Product Information

The TX6648 is an Uninterruptible Power Supply (UPS) with an intrinsically safe output and a 3.5 Ah battery backup. It is designed to convert an AC supply voltage into a stabilized and regulated power source for approved sensors and electronic control devices.

Product Usage Instructions

Connections

  1. Operating Features: The UPS has various operating features. Refer to the user manual for detailed information.
  2. Application: The UPS can be used in group areas. Consult the user manual for specific instructions.
  3. Product Options: UPS has different product options. Refer to the user manual for available options.
  4. Dimensions: The dimensions of the UPS are provided in the user manual.

Technical Maintenance

  1. Technical Information: Detailed technical information about UPS can be found in the user manual.
  2. Diagnostics: The UPS has diagnostic capabilities. Refer to the user manual for diagnostic instructions.
  3. Connectivity: The UPS supports connectivity options. Consult the user manual for connectivity instructions.
  4. Support: For technical support, refer to the user manual or contact customer support.

Safety Precautions

  1. Handling: Follow safety precautions while handling the UPS. Refer to the user manual for specific guidelines.
  2. Tools and Test Equipment: Certain tools and test equipment may be required for maintenance. Refer to the user manual for a list of recommended tools.
  3. Siting Recommendations: Proper positioning and siting recommendations are provided in the user manual.

Technical Specifications

  • Input Voltage: The UPS accepts an AC supply voltage.
  • Output Voltage: The UPS provides a stabilized 12V DC output voltage.
  • Output Current: The UPS has an output current of 750 mA.
  • Output Ripple/Noise: The UPS has a maximum output ripple/noise of 150 mV.
  • Line Regulation: The UPS has line regulation capabilities. Refer to the user manual for more details.
  • For more detailed information and instructions, please refer to the user manual.

Product Overview

The TX6648 Power Supply converts an ac supply voltage into a stabilised and regulated Intrinsically Safe source of power to approved sensors and electronic control devices.

Operating Features
  • Input voltage options: 110 V ac or 230 V ac or 24 V ac
  • Input supply is protected by two primary fuses
  • Intrinsically Safe output voltage: 12 V dc
  • Output circuit is resistively limited in accordance with certification standards for Intrinsically Safe, ia, equipment
  • Output circuit incorporates voltage regulation, current limiting and continuous short circuit protection
  • Robust stainless steel housing
  • Integral 3.5 Ah back-up battery with automatic uninterrupted power transfer and charge to full capacity
  • Output relay contact to signal power failure
  • Analogue output signal to indicate battery charge condition
  • Battery conserve timer for use on mobile machinery
Application
  • Mining
  • Tunnelling

Product Options

Dimensions
Technical Information

1| Input voltage| 110 V ac ± 10% or 230 V ac ± 10% (PS 24 7 BD +/- 10%

– 50/60 Hz

---|---|---
2| Output voltage| 12 V dc
 | Output current| 750 mA
 | Output ripple/noise| 150 mV max
 | Line regulation| <5% over the input voltage range
 | Load regulation| <5% over 0 to 90% of load current

<10% between 90% and 100% of load current

 | Voltage limiting| Over voltage detection with crowbar protection and short circuit protection
 | Current limiting| Automatic current limiting of the intrinsically safe output also limits the current to less than the rupturing capacity of the output protection fuse.
3| Max. operating temperature| –20°C to +40°C
---|---|---
 | Storage temperature| –20°C to +70°C
 | Humidity| 0 to 95% RH, non-condensing
 | Vibration limits / low frequency| 0.25 mm peak, sinusoidal vibration in the range 10 Hz to 100 Hz in 3 perpendicular planes
 | Medium frequency| 2g peak, sinusoidal vibration in the range 10 Hz to 600 Hz in 3 perpendicular planes
 | Mechanical shock| 1000 shocks of 40g minimum in 3 perpendicular planes
 | Housing material| Stainless steel
4| Back-up battery| Sealed lead-acid. 3 5 Ah

Automatic charge control to full capacity Automatic uninterrupted output power transfer following input power failure

---|---|---
 | Power fail indication| Relay contacts change state on power failure. Contact rating: 0.25 A at 30 V dc max.
 | Charge condition| Analogue output signal proportional to the charge level of the battery

