.
-
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities,or lack of experience or knowledge, unless they have been given supervision or instruction concerning the use of the appliance by a person responsible for their safety.
-
Polar recommend that this appliance should be periodically tested (at least annually) by a Competent Person. Testing should include, but not be limited to: Visual Inspection, Polarity Test, Earth Continuity, Insulation Continuity and Functional Testing.
-
POLAR recommend that this product is connected to a circuit protected by an appropriate RCD (Residual Current Device).
Caution: Risk of Fire
- Do not store explosive substances such as aerosol cans with a flammable propellant in this appliance.
Warning: Keep all ventilation openings clear of obstruction. Unit should not be boxed in without adequate ventilation.
- Warning: Do not use mechanical devices or other means to accelerate the defrosting process, other than those recommended by the manufacturer.
- Warning: Do not damage the refrigerant circuit.
- Warning: Do not use electrical appliances inside the food storage compartments of the appliance.
Introduction
Please take a few moments to carefully read through this manual. Correct maintenance and operation of this machine will provide the best possible performance from your POLAR product.
Pack Contents
The following is included:
POLAR Blast Chiller /Freezer Instruction manual
POLAR prides itself on quality and service, ensuring that at the time of
unpacking the contents are supplied fully functional and free of damage.
Should you find any damage as a result of transit, please contact your POLAR
dealer immediately.
Installation
Note: Not for use in vans or trailers, food trucks or similar vehicles.
Note: If the unit has not been stored or moved in an upright position,
let it stand upright for approximately 12 hours before operation. If in doubt
allow to stand.
- Remove the appliance from the packaging. Make sure that all protective plastic film and coatings are thoroughly removed from all surfaces.
- To optimize performance and longevity, ensure a minimum clearance of 2.5cm is maintained between the unit and walls and other objects, with a minimum 20cm clearance on the top.
NEVER LOCATE NEXT TO A HEAT SOURCE.
Note: Before using the appliance for the first time, clean the interior with soapy water then dry well.
Operation
Storing Food
To get the best results from your POLAR appliance, follow these instructions:
- It is important that food entering the Blast Chiller/Freezer does not exceed a temperature of 90°C.
- It is recommended that metal containers / trays are used as other materials such as plastic or polystyrene containers will act as an insulator and extend blast chilling times.
- Sufficient space must be left between products in order to guarantee a sufficient flow of cold air. Ensure product is not in contact with the internal walls of the unit, and leave sufficient gaps between trays.
- Never obstruct the inlet of the evaporator fans.
- Products that are more difficult to chill because of their composition and size should be placed in the centre of the unit.
- Blast chilling data refers to standard products (low fat content) with a thickness below 50 mm: therefore avoid overlaying products on trays or the insertion of pieces with a much higher thickness, as this will lead to an extension of blast chilling times. Always distribute the product well on the trays and in the case of thick pieces decrease the amount to blast chill.
- Limit the number of times and the duration of time the doors are opened.
- The chiller should be used for storage for short periods only.
- When removing product that has undergone blast chilling/shock freezing, always wear gloves to protect the hands from cold burns.
Introduction
The appliance has the following operational states:
On | • The appliance is switched on and an operating cycle is running |
---|---|
Standby | • The appliance is switched on but no operating cycle is running |
Off | • The appliance is not switched on |
- If power is interrupted during a timed blast chilling operation, when power is restored, chilling will continue from the time point at which the interruption occurred (with a maximum error of 10 minutes).
- If power is interrupted during a set temperature blast chilling operation, when power is restored, chilling will start again from the beginning.
- If power is interrupted during a storage operation, when power is restored the storage operation will be reset.
- If power is interrupted while in “stand-by” mode, when power is restored the device will be in the same state.
Turn On
- Ensure the power switch is set to [O] and turn on at the socket.
- Switch on the Power [I]. This will place the unit in standby whilst waiting for the cycle to be selected.
Insert the food probe
- Before selecting which cycle to use, the probe must be inserted into the food. This allows the internal temperature of the food to be measured.
- It is important that the probe is correctly connected to the unit.
Note: To prevent bacterial contamination or contamination of any other biological nature, the needle probe must be disinfected after use.
Control Panel
Switching the appliance on
- Power up the device and switch on.
- If the device is switched on and no cycle is active, the display will show the cabinet temperature.
- If the display shows an alarm code, see the section “Alarms”.
- If no cycle is active, after 10 seconds have elapsed without the keys being pressed, the display will automatically switch off, except for the low consumption LEDs.
- When 60 seconds have elapsed without the keys being pressed, the display will show the “Loc” label and the keypad will lock automatically.
Switching the display back on
Touch a key
Unlocking the keypad
Touch a key for 1 second. The display will show the label “UnL”.
Silencing the buzzer
Touch a key
Signals
LED | On | Off | Flashing |
---|---|---|---|
Compressor | |||
switched on | Compressor switched off | Compressor protection in progress | |
Defrost active | – | Dripping active | |
Evaporator fans on | Evaporator fans off | Evaporator fan delay in progress | |
Temperature controlled cycle active | – | •Temperature controlled cycle |
selected.
•Test to check needle probe is correctly inserted in progress; when time
controlled cycle LED is on, test has failed and time controlled cycle is
active.
•When alarm LED is on, blast chilling/freezing has failed and temperature
process is active.
•When alarm LED flashes, blast chilling/freezing has failed and conservation
is active.
| Conservation active| –| Setpoint during conservation being set
| Alarm active| –| –
°C/°F| Temperature displayed| –| –
min| Time displayed| –| Residual time maximum duration of temperature
controlled blast chilling/freezing displayed
| Time controlled cycle is selected| –| Time controlled cycle active
Activating an operating cycle
Check that the keypad is not locked and that defrosting is not active.
- Touch the SET key to select a cycle.
Label| LED| Description
---|---|---
PoS| | Time controlled blast chilling and conservation (if E0 = 0 or 1)
nEG| | Time controlled blast freezing and conservation (if E0 = 1 or 2)
PoS| | Temperature controlled blast chilling and conservation (if E0 = 0 or 1)
nEG| | Temperature controlled blast freezing and conservation (if E0 = 1 or 2) - Touch the START/STOP key within 15 s.
Activating the last cycle carried out
Check that the keypad is not locked and that defrosting is not active.
- Touch the SET key.
- Touch the START/STOP key within 15 s.
Interrupting an operating cycle
Check that the keypad is not locked.
- Touch the START/STOP key for 2 s.
Setting the cabinet setpoint during conservation
Check that the keypad is not locked.
- Touch the SET key.
- Touch the UP or DOWN key within 15 s to set the value.
- Touch the SET key (or take no action for 15 s).
The setting is temporary. When a new cycle is activated (and after a power failure), the device will restore the r9/rA values.
Operating cycles
Initial information
Cycles managed:
- Time controlled blast chilling and conservation
- Time controlled blast freezing and conservation
- Temperature controlled blast chilling and conservation
- Temperature controlled blast freezing and conservation
Before each temperature controlled cycle, a test is run to check that the
needle probe is correctly inserted.
The test consists of two phases. If the first phase is completed successfully,
the second one will not be carried out.
If the test fails, the corresponding time controlled cycle is activated.
Activating time controlled blast chilling/freezing and conservation
Check that the keypad is not locked and that defrosting is not active.
- Touch the SET key to select a cycle.
Label| LED| Description
---|---|---
PoS| | Time controlled blast chilling and conservation (if E0 = 0 or 1)
nEG| | Time controlled blast freezing and conservation (if E0 = 1 or 2) - Touch the DOWN key within 15 s to see the duration of the blast chilling/freezing.
- Touch the SET key.
- Touch the UP or DOWN key within 15 s to set the value.
- Touch the SET key (or take no action for 15 s).
- Touch the DOWN key within 15 s to see the cabinet setpoint during blast chilling/freezing.
- Touch the SET key.
- Touch the UP or DOWN key within 15 s to set the value.
- Touch the SET key (or take no action for 15 s).
- Touch the DOWN key within 15 s to see the cabinet setpoint during conservation.