Choice of 0.4 V to 2.0 V or 4 to 20 mA signals

 | Battery life| 6 years at 20°C 3 years at 30°C

1.5 years at 40°C

 | Net weight| 16 kg
 | Important note| Following initial commissioning or long periods of storage the TX6648 requires a minimum of

24 hours charge time before the batteries will be at full capacity.

 | Battery conserve timer| Selectable option to automatically switch off the battery power after 30 minutes

Certification & Conformity

| ATEX (European Union) certification for use in underground mines (Group I).
---|---
Complies with ATEX Directive 2014/34/EU.
Standards:
EN IEC 60079-0:2018
EN 60079-5:2015
EN IEC 60079-7:2015+A1:2018
EN 60079-11:2012
| IECEx (International) certification for use in underground mines (Group I).
---|---
Standards:

IEC 60079-0:2017

IEC 60079-5:2015

IEC 60079-7:2015+AMD1:2017

IEC 60079-11:2011

| EAC certification for use in underground mines in Eurasian Customs Union (including Russia).
---|---

Underground mines

Product Code: Ex Certificate Number: Ex Certification Code:

TX6648.35(.xx…).19

3.5 Ah UPS Power Supply

| ****

CML 21ATEX2404X IECEx CML 21.0048X

| I M2(M1) Ex eb q [ia Ma] I Mb (see Note 1) I M1 Ex ia I Ma (see Note 2)

Ta = -20 ˚C to +55 ˚C


TX6648.35(.xx…).14

3.5 Ah UPS Power Supply

| ****

RU C-GB.AA87.B.00155/19

| PП Ex e q [ia Ma] I Mc X (see Note 1)

PO Ex ia I Ma X (see Note 2) Ta = -20 ˚C to +40 ˚C

  • Note 1 – applies when mains powered
  • Note 2 – applies when powered from the backup battery

The following Specific Conditions of Use apply to the ATEX and ICE certificates listed above:
The following conditions relate to safe installation and/or use of the equipment:

  • All cable entries shall be made using suitably certified Ex e cable glands
  • The use of conduit is not permitted.

Installing

Safety Precautions
The installation of the product must only be carried out by competent personnel. Each installation needs to be considered with reference to the local safety regulations and authorities. Refer to the following standards for additional guidance:

  • IEC/EN 60079-14
  • IEC/EN 60079-25
  1. Make sure that all covers on Ex e housings and their fixing devices are properly secured in compliance with statutory regulations before switching on the input supply.
  2. Never remove the cover of an Ex e housing whilst the input supply is connected. Isolate elsewhere before removing the cover in accordance with statutory regulations.
  3. The housing of all power supplies must be securely earthed in compliance with statutory regulations.
  4. Carry out a current consumption audit to ensure that the maximum current loading of the power supply is not exceeded.
  5. Ensure that the installation of the power supply, particularly with regard to the connecting cables, complies with the certification parameters (section 2.1).
  6. The Ex e housing must be inspected and maintained regularly in accordance with statutory regulations.
  7. All cables entering the mains input terminal chamber must be terminated with suitable, certified cable entry devices.
  8. Do not drill holes in the Ex e housing or modify it in any way.
  9. The battery contains corrosive substances and must be disposed of in the correct way.
  10. Please return the complete unit to Trolex or an approved distributor for servicing and replacement.

Handling
The TX6648 weighs 16 kg and safe handling and transportation should be applied in line with the heath and safety recommendations on your site

Tools and Test Equipment Required

  • No special tools are needed.

Siting Recommendations

  1. The TX6648 may be located in hazardous areas of mines susceptible to firedamp and coal dust (Group I)
  2. The equipment should not be used outside of its certified ambient temperature range.
  3. Installation shall be carried out in accordance with the applicable code of practice by suitably trained personnel.

Positioning Recommendations
Mount horizontally as shown in the illustrations on pages 4 and 7.

Commissioning / verification tests prior to first use.
Prior to commissioning and first use, the product should be inspected for any visible damages and integrity of the enclosure. Never use the product that has damaged housing in hazardous locations.

Power Requirements

  • See Technical Information.

Output Signal

  • 0.4 to 2 V dc Battery charge level monitor
  • 4 to 20 mA Battery charge level monitor
  • Relay Mains fail output contact
Connections
  • Mains input 110 V ac or 230 V ac or 24 V ac

Battery Conserve Timer

  • The TX6648 Power Supply is fitted with a Battery Conserve Timer.
  • The timer is used to conserve battery power when used on mobile machinery where battery support will only be required for short intervals between long periods.
  • The battery back-up will be terminated 30 minutes after the main power is OFF.
  • The battery will be charged in the normal way when the main power is ON.
  • The timer is disabled by fitting a link between T1 and T2
  • The batter back-up may be re-instated at any time for a period of 30 minutes by operation of a pushbutton on the side of the power supply housing, or a remote pushbutton connected to T1 and T2.

Group | Areas
Connecting cables must conform to the requirements of the appropriate Approval and Certification standards for Mining applications. Trolex recommends that they conform to BS5308.

Maintenance

The maintenance of the product must only be carried out by competent personnel. Maintenance shall be considered with reference to the local safety regulations and authorities. Refer to the following standards for additional guidance:

IEC/EN 60079-17

  • Make periodic visual inspections to check for physical damage.
  • Check connections in both terminal chambers are secure.
  • The product is marked with the following warning, which is applicable to the power supply enclosure only:

THIS CONTAINER HAS BEEN PERMANENTLY SEALED AND CANNOT BE REPAIRED

Technical Maintenance
Trolex recommends that the batteries are replaced every three years. This must be carried out by a competent person. If the unit is returned to Trolex for this re-work, a test of the internal safety integrity will also be carried out.

Warranty

See Terms and Conditions for the Supply of Goods and/or Services at www.trolex.com.

Diagnostics

Condition: Output reading of 800mV instead of 12 V dc.
Diagnosis: The internal safety crowbars have activated due to an external

condition on the input voltage or output side, the crowbars will attempt to automatically reset. If this does not happen remove main power for about 2 minutes.
Condition:| The output has dropped to zero
Diagnosis:| It is probable that the input fuses have ruptured which has resulted in the batteries completely discharging. To check this, remove

main power momentarily. If the relay does not change state then it confirms the unit is continuously operating on the battery supply only.

Connectivity

  • Check the correct function of the mains-fail relay by connecting a suitable test meter across the contacts.
  • A 12 V dc output should be available at the intrinsically safe output terminals with mains power input present, or absent.
  • Also check that the analogue battery monitoring signal is available at the output terminals.

Support
If you need technical support to operate this product, or would like details of our after sales technical support packages, contact [email protected].

Disclaimers

The information provided in this document contains general descriptions and technical characteristics of the performance of the product. It is not intended as a substitute for and is not to be used for determining suitability or reliability of this product for specific user applications. It is the duty of any user or installer to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use. Trolex shall not be responsible or liable for misuse of the information contained herein. If you have any suggestions for improvements or amendments, or find errors in this publication, please notify us at [email protected].

  • No part of this document may be reproduced in any form or by any means, electronic or mechanical, including photocopying, without express written permission of Trolex.
  • All pertinent state, regional, and local safety regulations must be observed when installing and using this product. For reasons of safety and to help ensure compliance with documented system data, only Trolex or its affiliates should perform repairs to components.
  • When devices are used for applications with technical safety requirements, the relevant instructions must be followed.

Trademarks

© 2013 Trolex® Limited.
Trolex is a registered trademark of Trolex Limited. The use of all trademarks in this document is acknowledged.

Document History

  • Issue 1 20 July 2005 Original publication of this document
  • Issue 2 6 September 2013 New format and minor revisions
  • rev A 14 March 2022 General revisions

Trolex Ltd, Newby Road, Hazel Grove, Stockport, Cheshire, SK7 5DY,
UK+44 (0) 161 483 1435 [email protected].

At Trolex, we save lives.

  • We believe that no person should risk their life to earn a living.
  • Our aim is to become the world’s leading name in health and safety technology, through pioneering products that provide real-world benefits to our customers, whenever workers operate in hazardous environments.

For more information about Trolex, please contact us at:

  • Enquiries
    [email protected]

  • Telephone
    +44 (0) 161 483 1435

  • Fax
    +44 (0) 161 483 5556

  • Trolex Ltd
    Newby Road, Hazel Grove Stockport, Cheshire SK7 5DY, United Kingdom