- Touch the SET key.
- Touch the UP or DOWN key within 15 s to set the value.
- Touch the SET key (or take no action for 15 s).
- Touch the START/STOP key within 15 s.
The settings are temporary. When a new cycle is activated (and after a power
failure), the device will restore the r1/r2, r7/r8 and r9/rA values.
Information about the active cycle:
Phase | Information displayed |
---|---|
Blast chilling/freezing active | Residual time blast chilling/freezing cycle |
End blast chilling/ freezing | End (press a key) |
Conservation active | Cabinet temperature |
Viewing other information about the active cycle:
Check that the keypad is not locked.
- Touch the DOWN key to view the type of active cycle.
Label| LED| Description
---|---|---
PoS| | Time controlled blast chilling and conservation
nEG| | Time controlled blast freezing and conservation - Touch the DOWN key again to view the cabinet temperature.
- Touch the SET key (or take no action for 15 s) to exit the procedure.
After a power failure during a cycle, the cycle is automatically reactivated
from the phase it was in at the moment the power failed. If power fails during
blast chilling/freezing, the count is resumed with a maximum error of 10
minutes.
Activating temperature controlled blast chilling/freezing and conservation
Check that the keypad is not locked and that defrosting is not active.
- Touch the SET key to select a cycle.
Label| LED| Description
---|---|---
PoS| | Temperature controlled blast chilling and conservation (if E0 = 0 or 1)
nEG| | Temperature controlled blast freezing and conservation (if E0 = 1 or 2) - Touch the DOWN key within 15 s to view the product temperature at the end of blast chilling/freezing.
- Touch the SET key.
- Touch the UP or DOWN key within 15 s to set the value.
- Touch the SET key (or take no action for 15 s).
- Touch the DOWN key within 15 s to view the maximum duration of blast chilling/freezing.
- Touch the SET key.
- Touch the UP or DOWN key within 15 s to set the value.
- Touch the DOWN key within 15 s to view the cabinet setpoint during blast chilling/freezing.
- Touch the SET key.
- Touch the UP or DOWN key within 15 s to set the value.
- Touch the SET key (or take no action for 15 s).
- Touch the DOWN key within 15 s to view the cabinet setpoint during conservation.
- Touch the SET key.
- Touch the UP or DOWN key within 15 s to set the value.
- Touch the SET key (or take no action for 15 s).
- Touch the START/STOP key within 15 s.
The settings are temporary. When a new cycle is activated (and after a power
failure), the device will restore the r3/r4, r5/r6, r7/r8 and r9/rA values.
If the temperature of the needle does not reach the product temperature at the
end of blast chilling/freezing within the maximum duration of blast
chilling/freezing, the cycle fails but the temperature will keep pulling down
until it reaches the setting temperature.
Information about the active cycle:
Phase | Information displayed |
---|---|
Blast chilling/freezing active | Needle temperature |
End blast chilling/ freezing | End (press a key) |
Conservation active | Cabinet temperature |
Viewing other information about the active cycle:
Check that the keypad is not locked.
- Touch the DOWN key to view the remaining time of the maximum duration of the blast chilling/freezing cycle (or the elapsed time from the end of the maximum duration of the blast chilling/freezing cycle if it has failed).
- Touch the DOWN key again to view the type of active cycle.
Label| LED| Description
---|---|---
PoS| | Temperature controlled blast chilling and conservation
nEG| | Temperature controlled blast freezing and conservation - Touch the DOWN key again to see the cabinet temperature.
- Touch the SET key (or take no action for 15 s) to exit the procedure.
After a power failure during a cycle, the cycle is automatically reactivated
from the phase it was in at the moment the power failed. If power fails during
blast chilling/freezing, it is reactivated from the beginning.
Activating the last cycle carried out
Check that the keypad is not locked and that defrosting is not active.
- Touch the START/STOP key for 2 s.
- Touch the START/STOP key within 60 s. The display will show the duration of the time controlled blast chilling/freezing or the product temperature at the end of the temperature controlled blast chilling/freezing.
- Touch the SET key.
- Touch the UP or DOWN key within 15 s to set the value.
- Touch the SET key (or take no action for 15 s).
- Touch the START/STOP key again within 15 s.
The settings are temporary. When a new cycle is activated (and after a power failure), the device will restore the r1/r2 and r3/r4 values.
Interrupting an operating cycle:
Check that the keypad is not locked.
- Touch the START/STOP key for 2 s.
Settings
Check that the appliance is in Standby mode.
Setting first level configuration parameters
- Touch the SET key for 4 s: the display will show the label “PA”
- Touch the UP or DOWN key to select a parameter.
- Touch the SET key.
- Touch the UP or DOWN key within 15 s to set the value.
- Touch the SET key (or take no action for 15 s).
- Touch the SET key for 4 s (or take no action for 60 s) to exit the procedure.
Setting second level configuration parameters
-
Touch the SET key for 4 s: the display will show the label “PA”.
-
Touch the SET key.
-
Touch the UP or DOWN key within 15 s to set the PAS value (default “-19”).
-
Touch the SET key (or take no action for 15 s).
The display will show the label “CA1”. -
Touch the UP or DOWN key to select a parameter.
-
Touch the SET key.
-
Touch the UP or DOWN key within 15 s to set the value.
-
Touch the SET key (or take no action for 15 s).
-
Touch the SET key for 4 s (or take no action for 60 s) to exit the procedure.
Cleaning, Care & Maintenance
- Switch off and disconnect from the power supply before cleaning.
- Clean the interior of the appliance as often as possible.
- Do not use abrasive cleaning agents. These can leave harmful residues.
- Clean the door seal with water only.
- Always wipe dry after cleaning.
- Do not allow water used in cleaning to run through the drain hole into the evaporation pan.
- Take care when cleaning the rear of the appliance. Sharp edges can cut.
Condensation will form in refrigeration with frequent opening of the doors and on hot humid days, please ensure condensation is allowed to drain properly or is wiped dry.
Cleaning the condenser
- Periodically cleaning the condenser can extend the life of the appliance.
- POLAR recommend that a POLAR agent or qualified technician clean the condenser.
Cleaning the water pan
- The water pan is located underneath the evaporator at the back of the unit.
- To remove it for cleaning, simply slide out when necessary.
Alarms
Code | Meaning | Reset | To correct |
---|---|---|---|
Pri | Cabinet probe alarm | Automatic | •Check PO |
•Check integrity of the probe
•Check electrical connection
Pr2| Needle probe alarm| Automatic
AL| Low temperature alarm| Automatic| Check Al and A2
AH| High temperature alarm| Automatic| Check A4 and AS
id| Door open alarm| Automatic| Check i0 and il
iA| Multi-purpose input alarm| Automatic| Check i0 and il
Troubleshooting
A qualified technician must carry out repairs if required.
Fault | Probable Cause | Solution |
---|---|---|
The appliance is not working | The unit is not switched on | Check unit is |
plugged in correctly and switched on
Plug or lead is damaged| Replace plug or lead
Fuse in the plug has blown| Replace the fuse
Mains power supply fault| Check mains power supply
The appliance is leaking water| The appliance is not properly levelled| Adjust
the screw feet to level the appliance (if applicable)
The discharge outlet is blocked| Clear the discharge outlet
Movement of water to the drain is obstructed| Clear the floor of the appliance
(if applicable)
The water container is damaged| Replace the water container
The appliance is unusually loud| The appliance has not been installed in a
level or stable position| Check installation position and change if necessary
Loose nut/screw| Check and tighten all nuts and screws
Technical Specifications
Note: Due to our continuing program of research and development, the specifications herein may subject to change without notice.
Model| Voltage| Power| Current| Capacity| Dimensions HxWxD| Refrigerant|
Weight (kg)
---|---|---|---|---|---|---|---
CK640| 230V- 50Hz| 500W| 4A| 3 x GN 2/3| 420 x 660 x 650| R290| 42
Electrical Wiring
POLAR appliances are supplied with a 3 pin BS1363 plug and lead.
The plug is to be connected to a suitable mains socket.
POLAR appliances are wired as follows:
- Live wire (coloured brown) to terminal marked L
- Neutral wire (coloured blue) to terminal marked N
- Earth wire (coloured green/yellow) to terminal marked E
This appliance must be earthed.
If in doubt consult a qualified electrician.
Electrical isolation points must be kept clear of any obstructions. In the
event of any emergency disconnection being required they must be readily
accessible.
Disposal
EU regulations require refrigeration product to be disposed of by specialist
companies who remove or recycle all gasses, metal and plastic components.
Consult your local waste collection authority regarding disposal of your
appliance. Local authorities are not obliged to dispose of commercial
refrigeration equipment but may be able to offer advice on how to dispose of
the equipment locally.
Alternatively call the POLAR helpline for details of national disposal
companies within the EU.
Compliance
The WEEE logo on this product or its documentation indicates that the product
must not be disposed of as household waste. To help prevent possible harm to
human health and/or the environment, the product must be disposed of in an
approved and environmentally safe recycling process. For further information
on how to dispose of this product correctly, contact the product supplier, or
the local authority responsible for waste disposal in your area.
POLAR parts have undergone strict product testing in order to comply with
regulatory standards and specifications set by international, independent, and
federal authorities.
POLAR products have been approved to carry the following symbol:
All rights reserved. No part of these instructions may be produced or
transmitted in any form or by any means, electronic, mechanical, photocopying,
recording or otherwise, without the prior written permission of POLAR.
Every effort is made to ensure all details are correct at the time of going to
press, however, POLAR reserve the right to change specifications without
notice.
DECLARATION OF CONFORMITY
Equipment Type | Model |
---|---|
G-Series Countertop Blast Chiller/Freezer – 8/5Kg | CK640 (-E & -A) |
Application of Territory Legislation & Council Directives(s) | Machinery |
Directive 2006/42/EC
Supply of Machinery (Safety) Regulations 2008 (BS) EN 60335-1:2012 +A11:2014
+A13:2017 +A1:2019 +A14:2019
(BS) EN 60335-2-89:2010 +A1:2016 +A2:2017 (BS) EN 62233:2008
Electro-Magnetic Compatibility (EMC) Directive 2014/30/EU – recast of
2004/108/EC Electromagnetic Compatibility Regulations 2016 (S.I. 2016/1091)
(BS) EN IEC 55014-1:2021 (BS) EN IEC 55014-2:2021 (BS) EN IEC 61000-3-2:2019
+A1:2021
(BS) EN 61000-3-3:2013 +A1:2019 +A2:2021
Restriction of Hazardous Substances Directive (RoHS) 2015/863 amending Annex
II to Directive 2011/65/EU
Restriction of the Use of Certain Hazardous Substances in Electrical and
Electronic
Equipment Regulations 2012 (Si. 2012/3032)| Electrical Safety
IEC 60335-1:2010 +A1:2013
+A2:2016
IEC 60335-2-89:2010 +A1:2012 +A2:2015
EN 62233:2008
Electromagnetic Compatibility
EN IEC 55014-1:2021 EN IEC 55014-2:2021 EN IEC 61000-3-2:2019 +A1:2021
EN 61000-3-3:2013 +A1:2019 +A2:2021
Producer Name| Polar
I, the undersigned, hereby declare that the equipment specified above conforms to the above Territory Legislation, Directive(s) and Standard(s).
Date
Signature
Full Name
Position
Producer
Address
19th October 2022
| |
Ashley Hooper| Eoghan Donnellan| Brendan Denmeade
Technical & Quality
Manager| Commercial Manager/
Importer| Commercial Manager/ Responsible
Supplier
Fourth Way,
Avonmouth,
Bristol,
BS11 8TB
United Kingdom| Unit 9003,
Blarney Business Park,Blarney,
Co. Cork
Ireland| 15 Bagdally Road,
Campbelltown
NSW 2560
UK | +44 (0)845 146 2887 |
---|
http://www.polar-refrigerator.com/
CK640_ML_A5_v5_2022/10/25
CK640_ML_A5_v5_20221025.indb
2022/10/25 17:36
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>